L-03-027, January 2003 Monthly Operating Report for Beaver Valley Power Station

From kanterella
Revision as of 23:52, 23 March 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
January 2003 Monthly Operating Report for Beaver Valley Power Station
ML030560252
Person / Time
Site: Beaver Valley
Issue date: 02/07/2003
From: Bezilla M
FirstEnergy Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
GL-97-002, L-03-027
Download: ML030560252 (5)


Text

FENOC FIrtEnwgy =1lea1 O. ratgopa Beaver Valley Power Station P. O. Box 4 Shippingport,PA 15077 L-03-027 February 7, 2003 Beaver Valley Power Station Unit I - Docket No. 50-334, License No. DPR-66 Unit 2 - Docket No. 50-412, License No. NPF-73 Monthly Operating Report U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

In accordance with NRC Generic Letter 97-02, "Revised Contents of the Monthly Operating Report", and Unit 1 and 2 Technical Specification 6.9.4, the "Monthly Operating Report" is submitted for Unit 1 and Unit 2 for the month of January 2003.

Respectfully, M. B.Bezilla7 Vice-President DTJ/cmg Enclosures cc: NRC Regional Office King of Prussia, PA

UNIT SHUTDOWNS DOCKET NO. 50-334 UNIT NAME BVPS Unit #1 DATE February 3, 2003 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: January 2003 (1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Trip / Scram C - Refueling 3 - Automatic Trip / Scram D - Regulatory Restriction 4 - Continuation E - Operator Training / Ucense Examination 5 - Other (Explain)

F - Administrative G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output for the entire report period.

OPERATING DATA REPORT DOCKET NO.: 50-334 UNIT NAME: BVPS UNIT #1 REPORT DATE: 02/03/03 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962

"* Notes: Rated thermal power at

  • la. REPORTING PERIOD: JANUARY 2003 "* BVPS-I was uprated from 2652 MWt*

835

"* to 2689 MWt on 10/20/01. Net *

1. DESIGN ELECTRICAL RATING (Net MWe):

"*MDC was also uprated from *

-2.- 'MAX. DEPENDABLE-CAPACITY (Net MWe): 821

" B810_(We-to-821 MWe._

THIS MONTH YEAR TO DATE CUMULATIVE 3a. HOURS IN REPORTING PERIOD: 744.0 744.0 234528.0

3. NO. OF HRS. REACTOR WAS CRITICAL: 744.0 744.0 161335.5
4. SERVICE HOURS GENERATOR ON LINE: 744.0 744.0 158856.0
5. UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0
6. NET ELECTRICAL ENERGY GEN. (MWH): 624890.0 624890.0 119280897.0
7. GROSS ELECT. ENERGY GEN. (MWH): 661080.0 661080.0 127330670.0
8. GROSS THERMAL ENERGY GEN. (MWH): 1998176.0 1998176.0 392269485.5
9. (M): 100.0 100.0 69.2 UNIT AVAILABILITY FACTOR
10. UNIT CAPACITY FACTOR (MDC) (M:) 102.3 102.3 64.6
11. UNIT FORCED OUTAGE RATE (%): 0.0 0.0 15.6

UNIT SHUTDOWNS DOCKET NO. 50-412 UNIT NAME BVPS Unit #2 DATE February 3, 2003 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: January 2003 No. Date Type Duration Reason Method of Cause / Corrective Actions (Y/MID) F: Forced (Hours) (1) Shutting S: Scheduled Down (2) Comments NONE.

(1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Tnp / Scram C - Refueling 3 - Automatic Tnp / Scram D- Regulatory Restnction 4 - Continuation E - Operator Training / Ucense Examination 5 - Other (Explain)

F - Administrative G -Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output for the entire report period.

OPERATING DATA REPORT DOCKET NO.: 50-412 UNIT NAME: BVPS UNIT #2 REPORT DATE: 02/03/03 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962

  • Notes: Rated thermal power at
  • la. REPORTING PERIOD: JANUARY 2003
  • BVPS-2 was uprated from 2652 MWt*
  • to 2689 Mwt on 10/30/01. Net *
1. DESIGN ELECTRICAL RATING (Net MWe): 836
  • MDC was also uprated from *
  • _820-MWe to 831 MWe. *
2. MAX. DEPENDABLE CAPACITY-(Net MWe): 831 THIS MONTH YEAR TO DATE CUMULATIVE 3a. HOURS IN REPORTING PERIOD: 744.0 744.0 133311.0
3. NO. OF HERS . REACTOR WAS CRITICAL: 744.0 744.0 110299.1
4. SERVICE HOURS GENERATOR ON LINE: 744.0 744.0 109570.5
5. UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0
6. NET ELECTRICAL ENERGY GEN. (MWH): 631089.0 631089.0 85813492.0
7. GROSS ELECT. ENERGY GEN. (MWH): 662238.0 662238.0 90694283.0
8. GROSS THERMAL ENERGY GEN. (MWH): 1997888.0 1997888.0 276597499.0
9. UNIT AVAILABILITY FACTOR (M): 100.0 100.0 82.2
10. UNIT CAPACITY FACTOR (MDC) (M): 102.1 102.1 77.5 II. UNIT FORCED OUTAGE RATE (M): 0.0 0.0 9.7

