{{#Wiki_filter:APF 05-013-01, REV. 04
{{#Wiki_filter:}}
 
E-1F9905
 
FIRE HAZARD ANALYSIS
 
ENGINEERING REVIEW:
 
DigsigCert 3.5 1.75 DRAFTER:
 
CHECKER:
 
ENGINEER:
 
SUPERVISOR:
ELECTRONIC APPROVAL
: 1. APPROVED-MFG. MAY PROCEED
: 2. NOT APPROVED--RESUBMIT FINAL DOCUMENT/DRAWING-MFG. MAY PROCEED      YES      NO
: 3. APPROVED INFORMATION NOT CONTROLLED UNDER DESIGN PROCESS
: 4. ACCEPTABLE-MAINTAIN AS RECORD (INFO. ONLY)
: 5. RESTRICTED FOR WOLF CREEK PLANNING ONLY-MFG. MAY PROCEED      YES      NO APPROVAL OF THIS DOCUMENT/DRAWING DOES NOT RELIEVE SUPPLIER/CONTRACTOR FROM FULL COMPLIANCE WITH CONTRACT, SPECIFICATIONS AND/OR PURCHASE ORDER REQUIREMENTS.
COMMENTS:
REVISED ATTACHMENT A PAGES 1-13 FOR ADMIN. CHANGE OF AUTO. DETECTION NOTE REFERENCE.
P.O.#:                VENDOR MANUAL:
PAGE:
CHANGE PACKAGE #:    INCORPORATED CHANGE DOCUMENT(S):
020021                WIP-E-1F9905-008-A-1
 
REV. #                                                                          DC RELEASED:
DigsigDSR 3 0.50 12                                                                DC7 02/07/202
 
COMPONENT NUMBER(S)
 
COMPONENT NUMBERS ARE FOR INITIAL (REV, W01) DATA LINKING ONLY. ADDITIONAL COMPONENT LINKS ARE MADE IN DATABASE ONLY.
 
Page 1 of 275 Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Page 2 of 275 Fire Hazard Analysis
 
TABLE OF CONTENTS 1.0 PURPOSE 3 2.0                                                                                    SCOPE                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        3
 
==3.0 REFERENCES==
3 4.0                                                                                    FHA PROCESS                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  5 ATTACHMENT A        PLANT FIRE AREAS PROVIDED WITH A FHA                                                                                                                                                                                                                                                                                                                                                                                                            16 ATTACHMENT B        FIRE HAZARD ANALYSIS                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    30 ATTACHMENT C        NON-SAFETY RELATED SITE STRUCTURES                                                                                                                                                                                                                                                                                                                                                                                    274
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Page 3 of 275 Fire Hazard Analysis
 
1.0 PURPOSE
 
1.1                                                                                                          The purpose of the Fire Hazard Analysis (FHA) is to provide an evaluation of the effects of postulated fires within Wolf Creek Generating Station (WCGS). The overall intent of the FHA is to demonstrate that any single plant fire will not negatively affect post fire safe shutdown (PFSSD) capability, or result in a radiation release that exceeds 10 CFR Part 20 limits. The analysis was performed to demonstrate that WCGS comparison requirements to 10 CFR 50 Appendix R are satisfied.
 
1.2                                                                                                          This document supersedes the WCGS FHA that was historically maintained within Appendix 9.5B (Sections 9.5B.7 and 9.5B.8) of the USAR.
 
2.0 SCOPE
 
2.1                                                                                                            FHA for each plant Fire Area identified in Attachment  A. This includes all plant areas containing PFSSD equipment/circuits and non-safety plant areas that present a potential exposure hazard to areas containing PFSSD equipment/circuits due to proximity.
 
==3.0 REFERENCES==
 
3.1                                                                                                            BTP APCSB 9.5-1 Appendix A, Guidelines for Fire Protection for Nuclear Power Plants Docketed Prior to July 1, 1976  (USAR Appendix 9.5A)
 
3.2                                                                                                            10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior to January 1, 1979  (USAR Appendix 9.5E)
 
3.3                                                                                                            NRC Letter dated September 30, 1976 - Fire Protection Evaluation Wolf Creek Generating Station, Unit No. 1
 
3.4                                                                                                            NRC Letter dated October 21, 1981 - Appendix R of 10 CFR 50 Fire Protection Rule
 
3.5                                                                                                            NUREG-0881, Safety Evaluation Report Related to the Operation of Wolf Creek Generating Station Unit No. 1
 
3.6                                                                                                            NUREG/CR-4527, An Experimental Investigation of Internally Ignited Fires in Nuclear Power Plant Control Cabinets:  Part 1:  Cabinet Effects Tests
 
3.7                                                                                                            NUREG/CR-4527, An Experimental Investigation of Internally Ignited Fires in Nuclear Power Plant Control Cabinets:  Part 2:  Room Effects Tests
 
3.8                                                                                                            NUREG/CR-4596, Screening Tests of Representative Nuclear Power Plant Components Exposed to Secondary Environments Created by Fires, June 1986
 
3.9                                                                                                            NUREG/CR-6476, Circuit Bridging of Components By Smoke, October 1996
 
3.10                                                                                      Regulatory Guide 1.29, Seismic Design Classification
 
3.11                                                                                      Regulatory Guide 1.75, Physical Independence of Electric Systems
 
3.12                                                                                      SLNRC 82-046, Fire Protection Review, dated November 15, 1982 [SNUPPS Control Room Fire Hazards Analysis]
 
3.13                                                                                      SLNRC 84-109, Fire Protection Review, dated 8/23/1984 [Alternate Shutdown Response Plan]
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Page 4 of 275 Fire Hazard Analysis
 
3.14                                                                                      ASTM D 3286-1973, Standard Test Method for Gross Calorific Value of Coal and Coke by the Isoperibol Bomb Calorimeter
 
3.15                                                                                      ASTM E 84-1976, Standard Test Method for Surface Burning Characteristics of Building Materials
 
3.16                                                                                      ASTM E-119, Standard Test Methods for Fire Tests of Building Construction and Materials
 
3.17                                                                                      ASTM E-152, Standard Methods of Fire Tests of Door Assemblies
 
3.18                                                                                      UL-10B, Standard for Safety Fire Tests of Door Assemblies
 
3.19                                                                                      UL-555, Standard for Fire Dampers
 
3.20                                                                                      IEEE-383, Standard for Qualifying Class 1E Electric Cables and Field Splices for Nuclear Power Generating Stations
 
3.21                                                                                      IEEE-634, Standard for Cable Penetration Fire Stop Qualification Test
 
3.22                                                                                      DE88003808 (SAND87-2484C), Investigation of Smoke Corrosivity in Nuclear Power Plant Equipment
 
3.23                                                                                    M-663-00017A, Fire Protection Evaluations for Unique or Unbounded Fire Barrier Configurations
 
3.24                                                                                    AI 26A-003, Regulatory Evaluations (Other than 10 CFR 50.59)
 
3.25                                                                                    AP 10-106, Fire Preplans
 
3.26                                                                                    AP 15C-004, Preparation, Review, and Approval of Procedures, Instructions and Forms
 
3.27                                                                                    E-15000, Electrical Cable and Raceway List
 
3.28                                                                                    E-1F9900, Post Fire Safe Shutdown Manual Actions
 
3.29                                                                                    E-1F9910, Post Fire Safe Shutdown Fire Area Analysis
 
3.30                                                                                    XX-E-013, Post Fire Safe Shutdown Analysis
 
3.31                                                                                    XX-X-004, Combustible Loading Information Program
 
3.32                                                                                    Drawing Series A-1800, Fire Delineation
 
3.33                                                                                    Drawing Series M-12LF, P&IDs for Hot Machine Shop, Auxiliary, Radwaste, Fuel, Control, and Reactor Buildings Floor and Equipment Drain System
 
3.34                                                                                    Drawing Series M-12LE, P&IDs for Auxiliary Boiler Room, Turbine Building, Control Building, Diesel Generator Building, Tendon Access Gallery, and Auxiliary Feedwater Pump Rooms Oily Waste Drain System
 
3.35                                                                                    Drawing E-11013, Installation, Inspection and Testing Details for Electrical Equipment and Cable
 
3.36                                                                                    EPRI Technical Report TR-100370, Fire-Induced Vulnerability Evaluation (FIVE)
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Page 5 of 275 Fire Hazard Analysis
 
3.37                                                                                    PIR 2002-2246, Removal of Fire Protection Description from the USAR.
 
3.38                                                                                    KC-M-006, Water-Based Fire Protection System and Standpipe System Hydraulic Calculations
 
4.0 FHA PROCESS
 
4.1 General
 
4.1.1 Attachment A identifies the following:
 
x                                      All plant Fire Areas that are provided with a FHA.
 
x                                      Rooms within each Fire Area.
 
x                                      Rooms provided with automatic detection.
 
x                                      Rooms provided with automatic suppression.
 
x                                      Rooms that are within the Radiological Controlled Area (RCA) during normal operations.
 
x                                      Rooms containing PFSSD circuits.
 
4.1.2 Attachment B documents the FHA for each Fire Area identified in Attachment  A.
 
4.1.3 Attachment C identifies the Non-Safety Related Site Structures and their distance to the nearest structure containing PFSSD equipment and/or circuits.
These structures are remotely located from structures containing PFSSD equipment/circuits, and as such, a postulated fire within these structures does not pose a hazard to equipment and/or circuits required for PFSSD.
 
===4.2 Background===
 
4.2.1                                                                                                      The NRC originally requested that WCGS perform a fire hazard analysis for the facility in a {{letter dated|date=September 30, 1976|text=letter dated September 30, 1976}}. This letter also requested that a comparison to APCSB 9.5-1 Appendix A be provided. NRC {{letter dated|date=October 21, 1981|text=letter dated October 21, 1981}} requested that WCGS provide a comparison to 10 CFR 50 Appendix R. These requests were addressed via information provided within the following appendices of the SNUPPS Final Safety Analysis Report (FSAR) and WCGS Site Addendum:
 
x                                      Appendix 9.5A - Comparison to APCSB 9.5-1 Appendix A.
 
x                                      Appendix 9.5B - Fire Hazards Analysis.
 
x                                      Appendix 9.5E - Comparison to 10 CFR 50 Appendix R.
 
Additionally, a detailed report entitled SNUPPS Control Room Fire Hazard Analysis was submitted to the NRC by letter SLNRC 82-046. This report addressed transient fires originating between various panels in the Control Room.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Page 6 of 275 Fire Hazard Analysis
 
Subsequent to the above Control Room FHA report, the criteria for a Control Room fire was modified by the NRC. In response to these changes, a new detailed report entitled SNUPPS Response Plan for Immediate Evacuation of the Control Room Due to Fire was submitted to the NRC via SLNRC 84-0109.
 
NRC questions from the 1977-79 time frame concerning fire protection information within the FSAR and WCGS Site Addendum (including the SNUPPS/Wolf Creek responses to the questions) were documented within FSAR Appendices 9.5C and 9.5D. A future revision to the FHA will provide a reference to the current document addressing the issue of concern. This revision will occur in parallel with the release of the Fire Protection Program Manual, which is being developed in response to PIR 2002-2246.
 
Ultimately the FHA and other supporting fire protection within the SNUPPS FSAR and WCGS Site Addendum received NRC approval, as documented in Operating License Condition 2.C.(5)(a).
 
Wolf Creek has historically maintained facility fire protection information within what is now termed the Updated Safety Analysis Report (USAR), which is a consolidation of the SNUPPS FSAR and WCGS Site Addendum. Revisions have been incorporated as necessary to address plant changes, including enhancements to the original response plan provided in SLNRC 84-0109 for Control Room evacuation.In effort to eliminate repetitive information and provide a more efficient and consistent means to update and control fire protection program documents, the majority of USAR Appendix 9.5B is superseded by this document. The extent of USAR Appendix 9.5A, 9.5B, and 9.5E incorporation within this document is as follows:
 
x                                                                        Appendix 9.5A - Comparison to APCSB 9.5-1 Appendix A
 
Applicable elements of the comparison have been incorporated within this document. Specific paragraphs within this document that address an  APCSB 9.5-1 Appendix A comparison issue are provided with a parenthetical reference to APCSB 9.5-1 Appendix A, including the respective paragraph number addressed. The current  comparison provided in Appendix 9.5A of the USAR will remain active until release of the Fire Protection Program Manual,  which is being developed in response to  PIR 2002-2246.
 
x                                                                        Appendix 9.5B - Fire Hazards Analysis
 
The entire appendix was incorporated into this document with the exception of  the following:
 
                                              -                                            With limited exception, PFSSD analysis is documented in E-1F9910 with PFSSD supporting information provided by XX-E-013 and E-1F9900. PFSSD capability is specifically addressed within this document for Fire Areas KDB, RW, T-4, T-10, YARD-ESF, and YARD-SU, as these areas were not originally included in the USAR FHA.
 
