MONTHYEARML20206C9871999-04-27027 April 1999 NPDES Noncompliance Notification:On 990319,station Personnel Observed Foam Emanating from Manhole Vent Associated with Outfall 001,no Foam Was Observed on Any Waterway.Caused by Inappropriate Addition of Betz 3625 to Spray Pond ML20207D6171999-02-26026 February 1999 NPDES Noncompliance Notification:On 990111,discovered That Weelkly Analysis for non-oxidizing Biocide Betz 3625 Was Not Performed.Caused by Sample Being Inappropriately Delayed for Future Chemical Addition.Counseled Individuals Involved ML20202F0591999-01-19019 January 1999 NPDES Noncompliance Notification:On 990112,Auxiliary Boiler Source Number OAS502 Found to Have Malfunctioning Opacity Monitor.Caused by Stepdown Transformer within Power Supply. Power Supply Replaced ML20198J2811998-12-21021 December 1998 NPDES Noncompliance Notification:On 981102,release of 500 Gallons of 12% Sodium Hypochlorite to Environment Occurred. Caused by Failure of Tank Discharge Fittings.Integrity Testing Will Be Performed on All New Tanks.With ML20206R3491998-12-21021 December 1998 NPDES Noncompliance Notification:On 981102,500 Gallons of 12% Sodium Hypochlorite Released to Environ.Caused by Failure of Tank Discharge Fittings & Subsequent Leaks from Secondary Containment.Culvert Was Flushed Repeatedly ML20236V2001998-07-27027 July 1998 NPDES Noncompliance Notification:On 980619,geometric Mean Coliform Concentration Calculated to Be 223 Colonies Per 100 Ml.Sample Procedure Enhanced to Ensure Normal Operating Conditions ML20248C9461998-05-27027 May 1998 NPDES Noncompliance Notification:On 980414,total Iron Discharge Through Outfall 001 Exceeded Limits Set in Ltr Dtd 960508.Total Iron Discharge Limit Exceeded During Cleaning Evolution.Limit Revised ML20217N6921998-02-27027 February 1998 NPDES Noncompliance Notification:On 980107 Net Total Suspended Solids (TSS) for Units 1 & 2 Cooling Towers at Outfall 001 Exceeded NPDES Permit Daily Limit of 60 Ppm. Caused by Contaminated Sample Lines.Replaced Tygon Tubing ML20141G0271997-06-27027 June 1997 NPDES Noncompliance Notification:On 970512,sample for Kjeldahl Omitted Due to Personnel Error.Counseled Individual Responsible.On 970521,Net TSS Exceeded NPDES Daily Limit Due to Fouled Sample Tubing.Replaced Sample Tubing ML20137M5511997-03-27027 March 1997 NPDES Noncompliance Notification:On 970228,flow Integrator Used to Measure Spray Pond Effluent Flow Was Identified to Be Malfunctioning & Declared Inoperable Due to Lodged Debris.Revised Procedure for Spray Pond Effluent Flow ML20134G3241997-01-31031 January 1997 NPDES Noncompliance Notification:On 970108,util Informed NRC That PA Dept of Environ Protection Granted Approval for Temporary Discharge at Lgs,Per 961219 ML20138G9651996-12-24024 December 1996 NPDES Noncompliance Notification:On 960428,calibration of Flowmeter Used to Measure Spray Pond Flow Was Not Checked on Routine Basis Because Person Required to Develop Maint Was Unaware of Requirements.Installed New Meter ML20135A5851996-11-27027 November 1996 NPDES Noncompliance Notification:On July-Sept 1996 Re NPDES Limit for Fecal Coloform Concentration Not Met.Caused by Inadequate Gasket Installation.Ozonators Overhauled to Ensure Peak Performance ML20134E0641996-10-28028 October 1996 NPDES Noncompliance Notification:During Month of Sept 1996, NPDES Limit for Fecal Coliform Concentration at Discharge of Bradshaw Reservoir Pumps Was Not Met.Caused by Leaking Gaskets on Ozone Gas Diffusers.New Gaskets,Installed ML20129E5681996-09-27027 September 1996 NPDES Noncompliance Notification:On 960805,geometric Mean of Fecal Coliform Concentration Calculated to Be 641 Colonies Per 100 Ml.Cause Suspected to Be Due to Malfunctioning