n ANNUAL EFFLUENT RELEASE REPORT NO. 21 January 1, 1995 Through December 31, 1995 PECO NUCLEAR LIMERICK GENERATING STATION UNITS NO. 1 AND 2 DOCKET NO. 50-352 (Unit 1)

DOCKET NO. 50-353 (Unit 2)

Submitted to The United States Nuclear Regulatory Comunission Pursuant to Facility Operating License NPF-39 (Unit 1) and NPF-85 (Unit 2) i l

i R(W. Boyce, PlantMa%ger 9603050101 960229 PDR ADOCK 05000352 R

PDR

L TABLE OF CONTENTS i

I.

Introduction II.

Tables A.

Summary of Radioactiva Gaseous Effluents B.

Summary of Radioactive Liquid Effluents C.

Solid Waste Disposition Report D.

Offsite Radiation Dose Assessment E.

Radiation Dose to Members of the Public Due to Their

{

Activities Inside Site Boundary III. Attachments A.

Supplemental Information - Assumptions Used in Report Generation B.

Radiation Monitors Out-of-Service C.

Revision to Previous Submittal D.

Offsite Dose Calculation Manual Revision 16 and 17 (Sent under separate cover)

I.

INTRODUCTION This submittal complies with the format described in Regulatory Guide 1.21,

" Measuring, Evaluating and Reporting Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water Cooled Nuclear Power Plants", Revision 1, June, 1974.

The following information is included as Tables to this report:

A summary of the s 'seous and liquid ef fluent releases for the report period.

Where "0.00E+00" is used, it denotes the less than detectable level for the given isotope.

Composite particulate air samples, counted for beta emitters (eg. Sr-89, Sr-90), are submitted to an offsite vendor laboratory for analysis.

Vendor results were obtained prior to report calculation therefore the 1995 report is complete.

Since Limerick Technical Specification limits for liquid and gaseous effluent releases are stated in terms of quarterly and annual offsite doses, " percent technical specification limit" is given as 0.00E+00.

A summary of solid waste dispositioned during the report period, to include: total activity shipped by waste type and an estimate of the error in the reported totals; the estimated composition of each type of waste by isotope; the number of shipments, mode of transportation, destination, type of container, total container volume, and solidification agent.

There were no changess to the Fadioactive Waste Treatment Systems during the report period.

. - _. -. ~ _.. _

. -. =. _. _

t s

i i

4 1

l 1

)

t t

t i

i L

a

'i

)

h h

1 t

II.

TABLES 4

y A.

SUMMARY

OF RADIOACTIVE GASEOUS EFFLUENTS t

I January 1, 1995 to December 31, 1995 i

f 3,

s 1

i a

i i

i i

J 1

4 i

i i

SITE: LIMERICK UNIT: U1 & U2 1

i DATE: 02/27/96 21:04 1

EFFLUENT AND WASTE DISPOSAL REPORT I

GASEOUS EFFLUENTS -- SUMMATION OF ALL RELEASES

UNITS :

QUARTER QUARTER

EST.

TOTAL:

l 1

2

ERROR, i

A. FISSION AND ACTIVATION GASES i

i

1. TOTAL RELEASE CI
0.123E+02 : 0.338E+02 : 0.453E+02 :

)

2. AVERAGE RELEASE
UCI/SEC: 0.158E+01 : 0.429E+01 :

RATE FOR PERIOD 3.

PERCENT OF TECHNICAL:

0.000E+00 : 0.000E+00 :

i SPECIFICATION LIMIT :

i 4

B.

IODINES i

$ 5$ TbTEL 5bb5hE-555

~~$

b5 ~ $ b$d575

~ ~

~ $

..________________-bk'$

UIk95E5b5 $ b$kS5E+b2

2. AVERAGE RELEASE
UCI/SEC: 0.562E-05 : 0.627E-04 :

RATE FOR PERIOD i

l 3.

PERCENT OF TECHNICAL:

0.000E+00 : 0.000E+00 :

SPECIFICATION LIMIT :

i C. PARTICULATES 1.

PARTICULATES WITH CI

0.110E-04 : 0.218E-04 : 0.453E+02 :

HALF-LIVES >8 DAYS i

2. AVERAGE RELEASE
UCI/SEC: 0.142E-05 : 0.278E-05 :

RATE FOR PERIOD 3.

PERCENT OF TECHNICAL:

0.000E+00 : 0.000E+00 :

SPECIFICATION LIMIT :

4. GROSS ALPHA CI
0.105E-05 : 0.235E-05 :

RADIOACTIVITY D. TRITIUM 1.

TOTAL RELEASE CI

0.000E+00 : 0.000E+00 : 0.453E+02 :

1

2. AVERAGE RELEASE
UCI/SEC: 0.000E+00 : 0.000E+00 :

RATE FOR PERIOD 3.

PERCENT OF TECHNICAL:

0.000E+00 : 0.000E+00 :

SPECIFICATION LIMIT :

PAGE 1 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:04 EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

1 NORTH STACK i

1 1

l CONTINUOUS MODE BATCH MODE j

i NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2

1. FISSION GASES AR41 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR83M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR87 CI

0.412E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR88 CI

0.405E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

l XE131M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133 CI

0.447E+01 : 0.311E+02 : 0.000E+00 : 0.000E+00 :

XE135M CI

0.817E-01 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135 CI

0.685E+01 : 0.280E+00 : 0.000E+00 : 0.000E+00 :

XE137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE138 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.122E+02 : 0.314E+02 : 0.000E+00 : 0.000E+00 :

i (ABOVE) 1 l

l i

i d

PAGE 2 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:04 EFFLUENT AND WASTE DISPOSAL REPORT

, GASEOUS EFFLUENTS FOR RELEASE POINT:

1 NORTH STACK CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

E %RTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2

2. IODINES 1131 CI
0.261E-04 : 0.487E-03 : 0.000E+00 : 0.000E+00 :

I133 CI

0.000E+00 : 0.412E-03 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.261E-04 : 0.899E-03 : 0.000E+00 : 0.000E+00 :

(ABOVE)

3. PARTICULATES C14 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CR51 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

MN54 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

FE59 CI

0.000E+00 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO58 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO60 CI

0.000E+00 : 0.421E-06 : 0.000E+00 : 0.000E+00 :

ZN65 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR89 CI

0.110E-04 : 0.186E-04 : 0.000E+00 : 0.000E+00 :

SR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZR95 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SB124 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

1 CS134 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS136 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

PAGE 3 OF 12 i

SITE: LIMERICK UNIT: U1 & U2 i

DATE: 02/27/96 21:04 EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

1 NORTH STACK i

CONTINUOUS MODE BATCH MODE b

NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER l

RELEASED 1

2 1

2

- 3. PARTICULATES (CONTD)

BA140 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

)

CE141 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

)

CE144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.110E-04 : 0.190E-04 : 0.000E+00 : 0.000E+00 :

(ABOVE) l i

i i

PAGE 4 OF 12 l

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:04 l

EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

2 UNIT 1 - SOUTH STACK CONTINUOUS MODE BATCH MODE i

I NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2.