                                              -                                            The evaluation of unique or unbounded fire barrier features, which is documented in M-663-00017A.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Page 7 of 275 Fire Hazard Analysis
 
FHA revision was provided where necessary to eliminate redundancy, provide clarification, or to strengthen the existing analysis.
 
x                                                                        Appendix 9.5E - Comparison to 10 CFR 50 Appendix R
 
Applicable elements of the comparison have been incorporated within this document. Specific paragraphs within this document that address an  Appendix R comparison issue are provided with a parenthetical reference to Appendix R, including the respective paragraph number addressed. The current  comparison provided in Appendix 9.5E of the USAR will remain active until release of the Fire Protection Program Manual, which is being developed in response to  PIR 2002-2246.
 
4.3 Methodology
 
4.3.1                                                                                                      For each Fire Area analyzed in Attachment  B, the topics identified in Sections 4.3.2 through 4.3.8 below, are addressed.
 
4.3.2                                                                                                      Fire Area Description
: 1.                                                        The Rooms within the Fire Area are identified.
 
4.3.3 Major Equipment
: 1.                                                        Major equipment within the Fire Area is identified.
 
4.3.4 Design Features
: 1.                                                        Fire boundary separation from other Fire Areas is discussed.
: a.                                                        Fire barrier features separating Fire Areas are 3-hour rated, unless otherwise indicated. Unique or unbounded fire barrier configurations are addressed in M-663-00017A.
: 2.                                                        Passive barrier features within the Fire Area are discussed, where applicable.
 
4.3.5 Combustible Loading
: 1.                                                        Significant fire hazards within the Fire Area are discussed, where applicable.
: 2.                                                        The cumulative fire hazard classification (Low, Moderate, or High) for the Fire Area is identified. This classification is based on the Room and Fire Area combustible loading tabulation maintained in calculation XX-X-004.
Unless indicated otherwise, the specific location of combustible material within a room is not a significant factor in the combustible loading analysis.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Page 8 of 275 Fire Hazard Analysis
 
The three combustible loading classifications are defined as follows:
 
x                                      LOW:                                                                                                                                                                                              < 100,000 Btu/ft2
 
x                                      MODERATE:                                                        > 100,000 Btu/ft2 and < 200,000 Btu/ft2
 
x                                      HIGH:                                                                                                                                                                                      > 200,000 Btu/ft2
 
Typical combustibles include Class A and Class B hazards. Class A hazards are ordinary combustible materials such as wood, paper, fabric, nylon, plastic, rubber, and cable insulation. Class B hazards are flammable and combustible liquids and gases such as cleaning solvent, diesel fuel oil, lube oil, oxygen, and acetylene.
 
A significant amount of fixed combustibles in the plant is electric cable insulation. The specific calorific value of each type and size of cable was used in calculating the maximum heat leading for each Fire Area.
 
Class A combustibles in closed metal containers located in general corridor areas of the plant may not be considered to contribute to the fuel load in that area. Their contribution is considered based on the adjacent combustible loads and the probability of a long duration fire.
 
Although fire hazard effects on exposed conduits have been evaluated for safe shutdown, electric cable inside metal conduit has not been considered as contributing to the fire loading in the hazard areas.
: 3.                                                        Combustible Control Zones that are administratively maintained to control transient combustibles in the separation area between redundant PFSSD components/circuits are discussed, where applicable.
: 4.                                                        In some instances cable chase fire loading is Moderate or High with an equivalent fire severity either near or exceeding three hours. This is the case due to the small floor area in relation to the combustibles presented by cable and postulated transient combustibles. Under normal situations, no ignition sources are present within cable chases, and introduction of a transient ignition source is administratively controlled. As previously identified, cable is IEEE-383 rated. Electric Power Research Institute (EPRI) technical report TR-100370, Fire-Induced Vulnerability Evaluation (FIVE), identifies that such cable is not typically considered a fire source initiator due to a low ignition frequency considering past nuclear power plant experience and fire tests. Based on this and the defense in depth fire protection features discussed in the applicable Fire Area analysis section, the development of a cable chase fire severity that would challenge fire barrier integrity is not considered credible.
: 5.                                                        Administrative controls are in place to limit the use and location of transient combustibles. Based on these limits, the maximum increased fire loading permitted in any fire area will not exceed the areas fire protection capabilities. Where transient combustibles exceed the amounts qualified in Calculation XX-X-004, additional administrative controls are implemented commensurate with the hazard.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Page 9 of 275 Fire Hazard Analysis
 
4.3.6 Fire Protection
: 1.                                                        Automatic detection features are discussed.
: a.                                                        Automatic fire and smoke detection systems are provided throughout the plant on the basis of the Attachment  B fire hazards analysis and consequences of specific postulated fires. Attachment A identifies the automatic detection protection arrangement for each room that is encompassed within the Attachment  B FHA. In each case the FHA considers the impact to safe shutdown where no or partial automatic detection is provided.
: 2.                                                          Automatic suppression features are discussed.
: a.                                                  Automatic suppression systems are provided in the plant on the basis of the Attachment B fire hazards analysis and consequences of specific postulated fires. Attachment  A identifies the automatic suppression protection arrangement for each room that is encompassed within the Attachment  B FHA. In each case the FHA considers the impact to safe shutdown where no or partial automatic suppression is provided.
: b.                                                  KC-M-006 calculates the fire water delivery system supply, sprinkler system demands, standpipe demands, and evaluates the overall hydraulic adequacy of the fire water suppression systems.
: 3.                                                          Typical fire alarm system annunciation is identified in Table  4.3.6.3.
: 4.                                                        Suppression equipment available in the area for manual fire fighting is discussed.
: 5.                                                        Fire Area accessibility is discussed.
: 6.                                                        Fire water drainage is discussed.
: a.                    All areas of the plant protected with water suppression systems have sufficient drainage capacity to prevent the run-off of water into other Fire Areas such that it would affect equipment operability. All drains throughout the plant drain to their respective building sumps, from there, sump pumps transfer the water to the radwaste system.
: b.                    The method by which sprinkler systems control fire is termed fire control approach. This method anticipates that a certain number of sprinklers will be opened surrounding the fire event area. All sprinkler heads installed in a given Fire Area will not open for a given fire event.
Table 16.3.1 from the NFPA Handbook (20th Edition) reveals that the majority of fires are suppressed by a small number of sprinkler heads (10 or less). Additionally, hose stream application for a fire event would be controlled and of a short duration.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 10 of 275 Fire Hazard Analysis
 
Table 4.3.6.3, Typical Fire Alarm System Annunciation System Type and Condition                                                                                                                                                                                                                                                                                              Local                                                                                                                                                      Control Room General Area Detection General area detection or manual pull                                                                                                                                                                                                                                                                                              X                                                                                                                                                                                    X station activated                                                                                                                                                                                                                Area notification appliance(s)
Detector trouble or circuit fault                                                                                                                                                                                                                                                                                                                                                                                                                                                            None                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            X Automatic Wet Pipe Sprinkler System discharge                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                X X Notification appliance controlled at local junction box.
Pressure switch circuit fault                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                None                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            X Automatic Preaction Sprinkler Detection activated                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  X X System discharge (automatic)                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              X Notification appliance controlled by release panel, which is activated concurrent with system discharge System discharge (manual/pneumatic) None      X Low supervisory air pressure                                                                                                                                                                                                                                                                                                                                                                                                                                                                                None                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            X General trouble condition                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          None                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            X Automatic Water Spray Sprinkler (Single Zoned Detection)
Detection activated                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          X X System discharge (automatic)                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              X Notification appliance controlled by release panel, which is activated concurrent with system discharge System discharge (manual/pneumatic) None      X General trouble condition                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            None                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            X Automatic Water Spray Sprinkler (Crossed Zoned Detection) 1st zone detector activated                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              X X Notification appliance controlled by release panel 2nd zone detector activated                                                                                                                                                                                                                                            Notification appliance already                                                                                                                                                                                                                  X activated by 1st detector in alarm System discharge (automatic) None X System discharge (manual/pneumatic) None      X General trouble condition                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            None                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            X Automatic Halon Suppression (Crossed Zoned Detection) 1st zone detector activated                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              X X Area notification appliance 2nd zone detector activated                                                                                                                                                                                                                                            Notification appliance already                                                                                                                                                                                                                  X activated by 1st detector in alarm System discharge (automatic)                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                X X Notification appliance controlled by release panel System discharge (manual/pneumatic)                                                                                                                                                                                                                                                                                                                                                    X                                                                                                                                X Notification appliance controlled by release panel HVAC isolation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            None                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            X Visual General trouble condition                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          X                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            X Fire Water Valve Supervision Fire Water system isolation valve out of                                                                                                                                                                                                                                                                                None X normal position Circuit fault                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          None                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            X Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 11 of 275 Fire Hazard Analysis
 
4.3.7                                                                                                      Isolation and Smoke Removal
: 1.                                                        A description of fire isolation is provided.
: 2. AP 10-106, Fire Preplans, identifies fixed HVAC supply and exhaust fans servicing each Fire Area. Smoke removal tactics are dependent on several variables and fire ground conditions including wind patterns, fire intensity, smoke dispersion rate, location of the fire within the Fire Area, location of redundant PFSSD equipment, availability of normal exhaust, and power supply availability for portable ventilation. Therefore, it is not considered feasible to discuss each potential ventilation scenario within a given Fire Area. Portable ventilation strategies and tactics are addressed by the Fire Brigade training program.
 
NUREG/CR-4596 demonstrates that exposure to the corrosive products of a smoke environment can result in equipment damage. Therefore, the potential to expose redundant PFSSD equipment to a smoke environment is an important consideration during smoke control and removal activities.
However, corrosion from a secondary smoke environment is not expected to be a factor that impacts immediate PFSSD capability. This is substantiated by DE88003808 (SAND87-2484C), which identifies that corrosion from a smoke environment is an event that presents a problem on a time scale of days or even weeks. Additionally, NUREG/CR-6476 identifies that the most important fire scenarios from a plant risk perspective occur during time frames of roughly one hour or less. Thus, the issue of longer term exposures are more important to the question of general post-fire equipment reliability, which is ultimately a secondary concern to that of achieving initial safe shutdown.
 
4.3.8 Analysis
: 1. Fire Suppression
: a.                                                  A discussion of the fire suppression systems (fixed and manual) use and effectiveness in extinguishing a fire is provided.
: 2.                                                        Safe Shutdown Capability
: a.                                                  The safe shutdown design basis is the cold shutdown operational mode. If a fire hazard within the plant necessitates the plant being placed in a safe condition, the reactor will first be taken to a hot shutdown condition. An extended hot shutdown condition prior to achieving cold shutdown in order to perform repairs or temporary routings, if required, is a stable, safe condition.
: b.                                                  USAR Section 7.4 describes in detail how safe shutdown can be performed with safety related equipment, and provides a discussion of component redundancies and system diversity for achieving the safe shutdown functions. System and component redundancy for the various support and auxiliary systems is provided in the associated USAR section.
: c.                                                    The fuel storage pool cooling system components are listed as being required for safe shutdown for the fire hazards analysis of the Fuel Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 12 of 275 Fire Hazard Analysis
 
Building. However, they are neither required for safe shutdown nor are they associated circuits as defined in10 CFR 50 Appendix R, Section III.G. They have been included to ensure that repairs are not required for fires in the Fuel Building. Fuel storage pool cooling system component failures resulting from fires in the Auxiliary and Control Buildings are not evaluated in the FHA or E-1F9910.
: d.                                                  Associated circuits were reviewed as if they were redundant safe shutdown items.
: e.                                                  The determination of safe shutdown capability following a fire is based on the PFSSD Fire Area analysis documented in E-1F9910 and the PFSSD manual action feasibility analysis documented in E-1F9900, coupled with the FHA evaluation addressing fire hazards, fire protection features, and suppression capability. PFSSD capability is satisfied when analysis demonstrates that Wolf Creeks comparison response to 10 CFR 50 Appendix R, Section III.G is met.
 