Ozone Disinfection Sys.Adjustments to Sys Have Been Made ML20129E5411996-09-26026 September 1996 NPDES Noncompliance Notification:On 960812,discharge Observed from Unit 2 Cooling Tower Overflow to Outfall 021. Caused by Personnel Error in Performing Required Analysis of Cooling Tower Overflow Sample.Individual Counseled ML20117G7071996-08-23023 August 1996 NPDES Noncompliance Notification:On 960715,geometric Mean of Fecal Coliform Concentration Exceeded NPDES Permit Limit. Caused by Leaking Seals on Ozone Diffusers.Temporary Adjustments Made to Ozone Gas Flow Balance ML20116B3851996-07-24024 July 1996 NPDES Noncompliance Notification:On 960602 Identified Ph Levels Exceeded NPDES Permit Limitations.Caused by Natural Biological activity.CO2 Injection Established,Maintained & Monitored Until 960612 ML20115G1151996-07-12012 July 1996 NPDES Noncompliance Notification:On 960619,resulting Net TSS Value 82.8 mg/1,exceeded Max Daily Limit of 60 Mg/L.Caused by Excessive Storm Water Runoff.Net TSS Revised ML20113C4451996-06-24024 June 1996 NPDES Noncompliance Notification:On 960318,flow Integrator Used to Measure Spray Pond Effluent Flow Declared Inoperable.Caused by Faulty Flow Integrator.Frequency of Use of Instrument Changed to Daily as Stated in Issue Number ML20108A3671996-04-28028 April 1996 NPDES Noncompliance Notification:On 960314,personnel Observed Sewage Overflowing from MH-07 & Into Storm Drain W-4.Caused by Blockage of Pipe Section Between MH-07 & MH-08.Sewer Contract Svc Pressure Cleaned ML20108A3801996-04-28028 April 1996 NPDES Noncompliance Notification:On 960223,identified Seven Issues of Administrative non-compliance/ambiguity W/Permits. Caused by Inadequate Administration.Individuals Gained Better Understanding W/Guidance ML20101K4661996-03-28028 March 1996 NPDES Noncompliance Notification:On 960218,discovered That No Records Existed for Bradshae Reservoir Discharge Water Temp for Listed Time Periods.Caused by Temporary Reassigment of Personnel.Review of Staffing in Progress ML20100P6311996-02-28028 February 1996 NPDES Noncompliance Notification:On 951108,discharge 001 Net TSS in Excess of Maximum Daily Limit.Caused by Flaw in Methodology to Calculate Net TSS concentration.Follow-up Composite Samples Taken ML20072R4601994-08-31031 August 1994 NPDES Noncompliance Notification:On 940708 & 0815,Discharge 001 Total Zinc Concentrations Exceeded Max Daily Limitations.Daily Zinc Trending Analysis Will Be Upgraded & Chemistry Technician Involved in 940815 Event Counselled ML20071L1761994-07-27027 July 1994 NPDES Noncompliance Notification:On 940609,zinc Analyses Indicated That Discharge 001 Total Zinc Levels in Excess of Max Daily Limitations in Both Cooling Towers.Daily Zinc Control Limits Will Be Administratively Maintained Lower ML20149E7291994-07-26026 July 1994 NPDES Discharge Monitoring Rept:On 940713,approx 18 Gallons of Betz Clamtrol CT-1 Inadvertently Released from Injection Sys Located South of LGS Spraypond Pumphouse.Caused by Break in Pump Discharge Line.Polyethylene Piping Replaced ML20065B9221994-03-25025 March 1994 NPDES Noncompliances Notification:On 940204,discharge 001 Maximum Daily Limit of 1.0 mg/1 Total Zinc Was Exceeded. Caused by Low Ph Transient in Unit 2 Cooling Tower Water Sys.Isolated Acid Injection Sys ML20064C7701994-02-25025 February 1994 NPDES Noncompliance Notification:On 940116 & 17 Manual Reactor Scram Occurred.Caused by Failure to Adequately Throttle Cooling Tower Bypass Valves.Procedure Revised ML20059C4941993-10-26026 October 1993 NPDES Noncompliance Notification:On 930907,cooling Tower Blowdown Water Discharged Into Possum Hollow Creek Due to Loss of Two of Four Operating Circulating Water Pumps. Procedures for