i i

1. FISSION GASES

'i AR41 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I KR83M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR87 CI

0.000E+00 : 0.000E+F : 0.000E+00 : 0.000E+00 :

KR88 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

\\

l KR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I XE131M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135 CI

0.225E-01 : 0.000E+00 : 0.000E+C0 : 0.000E+09 :

XE137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

\\

\\

XE138 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.225E-01 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

(ABOVE)

PAGE 5 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:05 EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

2 UNIT 1 - SOUTH STACK CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2

2. IODINES I131 CI
0.000E+00 : 0.531E-05 : 0.000E+00 : 0.000E+00 :

I133 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.000E+00 : 0.531E-05 : 0.000E+00 : 0.000E+00 :

(ABOVE)

3. PARTICULATES C14 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CR51 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

MN54 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

FE59 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

C058 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO60 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 ZN65 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR89 CI

0.000E+00 : 0.282E-05 : 0.000E+00 : 0.000E+00 :

SR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZR95 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SB124 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS134 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS136 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i i

i

PAGE 6 OF 12 SITE: LIMERICK UNIT: U1 & U2 1

DATE: 02/27/96 21:05 l

EFFLUENT AND WASTE DISPOSAL REPORT i

I GASEOUS' EFFLUENTS FOR RELEASE POINT:

2 UNIT 1 - SOUTH STACK CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1-2-

1 2

3. PARTICULATES (CONTD) t BA140 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE141 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

PERIOD CI

0.000E+00 : 0.282E-05 : 0.000E+00 : 0.000E+00 :

(ABOVE) l I

i i

PAGE 7 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:05 EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

3 UNIT 2 - SOUTH STACK CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2

1. FISSION GASES AR41 CI
0.400E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR83M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR87 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR88 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE131M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133 CI

0.325E-01 : 0.772E+00 : 0.000E+00 : 0.000E+00 :

XE135M CI

0.566E-01 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135 CI

0.000E+00 : 0.159E+01 : 0.000E+00 : 0.000E+00 :

XE137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

)

XE138 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

PERIOD CI

0.890E-01 : 0.236E+01 : 0.000E+00 : 0.000E+00 :

j (ABOVE)

_-.._._m_

i l

l PAGE 8 OF 12

- SITE: LIMERICK UNIT: U1 & U2 i

DATE: 02/27/96 21:05 i

EFFLUENT AND WASTE DISPOSAL REPORT a

GASEOUS EFFLUENTS FOR RELEASE POINT:

3 UNIT 2 - SOUTH STACK i

i b

CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER

)

l RELEASED 1

2 1

2 1

i

2. IODINES i

l I131 CI

0.169E-04 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

l I133 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i TOTAL FOR :

i PERIOD CI

0.169E-04 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

(ABOVE)

3. PARTICULATES C14 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CR51 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

MN54 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

FE59 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO58 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO60 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZN65 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZR95 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SB124 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS134 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS136 CI 0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I CS137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

m..i.-

PAGE 9 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:05 EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

3 UNIT 2 - SOUTH STACK CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2-3o PARTICULATES (CONTD)

BA140 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE141 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

(ABOVE)

PAGE 10 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:05 EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

4 HOT MAINTENANCE SHOP CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2

1. FISSION GASES AR41 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR83M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR87 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR88 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE131M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.00n" 10 :

XE133M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E400 :

XE133 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE138 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

(ABOVE)

PAGE 11 OF 12 SITE: LIMERICK

{

UNIT: U1 & U2 j

DATE: 02/27/96 21:05 EFFLUENT AND WASTE DISPOSAT: REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

4 HOT MAINTENANCE SHOP 1

CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2 2.

IODINES i

I131 CI

0.738E-06 : 0.700E-06 : 0.000E+00 : 0.000E+00 :

I133 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.738E-06 : 0.700E-06 : 0.000E+00 : 0.000E+00 :

(ABOVE) l l

3. PARTICULATES l

C14 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CR51 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I MN54 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

FE59 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

C058 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO60 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZN65 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZR95 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SB124 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS134 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS136 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

~

PAGE 12 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:05 EFFLUENT AND WASTE DISPOSAL REPORT r

t GASEOUS EFFLUENTS FOR RELEASE POINT:

4 HOT MAINTENANCE SHOP i

CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2 3c PARTICULATES (CONTD) 1 BA140 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE141 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

(ABOVE)

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:44 EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS -- SUMMATION OF ALL RELEASES

UNITS :

QUARTER QUARTER

EST.

TOTAL:

3 4

ERROR, A. FISSION AND ACTIVATION GASES
1. TOTAL RELEASE CI
0.179E+03 : 0.359E+01 : 0.453E+02 :
2. AVERAGE RELEASE
UCI/SEC: 0.226E+02 : 0.449E+00 :

RATE FOR PERIOD 3.

PERCENT OF TECHNICAL:

0.000E+00 : 0.000E+00 :

SPECIFICATION LIMIT :

i l

l i

B.

IODINES i

1

1. TOTAL IODINE-131 CI
0.379E-02 : 0.453E-03 : 0.453E+02 :
2. AVERAGE RELEASE
UCI/SEC: 0.476E-03 : 0.570E-04 :

RATE FOR PERIOD

3.

PERCENT OF TECHNICAL:

0.000E+00 : 0.000E+00 :

SPECIFICATION LIMIT :

l C.

PARTICULATES 1.

PARTICULATES WITH CI

0.130E-03 : 0.641E-04 : 0.453E+02 :

HALF-LIVES >8 DAYS

2. AVERAGE RELEASE
UCI/SEC: 0.166E-04 : 0.806E-05 :

RATE FOR PERIOD 3.

PERCENT OF TECHNICAL:

0.000E+00 : 0.000E+00 :

SPECIFICATION LIMIT :

4. GROSS ALPHA CI
0.440E-05 : 0.326E-05 :

RADIOACTIVITY D. TRITIUM

1. TOTAL RELEASE CI
0.000E+00 : 0.000E+00 : 0.453E+02 :
2. AVERAGE RELEASE
UCI/SEC: 0.000E+00 : 0.000E+00 :

RATE FOR PERIOD

3.