4.4 Assumptions
 
4.4.1                                                                                                      The following assumptions were made in accordance with 10 CFR 50 Appendix R, to define the plant conditions for analysis purposes:
: 1.                                                        Only one fire is postulated to occur at any one time. Multiple fires are not postulated.
: 2.                                                        A design basis accident occurring simultaneously with a fire hazard is not assumed.
: 3.                                                        Extreme environmental phenomena, i.e., earthquake, flood, tornado, etc.,
occurring simultaneously with fire hazard are not assumed.
: 4.                                                        Failure of plant systems and components required for safe shutdown is not postulated unless that equipment is exposed to the fire. Wolf Creeks comparison response to Section III.G.2 of Appendix R is considered to provide an acceptable means to protect redundant safe shutdown equipment. Random single failures are not postulated in safe shutdown systems; only fire-related failures are evaluated. It should be noted that where automatic fire suppression systems are installed, the fire hazards analysis evaluates the effects of a failure of the automatic systems.
: 5.                                                        Loss of offsite power (LOSP) is assumed to occur simultaneously with the fire unless the area has been specifically evaluated to show that a LOSP could not occur as a result of the fire. For alternate shutdown, a LOSP is considered a simultaneous event. Failure of any of the onsite vital power supplies is not assumed unless it is caused as a direct consequence of a fire. Calculation XX-E-013 identifies the Fire Areas were LOSP due to fire is possible.
: 6.                                                        Refer to XX-E-013 and E-1F9910 for additional assumptions that are specific to the PFSSD analysis.
 
4.5                                                                                                          Fire Effects on Electrical Equipment and Safe Shutdown Information Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 13 of 275 Fire Hazard Analysis
 
4.5.1                                                                                                      The following discussions provide information on the WCGS plant design and nomenclature, the assumed effects of fire, and the response of certain devices.
: 1.                                                        Redundant PFSSD mechanical systems are referred to in the analysis as Train A and Train B. Train A is served by electrical separation groups 1 and 3, while Train B is served by electrical separation groups 2 and 4.
Electrical separation groups 5 and 6 are typically for non-safety related equipment. However, in limited cases these groups also provide a PFSSD success path.
: 2.                                                        The FHA and supporting documents XX-E-013 and E-1F9910 include the effects of a postulated fire hazard on PFSSD cables, exposed conduit and instrumentation. Embedded conduits are not considered due to the heat sink provided by the encasing barrier. Section 8.3.1.4 of the USAR provides the basis and criteria for the interdependence of redundant systems.
: 3.                                                        If a fire is postulated to cause a short in a circuit and that circuit is protected by an individual overcurrent protection device, that device is assumed to function to clear the fault without further degradation of the power source.
: 4.                                                        Separation of the devices for nuclear safety-related controls and instrumentation is achieved by physical separation, use of fire-resistive cable or barriers between separation groups for the same protective function, in accordance with Regulatory Guide 1.75.
 
4.6                                                                                                          General Information on Design Features
 
4.6.1                                                                                                      Redundant equipment and circuits required for safe shutdown are also protected against the effects of potential exposure fires. These protection features include fixed fire detection and suppression systems, fire barriers, control of combustibles, use of fire-resistive cable, and physical separation. The design goal for safety-related areas outside of the Containment was to provide the equivalent of a 3-hour rated fire barrier between redundant trains, as described in 10 CFR 50, Appendix R, Paragraph III.G.2.a. Where this was not possible, credit was taken for the detection and suppression systems installed in the plant, the use of fire-resistive cable, and compliance to the provisions of Appendix R, Paragraphs III.G.2.b and c, was addressed.
 
4.6.2                                                                                                      In most fire areas, the boundaries are defined by walls, floors, and ceilings. In the Reactor Building, however, such natural boundaries do not completely enclose localized fire hazards. For the Fire Areas inside of the Containment, the provisions of 10 CFR 50 Appendix R, Paragraphs III.G.2.d, e, and f were addressed.
 
4.6.3                                                                                                      Emergency lighting is provided for areas required for operation of safe shutdown equipment and for access and egress to those areas. It consists of sealed beam units with individual 8-hour minimum battery power supplies.
 
4.6.4                                                                                                      Safety-related cable in the general plant area is qualified to IEEE-383-1974. All single conductors inside control panels meet the flame resistance requirements of IPCEA S-19-81 or S-61-402.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 14 of 275 Fire Hazard Analysis
 
4.6.5                                                                                                      Noncombustible materials are defined to meet one of the following criteria:
: 1.                                                        Material of which no part will burn.
: 2.                                                        Surface materials not over 1/16-inch thick with a flame spread rating of 50 or less as measured by ASTM E 84- 1976.
: 3.                                                        Interior finishes which meet 4.6.5.1, or are listed by an approved organization for surface flame spread of 25 or less per ASTM E 84-1976 and potential heat release of 3,500 Btu/lb or less per ASTM D 3286-1973.
 
4.6.6                                                                                                      Lighting, fire protection, communication and specialty cables which are flame retardant but not qualified to IEEE-383-1974; and other communication and specialty cable, such as cords and computer ribbon cable, are limited in use in the following manner:
: 1.                                                        Covered with a flame retardant coating per the requirements of (BTP)
APCSB 9.5-1, Appendix A; or
: 2.                                                        Installed in a totally enclosed metal conduit system; or
: 3.                                                        Consist of short lengths of exposed cable between the end of a totally enclosed metal conduit system routed to a component and the connection to the component (e.g. at light fixtures and public address devices; or
: 4.                                                        Located in non-safety-related areas which are separated from safety-related areas by fire rated boundaries; or
: 5.                                                        Evaluated on a case-by-case basis for adverse impact on the fire protection program.
 
4.7 PFSSD Historical Information
 
Note:
The following historical information regarding the initial PFSSD analysis process was extracted verbatim from USAR Section 9.5B.6 (Rev. 14) so that the information would be readily available for reference purpose. E-15000 (Set-Route) is now the control means for PFSSD circuits.
 
The list of safe shutdown components shown on [USAR] Table 9.5B-2 was provided to electrical design engineers who located all associated circuits through the review of physical drawings and electrical schematics. Each circuit associated with these devices was then flagged as being safe shutdown related (following a fire) in the master electrical raceway routing program/data base E0580. This program is utilized to route the scheduled power block cable at WCGS. It ensures that train separation is maintained and provides the most direct/suitable routing for circuits.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 15 of 275 Fire Hazard Analysis
 
After the E0580 data base was updated, a special program (Electrical Fire Hazards Analysis Program [EFHAP]) was run to produce a listing of safe shutdown circuits by fire area and room number, and by electrical separation group. This listing also included "from" and "to" information for each circuit. When a safe shutdown incompatibility was determined to exist, a failure modes analysis was performed on the circuit, the physical location(s) of the circuits were evaluated, the availability of an alternate (diverse) shutdown system was identified, and/or the need for a rated fire barrier wrap was evaluated.
 
The need for a fire wrap was determined based on the installed detection and suppression systems and the physical distance separating the incompatible circuits. A summary of the final evaluation for each area is provided in Section X.X.7.2 of each fire area described in
[USAR] Appendix 9.5B (where "X.X" identifies the fire area).
 
Since the power block safety-related circuits are all routed in the design office through the application of computer technology and the EFHAP listings were generated from the base E0580 program, it has been determined that the inclusion of listings of conduit and raceway numbers in the USAR descriptions of each fire area is inappropriate. These listings would be of no benefit to any USAR holder or reviewer. The listings would be voluminous and add several hundred pages to the fire hazards analyses.
 
4.8 FHA Revision
 
4.8.1                                                                                                      The FHA is part of the Approved Fire Protection Program. As discussed in Operating License Condition 2.C.(5)(b), changes are allowed to the Approved Fire Protection Program provided they do not adversely affect the capability to achieve and maintain PFSSD. Therefore, technical changes to this analysis document require an evaluation in accordance with AI 26A-003. This evaluation, which requires Plant Safety Review Committee (PSRC) approval, is necessary to determine if proposed technical changes require prior NRC approval.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 16 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 1 of 14)
 
Fire Area                                                    Rm #                                                  Bldg.                                                          Elev.                                                                                                                                Description                                                                                                                                                              Auto.                                                                    Auto.                                                                  PFSSD                                                          RCA                                        FHA Detection                                                      Suppression                                                                              Circuits                                                    (Typ.)                                      Page A-1                                                                                                        1101                                                                Aux.                                                                      1974-0                    General Floor Area No. 1                                                                                                                                                                                                                                                                                                                                          T                                                                                                                                                        T                                                                                                                                                Yes                                                                                Yes                                                        30 1102                                                                Aux.                                                                      1974-0                    Chiller & Surge Tanks Area                                                                                                                                                                                                                                                                                                                T                                                                                                                                                        T                                                                                                                                                Yes                                                                                Yes
 
1103                                                                Aux.                                                                      1974-0                    Letdown Chiller Heat Exch Room                                                                                                                                                                                                                                    N (Note 6)      N No Yes
 
1104                                                                Aux.                                                                      1974-0                    Letdown Reheat Heat Exch Room                                                                                                                                                                                                                          N (Note 6)      N No Yes
 
1105 Aux. 1974-0 Valve Compartment                                                                                                                                                                                                                                                                                                                                              N (Note 6)      N No Yes
 
1106                                                                Aux.                                                                      1974-0                    Moderating Heat Exch Room                                                                                                                                                                                                                                                                                            N (Note 6)      N No Yes
 
1115                                                                Aux.                                                                      1974-0                    Normal Charging Pump Rm                                                                                                                                                                                                                                                                                                          T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1120                                                                Aux.                                                                      1974-0                    General Floor Area No. 2                                                                                                                                                                                                                                                                                                                                          T                                                                                                                                                        P                                                                                                                                                Yes                                                                                Yes 1121 Aux. 1974-0 Access Pit                                                  T          N          No  Yes 1122                                                                Aux.                                                                      1974-0                    General Floor Area No. 3                                                                                                                                                                                                                                                                                                                                          T                                                                                                                                                        P                                                                                                                                                Yes                                                                                Yes
 
1123 Aux. 1974-0 Passage                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            N (Note 6)      N No Yes
 
1124 Aux. 1974-0 Valve Compartment                                                                                                                                                                                                                                                                                                                                              N (Note 6)      N No Yes
 
1125                                                                Aux.                                                                      1974-0                    Letdown Heat Exch Room                                                                                                                                                                                                                                                                                                                              N (Note 6)      N No Yes
 
1128                                                                Aux.                                                                      1974-0                    Auxiliary Feedwater Pump Room                                                                                                                                                                                                                                        T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1129                                                                Aux.                                                                      1974-0                    Aux Steam Cond Recovery & Storage Tank                                                                                                  T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1130 Aux. 1974-0 North Corridor                                            T          P        Yes  Yes 1201 Aux. 1988-0 Vestibule                                                    T          N          No  Yes 1202                                                                Aux.                                                                      1988-0                    Access Area B & Chiller Surge Tank Area                                                                                                                        N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes Yes 1203                                                                Aux.                                                                      1988-0                    Pipe Space B                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            N                                                                                                                                                      N (Cold Yes shutdown only)
Yes 1204                                                                Aux.                                                                      1988-0                    Pipe Space A                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            N                                                                                                                                                      N (Cold Yes shutdown only) 1205                                                                Aux.                                                                      1988-0                    Access Area A                                                                                                                                                                                                                                                                                                                                                                                                                                                                            N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 1203A      Aux. 1988-0 Electrical Chase                                      T        T        Yes Yes A-2                                                                                                        1111                                                                Aux.                                                                      1974-0                    Residual Heat Removal Pump Room A                                                                                                                                                          T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                          33 1112                                                                Aux.                                                                      1974-0                    Containment Spray Pump Room A                                                                                                                                                                                                                  T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1113                                                                Aux.                                                                      1974-0                    Safety Injection Pump Room A                                                                                                                                                                                                                                                                    T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1114                                                                Aux.                                                                      1974-0                    Centrifugal Charging Pump Room A                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes A-3                                                                                                        1116                                                                Aux.                                                                      1974-0                    Boric Acid Tank Room B                                                                                                                                                                                                                                                                                                                                                  T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                          36 1117                                                                Aux.                                                                      1974-0                    Boric Acid Tank Room A                                                                                                                                                                                                                                                                                                                                                  T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1407                                                                Aux.                                                                      2026-0                    Boric Acid Batching Tank Area                                                                                                                                                                                                                                                                    N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes A-4                                                                                                        1107                                                                Aux.                                                                      1974-0                    Centrifugal Charging Pump Room B                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                          39 1108                                                                Aux.                                                                      1974-0                    Safety Injection Pump Room B                                                                                                                                                                                                                                                                    T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1109                                                                Aux.                                                                      1974-0                    Residual Heat Removal Pump Room B                                                                                                                                                          T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1110                                                                Aux.                                                                      1974-0                    Containment Spray Pump Room B                                                                                                                                                                                                                  T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes A-5                                                                                                        1119                                                                Aux.                                                                                    Stair                                    Aux. Stair A-1 & A-1A                                                                                                                                                                                                                                                                                                                                                                                      N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes                                                          42 1601                                                                Aux.                                                                      2064-4                    Elevator Machine Room No. 2                                                                                                                                                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes A-6                                                                                                        1127                                                                Aux.                                                                                    Stair                                    Aux. Stair A-2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes                                                          44 A-7                                                                                                        1126                                                                Aux.                                                                      1974-0                    Boron Injection Tank & Pump Room                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                          46 Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 17 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 2 of 14)
 