Performing Excavations Revised ML20056G3921993-08-27027 August 1993 NPDES Noncompliance Notification:On 930710,13,14 & 25, Water Processing Facility (Wpf) Discharge Temp Exceeded Max Limitation of 74 Degrees F.Rev to NPDES Permit,Removing Temp Limits Approved & Wpf Chillers Removed from Svc ML20024H8441993-08-19019 August 1993 NPDES Noncompliance Notification Re Perkiomen Storage Tank Overflow to Possum Hollow Run.Application for Amend to Permit PA0051926 Submitted ML20046B8051993-07-29029 July 1993 NPDES Noncompliance Notification:On 930618,20 & 27,water Processing Facility Temp Exceeded Permitted Max Limitation of 74 Degrees F.Caused by Lack of Training & Written Instructions.Training Provided & Addl Instruction Issued ML20044G7641993-05-21021 May 1993 NPDES Noncompliance Notification:From 930417-18,equipment Problems Occurred Which Rendered Dissolved Oxygen & Ph Monitoring Instrumentation Inoperable.Caused by Debris in Sample Line.Methods for Filtering Flow Under Investigation ML20044C4051993-03-16016 March 1993 NPDES Noncompliance Notification:On 930222,discovered That Contractor Personnel Discharged Treated Water from Fire Hydrant Supplied by Unit 1 Cooling Tower Into Storm Water Drain E-3.2.Caused by Personnel Error.Label Applied ML20128N1251993-02-17017 February 1993 NPDES Noncompliance Notification:On 930103,cooling Tower Blowdown Water Overflowed from Discharge 001 Pipeline & Flowed Into Possum Hollow Creek.Caused by Failure to Throttle Unit 2 Bypass Valves.Procedure Changed ML20128A5071993-01-25025 January 1993 NPDES Noncompliance Notification:On 921117 & 25,analytical Results for inductively-coupled Plasma Analyzer at Discharge Point 001 Exceeded Zinc Concentration.Total Zinc Concentration Analysis Will Be Performed Onsite ML20126G9991992-12-24024 December 1992 NPDES Noncompliance Notification:On 921104,dissolved Oxygen Monitoring Equipment at Bradshaw Reservoir Discharge & Water Processing Facility Became Fouled by Organic Concentrations. Caused by Heavy Rainfall.Manual Samples Will Be Obtained ML20117A5761992-11-23023 November 1992 NPDES Noncompliance Notification:On 921013 & 14,four of Five Samples Collected from Discharge Point 001 Exceeded Daily Max Permit Limit of 1.0 Mg/L.Caused by Heavy Rains Across Southeastern PA on 921009.Injection Rates Decreased ML20101H5321992-06-26026 June 1992 NPDES Noncompliance Notification:On 920504,crack Discovered on Above Ground Cleanout for Sewage Line Leading from Plant Training Ctr to Plant Sewage Sys Holding Tanks.Caused by Expansion of Sewage Spill Line.Clamps Installed ML20095J1201992-04-23023 April 1992 NPDES Noncompliance Notification:On 920322,cooling Tower Blowdown Water Discharged Into Possum Hollow Creek.Caused by Procedure Deficiency.Sys Operating Procedure S09.4.A Expected to Be Revised by 920501 ML20141M0551992-03-25025 March 1992 NPDES Noncompliance Notification:On 920206,rain Water Pumped from Eletrical Manhole Into Storm Water Runoff Drain Due to Inadequate Procedural Guidance.Blue Drains to Be Labelled, Indicating Use for Storm Water Runoff Only by 920801 ML20091Q4301992-01-23023 January 1992 NPDES Noncompliance Notification:On 911218 Cooling Tower Blowdown Water Discharged to Possum Hollow Creek Resulting in Unpermitted Discharge Due to Failure to Identify & Revise All Appropriate Procedures.Procedure GP-3 to Be Revised ML20086E4981991-11-22022 November 1991 NPDES Noncompliance Notification:On 911016 Underground Fire Water Pipeline Inadvertently Punctured by Contractor Backhoe Ram During Excavation of Trench.Caused by Inadequate Review of Required Prints.Backhoe Ram Operator Terminated ML20082L9871991-08-28028 August 1991 NPDES Noncompliance Notification:On 910707 & 19,electrical