Informs That Util Successfully Completed Repairs of MDAFWP B on 940831.Pump Parameters as Documented in Post Maint Testing of MDAFWP B Provided in Encl.Nrc Approved Enforcement Discretion Not Required or Used
ML17263A827
Person / Time
Site: Ginna Constellation icon.png
Issue date: 08/31/1994
From: MECREDY R C
ROCHESTER GAS & ELECTRIC CORP.
To: MARTIN T T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML17263A826 List:
References
NUDOCS 9411030359
Download: ML17263A827 (2)


Text

i//!iirrrrrr/I/Iarrriilifr//////////i///lf/Ill/8ROCHESTERGASANDEIECTRICCORPORATION~89EASTAVENU@C1ROBERTCMECREOYVicePreridenrCinnaNuclearPioduclionAugust31,1994TELEPHONErriiEACOOEPie546-2TOOU.S.NuclearRegulatoryCommissionRegionalAdministrator,RegionIMr.ThomasT.Martin475AllendaleRoadKingofPrussia,PA19406

Subject:

RequestForEnforcementDiscretionR.E.GinnaNuclearPowerPlantDocketNo.50-244

Reference:

a.LetterfromR.C.Mecredy,RG&E,toT.T.Martin,NRC,

Subject:

"RequestForEnforcementDiscretion,"datedAugust30,1994.

DearMr.Martin,

Inaccordancewith10CFRPart2,AppendixC,andusingtheguidancecontainedinNRCInspectionManualPart9900,RG&EhadrequestedEnforcementDiscretiononAugust30,1994withrespecttoGinnaStationTechnicalSpecification3.4.2.1.a(Ref.a).MlsrequestwasacontingencyactionintheeventthatnecessaryrepairsandtestingofMotor-DrivenAuxiliaryFeedwater(MDAFW)PumpBcouldnotbecompletedwithinthesevendayLCOlimitwhichexpiredonAugust31,1994at0530hours.MerequestedEnforcementDiscretionwasverballyapprovedbytheNRCduringaphoneconversationbetweenMr.WilliamLazarusNRC,RegionI,andRobertMecredy,VicePresident,NuclearProductionatapproximately1720ESTonAugust30,1994.RG&EsuccessfullycompletedrepairsofMDAFWPumpBonAugust31,1994at0508hours.ThepumpparametersasdocumentedinthepostmaintenancetestingofMDAFWPumpBareprovidedinAttachmentA.Therefore,theLCOwasexitedbeforetheexpirationofthesevendayLCOlimitandtheNRCauthorized.EnforcementDiscretionwasnotrequiredorused.Verylyyours,cC'obertC.MecredXC:U.S.NuclearRegulatoryCommissionOfficeofNuclearReactorRegulationAssistantDirectorforRegionIReactorsMr.JoseA.CalvoWashington,D.C.20555GinnaStationSeniorResidentInspectorII94gi030359~4>02IPDRADDCK05000244PPDR ATTACHMENTA"B"MotorDrivenAuxiliaryFeedwaterPumpPerformanceDataPre-MajorMaintenanceTest:(DegradedCondition)TestDateDP(PSID)AcceptanceCriteria(PSID)Flow(GPM)Vibration(MilsDisp)8/26/941123.21125.5InbdOutbdVertVert.08'10.12.14InbdOutbdHorizHorizPost-MajorMaintenanceTest:(RepairCompleted)TestDateDP(PSID)AcceptanceCriteria(PSID)Flow(GPM)Vibration(MilsDisp)8/31/941224.41125.5200InbdOutbdInbdVertVertHoriz.08.08.07OutbdHoriz.09