Fire Area                                            Rm #                                            Bldg.                                                Elev.                                                                                                              Description                                                                                                                                      Auto.                                                          Auto.                                                        PFSSD                                                RCA                                  FHA Detection                                              Suppression                                                                  Circuits                                              (Typ.)                                Page A-8                                                                                                          1301                                                                Aux.                                                                      2000-0                    Corridor No. 1                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      P                                                                                                                                                        P                                                                                                                                                Yes                                                                                Yes                                                        48 1302                                                                Aux.                                                                      2000-0                    Filter Compartments Typical of 5                                                                                                                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 1306                                                                Aux.                                                                      2000-0                    Valve Compartments Typical of 5                                                                                                                                                                                                                                  N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 1307                                                                Aux.                                                                      2000-0                    Corridor No. 2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 1308                                                                Aux.                                                                      2000-0                    Valve Compartments Typical of 8                                                                                                                                                                                                                                  N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 1311 Aux. 2000-0 Sampling Room                                          T          N        Yes  Yes Above 1312                                                                Aux.                                                                      2000-0                    Boron Meter & R.C. Activity Monitor Rm                                                                                                                                                N                                                            Ceiling - T                                                                        No Yes Below Ceiling -  N 1313                                                                Aux.                                                                      2000-0                    Volume Control Tank Rm                                                                                                                                                                                                                                                                                                                                          N (Note 6)      N Yes Yes
 
1314                                                                Aux.                                                                      2000-0                    Corridor No. 3                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1315                                                                Aux.                                                                      2000-0                    Ctmt Spray Additive Tank Area                                                                                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1318 Aux. 2000-0 Valve Compartment                                    T          N        Yes  Yes 1319                                                                Aux.                                                                      2000-0                    Demineralizer Compartments Typical of 8                                                                                                                          N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 1320                                                                Aux.                                                                      2000-0                    Corridor No. 4                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        P                                                                                                                                                Yes                                                                                Yes 1321 Aux. 2000-0 Exit Vestibule                                              T          T          No  Yes A-9                                                                                                        1309                                                                Aux.                                                                      2000-0                    Residual Heat Removal Heat Exch Rm B                                                                                                                                  N                                                                                                                                                                                                53 (Note 2)      N Yes Yes A-10                                                                                        1310                                                                Aux.                                                                      2000-0                    Residual Heat Removal Heat Exch Rm A                                                                                                                                  N                                                                                                                                                                                                              55 (Note 2)      N Yes Yes A-11          1335 Aux. 2000-0 Electrical Chase                                          T          T        Yes  Yes 57 A-12          1336 Aux. 2000-0 Electrical Chase                                          T          T        Yes  Yes 60 A-13                                                                                        1325                                                                Aux.                                                                      2000-0                    Aux Feedwater Pump Rm B                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No                                                                62 A-14                                                                                        1326                                                                Aux.                                                                      2000-0                    Aux Feedwater Pump Rm A                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No                                                                64 A-15                                                                                        1331                                                                Aux.                                                                      2000-0                    Aux Feedwater Pump Rm C                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N 66 (Note 7)        Yes No A-16          1401 Aux. 2026-0 Component Cooling Pump & Heat Exch Area                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      69 B                                T N Yes Yes 1402                                                                Aux.                                                                      2026-0                    Corridor No. 1                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        T                                                                                                                                                Yes                                                                                Yes 1406 Aux. 2026-0 Component Cooling Pump & Heat Exch Area A                                T N Yes Yes 1408                                                                Aux.                                                                      2026-0                    Corridor No. 2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        P                                                                                                                                                Yes                                                                                Yes A-17                                                                                        1409                                                                Aux.                                                                      2026-0                    Electrical Penetration Rm B                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                Yes                                                                                Yes                                                          73 A-18                                                                                        1410                                                                Aux.                                                                      2026-0                    Electrical Penetration Rm A                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                Yes                                                                                Yes                                                          76 A-19                                                                                        1504                                                                Aux.                                                                      2047-6                    Ctmt Purge Exhaust & Mech Equip Rm B                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                          79 1506                                                                Aux.                                                                      2047-6                    Ctmt Purge Supply Air Handling Unit A                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1513                                                                Aux.                                                                      2047-6                    Control Bldg Vent Supply A/C Unit Rm                                                                                                                                                                  T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes A-20                                                                                        1502                                                                Aux.                                                                      2047-6                    Component Cooling Water Surge Tk Area B                                                                                            P                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes                                                          82
 
1503                                                                Aux.                                                                      2047-6                    Component Cooling Water Surge Tk Area A                                                                                            N (Note 6)      N Yes Yes
 
1505 Aux. 2047-6 Corridor                                                      T          N          No  Yes 1507 Aux. 2047-6 Personnel Hatch Area                                  T          N        Yes  Yes A-21                                                                                        1501                                                                Aux.                                                                      2047-6                    Control Rm A/C & Filtration Units B                                                                                                                                                                                                            T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                          85 A-22                                                                                        1512                                                                Aux.                                                                      2047-6                    Control Rm A/C & Filtration Units A                                                                                                                                                                                                            T                                                                                                                                                        N                                                                                                                                              Yes                                                                        Yes                                                          88 Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 18 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 3 of 14)
 
Fire Area                                            Rm #                                            Bldg.                                                  Elev.                                                                                                              Description                                                                                                                                        Auto.                                                          Auto.                                                        PFSSD                                                  RCA                                  FHA Detection                                              Suppression                                                                  Circuits                                              (Typ.)                                Page A-23                                                                                        1411                                                                Aux.                                                                      2037-7                    Main Feedwater Rm No. 1                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                        91 1412                                                                Aux.                                                                      2037-7                    Main Feedwater Rm No. 2                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1508                                                                Aux.                                                                      2042-0                    Main Steam Isolation Valve Rm No. 1                                                                                                                                                                              T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 1509                                                                Aux.                                                                      2042-0                    Main Steam Isolation Valve Rm No. 2                                                                                                                                                                              T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes A-24                                                                                        1323                                                                Aux.                                                                      2000-0                    Pipe Penetration Rm A                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                          94 A-25                                                                                        1322                                                                Aux.                                                                      2000-0                    Pipe Penetration Rm B                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                          96 A-26                                                                                        1405                                                                Aux.                                                                      2026-0                    Chemical Storage Area                                                                                                                                                                                                                                                                                                                                                                  T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                          99 1415                                                                Aux.                                                                      2026-0                    I & C Hot Shop                                                                                                                                                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes A-27                                                                                        1403                                                                Aux.                                                                      2026-0                    MG Set Room                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    T                                                                                                                                                        T                                                                                                                                                Yes                                                                                Yes                                                102 A-28                                                                                        1413                                                                Aux.                                                                      2026-0                    Auxiliary Shutdown Panel Room                                                                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                  105 A-29                                                                                        1304                                                                Aux.                                                                      2013-6                    Aux Feedwater Pipe Chase                                                                                                                                                                                                                                                                                                              N                                                  107 (Note 1)      N Yes No 1324                                                                Aux.                                                                      2000-0                    Feedwater Pump Valve Compartment No. 1                                                                                              N (Note 1)      N Yes No
 
1327                                                                Aux.                                                                      2000-0                    Feedwater Pump Valve Compartment No. 2                                                                                              N (Note 1)      N Yes No A-30                                                                                        1305                                                                Aux.                                                                      2013-6                    Aux Feedwater Pipe Chase                                                                                                                                                                                                                                                                                                              N                                                  109 (Note 1)      N Yes Yes 1328                                                                Aux.                                                                      2000-0                    Feedwater Pump Valve Compartment No. 3                                                                                              N (Note 1)      N Yes Yes
 
1330                                                                Aux.                                                                      2000-0                    Feedwater Pump Valve Compartment No. 4                                                                                              N (Note 1)      N Yes Yes
 
A-31  - This Fire Area has been deleted.
A-32  - This Fire Area has been deleted.
A-33          1206 Aux. 1989-0 Pipe Chase                                                T          T        Yes  No 111 1207 Aux. 1989-0 Pipe Chase                                                T          T        Yes  No 1329 Aux. 2000-0 Vestibule                                                    N          N          No    No A-34                                                                                        1316                                                                Aux.                                                                      2000-0                    Seal Water Heat Exch. Valve Comp.                                                                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                    No                                                                                            No                                                        114 1317                                                                Aux.                                                                      2000-0                    Seal Water Heat Exchanger                                                                                                                                                                                                                                                                                                      N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes AB-1                                                                                      4315                                            Turbine                                                  2000-0                    Auxiliary Boiler Room                                                                                                                                                                                                                                                                                                                                                                                        T                                                                                                                                                        T                                                                                                                                                      No                                                                                            No                                                        116 C-1                                                                                                      3101                                              Control                                                    1974-0                    Pipe Space & Tank Area                                                                                                                                                                                                                                                                                                                                                P                                                                                                                                                        T                                                                                                                                                Yes                                                                                Yes                                                  118 3104                                              Control                                                                    Stair                                    Control, Stair No. C-2                                                                                                                                                                                                                                                                                                                                                                                      N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes N/A                                                      Control                                                    1974-0                    Duct Chase - East Wall of 3101                                                                                                                                                                                                                                                  N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes C-2                3106 Control 1974-0 Electrical Chase                                                          T                T                No      Yes  121 C-3                3105 Control 1974-0 Electrical Chase                                                          T                T                No      Yes  123 C-4  - This fire area has been deleted. The area above the suspended ceiling is now included in Fire Areas C-5 and C-6.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 19 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 4 of 14)
 
Fire Area                                                Rm #                                                Bldg.                                                    Elev.                                                                                                                        Description                                                                                                                                                    Auto.                                                              Auto.                                                              PFSSD                                                      RCA                                      FHA Detection                                                  Suppression                                                                        Circuits                                                  (Typ.)                                    Page C-5                3206 Control 1984-0 R.C.A. Egress                                                              T                T                No      No        125 3212                                              Control                                                    1984-0                    H.P. Lounge Area                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No 3213                                              Control                                                    1984-0                    H.P. Conference Room (West)                                                                                                                                                                                                                                                                      T                                                                                                                                                        T                                                                                                                                                      No                                                                                            No 3214 Control 1984-0 Hall                                                                                N                T                No      No
 
3216                                              Control                                                    1984-0                    R.P. Calibration Lab 2                                                                                                                                                                                                                                                                                                                                                                                  T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No 3217 Control 1984-0 Mens Toilet                                                                  N                N              Yes      No 3218                                              Control                                                    1984-0                    Exit Monitor Area                                                                                                                                                                                                                                                                                                                                                                                                                                              T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No
 