Storm Caused Loss of Power to Bedminster Water Processing Facility & Tripped Chillers.On 910721,discharge Temp Exceeded Permitted Limits.Permit Limits Changed ML20217C2131991-07-0808 July 1991 NPDES Noncompliance Notification:On 910629,chillers at Bedminster Water Processing Facility for Bradshaw Reservoir Tripped Due to Unexpected Failure of Logic Control Unit. Chiller Control to Primary Computer Restored ML20077G5771991-06-20020 June 1991 NPDES Noncompliance Notification:On 910528,chiller C at Bedminster Water Processing Facility Tripped Due to High Vibration & Temp at Discharge 001 Exceeding Permitted Instantaneous Temp.Discharge Temp Setpoint Lowered ML20077D8701991-05-17017 May 1991 NPDES Noncompliance Notification:On 910512,cooling Tower Experienced Failure,Causing Large Vol of Cooling Tower Water to Bypass Normal Blowdown Discharge Pathway.Cooling Tower Will Be Inspected During mid-yr Outage ML20070S3071991-03-22022 March 1991 NPDES Noncompliance Notification:On 910204,discovered That Misalignment of Diverter Valve to Outfall 003 May Have Allowed Mixture of Storm Water & Steam Condensate to Be Released from Outfall.Valve Repositioned ML20065M6811990-11-29029 November 1990 NPDES Noncompliance Notification:On 901003,routine Weekly Discharge 001 Sample Exceeded Max Permit Limits for Grease & Oil.Sample Contained 43.7 Mg Per Liter of Oil & Grease. Abnormal Reading Believed to Be Caused by Oily Silt 1999-04-27
[Table view] Category:TEXT-ENVIRONMENTAL REPORTS
MONTHYEARML20206C9871999-04-27027 April 1999 NPDES Noncompliance Notification:On 990319,station Personnel Observed Foam Emanating from Manhole Vent Associated with Outfall 001,no Foam Was Observed on Any Waterway.Caused by Inappropriate Addition of Betz 3625 to Spray Pond ML20207D6171999-02-26026 February 1999 NPDES Noncompliance Notification:On 990111,discovered That Weelkly Analysis for non-oxidizing Biocide Betz 3625 Was Not Performed.Caused by Sample Being Inappropriately Delayed for Future Chemical Addition.Counseled Individuals Involved ML20202F0591999-01-19019 January 1999 NPDES Noncompliance Notification:On 990112,Auxiliary Boiler Source Number OAS502 Found to Have Malfunctioning Opacity Monitor.Caused by Stepdown Transformer within Power Supply. Power Supply Replaced ML20206E2161998-12-31031 December 1998 1998 Annual Environ Operating Rept (Non-Radiological) for Limerick Generating Station,Units 1 & 2 ML20205T0581998-12-31031 December 1998 Annual Radiological Environ Operating Rept 15 for 1998 ML20206R3491998-12-21021 December 1998 NPDES Noncompliance Notification:On 981102,500 Gallons of 12% Sodium Hypochlorite Released to Environ.Caused by Failure of Tank Discharge Fittings & Subsequent Leaks from Secondary Containment.Culvert Was Flushed Repeatedly ML20198J2811998-12-21021 December 1998 NPDES Noncompliance Notification:On 981102,release of 500 Gallons of 12% Sodium Hypochlorite to Environment Occurred. Caused by Failure of Tank Discharge Fittings.Integrity Testing Will Be Performed on All New Tanks.With ML20236V2001998-07-27027 July 1998 NPDES Noncompliance Notification:On 980619,geometric Mean Coliform Concentration Calculated to Be 223 Colonies Per 100 Ml.Sample Procedure Enhanced to Ensure Normal Operating Conditions ML20248C9461998-05-27027 May 1998 NPDES Noncompliance Notification:On 980414,total Iron Discharge Through Outfall 001 Exceeded Limits Set in Ltr Dtd 960508.Total Iron Discharge Limit Exceeded During Cleaning Evolution.Limit Revised ML20217N6921998-02-27027 February 1998 NPDES Noncompliance Notification:On 980107 Net Total Suspended Solids (TSS) for Units 1 & 2 Cooling Towers at Outfall 001 Exceeded NPDES Permit Daily Limit of 60 Ppm. Caused by Contaminated Sample