PERCENT OF TECHNICAL:

0.000E+00 : 0.000E+00 :

SPECIFICATION LIMIT :

PAGE 1 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:44 EFFLUENT AND WASTE DISPOSAL REPORT l

1 1

GASEOUS EFFLUENTS FOR RELEASE POINT:

1 NORTH STACK b

l CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4

1. FISSION GASES i
- AR41 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR83M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

l KR85M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR87 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR88 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE131M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135 CI

0.173E+03 : 0.968E-01 : 0.000E+00 : 0.000E+00 :

1 XE137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE138 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

1 PERIOD CI

0.173E+03 : 0.968E-01 : 0.000E+00 : 0.000E+00 :

(ABOVE) h

I PAGE 2 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:45 EFFLUENT AND WASTE DISPOSAL REPORT

]

1 GASEOUS EFFLUENTS FOR RELEASE POINT:

1 NORTH STACK i

CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4

2. IODINES I131 CI
0.217E-02 : 0.520E-04 : 0.000E+00 : 0.000E+00 :

I133 CI

0.206E-02 : 0.322E-02 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.422E-02 : 0.328E-02 : 0.000E+00 : 0.000E+00 :

(ABOVE)

3. PARTICULATES C14 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CR51 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

MN54 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

FES9 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO58 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO60 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZN65 CI

0.470E-04 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR89 CI

0.272E-04 : 0.487E-04 : 0.000EF00 : 0.000E+00 :

j SR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZR95 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SB124 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS134 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS136 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

l

PAGE 3 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:45 1

EFFLUENT AND WASTE DISPOSAL REPORT I

GASEOUS EFFLUENTS FOR RELEASE POINT:

1 NORTH STACK i

CONTINUOUS MODE-BATCH MODE 3

i NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4 E

}

3. PARTICULATES (CONTD)

BA140 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i CE141 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.742E-04 : 0.487E-04 : 0.000E+00 : 0.000E+00 :

(ABOVE) r i

l l

PAGE 4 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:45 EFFLUENT AND WASTE DISPOSAL REPORT f

?

GASEOUS EFFLUENTS FOR RELEASE POINT:

2 UNIT 1 - SOUTH STACK i

t f;

CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4

1. FISSION GASES AR41 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

~

~

i Ek83k

~~ I Ci

$ b$bbbb bb I bIbbbE bb $ b$bbbb bb $ b$bbbb bb $

KR85M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR87 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR88 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

f KR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE131M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0,000E+00 :

XE133M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133 CI

0.482E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135 CI

0.272E+01 : 0.198E+01 : 0.000E+00 : 0.000E+00 :

XE137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE138 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.320E+01 : 0.198E+01 : 0.000E+00 : 0.000E+00 :

(ABOVE) l

PAGE 5 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:45 1

)

EFFLUENT AND WASTE DISPOSAL REPORT i

i i

GASEOUS EFFLUENTS FOR RELEASE POINT:

2 UNIT 1 - SOUTH STACK CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4 2.

IODINES t

I131 CI

0.154E-02 : 0.401E-03 : 0.000E+00 : 0.000E+00 :

I133 CI

0.253E-02 : 0.486E-02 : 0.000E+00 : 0.000E+00 :

)

TOTAL FOR :

PERIOD CI

0.407E-02 : 0.526E-02 : 0.000E+00 : 0.000E+00 :

(ABOVE) k

3. PARTICULATES l

C14 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

)

CR51 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

MN54 CI

0.874E-05 : 0.000E+00 : 0.000E+00 : 0.000E+00 i

t i

FE59 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

C058 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO60 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZN65 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR89 CI

0.109E-04 : 0.154E-04 : 0.000E+00 : 0.000E+00 :

SR90 CI

0.869E-06 : 0.000E+00 : 0.000E+00 : 0.000E+00 ZR95 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SB124 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS134 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS136 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

l 1

I

l PAGE 6 OF 12 i

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:45 EFFLUENT AhD WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

2 UNIT 1 - SOUTH STACK l

l CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4 3o PARTICULATES (CONTD)

BA140 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE141 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i TOTAL FOR :

PERIOD CI

0.205E-04 : 0.154E-04 : 0.000E+00 : 0.000E+00 :

(ABOVE)

I l

I 1

i 1

i i

l

.~.

~

1 PAGE 7 OF 12

- SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:45 EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

3 UNIT 2 - SOUTH STACK 1

CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4

1. FISSION GASES AR41 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 KR83M CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR87 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR88 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR89 CI 0.000E+00

0.000E+00 : 0.000E+00 : 0.000E+00 :

\\

KR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE131M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135

'CI
0.349E+01 : 0.149E+01 : 0.000E+00 : 0.000E+00 :

XE137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE138 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

j TOTAL FOR :

PERIOD CI

0.349E+01 : 0.149E+01 : 0.000E+00 : 0.000E+00 :

(ABOVE) 1 4

1 I

l PAGE 8 OF 12 SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:45 c

i EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

3 UNIT 2 - SOUTH STACK CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4

2. IODINES I131 CI
0.724E-04 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I133 CI

0.202E-04 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.925E-04 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

(ABOVE)

3. PARTICULATES i

C14 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CR51 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

MN54 CI

0.373E-04 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

FE59 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I CO58 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO60 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZN65 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZR95 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SB124 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 CS134 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS136 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

1 1

PAGE 9 OF 12

' SITE: LIMERICK' UNITS.U1 & U2 DATE: 02/29/96 04:45 i

i EFFLUENT AND WASTE DISPOSAL REPORT A

GASEOUS EFFLUENTS FOR RELEASE POINT:

3 UNIT 2 - SOUTH STACK CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4

3. PARTICULATES (CONTD)

BA140 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 CE141 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

{

CE144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

4 PERIOD CI

0.373E-04 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

(ABOVE) b t

J

+

4 3

r

I r

I PAGE 10 OF 12 SITE: LIMERICK UNIT: U1 & U2 1

DATE: 02/29/96 04:45

[

1 EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

4 HOT MAINTENANCE SHOP CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER PELEASED 3

4 3

4

1. FISSION GASES AR41 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

l KR83M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR85 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i I

KR87 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR88 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

KR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE131M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE133 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE135 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

XE138 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

(ABOVE) i

PAGE 11 OF 12 SITE: LIMERICK UNIT U1 & U2 DATE: 02/29/96 04:45 EFFLUENT AND WASTE DISPOSAL REPORT i

L t

GASEOUS EFFLUENTS FOR RELEASE POINT:

4 HOT MAINTENANCE SHOP CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4 i

i i

l 2, IODINES I131 CI

0.521E-05 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I133 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i TOTAL FOR :

PERIOD CI

0.521E-05 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

(ABOVE) l 1

3. PARTICULATES j

C14 CI

0.000E+00 : 0.000E+00 : 0.000E+00 I

0.000E+00 :

CR51 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

MN54 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

FES9 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

C058 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CO60 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZN65 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000EA00 :

SR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZR95 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SB124 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS134 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS136 CI

0.000Ev00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS137 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

m.

,.v-~

-t-

PAGE 12 OF 12 SITE: LIMERICK UNIT: U1 ft U2 DATE: 02/29/96 04:45 EFFLUENT AND WASTE DISPOSAL REPORT GASEOUS EFFLUENTS FOR RELEASE POINT:

4 HOT MAINTENANCE SHOP CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4

3. PARTICULATES (CONTD)

BA140 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE141 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

PERIOD CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

(ABOVE) t h

f

+

r I

t

l i

II.

TABLES B.

SUMMARY

OF RADIOACTIVE LIQUID EFFLUENTS l

January 1, 1995 to December 31, 1995 i

1 i

I i

4 l

l

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:05 EFFLUENT AND WASTE DISPOSAL REPORT LIQUID EFFLUENTS -- SUMMATION OF ALL RELEASES

UNITS :

QUARTER QUARTER

EST.

