UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555-0001 November 6, 2002 NRC INFORMATION NOTICE 2002-29 (ERRATA): RECENT DESIGN PROBLEMS IN
SAFETY FUNCTIONS OF PNEUMATIC
SYSTEMS
Addressees
All holders of operating licenses or construction permits for nuclear power reactors.
Discussion
A typographical error has been identified in Information Notice 2002-29, Recent Design
Problems in Safety Functions of Pneumatic Systems, issued on October 15, 2002. The Event
Notification number of the event report submitted by the San Onofre licensee is incorrectly
given as 36980; the correct number is 36960.
If you have any questions about this matter, contact the staff member listed below or the
appropriate Office of Nuclear Reactor Regulation (NRR) project manager.
/RA/
William D. Beckner, Program Director
Operating Reactor Improvements Program
Division of Regulatory Improvement Programs
Office of Nuclear Reactor Regulation
Technical contact: V. Hodge, NRR
301-415-1861 E-mail: cvh@nrc.gov
Attachment: List of Recently Issued NRC Information Notices
ML023110005
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555-0001 November 6, 2002 NRC INFORMATION NOTICE 2002-29 (ERRATA): RECENT DESIGN PROBLEMS IN
SAFETY FUNCTIONS OF PNEUMATIC
SYSTEMS
Addressees
All holders of operating licenses or construction permits for nuclear power reactors.
Discussion
A typographical error has been identified in Information Notice 2002-29, Recent Design
Problems in Safety Functions of Pneumatic Systems, issued on October 15, 2002. The Event
Notification number of the event report submitted by the San Onofre licensee is incorrectly
given as 36980; the correct number is 36960.
If you have any questions about this matter, contact the staff member listed below or the
appropriate Office of Nuclear Reactor Regulation (NRR) project manager.
/RA/
William D. Beckner, Program Director
Operating Reactor Improvements Program
Division of Regulatory Improvement Programs
Office of Nuclear Reactor Regulation
Technical contact: V. Hodge, NRR
301-415-1861 E-mail: cvh@nrc.gov
Attachment: List of Recently Issued NRC Information Notices
ML023110005 DISTRIBUTION:
ADAMS
IN File
DOCUMENT NAME: G:\RORP\OES\STAFF FOLDERS\Shapaker\1101-Hodge-errata-jws.wpd
OFFICE SC:EEIB:DE SC:RORP:DRIP PD:RORP:DRIP
NAME JWShapaker TReis WDBeckner
DATE 11/05/2002 11/ /2002 11/06/2002 OFFICIAL RECORD COPY
Attachment
IN 2002-29 (Errata) LIST OF RECENTLY ISSUED
NRC INFORMATION NOTICES
_____________________________________________________________________________________
Information Date of
Notice No. Subject Issuance Issued to
_____________________________________________________________________________________
2002-32 Electromigration on 10/31/2002 All holders of operating licenses
Semiconductor Integrated for nuclear power reactors except
Circuits those who have ceased
operations and have certified that
fuel has been permanently
removed from the reactor vessel.
2002-31 Potentially Defective UF6 10/31/2002 All licensees authorized to
Cylinder Valves (1-inch) possess and use source material
and/or special nuclear material for
the heating, emptying, filling, or
shipping of uranium hexafluoride
(UF6) in 30- and 48-inch
cylinders.
2002-30 Control and Surveillance of 10/30/2002 All NRC licensees authorized to
Portable Gauges During Field possess, use, transport, and store
Operations portable gauges.
2002-29 Recent Design Problems in 10/15/2002 All holders of operating licenses
Safety Functions of Pneumatic or construction permits for
Systems nuclear power reactors.
2002-28 Appointment of Radiation 09/27/2002 All medical licensees.
Safety Officers and Authorized
Users Under 10 CFR Part 35
2002-27 Recent Fires at Commercial 09/20/2002 All holders of operating licenses
Nuclear Power Plants in the for nuclear power reactors, United States except those who have
permanently ceased operations
and have certified that fuel has
been permanently removed from
the reactor.