Lines.Replaced Tygon Tubing ML20203H1911997-12-31031 December 1997 Annual Effluent Release Rept 23 for Jan-Dec 1997 ML20216F3371997-12-31031 December 1997 Annual Environmental Operating Rept (Non-Radiological) for 970101-1231 ML20203L5691997-12-31031 December 1997 Occupational Exposure Tabulation Rept for LGS Units 1 & 2 for 1997 ML20203H2201997-12-31031 December 1997 Tower 1 Joint Frequency Distributions of Wind Speed & Direction by Atmospheric Stability Class Rept 13 for 1997 ML20217P1941997-12-31031 December 1997 Annual Environ Operating Rept (Non-Radiological) for Jan-Dec 1997, for LGS Units 1 & 2 ML20217M6471997-12-31031 December 1997 Annual Radiological Environ Operating Rept 14,Jan-Dec 1997 for Limerick Generating Station,Units 1 & 2 ML20141G0271997-06-27027 June 1997 NPDES Noncompliance Notification:On 970512,sample for Kjeldahl Omitted Due to Personnel Error.Counseled Individual Responsible.On 970521,Net TSS Exceeded NPDES Daily Limit Due to Fouled Sample Tubing.Replaced Sample Tubing ML20137M5511997-03-27027 March 1997 NPDES Noncompliance Notification:On 970228,flow Integrator Used to Measure Spray Pond Effluent Flow Was Identified to Be Malfunctioning & Declared Inoperable Due to Lodged Debris.Revised Procedure for Spray Pond Effluent Flow ML20134G3241997-01-31031 January 1997 NPDES Noncompliance Notification:On 970108,util Informed NRC That PA Dept of Environ Protection Granted Approval for Temporary Discharge at Lgs,Per 961219 ML20135D0161996-12-31031 December 1996 Occupational Exposure Tabulation Rept for LGS Units 1 & 2 for 1996 ML20148B6671996-12-31031 December 1996 LGS Units 1 & 2 Annual Radiological Environ Operating Rept 13 for 960101-1231 ML20135C7691996-12-31031 December 1996 1996 Annual Effluent Release Rept No 22 ML20138J5291996-12-31031 December 1996 Annual Environ Operating Rept (Non-Radiological) for Jan- Dec 1996 ML20135C7731996-12-31031 December 1996 1996 Annual Tower No 1 Joint Frequency Distribution of Wind Speed & Direction by Atmospheric Stability Class Rept No 12 ML20138G9651996-12-24024 December 1996 NPDES Noncompliance Notification:On 960428,calibration of Flowmeter Used to Measure Spray Pond Flow Was Not Checked on Routine Basis Because Person Required to Develop Maint Was Unaware of Requirements.Installed New Meter ML20135A5851996-11-27027 November 1996 NPDES Noncompliance Notification:On July-Sept 1996 Re NPDES Limit for Fecal Coloform Concentration Not Met.Caused by Inadequate Gasket Installation.Ozonators Overhauled to Ensure Peak Performance ML20134E0641996-10-28028 October 1996 NPDES Noncompliance Notification:During Month of Sept 1996, NPDES Limit for Fecal Coliform Concentration at Discharge of Bradshaw Reservoir Pumps Was Not Met.Caused by Leaking Gaskets on Ozone Gas Diffusers.New Gaskets,Installed ML20129E5681996-09-27027 September 1996 NPDES Noncompliance Notification:On 960805,geometric Mean of Fecal Coliform Concentration Calculated to Be 641 Colonies Per 100 Ml.Cause Suspected to Be Due to Malfunctioning Ozone Disinfection Sys.Adjustments to Sys Have Been Made ML20129E5411996-09-26026 September 1996 NPDES Noncompliance Notification:On 960812,discharge Observed from Unit 2 Cooling Tower Overflow to Outfall 021. Caused by Personnel Error in Performing Required Analysis of Cooling Tower Overflow Sample.Individual Counseled ML20117G7071996-08-23023 August 1996 NPDES Noncompliance Notification:On 960715,geometric Mean of Fecal Coliform Concentration Exceeded NPDES Permit Limit. Caused by Leaking Seals on Ozone Diffusers.Temporary Adjustments Made to Ozone Gas Flow Balance ML20116B3851996-07-24024 July 1996 NPDES Noncompliance Notification:On 960602 Identified Ph Levels Exceeded NPDES Permit Limitations.Caused by