3220                                              Control                                                    1984-0                    Sign In/Out Area                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 3221                                              Control                                                    1984-0                    Vestibule No. 1                                                                                                                                                                                                                                                                                                                                                                                                                                                                        P                                                                                                                                                        T                                                                                                                                                      No                                                                                            No 3222 Control 1984-0 H.P. office                                                                    T                T              Yes      No 3223 Control 1984-0 Closet                                                                            T                T                No      No 3224                                              Control                                                    1984-0                    Vestibule No. 2                                                                                                                                                                                                                                                                                                                                                                                                                                                                      N                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No 3231                                              Control                                                    1984-0                    Womens Toilet                                                                                                                                                                                                                                                                                                                                                                                                                                                      N                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No None                                            Control                                                    1984-0                    Pipe Chase South of 3213                                                                                                                                                                                                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                            N                                                                                                    No None                                            Control                                                    1984-0                    Pipe Chase South of 3216                                                                                                                                                                                                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                            N                                                                                                    No None                                            Control                                                    1984-0                    Pipe Chase North of 3217/ 3231                                                                                                                                                                                                                                                N                                                                                                                                                      N                                                                                                                                                            N                                                                                                    No None                                            Control                                                    1984-0                    Pipe Chase South of 3217/3231                                                                                                                                                                                                                                                  N                                                                                                                                                      N                                                                                                                                                            N                                                                                                    No None                                            Control                                                    1984-0                    Pipe Chase North of 3213                                                                                                                                                                                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                            N                                                                                                    No None                                            Control                                                    1984-0                    Pipe Chase North of 3223                                                                                                                                                                                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                            N                                                                                                    No 3212A      Control 1984-0 Partial Height Electrical Chase (Accessible from 3212)                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    (Note 3)                                                                  (Note 3)                                                                                                                    Y                                                                                                    No NAC                                                Control                                                    1984-0                    Area Above Suspended Ceiling                                                                                                                                                                                                                                                          P                                                                                                                                                        P                                                                                                                                                              Y                                                                                                    No Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 20 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 5 of 14)
 
Fire Area                                                Rm #                                                Bldg.                                                      Elev.                                                                                                                        Description                                                                                                                                                  Auto.                                                                Auto.                                                              PFSSD                                                      RCA                                      FHA Detection                                                    Suppression                                                                        Circuits                                                  (Typ.)                                    Page C-6                                                                                                      3201                                              Control                                                                    Stair                                    Control, Stair C-1                                                                                                                                                                                                                                                                                                                                                                                                                                            N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes                                                128 3202                                              Control                                                    1984-0                    Controlled H.P. Tool & Inst. Storage Room                                                                                                              T                                                                                                                                                        T                                                                                                                                                      No                                                                                      Yes 3203                                              Control                                                    1984-0                    Hot Janitors Closet                                                                                                                                                                                                                                                                                                                                                                                                                        T                                                                                                                                                        T                                                                                                                                                      No                                                                                      Yes 3204                                              Control                                                    1984-0                    Corridor No. 1                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    N                                                                                                                                                        T                                                                                                                                                Yes                                                                                Yes 3205 Control 1984-0 H.P. Area                                                                      T                T                No      Yes 3207 Control 1984-0 R.C.A. Ingress                                                            T                T                No      Yes 3208                                              Control                                                    1984-0                    R.P. Calibration Lab 1                                                                                                                                                                                                                                                                                                                                                                                  T                                                                                                                                                        T                                                                                                                                                Yes                                                                                Yes 3209 Control 1984-0 Decon Area                                                                  T                T                No      Yes 3210 Control 1984-0 Decon Shower                                                            N                N              No      Yes 3211                                              Control                                                    1984-0                    H.P Conference Room (East)                                                                                                                                                                                                                                                                                      T                                                                                                                                                        T                                                                                                                                                Yes                                                                                Yes None                                            Control                                                    1984-0                    Pipe Chase North of 3207                                                                                                                                                                                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                            N                                                                                              Yes None                                            Control                                                    1984-0                    Pipe Chase South of 3207                                                                                                                                                                                                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                            N                                                                                              Yes None                                            Control                                                    1984-0                    Pipe Chase South of 3209                                                                                                                                                                                                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                            N                                                                                              Yes None                                            Control                                                    1984-0                    Pipe Chase North of 3210                                                                                                                                                                                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                            N                                                                                              Yes None                                            Control                                                    1984-0                    Pipe Chase Behind Hose Cabinet in 3204                                                                                                                        N                                                                                                                                                      N                                                                                                                                                            N                                                                                              Yes 3205A      Control 1984-0 Partial Height Electrical Chase (Accessible from 3205)                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    (Note 3)                                                                  (Note 3)                                                                                                                    Y                                                                                              Yes SAC                                                  Control                                                    1984-0                    Area Above Suspended Ceiling                                                                                                                                                                                                                                                          P                                                                                                                                                        P                                                                                                                                                              Y                                                                                              Yes C-7                3230 Control 1984-0 Electrical Chase                                                          T                T              Yes      No        131 C-8                3229 Control 1984-0 Electrical Chase                                                          T                T                No      Yes  133 C-9                                                                                                      3301                                              Control                                                    2000-0                    ESF Switchgear Room No. 1                                                                                                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                        135 C-10                                                                                        3302                                              Control                                                    2000-0                    ESF Switchgear Room No. 2                                                                                                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                        138 C-11            3305 Control 2000-0 Electrical Chase                                                          T                T              Yes      No        141 C-12            3306 Control 2000-0 Electrical Chase                                                          T                T              Yes      No        143 C-13                                                                                        3415                                              Control                                                    2016-0                    Access Ctrl & Elec Equip A/C Units No. 1                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No                                                        145 C-14                                                                                        3416                                              Control                                                    2016-0                    Access Ctrl & Elec Equip A/C Units No. 2                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No                                                        147 C-15                                                                                        3403                                              Control                                                    2016-0                    Non-Vital Swgr & Xfmr Rm No. 1                                                                                                                                                                                                                                          T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                        149 3404                                              Control                                                    2016-0                    Switchboard Rm No. 4                                                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No 3405                                              Control                                                    2016-0                    Battery Rm No. 4                                                                                                                                                                                                                                                                                                                                                                                                                                              T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 3410                                              Control                                                    2016-0                    Switchboard Rm No. 2                                                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No 3411                                              Control                                                    2016-0                    Battery Rm No. 2                                                                                                                                                                                                                                                                                                                                                                                                                                              T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No C-16                                                                                        3407                                              Control                                                    2016-0                    Battery Rm No. 1                                                                                                                                                                                                                                                                                                                                                                                                                                              T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No                                                        152 3408                                              Control                                                    2016-0                    Switchboard Rm No. 1                                                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No 3409                                              Control                                                    2016-0                    Non-Vital Swgr & Xfmr Rm No. 2                                                                                                                                                                                                                                          T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No 3413                                              Control                                                    2016-0                    Battery Rm No. 3                                                                                                                                                                                                                                                                                                                                                                                                                                              T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 3414                                              Control                                                    2016-0                    Switchboard Rm No. 3                                                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No C-17            3418 Control 2016-0 Electrical Chase                                                          T                T              Yes      No        155 C-18            3419 Control 2016-0 Electrical Chase                                                          T                T              Yes      No        157 C-19                                                                                            C19                                                    Control                                                    2016-0                    Cable Chase @ CA-C3, 2016-0 to 2032-0                                                                                                                T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                      159 C-20                                                                                            C20                                                    Control                                                    2016-0                    Cable Chase @ CA-C6, 2016-0 to 2032-0                                                                                                                        T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                      161 C-21                                                                                        3501                                              Control                                                    2032-0                    Lower Cable Spreading Room                                                                                                                                                                                                                                                                          T                                                                                                                                                        P                                                                                                                                                Yes                                                                                      No                                                        163 C-22                                                                                        3801                                              Control                                                    2073-6                    Upper Cable Spreading Room                                                                                                                                                                                                                                                                          T                                                                                                                                                        P                                                                                                                                                Yes                                                                                      No                                                        166 C-23            3505 Control 2032-0 Electrical Chase                                                          T                T              Yes      No        169 C-24            3504 Control 2032-0 Electrical Chase                                                          T                T              Yes      No        171 C-25                                                                                            C25                                                    Control                                                    2032-0                    Cable Chase @ CA-C6, 2032-0 to 2047-6                                                                                                                        T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                      173 C-26                                                                                            C26                                                    Control                                                    2032-0                    Cable Chase @ CA-C3, 2032-0 to 2047-6,                                                                                                                T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                      175 C-27            3601 Control 2047-6 Control Room                                                              T                N              Yes      No        177 Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 21 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 6 of 14)
 
Fire Area              Rm #                Bldg.                  Elev.                                            Description                                                    Auto.                      Auto.                      PFSSD                  RCA              FHA Detection                Suppression                      Circuits              (Typ.)          Page RL001 2047-6 Panel Board                                                      T            N          Yes    No RL002 2047-6 Panel Board                                                      T            N          Yes    No RL003 2047-6 Panel Board                                                      T            N          Yes    No RL004 2047-6 Panel Board                                                      T            N            No    No RL005 2047-6 Panel Board                                                      T            N          Yes    No RL006 2047-6 Panel Board                                                      T            N          Yes    No RL011 2047-6 Panel Board                                                      T            N            No    No RL012 2047-6 Panel Board                                                      T            N            No    No RL013 2047-6 Panel Board                                                      T            N            No    No RL014 2047-6 Panel Board                                                      T            N            No    No RL015 2047-6 Panel Board                                                      T            N          Yes    No RL016 2047-6 Panel Board                                                      T            N          Yes    No RL017 2047-6 Panel Board                                                      T            N          Yes    No RL018 2047-6 Panel Board                                                      T            N          Yes    No RL019 2047-6 Panel Board                                                      T            N          Yes    No RL020 2047-6 Panel Board                                                      T            N          Yes    No RL021 2047-6 Panel Board                                                      T            N          Yes    No RL022 2047-6 Panel Board                                                      T            N          Yes    No RL023 2047-6 Panel Board                                                      T            N          Yes    No RL024 2047-6 Panel Board                                                      T            N          Yes    No RL025 2047-6 Panel Board                                                      T            N          Yes    No RL026 2047-6 Panel Board                                                      T            N            No    No RL027 2047-6 Panel Board                                                      T            N          Yes    No RL028 2047-6 Panel Board                                                      T            N            No    No 3603                                              Control                                                    2047-6                    Shift Supervisors office                                                                                                                                                                                                                                                                                                                                                                    T                                                                                                                                                        N                                                                                                                                                    No                                                                                            No 3604      Control 2047-6 Foyer                                                                      N            N            No      No 3605                                              Control                                                    2047-6                    Equipment Cabinet Area                                                                                                                                                                                                                                                                                                                                                P                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No RP068 2047-6 Panel Board                                                        T            N            Yes    No NF039A 2047-6 Panel Board                                                                  T                N              Yes      No NF039B 2047-6 Panel Board                                                                  T                N              Yes      No NF039C 2047-6 Panel Board                                                                    T                N              Yes      No 3606                                              Control                                                    2047-6                    Emergency Equipment Storage Room                                                                                                                                                                        T                                                                                                                                                        N                                                                                                                                                    No                                                                                            No 3616      Control 2047-6 Vestibule                                                                N            N            No      No N/A                                                      Control                                                    2047-6                    Duct Chase - Northwest Corner of 3601                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                    No                                                                                            No N/A                                                      Control                                                    2047-6                    Duct Chase - Southeast Corner of 3604                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                    No                                                                                            No N/A                                                      Control                                                        Varies                        Cable Trenches and Vertical Shaft                                                                                                                                                                                                                      T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No C-28 3602 Control 2047-6 Pantry                                                                    T              N            Yes    No  182 3607      Control 2047-6 Toilet                                                                      N            N            Yes    No 3608      Control 2047-6 Janitors Closet                                                      T              N            Yes    No C-29 3609 Control 2047-6 SAS Room                                                            T              N            No      No  184 C-30 3617 Control 2047-6 Electrical Chase                                                    T              T            Yes    No    186 C-31 3618 Control 2047-6 Electrical Chase                                                    T              T            Yes    No    188 C-32 C32 Control                                                    2047-6                    Cable Chase @ CA-C6, 2047-6 to 2073-6,                                                                                                                T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                      190 C-33 3804 Control 2073-6 Electrical Chase                                                    T              T            Yes    No    192 C-34 C34 Control                                                    2073-6                    Cable Chase @ CA-C6                                                                                                                                                                                                                                                                                                                                                                  T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                        194 C-35 3401 Control                                                    2016-0                    Corridor No. 1                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      N 196 (Note 4)      N Yes No Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 22 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 7 of 14)
 
Fire Area                                                        Rm #                                                      Bldg.                                                            Elev.                                                                                                                                      Description                                                                                                                                                                      Auto.                                                                        Auto.                                                                      PFSSD                                                            RCA                                          FHA Detection                                                          Suppression                                                                                    Circuits                                                        (Typ.)                                          Page
 
