Information Notice 2002-34, Failure of Safety-Related Circuit Breaker External Auxiliary Switches at Columbia Generating Station
| ML023300015 | |
| Person / Time | |
|---|---|
| Site: | Columbia |
| Issue date: | 11/25/2002 |
| From: | Beckner W NRC/NRR/DRIP/RORP |
| To: | |
| Hodge, CV, NRR/DRIP/RORP, (415-1861) | |
| References | |
| IN-02-034 | |
| Download: ML023300015 (7) | |
UNITED STATESNUCLEAR REGULATORY COMMISSIONOFFICE OF NUCLEAR REACTOR REGULATIONWASHINGTON, DC 20555-0001November 25, 2002NRC INFORMATION NOTICE 2002-34:FAILURE OF SAFETY-RELATED CIRCUITBREAKER EXTERNAL AUXILIARY SWITCHES
AT COLUMBIA GENERATING STATION
Addressees
All holders of operating licenses or construction permits for nuclear power reactors.
Purpose
The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice to informaddressees of failures of circuit breaker external auxiliary switches because of inadequate
maintenance of the associated switchgear. It is expected that recipients will review the
information for applicability to their facilities and consider actions, as appropriate, to avoid
similar problems. However, suggestions in this information notice are not NRC requirements;
therefore, no specific action or written response is required.
Description of Circumstances
On February 14, 2002, at the Columbia Generating Station, the licensee initiated a requiredplant shutdown because of a mechanical problem in an emergency diesel generator (EDG)
output circuit breaker. Although the breaker was capable of closing and connecting the EDG to
its safety bus, its cubicle-mounted auxiliary contacts, called mechanism-operated cell (MOC)
switches, failed to change state as designed. The licensee determined that the MOC switch
failures associated with this breaker and other breakers of this type resulted in failure of various
electrical distribution system control functions, including some non-safety loads not being
removed from the EDG bus following an accident signal.On June 29, 2001, during a refueling outage at the same plant, after breaker replacement, astandby service water pump breaker MOC switch failed to reposition during breaker closure.
This failure recurred on November 19, 2001. A MOC switch contact prevented the pump
discharge valve from opening after a pump start, rendering the service water system and
supported systems, such as EDGs, inoperable.
DiscussionThe licensee believes the failure was caused by excessive resistance in the linkage betweenthe breaker and the MOC switches. The licensee had not performed periodic maintenance on
this linkage in the breaker cell housing. Over time, dirt and dust accumulated and grease
hardened to increase the resistance in the linkage mechanism. During the preceding refueling outage, ending in July 2001, the licensee replaced 22 safety-related 4160-volt circuit breakers, exchanging older design Westinghouse Type DHP-350 (air- magnetic) breakers with newer design, Westinghouse-dedicated, Cutler Hammer Type
DHP-VR (vacuum replacement) breakers using Sure-Close
TM mechanisms to operate the MOCswitches. In the DHP-VR, the Sure-Close
TM mechanism operates the MOC switches independently of thebreaker's main contacts so that the MOC switches can be operated at a slower speed to avoid
excessive kinetic energy and wear. In addition, the external MOC switch linkage drag won't
stall the main contacts, even if the linkage is poorly maintained. However, because the design
of the Sure-Close
TM mechanism intentionally limits the force on the linkage, it does not havesufficient force margin to overcome the excessive drag of poorly maintained MOC switch
linkages (for an explanation of Sure-Close
TM operation, see "DHP -VR SURE CLOSEMechanism: A Kinematic System Solution for Medium Voltage Circuit Breaker MOC Auxiliaries
Operation," U. S. Patent 5,856,643, Ronald E. Vaill, available from Cutler-Hammer Nuclear
Programs).The Columbia Generating Station experience illustrates that the newer design breakers with theSure-Close
TM mechanisms operating the MOC switches depend more heavily on the state ofmaintenance of the linkage than do the older design breakers coupled directly to the MOC
switches. Older design breakers will eventually cause damage to poorly maintained MOC
switches and linkages. In severe cases, poorly maintained MOC switches and linkages could
stall the older design breaker main contacts with potentially serious results.This information notice requires no specific action or written response. If you have anyquestions about the information in this notice, please contact one of the technical contacts
listed below or the appropriate project manager from the NRC's Office of Nuclear Reactor
Regulation (NRR). /RA/William D. Beckner, Program Director
Operating Reactor Improvements Program
Division of Regulatory Improvement Programs
Office of Nuclear Reactor RegulationTechnical contacts:V. Hodge, NRRSteven Alexander, NRR301-415-1861301-415-2995 E-mail: cvh@nrc.govE-mail: sda@nrc.govAttachment: List of Recently Issued NRC Information Notices
ML023300015 DOCUMENT NAME: G:\RORP\OES\STAFF FOLDERS\Hodge\event reviews\col_brkr\21016 short col_brkr inf.wpdOFFICEOES:RORP:DRIPTech EditorIQMB:DIPMEEIB:DENAMECVHodgePKleene*SDAlexander*ASGillDATE11/07/200205/07200211/07/200211/19/2002OFFICEC:EEIB:DESC:RORP:DRIPPD:RORP:DRIPNAMEJACalvoTReisWDBecknerDATE11/20/200211/22/200211/25/2002
______________________________________________________________________________________OL = Operating License
CP = Construction PermitAttachment 1 LIST OF RECENTLY ISSUEDNRC INFORMATION NOTICES
_____________________________________________________________________________________InformationDate of
Notice No. SubjectIssuanceIssued to
_____________________________________________________________________________________2002-33Notification of PermanentInjunction Against Neutron
Products Incorporated of
Dickerson, Maryland11/21/2002All teletherapy and radiationprocessing licensees. 2002-29(Errata)Recent Design Problems in Safety Functions of Pneumatic
Systems11/06/2002All holders of operating licensesor construction permits for
nuclear power reactors.2002-32Electromigration onSemiconductor Integrated
Circuits10/31/2002All holders of operating licensesfor nuclear power reactors except
those who have ceased
operations and have certified that
fuel has been permanently
removed from the reactor vessel.2002-31Potentially Defective UF
6Cylinder Valves (1-inch)10/31/2002All licensees authorized topossess and use source material
and/or special nuclear material for
the heating, emptying, filling, or
shipping of uranium hexafluoride
(UF 6) in 30- and 48-inchcylinders.2002-30Control and Surveillance ofPortable Gauges During Field
Operations10/30/2002All NRC licensees authorized topossess, use, transport, and store
portable gauges.2002-29Recent Design Problems inSafety Functions of Pneumatic
Systems10/15/2002All holders of operating licensesor construction permits for
nuclear power reactors.2002-28Appointment of RadiationSafety Officers and Authorized
Users Under 10 CFR Part 3509/27/2002All medical licensees.Note:NRC generic communications may be received in electronic format shortly after they areissued by subscribing to the NRC listserver as follows:To subscribe send an e-mail to <listproc@nrc.gov >, no subject, and the followingcommand in the message portion:subscribe gc-nrr firstname lastname