TOTAL:

1 2

ERROR, A. FISSION AND ACTIVATION PRODUCTS
1. TOTAL RELEASE (EXCL.:

CI

0.366E-01 : 0.142E-01 : 0.628E+01 :

TRIT., GASES, ALPHA) :

2. AVERAGE DILUTED
UCI/ML : 0.122E-07 : 0.457E-08 :

CONC. DURING PERIOD :

3.

PERCENT OF

0.000E+00 : 0.000E+00 :

APPLICABLE LIMIT D. TRITIUM

1. TOTAL RELEASE CI
0.704E+01 : 0.300E+01 : 0.628E+01 :
2. AVERAGE DILUTED
UCI/ML : 0.235E-05 : 0.968E-06 :

CONC. DURING PERIOD :

3.

PERCENT OF-

0.000E+00 : 0.000E+00 :

APPLICABLE LIMIT C. DISSOLVED AND ENTRAINED GASES

1. TOTAL RELEASE CI
0.926E-02 : 0.323E-03 : 0.628E+01 :
2. AVERAGE DILUTED
UCI/ML : 0.309E-08 : 0.104E-09 :

CONC. DURING PERIOD :

3. PERCENT OF
0.149E-02 : 0.520E-04 :

APPLICABLE LIMIT D.

GROSS. ALPHA RADIOACTIVITY

1. TOTAL RELEASE CI
0.000E+00 : 0.000E+00 : 0.628E+01 :

E. VOLUME WASTE RELEASED : LITERS : 0.840E+07 : 0.397E+07 : 0.000E+00 :

(PRIOR TO DILUTION)

F. VOLUME DILUTION WATER : LITERS : 0.300E+10 : 0.310E+10 : 0.000E+00 :

USED DURING PERIOD l

PAGE 1 OF 5

SITE: LIMERICK UNIT: U1 & U2 i

DATE: 02/27/96 21:06 EFFLUENT AND WASTE DISPOSAL REPORT LIQUID EFFLUENTS FOR RELEASE POINT:

1 LIQUID RAD WASTE DISCHARGE TO SCHUYLKILL RIVER

?

I CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER l

RELEASED 1

2 1

2 l

H3 CI

0.000E+00 : 0.000E+00 : 0.704E+01 : 0.300E+01 :

C14 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I NA24 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

P32 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 CR51 CI
0.000E+00 : 0.000E+00 : 0.350E-02 : 0.826E-04 :

i MN54 CI

0.000E+00 : 0.000E+00 : 0.933E-02 : 0.723E-02 :

MN56 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

FESS CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

FE59 CI

0.000E+00 : 0.000E+00 : 0.136E-02 : 0.000E+00 :

C058 CI

0.000E+00 : 0.000E+00 : 0.228E-02 : 0.166E-03 :

CO60 CI

0.000E+00 : 0.000E+00 : 0.694E-02 : 0.181E-02 :

NI63 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

NI65 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CU64 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZN65 CI

0,000E+00 : 0.000E+00 : 0.109E-01 : 0.214E-02 :

ZN69 CI

0.200E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

BR83 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

BR84 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 BR85 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

PAGE 2 OF 5

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:06 EFFLUENT AND WASTE DISPOSAL REPORT l

l LIQUID EFFLUENTS FOR RELEASE POINT:

1 LIQUID RAD WASTE DISCHARGE TO SCHUYLKILL RIVER CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2 LIQUID EFFLUENTS (CONTD)

RB86 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

RB88 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

RB89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I SR89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.487E-05 :

SR91 CI

0.000E+00 : 0.000E+00 : r.000E+00 : 0.000E+00 :

SR92 CI

0.000E+00 : 0.000E+00 0.000E+00 : 0.000E+00 :

Y90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

Y91M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

Y91 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

Y92 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

Y93 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZR95 CI

0.000E+00 : 0.000E+00 : 0.693E-04 : 0.000E+00 :

ZR97 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

l NB95 CI

0.000E+00 : 0.000E+00 : 0.837E-04 : 0.000E+00 :

i l

MO99 CI

0.000E+00 : 0.000E+00 : 0.612E-05 : 0.000E+00 :

j TC99M CI

0.000E+00 : 0.000E+00 : 0.705E-05 : 0.000E+00 :

i TC101 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

3

PAGE 3 OF 5

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:06 EFFLUENT AND WASTE DISPOSAL REPORT LIQUID EFFLUENTS FOR RELEASE POINT:

1 LIQUID RAD WASTE DISCHARGE TO SCHUYLKILL RIVER CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2 LIQUID EFFLUENTS (CONTD)

RU103 CI

0.000E+00 : 0.000E+00 : 0.135E-03 : 0.000E+00 :

RU105 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

RU106 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

AG110M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE125M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE127M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE127 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE129M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE129 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE131M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE131 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE132 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I130 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i I131 CI

0.000E+00 : 0.000E+00 : 0.828E-04 : 0.592E-04 :

I132 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I133 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I134 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I135 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

PAGE 4 OF 5

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:06 EFFLUENT AND WASTE DISPOSAL REPORT LIQUID EFFLUENTS FOR RELEASE POINT:

1 LIQUID RAD WASTE DISCHARGE TO SCHUYLKILL RIVER CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2 LIQUID EFFLUENTS (CONTD)

CS134 CI

0.000E+00 : 0.000E+00 : 0.116E-03 : 0.409E-03 :

CS136 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i CS137 CI

0.000E+00 : 0.000E+00 : 0.157E-02 : 0.227E-02 :

CS138 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

BA139 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i BA140 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

BA141 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i BA142 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

i LA140 CI

0.000E+00 : 0.000E+00 : 0.117E-u3 : 0.000E+00 :

LA142 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE141 CI

0.000E+00 : 0.000E+00 : 0.924E-04 : 0.000E+00 :

CE143 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

PR143 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

PR144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ND147 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

AS76 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

W187 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000R+00 :

l 1

I --.

~...-..

l PAGE 5 OF 5

l SITE: LIMERICK UNIT: U1 & U2 DATE: 02/27/96 21:06 1

EFFLUENT AND WASTE DISPOSAL REPORT 4

l LIQUID EFFLUENTS FOR RELEASE POINT:

1 LIQUID RAD WASTE DISCHARGE TO SCHUYLKILL RIVER l

CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 1

2 1

2 l

LIQUID EFFLUENTS (CONTD) i hbbb bk I b$bbbb$bb $ b$bbbb bb $ b$bbbb bb $ b$bbbbAbb $

l TOTAL FOR :

PERIOD CI

0.000E+00 : 0.000E+00 : 0.803E+01 : 0.301E+01 :

1 (ABOVE)

XE-133 CI

0.000E+00 : 0.000E+00 : 0.192E-02 : 0.299E-03 :

XE-135 CI

0.000E+00 : 0 000E+00 : 0.734E-02 : 0.235E-04 :

i

)

i I

I i

i

._w

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:45 EFFLUENT AND WASTE DISPOSAL REPORT LIQUID EFFLUENTS -- SUMMATION OF ALL RELEASES

UNITS :

QUARTER QUARTER

EST.