3406                                              Control                                                    2016-0                    Corridor No. 2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        N (Note 4)      N No No
 
3412                                              Control                                                    2016-0                    Emergency Shower & Eyewash Area                                                                                                                                                                                    N (Note 4)      N Yes No C-36                                                                                            C36                                                    Control                                                    2000-0                    Cable Chase @ CA-C6, 2000-0 to 2016-0,                                                                                                              N                                                                                                                                                                                                                                                                                                                                                                                            198 (Note 5)      T Yes No C-37                                                                                            C37                                                    Control                                                    2000-0                    Cable Chase @ CA-C3, 2000-0 to 2016-0                                                                                                                      N                                                                                                                                                                                                                                                                                                                                                                                      200 (Note 5)      T Yes No CC-1 3102                                  Cm Corr.                                        1974-0                    Pipe Space, Tank & Storage Area                                                                                                                                                                                                                            P                                                                                                                                                      N                                                                                                                                                    No                                                                                            No                                                        202 3103                                  Cm Corr.                                                        Stair                                    Stair No. CC-1                                                                                                                                                                                                                                                                                                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                                    No
 
3225                                  Cm Corr.                                        1984-0                    Corridor No. 2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      P                                                                                                                                                      N                                                                                                                                              Yes Above 3226                                  Cm Corr.                                        1984-0                    Counting Room                                                                                                                                                                                                                                                                                                          Ceiling - T                                                                                        N Yes Yes Below Ceiling -  T 3227                                  Cm Corr.                                        1984-0                    Vestibule No. 3                                                                                                                                                                                                                                                                                                                                                                                                                                                                      N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes Above 3228                                  Cm Corr.                                        1984-0                    Hot Laboratory                                                                                                                                                                                                                                                                                                          Ceiling - T                                                                                        N Yes Yes Below Ceiling -  T N/A                                            Cm Corr.                                        1984-0                    Pipe Chase - South of 3227 & 3228                                                                                                                                                                                                N                                                                                                                                                      N                                                                                                                                                    No                                                                                            No 3303 Cm Corr. 2000-0 Corridor                                                                                                T                      N                    Yes          No 3304                                  Cm Corr.                                        2000-0                    General Floor Area                                                                                                                                                                                                                                                                                                                                                                                                                    N                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No 3402                                  Cm Corr.                                        2016-0                    Corridor No. 3                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 3502 Cm Corr. 2032-0 Lobby                                                                                                    T                      N                    Yes          No 3503                                  Cm Corr.                                        2032-0                    General Floor Area                                                                                                                                                                                                                                                                                                                                                                                                                      P                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No 3611                                  Cm Corr.                                        2047-6                    Corridor No. 2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      P                                                                                                                                                      N                                                                                                                                                    No                                                                                            No 3612                                  Cm Corr.                                        2047-6                    Operations Conference Room                                                                                                                                                                                                                                                                              T                                                                                                                                                        N                                                                                                                                                    No                                                                                            No 3613                                  Cm Corr.                                        2047-6                    Work Control Center                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                                    No                                                                                            No 3614                                  Cm Corr.                                        2047-6                    Corridor No. 3                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 3619                                  Cm Corr.                                        2047-6                    General Floor Area                                                                                                                                                                                                                                                                                                                                                                                                                    N                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No 3701                                  Cm Corr.                                        2061-6                    General Floor Area                                                                                                                                                                                                                                                                                                                                                                                                                      P                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No 3702                                  Cm Corr.                                        2061-6                    Battery Room                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 3703                                  Cm Corr.                                        2061-6                    Radio Equipment Room                                                                                                                                                                                                                                                                                                                                                          T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 3704                                  Cm Corr.                                        2061-6                    General Floor Area                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 3705                                  Cm Corr.                                        2061-6                    Battery Room                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 3802                                  Cm Corr.                                        2078-0                    Elevator No. 1 Machine Room                                                                                                                                                                                                                                                                            T                                                                                                                                                        N                                                                                                                                                    No                                                                                            No 3803 Cm Corr. 2073-6 Corridor                                                                                                T                      N                    Yes          No OP-7                                  Cm Corr.                                        2032-0                    Observation Post                                                                                                                                                                                                                                                                                                                                                                                                                                            N                                                                                                                                                      N                                                                                                                                                    No                                                                                            No CST                                                                                            9101                                                          Other                                                                                    N/A                                          Condensate Storage Tank & Pipe House                                                                                                                                  N                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No                                                        265 D-1                                                                                                      5203                                            D. Gen.                                                2000-0                    Emergency Diesel Generator A Room                                                                                                                                                      T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                        205 5203A                                                              Yard                                                                        Buried                        Emergency Fuel Oil Tank Area                                                                                                                                                                                                                                                                N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 23 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 8 of 14)
 
Fire Area                                                  Rm #                                                  Bldg.                                                        Elev.                                                                                                                              Description                                                                                                                                                        Auto.                                                                  Auto.                                                                PFSSD                                                        RCA                                      FHA Detection                                                    Suppression                                                                            Circuits                                                    (Typ.)                                      Page D-2                                                                                                      5201                                            D. Gen.                                                2000-0                    Emergency Diesel Generator B Room                                                                                                                                                      T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                        208 5201A                                                              Yard                                                                        Buried                        Emergency Fuel Oil Tank Area                                                                                                                                                                                                                                                                N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes ESWA                                                                K105                                                          ESW                                                                  2000-0                    ESW Pump House - Room A                                                                                                                                                                                                                                                                                          T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No                                                        211 K105A                                                  ESW                                                                  2000-0                    Train A ESW Electrical Duct Banks and Vaults                                                            N                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No ESWB                                                                K104                                                          ESW                                                                  2000-0                    ESW Pump House - Room B                                                                                                                                                                                                                                                                                          T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No                                                        214 K104A                                                  ESW                                                                  2000-0                    Train B ESW Electrical Duct Banks and Vaults                                                            N                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No ESWV AV1,                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    217 AV2, AV3,                                                  Yard Multiple ESW Vaults                                                N          N          No    No AV4, AV5, AV6 F-1            6101 Fuel  Stair Stair F-1                                                    N          N          No  Yes 219 6102 Fuel 2000-0 Laydown Area                                            T          P          No  Yes 6103                                                                  Fuel                                                                      2000-0                    Cask Loading Pool                                                                                                                                                                                                                                                                                                                                                                                                                        N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 6106                                                                  Fuel                                                                      2000-0                    Spent Fuel Pool & Storage Racks                                                                                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 6201 Fuel 2026-0 Passage                                                    N          N          No  Yes 6204                                                                  Fuel                                                                      2026-0                    Cask Washdown Pit                                                                                                                                                                                                                                                                                                                                                                                                        N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 6205                                                                  Fuel                                                                      2026-0                    Fuel Transfer Canal                                                                                                                                                                                                                                                                                                                                                                                                            N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 6210                                                                  Fuel                                                                      2032-6                    New Fuel Storage Area                                                                                                                                                                                                                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 6301                                                                  Fuel                                                                      2047-6                    General Floor Area                                                                                                                                                                                                                                                                                                                                                                                                                      P                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes 6302 Fuel 2047-6 Laydown Area                                            N          N          No  Yes F-2                                                                                                          6104                                                                  Fuel                                                                      2000-0                    Fuel Pool Cooling Heat Exch Room                                                                                                                                                                                                        T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                  222 F-3                                                                                                          6105                                                                  Fuel                                                                      2000-0                    Fuel Pool Cooling Heat Exch Room                                                                                                                                                                                                        T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes                                                  224 F-4                                                                                                          6203                                                                  Fuel                                                                      2026-0                    Air Handling Equipment Room                                                                                                                                                                                                                                                                        P                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes                                                  226 F-5                                                                                                          6202                                                                  Fuel                                                                      2026-0                    Electrical Equipment Room                                                                                                                                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                  228 F-6                                                                                                          6304                                                                  Fuel                                                                      2047-6                    Exhaust Filter Absorber Room A                                                                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes                                                  230 F-7                                                                                                          6303                                                                  Fuel                                                                      2047-6                    Exhaust Filter Absorber Room B                                                                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes                                                  232 HMS-1                                                            1332            Hot Machine Shop                                                                2000-0                    Hot Machine Shop                                                                                                                                                                                                                                                                                                                                                                                                                              T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes                                                233 1333            Hot Machine Shop                  2000-0 Decontamination Room                                                                                            T                                    N                                    No                  Yes
 
1334            Hot Machine Shop                                                                2000-0                    Hot Instrument Shop                                                                                                                                                                                                                                                                                                                                                                                                    T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 24 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 9 of 14)
 
Fire Area                                          Rm #                                          Bldg.                                              Elev.                                                                                                          Description                                                                                                                                  Auto.                                                        Auto.                                                      PFSSD                                              RCA                                  FHA Detection                                            Suppression                                                                Circuits                                            (Typ.)                              Page RB                                                                                                            RB1                                              Reactor                                                2000-0                    Area Within Secondary Shield Wall                                                                                                                                                                                                            N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes                                                  236 RB2 2201                                          Reactor                                                2000-0                    Area Outside Secondary Shield Wall                                                                                                                                                                                          P                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes RB3                                              Reactor                                                2026-0                    North Electrical Penetration Area                                                                                                                                                                                                                                P                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes RB4                                              Reactor                                                2026-0                    South Electrical Penetration Area                                                                                                                                                                                                                                    P                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes RB5                                              Reactor                                                2047-6                    Cable Tray Area                                                                                                                                                                                                                                                                                                                                                                                                                                                  P                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes RB6                                                                                                                                General Area, Pressurizer Valve Control 2601                                    Reactor 2068-8 Room, & Pressurizer Safety Valve Room      N N Yes Yes 2602 RB6 2603                                          Reactor                                                2068-8                    Elevator Machine Room                                                                                                                                                                                                                                                                                                                                                      N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes RB7 Reactor 2026-0 West Area                                                                    P                N              Yes    Yes RB8 Reactor 2026-0 East Area                                                                      P                N              Yes    Yes RB9 2101                                          Reactor                                                1974-0                    Tendon Access Gallery                                                                                                                                                                                                                                                                                                                                                                N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes RB10                                      Reactor                                                2047-6                    El 2047-6, Except Cable Tray Area                                                                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes RB11 2102                                          Reactor                                            Multiple                Area Within Primary Shield Wall                                                                                                                                                                                                                                                  N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 25 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 10 of 14)
 
Fire Area                                    Rm #                                  Bldg.                                        Elev.                                                                                          Description                                                                                                              Auto.                                                Auto.                                              PFSSD                                        RCA                            FHA Detection                                    Suppression                                                      Circuits                                    (Typ.)                          Page RW                                                                                                      7101                              Radwaste                                  1976-0                    Waste Gas Compressor Room No. 1                                                                                                                                                                                        N                                                                                                            243 (Note 6)      N No Yes 7102                              Radwaste                                  1976-0                    Hydrogen Recombiner Room No. 1                                                                                                                                                                                                            N (Note 6)      N No Yes
 
7103                              Radwaste                                  1976-0                    Valve Room No. 1                                                                                                                                                                                                                                                                                                                                                                                                                                  T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes 7104                              Radwaste                                  1976-0                    Recycle Evaporator Feed Pump Room                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7105                              Radwaste                                  1976-0                    Recycle Hold-Up Tank Room No. 1                                                                                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes
 
7106                              Radwaste                                  1976-0                    Waste Gas Compressor Room No. 2                                                                                                                                                                                        N (Note 6)      N No Yes
 
7107                              Radwaste                                  1976-0                    Hydrogen Recombiner Room No. 2                                                                                                                                                                                                            N (Note 6)      N No Yes
 
7108                              Radwaste                                  1976-0                    Valve Room No. 2                                                                                                                                                                                                                                                                                                                                                                                                                                  T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes 7109                              Radwaste                                  1976-0                    Corridor No. 1                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes 7110                              Radwaste                                  1976-0                    Recycle Hold-Up Tank Room No. 2                                                                                                                                                                                                          N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes
 
7111                              Radwaste                                  1976-0                    Waste Gas Decay Tank Room No. 1                                                                                                                                                                                            N (Note 6)      N No Yes
 
7112                              Radwaste                                  1976-0                    Valve Room No. 3                                                                                                                                                                                                                                                                                                                                                                                                                                    N (Note 6)      N No Yes
 