Natural Biological activity.CO2 Injection Established,Maintained & Monitored Until 960612 ML20115G1151996-07-12012 July 1996 NPDES Noncompliance Notification:On 960619,resulting Net TSS Value 82.8 mg/1,exceeded Max Daily Limit of 60 Mg/L.Caused by Excessive Storm Water Runoff.Net TSS Revised ML20113C4451996-06-24024 June 1996 NPDES Noncompliance Notification:On 960318,flow Integrator Used to Measure Spray Pond Effluent Flow Declared Inoperable.Caused by Faulty Flow Integrator.Frequency of Use of Instrument Changed to Daily as Stated in Issue Number ML20108A3801996-04-28028 April 1996 NPDES Noncompliance Notification:On 960223,identified Seven Issues of Administrative non-compliance/ambiguity W/Permits. Caused by Inadequate Administration.Individuals Gained Better Understanding W/Guidance ML20108A3671996-04-28028 April 1996 NPDES Noncompliance Notification:On 960314,personnel Observed Sewage Overflowing from MH-07 & Into Storm Drain W-4.Caused by Blockage of Pipe Section Between MH-07 & MH-08.Sewer Contract Svc Pressure Cleaned ML20101K4661996-03-28028 March 1996 NPDES Noncompliance Notification:On 960218,discovered That No Records Existed for Bradshae Reservoir Discharge Water Temp for Listed Time Periods.Caused by Temporary Reassigment of Personnel.Review of Staffing in Progress ML20100P6311996-02-28028 February 1996 NPDES Noncompliance Notification:On 951108,discharge 001 Net TSS in Excess of Maximum Daily Limit.Caused by Flaw in Methodology to Calculate Net TSS concentration.Follow-up Composite Samples Taken ML20108C9281995-12-31031 December 1995 LGS Units 1 & 2 1995 Annual Environ Operating Rept (Non- Radiological) Jan-Dec 1995 ML20100L8861995-12-31031 December 1995 Annual Effluent Release Rept 21,Jan-Dec 1995 ML20108B7391995-12-31031 December 1995 Annual Radiological Environ Operating Rept 12 Jan-Dec 1995 ML20100L8961995-12-31031 December 1995 Tower 1 Joint Frequency Distributions of Wind Speed & Direction by Atmospheric Stability Class 1995 Rept 11 ML20080N1061994-12-31031 December 1994 Annual Effluent Release Rept 20 Jan-Dec 1994 PECO Energy LGS Units 1 & 2 ML20082N5061994-12-31031 December 1994 Annual Environ Operating Rept ML20087H7231994-12-31031 December 1994 Annual Radiological Environ Operating Rept 11 for Jan-Dec 1994 ML20080N1121994-12-31031 December 1994 Tower 1 Joint Frequency Distributions of Wind Speed & Direction by Atmospheric Stability Class 1994 Rept 10 ML20072R4601994-08-31031 August 1994 NPDES Noncompliance Notification:On 940708 & 0815,Discharge 001 Total Zinc Concentrations Exceeded Max Daily Limitations.Daily Zinc Trending Analysis Will Be Upgraded & Chemistry Technician Involved in 940815 Event Counselled ML20071L1761994-07-27027 July 1994 NPDES Noncompliance Notification:On 940609,zinc Analyses Indicated That Discharge 001 Total Zinc Levels in Excess of Max Daily Limitations in Both Cooling Towers.Daily Zinc Control Limits Will Be Administratively Maintained Lower ML20149E7291994-07-26026 July 1994 NPDES Discharge Monitoring Rept:On 940713,approx 18 Gallons of Betz Clamtrol CT-1 Inadvertently Released from Injection Sys Located South of LGS Spraypond Pumphouse.Caused by Break in Pump Discharge Line.Polyethylene Piping Replaced ML20065B9221994-03-25025 March 1994 NPDES Noncompliances Notification:On 940204,discharge 001 Maximum Daily Limit of 1.0 mg/1 Total Zinc Was Exceeded. Caused by Low Ph Transient in Unit 2 Cooling Tower Water Sys.Isolated Acid Injection Sys ML20064C7701994-02-25025 February 1994 NPDES Noncompliance Notification:On 940116 & 17 Manual Reactor Scram Occurred.Caused by Failure to Adequately Throttle Cooling Tower Bypass Valves.Procedure Revised 1999-04-27
[Table view] |
Text
- -
, ;. Cobart W. Coyce .