TOTAL:

3 4

ERROR, A.

FISSION AND ACTIVATION PRODUCTS 1.

TOTAL RELEASE (EXCL.:

CI

0.986E-02 : 0.502E-01 : 0.628E+01 :

TRIT., GASES, ALPHA):

2. AVERAGE DILUTED
UCI/ML : 0.329E-08 : 0.162E-07 :

CONC. DURING PERIOD :

3.

PERCENT OF

0.000E+00 : 0.000E+00 :

APPLICABLE LIMIT l

l l

B. TRITIUM

1. TOTAL RELEASE CI
0.676E+01 : 0.545E+01 : 0.628E+01 :

2.

AVERAGE DILUTED

UCI/ML : 0.225E-05 : 0.176E-05 :

CONC. DURING PERIOD :

3.

PERCENT OF

0.000E+00 : 0.000E+00 :

i APPLICABLE LIMIT i

C. DISSOLVED AND ENTRAINED GASES 1.

TOTAL RELEASE CI

0.829E-01 : 0.203E-01 : 0.628E+01 :
2. AVERAGE DILUTED
UCI/ML : 0.280E-07 : 0.655E-08 :

CONC. DURING PERIOD :

3.

PERCENT OF

0.138E-03 : 0.328E-02 :

APPLICABLE LIMIT D. GROSS ALPHA RADIOACTIVITY 1.

TOTAL RELEASE CI

0.000E+00 : 0.000E+00 : 0.628E+01 :

E. VOLUME WASTE RELEASED : LITERS : 0.840E+07 : 0.397E+07 : 0.000E+00 :

(PRIOR TO DILUTION)

F. VOLUME DILUTION WATER : LITERS : 0.300E+10 : 0.310E+10 : 0.000E+00 :

USED DURING PERIOD

~~--e

E i

PAGE 1 OF 5

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:46 EFFLUENT AND WASTE DISPOSAL REPORT LIQUID EFFLUENTS FOR RELEASE POINT:

1 LIQUID RAD WASTE DISCHARGE TO SCHUYLKILL RIVER CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER l

RELEASED 3

4 3

4 H3 CI

0.000E+00 : 0.000E+00 : 0.676E+01 : 0.545E+01 :

C14 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

NA24 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

P32 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CR51 CI

0.000E+00 : 0.000E+00 : 0.110E-02 : 0.455E-02 :

MN54 CI

0.000E+00 : 0.000E+00 : 0.185E-02 : 0.293E-02 :

MN56 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

FESS CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.350E-01 :

FE59 CI

0.000E+00 : 0.000E+00 : 0.512E-04 : 0.000E+00 :

C058 CI

0.000E+00 : 0.000E+00 : 0.243E-03 : 0.215E-03 :

CO60 CI

0.000E+00 : 0.000E+00 : 0.110E-02 : 0.968E-03 :

NI63 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

NI65 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CU64 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZN65 CI

0.000E+00 : 0.000E+00 : 0.220E-02 : 0.295E-02 :

1 ZN69 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

BR83 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

BR84 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

BR85 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I i

i i

PAGE 2 OF 5

i i

SITE: LIMERICK UNIT: U1 E U2 i

i DATE: 02/29/96 04:46 EFFLUENT AND WASTE DISPOSAL REPORT LIQUID EFFLUENTS FOR RELEASE POINT:

1 LIQUID RAD WASTE DISCHARGE TO SCHUYLKILL RIVER CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4 LIQUID EFFLUENTS (CONTD)

RB86 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

RB88 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

RB89 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR89 CI

0.000E+00 : 0.000E+00 : 0.290E-03 : 0.000E+00 :

SR90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR91 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

SR92 CI

0.000E+00 : 0.000E+00 0.000E+00 : 0.000E+00 :

Y90 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

Y91M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

Y91 CI

0.000E+00 : 0.000E,00 : 0.000E+00 : 0.000E+00 :

Y92 CI

0.000E+00 : 0.000E+00 : 0.118E-03 : 0.000E+00 :

Y93 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZR95 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ZR97 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

NB95 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

1 MO99 CI

0.000E+00 : 0.000E+00 : 0.434E-04 : 0.121E-03 :

TC99M CI

0.000E+00 : 0.000E+00 : 0.442E-04 : 0.868E-04 :

TC101 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

l i

i PAGE 3 OF 5

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:46 EFFLUENT AND WASTE DISPOSAL REPORT LIQUID EFFLUENTS FOR RELEASE POINT:

1 LIQUID RAD WASTE DISCHARGE TO SCHUYLKILL RIVER CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4 LIQUID EFFLUENTS (CONTD)

I RU103 CI

0.000E+00 : 0.000E+00 : 0.184E-04 : 0.000E+00 :

RU105 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.538E-04 :

RU106 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

AG110M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE125M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE127M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I TE127 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE129M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I TE129 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE131M CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE131 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TE132 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

1130 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I131 CI

0.000E+00 : 0.000E+00 : 0.139E-03 : 0.227E-03 :

I132 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I133 CI

0.000E+00 : 0.000E+00 : 0.262E-04 : 0.731E-03 :

I134 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

I135 CI

0.000E+00 : 0.000E+00 : 0.000E+00 0.000E+00 :

1 4

PAGE 4 OF 5

SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:46 EFFLUENT AND WASTE DISPOSAL REPORT LIQUID EFFLUENTS FOR RELEASE POINT:

1 LIQUID RAD WASTE DISCHARGE TO SCHUYLKILL RIVER CONTINUOUS MODE BATCH MODE NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER RELEASED 3

4 3

4 LIQUID EFFLUENTS (CONTD)

CS134 CI

0.000E+00 : 0.000E+00 : 0.501E-03 : 0.883E-03 CS136 CI
0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CS137 CI

0.000E+00 : 0.000E+00 : 0.196E-03 : 0.105E-02 :

CS138 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

BA139 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

BA140 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

1 BA141 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

BA142 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

LA140 CI

0.000E+00 : 0.000E+00 : 0.437E-04 : 0.483E-04 :

LA142 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE141 CI

0.000E+00 : 0.000E+00 : 0.874E-04 : 0.432E-03 :

CE143 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

CE144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

PR143 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

PR144 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

ND147 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

AS76 CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

NP239 CI

0.000E+00 : 0.000E+00 : 0.488E-04 : 0.000E+00 :

..._m.___

i i

t PAGE 5 OF 5

i SITE: LIMERICK UNIT: U1 & U2 DATE: 02/29/96 04:46 F

EFFLUENT AND WASTE DISPOSAL REPORT i

i t

i t

LIQUID EFFLUENTS FOR RELEASE POINT:

1 LIQUID RAD WASTE DISCHARGE TO SCHUYLKILL RIVER CONTINUOUS MODE BATCH MODE i

t NUCLIDES

UNITS :

QUARTER QUARTER QUARTER QUARTER i

RELEASED 3

4 3

4 1

LIQUID EFFLUENTS (CONTD) i NONE CI

0.000E+00 : 0.000E+00 : 0.000E+00 : 0.000E+00 :

TOTAL FOR :

l PERIOD CI

0.000E+00 : 0.000E+00 : 0.684E+01 : 0.550E+01 :

(ABOVE) i XE-133 CI

0.000E+00 : 0.000E+00 : 0.635E-01 : 0.582E-02 :

i XE-135 CI

0.000E+00 : 0.000E+00 : 0.194E-01 : 0.145E-01 :

p

I e

l i

i t

i P

II.