7113                              Radwaste                                  1976-0                    Load Center and General Area                                                                                                                                                                                                                                                                  T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 7114 Radwaste    Stair  Radwaste, Stair RW-1                                                                        N                          N                          No            Yes
 
7115                              Radwaste                                  1976-0                    Waste Gas Decay Tank Room No. 2                                                                                                                                                                                            N (Note 6)      N No Yes
 
7116                              Radwaste                                  1976-0                    Valve Room No. 4                                                                                                                                                                                                                                                                                                                                                                                                                                    N (Note 6)      N No Yes
 
7117                              Radwaste                                  1976-0                    Corridor No. 2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes 7118 Radwaste  1976-0 Steam Gen Blowdown Surge Tank and Pump Room                              N N No Yes 7119                              Radwaste                                  1976-0                    Radioactive Pipe Chase                                                                                                                                                                                                                                                                                                                                                      N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7120                              Radwaste                                  1976-0                    Chemical Drain Tank and Pump Room                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7121                              Radwaste                                  1976-0                    Waste Evaporator Feed Pump Room                                                                                                                                                                                    T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes
 
7122                              Radwaste                                  1976-0                    Waste Hold-Up Tank Room                                                                                                                                                                                                                                                                                                              N (Note 6)      N No Yes 7123 Radwaste  1976-0 Waste Evaporator Bottoms Tank Room                                                                                                                                                                                                                                                              N Primary                                                                                                                                                                                (Note 6)      N No Yes 7124                              Radwaste                                  1976-0                    Waste Evaporator Bottoms Tank Pump Room                                                                    T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes 7125                              Radwaste                                  1976-0                    Floor Drain Tank Pump Room No. 1                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes
 
7126                              Radwaste                                  1976-0                    Floor Drain Tank Room No. 1                                                                                                                                                                                                                                                                                    N (Note 6)      N No Yes
 
7127                              Radwaste                                  1976-0                    Waste Monitor Tank and Pump Room                                                                                                                                                                            N (Note 6)      N No Yes
 
7128                              Radwaste                                  1976-0                    Floor Drain Tank Pump Room No. 2                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes
 
7129                              Radwaste                                  1976-0                    Floor Drain Tank Room No. 2                                                                                                                                                                                                                                                                                    N (Note 6)      N No Yes 7130 Radwaste  1976-0 Waste Evaporator Condensate Tank and                                                                                                                                                                                                                                                            N Pump Room                                                                                                                                                                              (Note 6)      N No Yes 7131 Radwaste  1976-0 Vestibule                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          N (Note 6)      N No Yes
 
7132 Radwaste    Stair  Radwaste, Stair RW-2                                                                        N                          N                          No            Yes 7135 Radwaste  1976-0 Gaseous Radwaste Drain Collection Tk & Gas Decay Tk Drain Pump Room              N N No Yes 7201                              Radwaste                                  2000-0                    Recycle Evapor Room                                                                                                                                                                                                                                                                                                                                                                              N (Note 6)      N No Yes
 
7202                              Radwaste                                  2000-0                    Recycle Evaporator Valve Gallery                                                                                                                                                                                                                              N (Note 6)      N No Yes
 
7203                              Radwaste                                  2000-0                    Corridor No. 1                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes RW                                                                                                      7204                              Radwaste                                  2000-0                    Waste Evapor Room                                                                                                                                                                                                                                                                                                                                                                                                    N (Note 6)      N No Yes 7205                              Radwaste                                  2000-0                    Waste Evaporator Valve Gallery                                                                                                                                                                                                                                                    N (Note 6)      N No Yes Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 26 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 11 of 14)
 
Fire Area                                          Rm #                                          Bldg.                                              Elev.                                                                                                          Description                                                                                                                                Auto.                                                        Auto.                                                      PFSSD                                                RCA                                FHA Detection                                            Suppression                                                              Circuits                                            (Typ.)                              Page
 
7206                              Radwaste                                  2000-0                    SLWS Evaporator Reagent Tank Room                                                                                                                                                    N (Note 6)      N No Yes
 
7207                              Radwaste                                  2000-0                    SLWS Pump Room                                                                                                                                                                                                                                                                                                                                                                                                                    N (Note 6)      N No Yes
 
7208                              Radwaste                                  2000-0                    MCC Equipment, Load Center & General Area                                                            T                                                                                                                                                        N                                                                                                                                              Yes                                                                                Yes 7209 Radwaste  2000-0 Control Room                                                                                                T                          N                        Yes          Yes 7210                              Radwaste                                  2000-0                    Nuclear Sample Panel Room                                                                                                                                                                                                                                                                                      N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7211 Radwaste  2000-0 Sample Lab                                                                                                    N                          N                          No            Yes
 
7212                              Radwaste                                  2000-0                    Spent Resin Stg. Tank Room Primary                                                                                                                                                                            N (Note 6)      N No Yes
 
7213                              Radwaste                                  2000-0                    Corridor No. 3                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        N (Note 6)      N No Yes 7214 Radwaste  2000-0 Spent Resin and Evaporator Bottom Tk and                                                                                                                                                                                                                                                                                                      N Pump Room Secondary                                                                                                                                                                                              (Note 6)      N No Yes 7215                              Radwaste                                  2000-0                    Liquid Radwaste Demineralizer Room                                                                                                                                                                          N (Note 6)      N No Yes
 
7216                              Radwaste                                  2000-0                    Corridor No. 2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes
 
7217                              Radwaste                                  2000-0                    SLWS Monitor Tank Room                                                                                                                                                                                                                                                                                                                      N (Note 6)      N No Yes
 
7218                              Radwaste                                  2000-0                    Solid Radwaste Disposal Station                                                                                                                                                                                                                                              N (Note 6)      N No Yes
 
7219                              Radwaste                                  2000-0                    Solidification Control Panel Room                                                                                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes
 
7220 Radwaste  2000-0 Valve Room                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    N (Note 6)      N No Yes
 
7221                              Radwaste                                  2000-0                    Emergency Shower and Eyewash Area                                                                                                                                                        T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes 7222                              Radwaste                                  2000-0                    Misc. Storage Area                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes 7223 Radwaste  2000-0 Vestibule                                                                                                            T                          N                          No            Yes 7224                              Radwaste                                  2000-0                    High Level Drum Storage Area                                                                                                                                                                                                                                                                  N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7225                              Radwaste                                  2000-0                    Low Level Drum Storage Area                                                                                                                                                                                                                                                                        N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7226                              Radwaste                                  2000-0                    Empty Drum Storage / Truck Bay                                                                                                                                                                                                                                      T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes
 
7227 Radwaste  2000-0 Dewatering Station                                                                                                                                                                                                                                                                                                                                                                                            N (Note 6)      N No Yes
 
7228                              Radwaste                                  2000-0                    Drywaste Compactor Area                                                                                                                                                                                                                                                                                                                          T                                                                                                                                                        P                                                                                                                                                      No                                                                                      Yes
 
7229                              Radwaste                                  2000-0                    Concentrates Pump Room                                                                                                                                                                                                                                                                                                                          N (Note 6)      N No Yes
 
7230 Radwaste  2000-0 Instrument Rack Area                                                                                                                                                                                                                                                                                                                                                          N (Note 6)      N No Yes
 
7231                            Radwaste                                  2010-6                    Subcoolers and Condenser Room                                                                                                                                                                                                                    N                                                                                                                                                  N                                                                                                                                                No                                                                                    Yes 7232 Radwaste  2000-0 Elec Chase                                                                                                      T                          N                          No            Yes
 
7233                              Radwaste                                  2013-4                    Area Over Valve Room                                                                                                                                                                                                                                                                                                                                                                      N (Note 6)      N No Yes
 
7234                              Radwaste                                  2000-0                    Drum Storage Area A                                                                                                                                                                                                                                                                                                                                                                                        T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes 7235                              Radwaste                                  2000-0                    Drum Storage Area B                                                                                                                                                                                                                                                                                                                                                                                        T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes 7236                              Radwaste                                  2000-0                    Waste Bale Corridor                                                                                                                                                                                                                                                                                                                                                                                                        T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes 7301                              Radwaste                                  2022-0                    Radioactive Pipe Chase Area                                                                                                                                                                                                                                                                                  N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7302                              Radwaste                                  2022-0                    HVAC Equip Area                                                                                                                                                                                                                                                                                                                                                                                                                                    N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7303 Radwaste  2022-0 Vestibule                                                                                                            N                          N                          No            Yes 7304                              Radwaste                                  2022-0                    MCC Equip Area                                                                                                                                                                                                                                                                                                                                                                                                                                                  N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7305 Radwaste  2022-0 Electrical Chase                                                                                        T                          N                          No            Yes 7401                              Radwaste                                  2031-6                    Filter Compartment Typ of 19                                                                                                                                                                                                                                                                                    N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes RW                                                                                                      7402                              Radwaste                                  2031-6                    Valve Room Typ of 19                                                                                                                                                                                                                                                                                                                                                                            N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7403 Radwaste  2031-6 Corridor                                                                                                              T                          N                          No            Yes 7404                              Radwaste                                  2031-6                    Valve Room Typ of 12                                                                                                                                                                                                                                                                                                                                                                            N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7405                              Radwaste                                  2031-6                    Demineralizer Compartments, Typ of 12                                                                                                                                            N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 27 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 12 of 14)
 
Fire Area                                              Rm #                                            Bldg.                                                  Elev.                                                                                                                Description                                                                                                                                          Auto.                                                            Auto.                                                          PFSSD                                                  RCA                                  FHA Detection                                                Suppression                                                                    Circuits                                              (Typ.)                                Page 7406 Radwaste  2031-6 Valve Room                                                                                                    N                          N                          No            Yes
 
7407                              Radwaste                                  2031-6                    Fuel Pool Cleanup Demin Compartment                                                                                                                                              N (Note 6)      N No Yes
 
7408                            Radwaste                                  2031-6                    Laundry and Hot Shower Tank Area                                                                                                                                                                                                  N (Note 6)      N No Yes
 
7409                              Radwaste                                  2031-6                    Acid Tank Area                                                                                                                                                                                                                                                                                                                                                                                                                                                                        N (Note 6)      N No Yes
 
7410                              Radwaste                                  2031-6                    General Fl Area                                                                                                                                                                                                                                                                                                                                                                                                                                                                T                                                                                                                                                        N                                                                                                                                                    No                                                                                      Yes
 
7411                              Radwaste                                  2031-6                    Waste Monitor Tank Area                                                                                                                                                                                                                                                                                                                                      N (Note 6)      N No Yes
 
7413 Radwaste  2031-6 HVAC Platform                                                                                            N                          N                          No            Yes 7501                              Radwaste                                  2040-6                    General Fl Area                                                                                                                                                                                                                                                                                                                                                                                                                                                        N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7502                              Radwaste                                  2041-6                    General Fl Area                                                                                                                                                                                                                                                                                                                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7503                              Radwaste                                  2047-6                    General Fl Area                                                                                                                                                                                                                                                                                                                                                                                                                                                              N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes 7504 Radwaste  2051-6 Platform                                                                                                              N                          N                          No            Yes
 