Text

FENOC FIrtEnwgy =1lea1 O. ratgopa Beaver Valley Power Station P. O. Box 4 Shippingport,PA 15077 L-03-027 February 7, 2003 Beaver Valley Power Station Unit I - Docket No. 50-334, License No. DPR-66 Unit 2 - Docket No. 50-412, License No. NPF-73 Monthly Operating Report U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

In accordance with NRC Generic Letter 97-02, "Revised Contents of the Monthly Operating Report", and Unit 1 and 2 Technical Specification 6.9.4, the "Monthly Operating Report" is submitted for Unit 1 and Unit 2 for the month of January 2003.

Respectfully, M. B.Bezilla7 Vice-President DTJ/cmg Enclosures cc: NRC Regional Office King of Prussia, PA

UNIT SHUTDOWNS DOCKET NO. 50-334 UNIT NAME BVPS Unit #1 DATE February 3, 2003 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: January 2003 (1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Trip / Scram C - Refueling 3 - Automatic Trip / Scram D - Regulatory Restriction 4 - Continuation E - Operator Training / Ucense Examination 5 - Other (Explain)

F - Administrative G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output for the entire report period.

OPERATING DATA REPORT DOCKET NO.: 50-334 UNIT NAME: BVPS UNIT #1 REPORT DATE: 02/03/03 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962

"* Notes: Rated thermal power at

  • la. REPORTING PERIOD: JANUARY 2003 "* BVPS-I was uprated from 2652 MWt*

835

"* to 2689 MWt on 10/20/01. Net *

1. DESIGN ELECTRICAL RATING (Net MWe):

"*MDC was also uprated from *

-2.- 'MAX. DEPENDABLE-CAPACITY (Net MWe): 821

" B810_(We-to-821 MWe._

THIS MONTH YEAR TO DATE CUMULATIVE 3a. HOURS IN REPORTING PERIOD: 744.0 744.0 234528.0

3. NO. OF HRS. REACTOR WAS CRITICAL: 744.0 744.0 161335.5
4. SERVICE HOURS GENERATOR ON LINE: 744.0 744.0 158856.0
5. UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0
6. NET ELECTRICAL ENERGY GEN. (MWH): 624890.0 624890.0 119280897.0
7. GROSS ELECT. ENERGY GEN. (MWH): 661080.0 661080.0 127330670.0
8. GROSS THERMAL ENERGY GEN. (MWH): 1998176.0 1998176.0 392269485.5
9. (M): 100.0 100.0 69.2 UNIT AVAILABILITY FACTOR
10. UNIT CAPACITY FACTOR (MDC) (M:) 102.3 102.3 64.6
11. UNIT FORCED OUTAGE RATE (%): 0.0 0.0 15.6

UNIT SHUTDOWNS DOCKET NO. 50-412 UNIT NAME BVPS Unit #2 DATE February 3, 2003 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: January 2003 No. Date Type Duration Reason Method of Cause / Corrective Actions (Y/MID) F: Forced (Hours) (1) Shutting S: Scheduled Down (2) Comments NONE.

(1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Tnp / Scram C - Refueling 3 - Automatic Tnp / Scram D- Regulatory Restnction 4 - Continuation E - Operator Training / Ucense Examination 5 - Other (Explain)

F - Administrative G -Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output for the entire report period.

OPERATING DATA REPORT DOCKET NO.: 50-412 UNIT NAME: BVPS UNIT #2 REPORT DATE: 02/03/03 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962

  • Notes: Rated thermal power at
  • la. REPORTING PERIOD: JANUARY 2003
  • BVPS-2 was uprated from 2652 MWt*
  • to 2689 Mwt on 10/30/01. Net *
1. DESIGN ELECTRICAL RATING (Net MWe): 836
  • MDC was also uprated from *
  • _820-MWe to 831 MWe. *
2. MAX. DEPENDABLE CAPACITY-(Net MWe): 831 THIS MONTH YEAR TO DATE CUMULATIVE 3a. HOURS IN REPORTING PERIOD: 744.0 744.0 133311.0
3. NO. OF HERS . REACTOR WAS CRITICAL: 744.0 744.0 110299.1
4. SERVICE HOURS GENERATOR ON LINE: 744.0 744.0 109570.5
5. UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0
6. NET ELECTRICAL ENERGY GEN. (MWH): 631089.0 631089.0 85813492.0
7. GROSS ELECT. ENERGY GEN. (MWH): 662238.0 662238.0 90694283.0
8. GROSS THERMAL ENERGY GEN. (MWH): 1997888.0 1997888.0 276597499.0
9. UNIT AVAILABILITY FACTOR (M): 100.0 100.0 82.2
10. UNIT CAPACITY FACTOR (MDC) (M): 102.1 102.1 77.5 II. UNIT FORCED OUTAGE RATE (M): 0.0 0.0 9.7