TABLES t

E C.

SOLID WASTE DISPOSITION REPORT January 1, 1995 to December 31, 1995 l

I i

l Page 1 of 6 A.

SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (NOT IRRADIATED FUEL) 1/1/95 - 12/31/95 1

1.

T/PE OF WASTE UNIT 12-MONTH EST m

PERIOD ERROR %

a.

Spent resin, filter sludges, m(3) 1.78E + 2 25%

evaporator bottoms, etc.

Ci 1.88E+ 2 b.'

Dry compressible waste, m(3) 5.85E+ 1 25 %

contaminated equip., etc.

Ci 1.67E + 0 j

c.

Irradiated components, control NONE rods, etc.

j d.

Other (Describe)

NONE Activity is estimated i

i

Paga 2 of 6 2.

ESTIMATE OF MAJOR NUCLIDE COMPOSITION (BY WASTE TYPE)

CATEGORY A - SPENT RESINS, CATEGORY B - DRY FILTER SLUDGES, COMPRESSIBLE WASTE, EVAPORATOR BOTTOMS, ETC.

CONTAMINATED EQUIPMENT, ETC.

ISOTOPE WASTE PERCENT WASTE PERCENT WASTE PERCENT CLASS B ABUNDANCE CLASS A ABUNDANCE CLASS A ABUNDANCE CURIES CURIES CURIES Cr-51 0

0 1.95E + 0 2.48 3.70E-1 22.14 Mn-54 4.00E + 0 3.68 1.07E + 1 13.60 1.78E-1 10.65 Fe-55 0

0 1.96E + 0 2.49 4.60E-2 2.75 Co-58 0

0 1.48E-1 0.19 5.45E-2 3.26 Co-60 4.83E + 1 44.41 1.89E + 1 24.03 3.64E-1 21.78 Ni-63 4.53E-1

.42 7.89E + 0 10.03 1.40E-2 0.84 Zn-65 5.16E + 1 47.44 2.16E + 1 27.37 4.23E-1 25.31 H-3 2.27E + 0 2.09 1.34E-1 0.17 2.50E-2 1.50 C-14 2.16E-3 0

4.75E-1 0.60 6.00E-3 0.36 CS-134 0

0 1.35E + 0 1.72 1.70E-2 1.02 CS-137 1.73E + 0 1.59 9.28E + 0 11.80 4.30E-2 2.57 l-131 0

0 1.83E + 0 2.33 6.00E-3 0.36 Pu-238 1.32E-3 0

0 0

0 0

Pu-239/40 1.53E-3 0

0 0

0 0

Cm-242 1.64 E-4 0

6.00E-4 0

2.00E-4 0.02 Sr-90 4.05E-1 0.37 1.43E-1 0.18 8.00E-3 0.48 Sr-89 0

0 1.95E-1 0.25 4.00E-2 2.39 Fe-59 0

0 0

0 1.80E-2 1.08 Ba/La-140 0

0 1.76E + 0 2.24 2.26E-2 1.35 Cs-144 0

0 2.19E-1 2.28 0

0 Cs-141 0

0 1.10E-1 0.14 2.47E-2 1.48 Nb-95 0

0 0

0 3.00E-3 0.18 P-32 0

0 0

0 8.00E-3 0.48 TOTALS 1.09E + 2 100 7.86E + 1 100 1.67E + 0 100 Activity is estimated.

I I

t Page 3 of 6 CATEGORY A - 1 SHIPMENT > TYPE A LSA CATEGORY A - 31 SHIPMENTS TYPE A LSA CATEGORY B - 36 SHIPMENTS TYPE A LSA CATEGORY C - NO SHIPMENTS MADE CATEGORY D - NO SHIPMENTS MADE l

t i

)

i N

I i

)

Page 4 of 6 SOLID WASTE DISPOSITION NUMBER OF MODE OF DESTINATION i

SHIPMENTS MADE TRANSPORTATION 27 TRUCK LIMERICK TO BARNWELL 41 TRUCK SEG TO BARNWELL i

COMMENTS:

22 Shipments were made from Limerick to SEG for processing. No solidifications were performed.

i l

4

l I

Page 5 of 6 1

B.

IRRADIATED FUEL SHIPMENTS (DISPOSITION) l 1

i NUMBER OF SHIPMENTS MODE OF TRANSPORTATION DESTINATION O

N/A N/A PCP Chanaes l

The following is a brief summary of the one revision that was made to the Solid Radwaste Process Control Program.

Revision 1 to this document, RW-C-100, was effective 1/19/95.

o Step 1.1 was revised to clarify the purpose of the document.

The " Sources and References" section was revised to comply with the governing e

procedure writer's guide.

1 e

Step 2.1.4 was revised to correct the title of the UFSAR.

Step 2.1.11 was added to reference the SEG dewatering system, used to process e

spent ion exchange resin.

A note, associated with step 2.2.2 was formatted to comply with the applicable e

writer's guide.

e Step 2.2.10 was added to refer to the 50.59 Review associated with the SEG dewatering system.

Step 3.3 was revised to refer to the new title of the Nuclear Quality Assurance e

Department.

Step 3.4 was revised to indicate the title of the Manager-Radwaste.

e Steps 3.4.6,3.5,3.6, and 3.6.1, and 4.1 were revised for clarification.

Step 4.1 was revised to indicate the time frame for which vendor training records e

are to be maintained.

e Steps 4.3,4.5,5.1, and 5.5 were revised for clarification.

Section 7.1.1 was revised to indicate the use of precoatless elements.

Page 6 of 6 i

PCP Changes (cont'd)

Section 5 of step 7.1.1 was revised to incorporate off-site oil incineration.

e Steps 7.2.1(d), 7.2.2(d), and 7.2.3 were revised to address the appropriate 50.59 e

reviews for various systems.

Step 7.3.8 (2) was revised to indicate requirements associated with gas buildup in shipments.

Steps 7.4, 7.4.5, 7.5, 7.6.1, 7.6.2, 7.6.3, 7.8.2, and 8.2 were revised to address new titles for various documents and to provide minor clarifications.

j MAJOR CHANGES TO PLANT RADWASTE SYSTEMS There were no major changes to Plant Radwaste Systems.

l l

l l

HWM/jaj RWO96012 4

l t

l 1

II.