Note: NRC generic communications may be received in electronic format shortly after they are
issued by subscribing to the NRC listserver as follows:
To subscribe send an e-mail to <listproc@nrc.gov >, no subject, and the following
command in the message portion:
subscribe gc-nrr firstname lastname
______________________________________________________________________________________
OL = Operating License
CP = Construction Permit
|
---|
|
list | - Information Notice 2002-01, Metal Clad Switchgear Failures and Consequent Losses of Offsite Power (8 January 2002, Topic: Emergency Lighting)
- Information Notice 2002-02, Recent Experience with Plugged Steam Generator Tubes (17 July 2002)
- Information Notice 2002-03, Highly Radioactive Particle Control Problems During Spent Fuel Pool Cleanout (10 January 2002, Topic: Significance Determination Process)
- Information Notice 2002-04, Wire Degradation at Breaker Cubicle Door Hinges (10 January 2002)
- Information Notice 2002-06, Design Vulnerability in BWR Reactor Vessel Level Instrumentation Backfill Modification (18 January 2002, Topic: Reactor Vessel Water Level)
- Information Notice 2002-07, Use of Sodium Hypochlorite for Cleaning Diesel Fuel Oil Supply Tanks (28 January 2002)
- Information Notice 2002-09, Potential for Top Nozzle Separation and Dropping of a Certain Type of Westinghouse Fuel Assembly (13 February 2002)
- Information Notice 2002-10, Manual Reactor Trip and Steam Generator Water Level Setpoint Uncertainties (28 June 2002, Topic: Safe Shutdown, Unanalyzed Condition)
- Information Notice 2002-11, Recent Experience with Degradation of Reactor Pressure Vessel Head (12 March 2002, Topic: Boric Acid, Pressure Boundary Leakage)
- Information Notice 2002-12, Submerged Safety-Related Electrical Cables (21 March 2002)
- Information Notice 2002-13, E-mail from H. Nieh, Oedo to A. Levin, Ocm, Et Al., Issuance of Information Notice 2002-13, Fwd: E-mail from D. Pickett T Davis-Besse Communication Plan (4 April 2002, Topic: Boric Acid)
- Information Notice 2002-14, Ensuring a Capability to Evacuate Individuals, Including Members of the Public, from the Owner-Controlled Area (8 April 2002)
- Information Notice 2002-15, Hydrogen Combustion Events in Foreign BWR Piping (12 April 2002)
- Information Notice 2002-17, Attachment: Recent Misadministrations Caused by Incorrect Calibrations of STRONTIUM-90 Eye Applicators (30 May 2002, Topic: Brachytherapy)
- Information Notice 2002-18, Effect of Adding Gas Into Water Storage Tanks on the Net Positive Suction Head for Pumps (6 June 2002, Topic: Brachytherapy)
- Information Notice 2002-19, Medical Misadministrations Caused by Failure to Properly Perform Tests on Dose Calibrators for Beta-and-Low-Energy Photon-Emitting Radionuclides (14 June 2002, Topic: Brachytherapy)
- Information Notice 2002-21, Axial Outside-Diameter Crackling Affecting Thermally Treated Alloy 600 Steam Generator Tubing (1 April 2003, Topic: Boric Acid)
- Information Notice 2002-22, Degraded Bearing Surfaces in Gm/Emd Emergency Diesel Generators (28 June 2002, Topic: Brachytherapy)
- Information Notice 2002-23, Unauthorized Administration of Byproduct Material for Medical Use (21 March 2006)
- Information Notice 2002-24, Potential Problems with Heat Collectors on Fire Protection Sprinklers (19 July 2002, Topic: Fire Protection Program, Brachytherapy)
- Information Notice 2002-25, Challenges to Licensees' Ability to Provide Prompt Public Notification and Information During An Emergency Preparedness Event (26 August 2002, Topic: Inadvertent Siren Activation)
- Information Notice 2002-25, Challenges to Licensees' Ability to Provide Prompt Public Notification and Information During an Emergency Preparedness Event (26 August 2002, Topic: Inadvertent Siren Activation)
- Information Notice 2002-26, Vermont Yankee July 2008 Evidentiary Hearing - Intervenor Exhibit NEC-JH 56, NRC Information Notice 2002-26, Supplement 2: Additional Flow-Induced Vibration Failures After a Recent Power Uprate (9 January 2004, Topic: Safe Shutdown)
- Information Notice 2002-27, Recent Fires at Commercial Nuclear Power Plants in the United States (20 September 2002, Topic: Safe Shutdown, Temporary Modification)
- Information Notice 2002-28, Appointment of Radiation Safety Officers and Authorized Users Under 10 CFR Part 35 (27 September 2002, Topic: Brachytherapy)
- Information Notice 2002-29, (Errata): Recent Design Problems in Safety Functions of Pneumatic Systems (6 November 2002)
- Information Notice 2002-30, Control and Surveillance of Portable Gauges During Field Operations (30 October 2002, Topic: Brachytherapy, Moisture Density Gauge, Moisture-Density Gauge, Stolen)
- Information Notice 2002-31, Potentially Defective UF6 Cylinder Valves (1-inch) (24 March 2003)
- Information Notice 2002-31, Potentially Defective Uf6 Cylinder Valves (1-inch) (24 March 2003)
- Information Notice 2002-32, Electromigration on Semiconductor Integrated Circuits (31 October 2002)
- Information Notice 2002-33, Notification of Permanent Injunction Against Neutron Products Incorporated of Dickerson, Maryland (22 November 2002, Topic: Uranium Hexafluoride)
- Information Notice 2002-34, Failure of Safety-Related Circuit Breaker External Auxiliary Switches at Columbia Generating Station (25 November 2002)
- Information Notice 2002-35, Changes to 10 CFR Parts 71 and 72 Quality Assurance Programs (20 December 2002)
- Information Notice 2002-36, Incomplete or Inaccurate Information Provided to the Licensee And/Or NRC by Any Contractor or Subcontractor Employees (27 December 2002)
|
---|