,- Plant Manager Limenck Generating Stanon
+
'PECO ENERGY n=~c-Limerick Generating Stanon PO Box 2MO Sanatoga PA 194&t 0920 215 3271200 Ext 2000 3
March 25, 1994 Robert Bauer, Jr.
Department of Environmental Resources Bureau of Water Quality Management Suite 6010, Lee Park 555 North Lane Conshohocken, PA 19428 .
SUBJECT:
Limerick Generating Station, Units 1 and 2 Two Noncompliances of NPDES Permit No. PA-0051926,
- 1. Discharge 001 Total Zinc Concentrations in Excess of Maximum Daily Limitations, and
- 2. Cooling Tower Water Discharge at Storm Water Outfall 021.
Dear Mr. Bauer:
Description of the Events:
On February 4, 1994, the Discharge 001 maximum daily limit of 1.0 mg/l total zinc was exceeded, since a value of 1.75 mg/l was present. This condition resulted from a low pH transient in the Unit 2 cooling tower water system.
Prior to the occurrence of the first noncompliance, as part of the Unit 1 refueling outage that started on February 4, 1994,.the Unit 1 cooling tower water was to be: pumped over to the Unit 2 cooling tower in lieu of makeup water from the river. This process would not only expedite draining, but also minimize the potential for overwhelming the blowdown line during-normal bottom' draining of the cooling, tower.
Since the Unit.1 cooling tower water was more concentrated than the river water, itsfuse in the Unit'2 cooling tower could have resulted:in a highly concentrated condition.
Therefore, adjustments to the water chemistry (i.e., the injection of-acid for pH control) for both cooling towers were being implemented in an attempt to avoid exceeding the permit limitations, and to prevent the fouling of plant systems.
Y
-9404040201 940325 ADOCK;O5000352 f- 'h-1 PDR _
9 PDR
.t March 25, 1994
. Page Two During the week of February 4, 1994, numerous actions were taken to adjust the water chemistry of the cooling towers.
Both cooling towers were deconcentrated, and scaling and corrosion inhibitor product additions were decreased, then-ceased-entirely. Throughout the week,_the Unit 2 circulating water system pH was also decreased towards a target value of 7.0. On February.3, 1994, prior to transferring water from the Unit I cooling tower to the Unit 2 cooling tower, the Unit 2 cooling tower pH was identified-to be 7.5, and therefore, the acid injection system addition rate was increased 10%. By approximately 0800 hours0.00926 days <br />0.222 hours <br />0.00132 weeks <br />3.044e-4 months <br /> on February 4, 1994, pH had unexpectedly dropped to 5.97. This low pH condition significantly increased the solubility of zinc that had been previously deposited in the plant systems. While the blowdown from the Unit 1 cooling tower provided sufficient buffering to maintain the pH limitations at Discharge 001, zine limitations were still exceeded.
Immediate corrective actions involved the isolation of the acid injection system, maintaining high cooling tower blowdown rates to minimize further concentration increase, and more frequent pH monitoring. Since zinc was not being added due to the outage preparations, no action was required in this regard. As of 2350 hours0.0272 days <br />0.653 hours <br />0.00389 weeks <br />8.94175e-4 months <br /> on February 5, 1994, the-total zinc concentration at Discharge 001 was 0.9 mg/1, and within the permit limitations.
On February 22, 1994, a second noncompliance occurred when cooling tower water was discharged via the storm water Outfall 021 instead of being released to Discharge 001. On February 21, 1994, Operations personnel discovered that rainwater flow was flooding the Unit 1 cooling tower chemical injection system building sump pump pit. This overwhelming rainwater flow resulted from a combination of the snow melting and the heavy rain precipitation. :Since the normal sump pump was out of service, a temporary pump was installed to discharge the rainwater to a nearby normal-waste water system manhole. Later, on February 21, 1994, Operations personnel discovered tnat the normal waste water system manhole had become blocked with debris, due to outage-activities being performed on the. Unit 1 cooling tower.