TABLES D.

OFFSITE RADIATION DOSE ASSESSMENT January 1, 1995 to.Decemoer 31, 1995 One (1) page is included in Table D.

=.

i i

SITE: LIMERICK i

UNIT: U1 & U2 DATE:'02/29/96 04:42

SUMMARY

OF MAXIMUM INDIVIDUAL DOSES TOTAL ACCUMULATION FOR PERIODS:

i LIQUID:

FROM 01/01/95 0:00 TO 12/31/95 23:00 GASEOUS: FROM 01/01/95 0:00 TO 12/31/95 23:00 i

AIR:

FROM 01/01/95 0:00 TO 12/31/95 23:00 APPLICABLE ESTIMATED AGE LOCATION

% OF LIMIT

' EFFLUENT ORGAN DOSE GROUP DIST DIR' APPLICABLE (MR)

(MREM)

(M) (TOWARD)

LIMIT i

LIQUID TOTAL BODY 1.07E-01 ADULT RECEPTOR 1 1.8E+00 6.0 LIQUID LIVER 1.72E-01 TEEN RECEPTOR 1 8.6E-01 20.0 NOBLE GAS AIR DOSE 1.91E-01 793. ENE 9.6E-01 20.0 (GAMMA-MRAD)

E WOBLE GAS AIR DOSE 2.45E-01 793. ENE 6.1E-01 40.0

(; BETA-MRAD) l NOBLE GAS T. BODY j

(GAMMA)

~

8.55E-02 ALL 965. ENE 4.3E-01 20.0 NOBLE GAS SKIN 1

(BETA)

I 2.25E-01 ALL 965. ENE 5.6E-01 40.0

)

IODINE +

THYROID 5.95E-03 CHILD 805. ESE 2.0E-02 30.0 PARTICULATES

SUMMARY

OF POPULATION DOSES TOTAL ACCUMULATION FOR PERIODS:

LIQUID:

FROM 01/01/95 0:00 TO 12/31/95 23:00 GASEOUS: FROM 01/01/95 0:00 TO 12/31/95 23:00 EFFLUENT APPLICABLE ESTIMATED ORGAN POPULATION DOSE (PERSON-REM)

LIQUID TOTAL BODY 1.6E+00 LIQUID THYROID 1.6E+00 GASEOUS TOTAL BODY 8.8E-01 GASEOUS.

THYROID 1.2E+00

II.

TABLES E.

RADIATION DOSES TO MEMBERS OF THE PUBLIC DUE TO THEIR ACTIVITIES INSIDE SITE BOUNDARY January 1, 1995 to December 31, 1995 Two (2) pages are included in Table E.

l TABLE II. E Page 1 of 2 RADIATION DOSES TO MEMBERS OF THE PUBLIC DUE TO THEIR ACTIVITIES INSIDE SITE BOUNDARY Per ODCM Control 3.6, the Annual Effluent Release' Report shall include an assessment of the radiation doses from radioactive liquid and gaseous effluents to members of the public due to their l

activities inside the Site Boundary during the report period.

Technical Specifications /ODCM Controls state that Members of the Public shall include all persons not occupationally associated with the plant.

This category does not include employees of the utility or contractors.

Also excluded from this category are persons who enter the site to service equipment or to make deliveries.

This category does include persons who use portions of the site for recreational, occupational education, or other purposes not associated with the plant.

The Limerick Information Center on Longview Road near the rear exit of the - plant, Frick's Lock Environmental Laboratory on the west shore of the river and the railroad tracks which run above the east shore of the Schuylkill River are all areas within the site boundary where radiation dose of this. type could occur.

The radiation doses to Members of the Public have been estimated using methodology stated in the ODCM.

The maximum gaseous dose to members of the public at these locations is based on the following assumptions:

1.

Real time meteorology and actual effluent releases.

2.

Beta air dose attributed to noble gas releases.

3.

Highest exposed sector of the railroad tracks (W), and the sectors enclosing Frick's Lock and the Information Center available for occupancy.

4.

The maximum expected occupancy factor is 25% of a working year in all locations.

l 5.

Distance to the railroad tracks, which pass through the Site i

Boundary in the W sector, is approximately 225 meters.

6.

Distance to the Limerick Information Center is approximately 884 meters in the ESE sector.

7.

Distance to Frick's Lock Environmental Laboratory is approximately 450 meters in the WSW sector.

1 A summary of gaseous radiation doses to members of the public at these locations is included in this Attachment.

l l

l.

i TABLE II.E Page 2 of 2 RADIATION DOSE TO MEMBERS OF PUBLIC WITHIN LIMERICK GENERATING STATION SITE BOUNDARY FOR AFFECTED SECTORS AND DISTANCES LOCATION SECTOR APPROX.

GAMMA AIR BETA AIR

' IODINE / PARTICULATE H3/ BETA-EMITTERS DISTANCE DOSE, MRAD DOSE, MRAD ORGAN ~ DOSE, MREM INGESTION DOSE, MREM (METERS)

FRICK'S LOCK WSW 450 1.20E-07 1.59E-07 1.92E+01 3.56E-02 IMFO. CENTER ESE 884 1.42E-07 1.87E-08 1.96E+01 3.58E-02 R.R.

TRACKS WSW 225 3.99E-07 5.28E-7 6.19E+01 1.09E-01

III. ATTACHMENTS A.

SUPPLEMENTAL INFORMATION Facility: Limerick Generating Station - Units 1 and 2 License : NPF-39 (Unit 1) and NPF-85 (Unit 2) 1.

Reculatory Litiits (Technical Soecification Limits)

A.

Noble Gases:

500 mrem /yr - total body

- " instantaneous" limits 1.

s 3000 mrem /yr - skin and ODCM Control 3.3.2 s

10 mrad - air gamma

- quarterly air dose limits 2.

s s 20 mrad - air beta and ODCM Control 3.3.3 i

20 mrad - air gamma

- yearly air dose limits 3.

s s 40 mrad - air beta and ODCM Control 3.3.3 B.

Iodines, tritium, carticulates with half life > 8 days:

1500 mrem /yr - any organ

- " instantaneous" limits 1.

s (inhalation path)

ODCM Control 3.3.2 2.

s 15 mrem - any organ

- quarterly dose limits ODCM Control 3.3.4 3.

s 30 mrem - any organ

- yearly dose limits ODCM Control 3.3.4 C.

Licuid Effluents:

1. Concentration s 10CFR20

" instantaneous" limits Appendix B, Table II, Col.2 ODCM Control 3.2.2 3 mrem - total body

- quarterly dose limits per 2.

s s 10 mrem - any organ ODCM Control 3.2.3 3.

s 6 mrem - total body

- yearly dose limits per s 20 mrem - any organ ODCM Control 3.2.3 2.

Maximum Permisuible Concentrations Per LGS ODCM Control 3.2.2, MPCs are not used to calculate permissible release rates and concentrations for gaseous releases. The MPCs specified in 10CFR20, Appendix B, Table II, Column 2

for identified nuclides are used to calculate permissible release rates and concentrations for liquid releases.

