License Amendment Request; Mode 3 Applicability - Lpci/Sdc; NRC Pre-Submittal Teleconference - March 7, 2017
ML17067A362
Person / Time
Site: Clinton Constellation icon.png
Issue date: 03/07/2017
From: Rankin J K
Plant Licensing Branch III
To: Bryan Hanson
Exelon Generation Co
Rankin J K
References
CAC MF9152
Download: ML17067A362 (8)


Text

Clinton Power StationLicense Amendment Request Mode 3 Applicability -LPCI/SDCNRC Pre-Submittal TeleconferenceMarch 7, 2017 1Agenda 1*Objective of Meeting

  • Background and Need for Amendment
  • Schedule 2Objective*Present information to the NRC staff describing a proposed License Amendment Request (LAR) for Clinton Power Station (CPS) to resolve a CDBI violation concerning incapability of the residual heat removal (RHR) design to support Technical Specification (TS) operability requirements.*Obtain feedback from the NRC staff on the proposed LAR and gain an understanding of the NRC staff's expectations for the content of a high quality submittal.*Answer any questions from the NRC staff regarding the proposed LAR.

3BackgroundDecember 2016 NRC CDBI Inspection

  • Green finding and associated Non-cited Violation (NCV) for failure to promptly identify that the incapability of the RHR design to support TS operability requirements was a condition adverse to quality.
  • CPS captured this issue in the Corrective Action Program (CAP) both prior to, and subsequent to the inspection. The planned corrective action, as documented in NRC Inspection Report 05000461/12016009, was to submit an LAR to align TS requirements with the design capabilities.

4Background (cont.)

CPS Design

  • TS 3.5.1 (1)requires all low pressure ECCS injection/spray systems to be OPERABLE in Modes 1, 2, and 3.
  • By design, the suppression pool suction valve on the ECCS Loop that is supporting SDC operations must be shut, otherwise the reactor coolant would drain to the suppression pool. The suppression pool suction valve does not automatically realign on a LPCI signal.
  • In addition, the suppression pool suction valve is not capable of opening for manual realignment, due to both water hammer and pressure locking/thermal binding concernswhich have not been analyzed above 150 °F.(1)TS 3.5.1, ECCS -Operating 5Background (cont.)

TS History

  • Prior to implementing NUREG-1434 Improved Tech Specs (ITS) in 1994, the CPS TS 3.5.1 recognized the required LPCI inoperability, and annotated Mode 3 applicability with a Note that stated
One LPCI subsystem of the RHR system may be aligned in the shutdown cooling mode when reactor vessel pressure is less than the LPCI cut-in permissive set point.

being realigned.

  • However, since the suppression pool suction valve is not capable of opening for manual realignment (i.e., as previously discussed), CPS is not able to implement the ITS Note, and therefore, declares LPCI inoperable during decay heat removal in Mode 3 with reactor pressure less than the cut-in permissive.
  • The current NRC interpretation of the ITS LCO and associated Note is that the systems are required to be OPERABLE, and failure to implement the Note (i.e., declaring LPCI inoperable) constitutes entry into the ACTIONS for operational convenience.

7Proposed Resolution

  • The NRC issued a similar Green Finding and associated NCV to LaSalle County Station (LSCS) in 2012. In response to that Finding/NCV, LSCS submitted, and the NRC approved an LAR in October 2015 that deleted this Note [ML15244B410].

8Schedule*Submit license amendment request on, or before 05-May-2017

  • Request review and approval in 12 months.