Operations personnel then notified. Chemistry personnel of the problem. An analysis _and inspection of the water collecting in the sump pump pit verified it:to be rainwater.
From this conclusion, Operations personnel were then given permission to discharge the rainwater collecting in the sump pump pit into the storm water drainage system. This action resulted in the rainwater being discharged to Outfall'021.
March 25, 1994
.. Page Three In a followup inspection on February 22, 1994, Operations -
personnel identified that the input flow to the sump pump pit had continued, despite'the fact that precipitation had stopped and outside ambient temperatures had dropped below freezing. Upon further inspection, Operations personnel discovered the input source to be a cracked service water (SW) system valve that had apparently frozen overnight.
Chemistry personnel were again notified and an analysis'and inspection of the water being discharged through Outfall 021-verified it to be free of oil sheen, and of typical chemistry make-up'for cooling tower water. By 2030 hours0.0235 days <br />0.564 hours <br />0.00336 weeks <br />7.72415e-4 months <br /> cn1 February 22, 1994, after additional. provisions were made, the temporary pump flow was routed to the Unit 1 cooling tower blowdown line, thereby terminating the discharge to Outfall 021.
Cange of the Noncompliance:
The primary cause of the first noncompliance was less than adequate monitoring of the Unit 2 circulating water system pH during the outage preparations. This was due in part to the lack of procedural guidance to ensure more frequent monitoring is performed as pH approaches 7.0. In addition, since the activity of pumping one Unit's cooling tower water to another cooling tower was relatively new, the chemistry related considerations were not fully addressed in a procedure.
A second cause of the first noncompliance was the lack of reliable automatic controls on the acid injection system.
While the system was recently modified to enable automatic operation (i.e., in response to a previous pH excursion and zinc violation), the equipment has been unreliable due to less than adequate cleaning and maintenance of the 431 probes. Therefore, the system was placed in manual operation prior to the occurrence of the second noncompliance. '
The primary cause of the second noncompliance was the i material failure of a SW system valve. Contributing causes were the obstructed normal waste system manhole, and the inappropriate action of directing this overflow to the storm water system and Outfall 021.
l i
i
~
, March 25, 1994
.. Page Four Prevention of Future Occurrencea:
To preclude the. recurrence of the firat event, Chemistry sampling and analysis procedures will be revised by May 1, >
1994, to require more frequent monitoring of the circulating water system pH when pH is less than 7.5, and the acid injection system is in the manual' mode of operation.
Additional procedural guidance will also be added to the cooling tower draining procedure prior to the next refueling outage, to address water chemistry considerations. To enable regular utilization of the automatic controls for the acid injection system, corrective maintenance will be performed to replace the pH probes, and a periodic. cleaning and maintenance program will be established by July 1, 1994.
In response to the second noncompliance, the defective SW system valve has been replaced, and measures have been initiated to correct the normal waste system obstruction.
As part of our NPDES permit renewal process, we have previously requested approval for periodic monitored releases of cooling tower water from Outfall 021, due to its ;
close proximity to both basins. Since this request.is still l being evaluated, a site wide communication will be provided' to reinforce with site' personnel the restrictions on discharges via storm water outfalls.
If you have any questions please contact Jim Kantner at 327-1200 extension 3400.
q Sincerely, !
htcG V
~
CGD/SCD:cah o Ld cc _
cc: U.S. Nuclear Regulatory Commission l Document Control-Desk
Docket Nos. 50-352/353 Washington, D.C. 20555 T. T. Martin Administrator, Region'I, USNRC
} Docket Nos. 50-352/353 N. S. Perry USNRC Senior Resident Inspector, LGS '
Docket Nos. 50-352/353
1 J*
,; a Program' Management Section (3WM52)
. . Permits Enforcement Branch Environmental Protection Agency Water Management Division Environmental Protection Agency Water Permits Section Region III 841 Chestnut Building Philadelphia, PA 19107 bec: D. R. Helwig - SMB1-1 K. S. Kemper - SSB2-1 L. A.'Hopkins - GML 5-1.
G. A. Hunger, Jr. - 62A-1 J. L. Kantner - SMB3-4 G. M. Morley, Jr. - N4-10 >
S. C. Dietch --SSB2-1 Commitment Coordinator -162A-1 PA DER BRP Inspector - SMB2-4 Correspondence Release Point - SMB1-2 4