3.

Averace Enercy Based on gaseous effluent releases for the report period, average beta energy is 0.289 MeV and average gamma energy is 0.219 MeV.

4.

Measurements and Rooroximations of Total Radioactivity l

A.

Fission and Activation Gases i

The method used is the Canberra Series 90 Counting System; GS - Gas Marinelli.

B.

Iodine:

The method used is the Canberra Series 90 Counting System; CH - Charcoal Cartridge, j

.i C.

Particulate:

i The method used is the. Canberra Series 90 Counting System; l

PT - Air Particulate Sample, 47 mm filter, j

1 D.

Liould Effluents:

~

'The method used is the Canberra Series 90 Counting' System and the Radwaste Liquid Discharge Pre-Release Method with l

a 1.0 liter Marinelli.

S.

Batch Releases January 1995 - June 1995

]

A.

Lignid Ql-Q2 d

  1. of Batch Releases:

100 42 Total time period for batch releases, 6,888 2,809 Maximum time period for a batch release

  • 90 75 i

Average time period for batch release, 68.8 66.8 Minimum time period for a batch release, 50 60 Average stream flow (Schuylkill River) 8.90E+7.

3.89E+7 i

during periods of release of effluents into a flowing stream, gpm.

  • = Minutes B.

Gaseous Q1 Q2

  1. of Batch Releases:

0 0

Total time period for batch releases, 0

0 Maximum time period for a batch release, 0

0 l

Average time period for batch release, O

O e

Minimum time period for a batch release, 0

0 i

i

  • = Minutes l

._y

6.

Batch Releases July 1995 - December 1995 A.

Liauid Q3 Q1

  1. of Batch Releases:

82 59 Total time period for batch releases, 5,557 4,385 Maximum time period for a batch release

  • 89 9c Average time period for batch release, 67.7 74.3 Minimum time period for a batch release, 22 57 Average stream flow (Schuylkill River) 2.14E+7 7.01E+7 during periods of release of effluents into a flowing stream, gpm.
  • = Minutes B.

Gaseous Q1 Q1

  1. of Batch Releases:

0 0

Total time period for batch releases, 0

0 l

Maximum time period for a batch release, 0

0 Average time period for batch release, 0

0 Minimum time period for a batch release, 0

0

  • = Minutes 7.

Abnormal Releases A.

Licuid None B.

Gaseous None 8.

Description of LGS Effluent Release Points Release Point 1 = North Stack, Common Release Point 2 = South Stack, Unit 1 Release Point 3 = South Stack, Unit 2 1

Release Point 4 = Hot Maintenance Shop Release Point 5 = Auxiliary Boiler A Liquid Release Point LGS Liquid Radwaste Discharge

=

i

9.

Descriotion of LGS Licuid Dose Receptors 4

Receptor 1 = LGS Liquid Radwaste Discharge Point Receptor 2 = Citizens Home Water Company Receptor 3 = Phoenixville Water Company j

Receptor 4 Philadelphia Suburban Water Company

=

J Receptor 5 = City of Philadelphia Crew Course i

i i

1

)

i

l l

l III. ATTACHMENTS (continued)

B.

RADIATION MONITORS OUT-OF-SERVICE CONDITION On 08/04/95 at 16:03, the Unit 2 South Stack Effluent. Monitoring System Flow Rate Transmitter (FT-26-286) failed surveillance test ST-2-026-642-2 and was declared inoperable.

With the Flow Rate

Transmitter inoperable, ODCM Section 3.3_and Table I3.3-1 action statement 113 was entered.

This action states in part:

With _less than the _ minimum Required Channels

OPERABLE, effluent-releases via the NS, SS or HMS may continue for up to 30 days provided the flow rate is estimated by adding the normal flow rates indicated in P&ID M-26 for each in service fan.

This shall be documented in the MCR operations Shif t Log at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

Pursuant to the ACTION statement, the flow was estimated to be 234,000 scfm.

The Flow Rate Transmitter was replaced.

Delay in I

its replacement was due to difficulty in obtaining parts from the manufacturer.

The new transmitter was tested using ST-2-026-442-2 (Rad Gaseous Effluent Monitor - South Stack Effluent - Flow Rate-Monitor Calibration / Functional Test FT-26-286) tnd declared-operable on 10/10/95 at 14:32.

Operations continued to estimate stack flow and logged it every 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> during the entire inoperable status-time frame.

(08/04/95 16:03 - 10/10/95 14:32).

Releases recorded through the Unit 2 South Stack during this time period l

used the estimated flow of 234,000 scfm.

l l

l l

l

III. ATTACHMENTS (continued)

C.

REVISION TO PREVIOUS SUBMITTAL Composite particulate air samples, counted for beta and alpha l

emitters are submitted to an offsite vendor laboratory for analysis.

Data for the fourth quarter of 1994 was not available at the time Annual Ef fluent Release Report 20 (January 1, 1994 through i

December 31, 1994) was generated.

Report number 20 revisions are given below. These revisions include fourth quarter Alpha and Sr-89 results plus corrections due to data entry errors.

Doses for 1994 were not recalculated since they were conservatively reported.

(

Effluent and Waste Disposal Report 1

Gaseous Effluents -- Summation of All Releases C.

Particulates 4.

Gross Alpha Ci Quarter 1 Quarter 2 Quarter 3 Quarter 4 Radioactivity Reported 0.120E+01 0.139E+01 0.732E+01 0.437E+00 4.

Gross Alpha Ci Quarter 1 Quarter 2 Quarter 3 Quarter 4 Radioactivity Corrected 0.184E-7 0.00E00 0.274E-7 0.130E-7 i

Gaseous Effluents for Release Point:

1 North Stack 3.

Particulates l

Sr-89 Reported Ci Quarter 1 Quarter 2 Quarter 3 Quarter 4 0.231E+00 0.931E+02 0.000E+00 0.000E+00 Sr-89 Corrected Ci Quarter 1 Quarter 2 Quarter 3 Quarter 4 0.380E-4 0.457E-4 0.419E-4 0.318E-4 Gaseous Effluents for Release Point:

2 Unit 1 - South Stack 3.

Particulates Sr-89 Reported Ci Quarter 1 Quarter 2 Quarter 3 Quarter 4 0.000E+00 0.000E+00 0.000E+00 0.000E+00 Sr-89 Corrected Ci Quarter 1 Quarter 2 Quarter 3 Quarter 4 0.701E-6 0.101E-5 0.139E-5 0.161E-5 l

Gaseous Effluents for Release Point:

3 Unit 2 - South Stack 3.

Particulates i

Sr-89 Reported Ci Quarter 1 Quarter 2 Quarter 3 Quarter 4 0.000E+00 0.000E+00 0.000E+00 0.000E+00 Sr-89 Corrected Ci Quarter 1 Quarter 2 Quarter 2 Quarter 4 0.185E-5 0.851E-6 0.184E-5 0.272E-5 l

L