None                            Radwaste Storage                                                2000-0                    Radwaste Storage Building                                                                                                                                                                                                                                                                                                              N                                                                                                                                                        T                                                                                                                                                      No                                                                                      Yes RW-1                                                                            7133                              Radwaste                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              246 Tunnel                                                      1974-0                    Elec. Chase Non Radioactive Pipe Tunnel & Personnel Access                      T N Yes Yes 7134                              Radwaste Tunnel                                                      1974-0                    Radioactive Pipe Tunnel                                                                                                                                                                                                                                                                                                                                                  N                                                                                                                                                      N                                                                                                                                                    No                                                                                      Yes RWST                                                                  9102                                                          Other                                                                                    N/A                                          Refueling Water Storage Tank & Valve House                                                                  N                                                                                                                                                      N                                                                                                                                              Yes                                                                                Yes                                                  265 SBO                                                                                SBOA                                                      SBO                                                                    2000-0                    SBO Diesel Generator KU01A                                                                                                                                                                                                                                                                          P                                                                                                                                                      N                                                                                                                                                    No                                                                                            No                                                        249 SBOB                                                      SBO                                                                    2000-0                    SBO Diesel Generator KU01B                                                                                                                                                                                                                                                                          P                                                                                                                                                      N                                                                                                                                                    No                                                                                            No SBOC                                                      SBO                                                                    2000-0                    SBO Diesel Generator KU01C                                                                                                                                                                                                                                                                        P                                                                                                                                                      N                                                                                                                                                    No                                                                                            No SBOD                                                      SBO                                                                    1981-5                    Manhole EMH175 and Duct Bank                                                                                                                                                                                                                                N                                                                                                                                                      N                                                                                                                                                    No                                                                                            No SBOE                                                      SBO                                                                    2000-0                    SBO Power Equipment Center                                                                                                                                                                                                                                                                    P                                                                                                                                                      N                                                                                                                                                    No                                                                                            No T-1                4101 Turbine    Stair Turbine, Stair T-1                                                          T                N              Yes      No          249 T-2                                                                                                          4301                                            Turbine                                                  2000-0                    General Fl Area, Col TF-TG, T8-A1                                                                                                                                                                                                          T                                                                                                                                                        P                                                                                                                                                Yes                                                                                      No                                                      254 4302                                            Turbine                                                  2000-0                    Condensate Vacuum Pump Area                                                                                                                                                                                                                                        T                                                                                                                                                        P                                                                                                                                                Yes                                                                                      No 4303 Turbine 2000-0 Air Compressor Area                                                    T                P                No        No 4304 Turbine 2000-0 Mens Toilet                                                                    N                N                No        No 4305 Turbine 2000-0 Womens Toilet                                                              N                N                No        No 4306 Turbine 2000-0 Janitors Closet                                                                N                N                No        No 4322                                            Turbine                                                  2000-0                    Truck Bay & Laydown Area                                                                                                                                                                                                                                                                                                                T                                                                                                                                                        P                                                                                                                                                Yes                                                                                      No 4351                                            Turbine                                                  2015-4                    General Floor Area                                                                                                                                                                                                                                                                                                                                                                                                                      T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No 4401                                            Turbine                                                  2033-0                    General Fl Area, Col TA-TG, T8-A1                                                                                                                                                                                                          T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No 4501                                            Turbine                                                  2065-0                    General Fl Area, Col TA-TG, T8-A1                                                                                                                                                                                                        N                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No 4504                                            Turbine                                                  2065-0                    EHC Control Cabinet Room                                                                                                                                                                                                                                                                                                        N                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No T-4                                                                                                          4308                                            Turbine                                                  2000-0                    Lube Oil Storage Tanks                                                                                                                                                                                                                                                                                                                                                              T                                                                                                                                                        T                                                                                                                                                      No                                                                                            No                                                        257 T-10                                                                                          4403                                            Turbine                                                  2033-0                    Lube Oil Reservoir Room                                                                                                                                                                                                                                                                                                                                        T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                        259 Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 28 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 13 of 14)
 
Fire Area                                      Rm #                                      Bldg.                                          Elev.                                                                                                Description                                                                                                                    Auto.                                                  Auto.                                                PFSSD                                          RCA                              FHA Detection                                        Suppression                                                        Circuits                                      (Typ.)                            Page TURB                                                                        4201                                            Turbine                                                  1983-0                    Condenser Pit - General Floor Area                                                                                                                                                                                                      P                                                                                                                                                        P                                                                                                                                                      No                                                                                            No                                                        261 4203 Turbine 1983-0 SGFP Turbine Lube Oil Conditioner, Cond Pump                            N P No No 4204 Turbine 1983-0 Secondary Liquid Waste Collection Tank Pumps                            N T No No 4205                                            Turbine                                                  1983-0                    High TDS & Low TDS Tank & Pump Area                                                                                                                          N                                                                                                                                                        T                                                                                                                                                      No                                                                                            No 4309 Turbine    Stair Turbine, Stair T-2                                                          N                N                No        No 4310 Turbine    Stair Turbine, Stair T-3                                                          N                N                No        No 4312 Turbine    Stair Turbine, Stair T-5                                                          N                N                No        No 4313 Turbine    Stair Turbine, Stair T-4                                                          N                N                No        No 4314 Turbine    Stair Turbine, Stair T-6                                                          N                N                No        No 4316                                            Turbine                                                  2000-0                    Condensate Polishing Area                                                                                                                                                                                                                                                                                                                T                                                                                                                                                        P                                                                                                                                                Yes                                                                                      No 4317                                            Turbine                                                  2000-0                    Process Sampling Lab                                                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 4318                                            Turbine                                                  2000-0                    Turbine Cool Water Heat Exchange Area                                                                                                                                  T                                                                                                                                                        T                                                                                                                                                      No                                                                                            No 4319                                            Turbine                                                  2000-0                    Condensate Chemical Add Units Area                                                                                                                                                                        T                                                                                                                                                        T                                                                                                                                                      No                                                                                            No 4320                                            Turbine                                                  2000-0                    Secondary Liquids Drain Collection Tanks                                                                                                                      T                                                                                                                                                        T                                                                                                                                                      No                                                                                            No 4321                                            Turbine                                                  2000-0                    Railroad Bay & Laydown Area                                                                                                                                                                                                                                                                            P                                                                                                                                                        T                                                                                                                                                      No                                                                                            No 4323                                            Turbine                                                  2010-0                    Cold Chemistry Lab                                                                                                                                                                                                                                                                                                                                                                                                              T                                                                                                                                                        N                                                                                                                                              Yes                                                                                      No 4324                                            Turbine                                                  2000-0                    Acid Day Tank Area                                                                                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        P                                                                                                                                                      No                                                                                            No 4325                                            Turbine                                                  2000-0                    Caustic Day Tank Area                                                                                                                                                                                                                                                                                                                                                                    T                                                                                                                                                        P                                                                                                                                                      No                                                                                            No 4326 Turbine 2000-0 Ph Control & O2 Control Chemical Storage Area                              T T No No 4402 Turbine 2033-0 Battery Room                                                                  T                N                No        No 4404 Turbine 2033-0 Battery Room                                                                  T                N              Yes      No 4405 Turbine 2033-0 Battery Charger Room                                                T                N              Yes      No 4502 Turbine 2065-0 Womens Toilet                                                              N                N                No        No 4503 Turbine 2065-0 Mens Toilet                                                                    N                N                No        No 4505                                            Turbine                                                  2065-0                    Turbine Deck office and Storage Area                                                                                                                                                                          N                                                                                                                                                        T                                                                                                                                                      No                                                                                            No 4601                                            Turbine                                                  2083-0                    Elevator Machine Room                                                                                                                                                                                                                                                                                                                                                      N                                                                                                                                                      N                                                                                                                                                    No                                                                                            No 4301E                                            Turbine                                                  2000-0                    General Fl Area, Col TA-TD, T4-T8                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                      No                                                                                            No 4301W                                        Turbine                                                  2000-0                    General Fl Area, Col TD-TG, T4-T8                                                                                                                                                                                                          T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No 4401E                                            Turbine                                                  2033-0                    General Fl Area, Col TA-TD, T1-T8                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                      No                                                                                            No 4401W                                        Turbine                                                  2033-0                    General Fl Area, Col TD-TG, T1-T8                                                                                                                                                                                                          T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No 4501E                                            Turbine                                                  2065-0                    General Fl Area, Col TA-TD, T1-T8                                                                                                                                                                                                            P                                                                                                                                                        P                                                                                                                                                Yes                                                                                      No 4501W                                        Turbine                                                  2065-0                    General Fl Area, Col TD-TG, T1-T8                                                                                                                                                                                                        N                                                                                                                                                      N                                                                                                                                              Yes                                                                                      No OP-1 Turbine  2065-0 Observation Post                                                            N                N                No        No OP-2 Turbine  2000-0 Observation Post                                                            N                N                No        No OP-7 Turbine  2087-0 Observation Post                                                            N                N                No        No YARD-ESF                                                                                                      EXFMR                                                      Yard                                                                    2000-0                    ESF Transformer XNB01                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                        267 EXFMR                                                      Yard                                                                    2000-0                    ESF Transformer XNB02                                                                                                                                                                                                                                                                                                                                            T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No
 
YARD-SU              SXFMR                                                      Yard                                                                    2000-0                    Startup Transformer XMR01                                                                                                                                                                                                                                                                                                  T                                                                                                                                                        T                                                                                                                                                Yes                                                                                      No                                                        269 ESWC                                                                                    8000                                                          ESWC                                                        2000-0                    ESW Vertical Loop Chase                                                                                                                                                                                                                                                                                                                              T                                                                                                                                                        N                                                                                                                                                    No                                                                                            No                                                        243
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Page 29 of 275 Fire Hazard Analysis
 
ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 14 of 14)
Legend:
 
T -  Total Coverage P -    Partial Coverage N -    No Coverage
 
Notes:
: 1.                                                                                      Fire Areas A-29 and A-30 contain no fire detectors. These areas contain low fixed and transient combustibles. Each area consists of three small rooms.
: 2.                                                                                      Fire Areas A-9 and A-10 consist of one room each, which can be high radiation areas (depending upon plant conditions). The rooms contain low fixed and transient combustibles. Typically, only mechanical equipment and piping are present.
: 3.                                                                                      Electrical Chase is open to the area above suspended ceiling where smoke detection and sprinkler protection is provided.
: 4.                                                                                      Fire Area C-35 has no detection. Low fixed combustibles are present.
: 5.                                                                                      Fire Areas C-36 and C-37 are small electrical chases containing separation group 2 and 3 circuits, respectively. A wet pipe sprinkler system is installed. Transient combustibles are low. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
: 6.                                                                                      Room is open to an area with detection.
: 7.                                                                                      A fixed manual water spray system is provided for the steam driven auxiliary feedwater pump lubricating oil lines and bearings.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 30 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 1 of 244)
 
Fire Area A-1 (Reference A-1801)
 
A.1.1                                                                                                        Fire Area Description
 
Auxiliary building - El. 1974 1988, general area Rooms 1101, 1102, 1103, 1104, 1105 1106, 1115, 1120, 1121,1122, 1123, 1124, 1125, 1128, 1129 1130, 1201, 1202, 1203, 1204, and 1205.
 
A.1.2 Major Equipment
 
Letdown heat exchanger and associated piping, valves and instrumentation, reactor makeup water pumps, normal charging pump, CVCS chiller pumps, moderating heat exchanger, letdown reheat heat exchanger, letdown chiller heat exchanger, chiller surge tank,  CVCS chiller unit, auxiliary steam deaerator feed pumps, auxiliary steam condenser recovery and storage tank, auxiliary building sump pumps, auxiliary feedwater pump room sump and sump pumps.
 
A.1.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 31 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 2 of 244)
Table A.1.3-1 Fire Area A-1, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                                                        M-663-00017A Closure Component Category North equipment hatch                                                                                                                                                                                                                                                                                                                                                                        Hatch South equipment hatch                                                                                                                                                                                                                                                                                                                                                                  Hatch Hatches for RHR & containment spray                                                                                    Hatch valve encapsulation tanks Flanges for encapsulated valve                                                                                          Fire Barrier Tanks Personnel hatch from Room 1129 to 1207                            Hatch Dumbwaiter doors and shaft                                                                                                                                                                                                                                                                          Fire Door South personnel elevator doors and shaft                                      Fire Door 1-hour rated fire wrap protection for                                                                                  Fire Wrap redundant PFSSD circuits Penetration seals that exceed the                                                                                      Penetration Seal bounding limitations of M-663-00017 Structural Steel Fireproofing with                                                                                      Structural Steel Fireproofing unprotected thermal shorts
 
The letdown heat exchanger (Room 1125) and the valve compartment (Room 1124) are enclosed by 18-inch-thick (minimum) concrete walls. Openings are located in these walls, near the ceiling, for venting these rooms in the event of a high-energy pipe break.
The normal charging pump  room (Room 1115) is enclosed by 2-foot-thick concrete walls with a 3-hour-rated fire door and penetration seals. However, Room 1115 is not credited as a separate Fire Area.
 
A.1.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-1 is Low.
 
A.1.5 Fire Protection
 
An automatic smoke detection system  is installed in this area, except as noted in Attachment A. Manual-pull stations are located at exit doors. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control  Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Attachment A summarizes the partial automatic suppression coverage provided for this Fire Area. Specifically, an automatic preaction-type sprinkler system is installed over inaccessible cable tray concentrations in Rooms 1101, 1102, 1130, and    1122. The system also provides protection for the north and south hatchways at the ceiling    of this area (El. 2000'). Sprinklers are located to minimize  obstructions with structural steel.
 
Hose stations and portable extinguishers are located throughout the  area, as delineated on drawing A-1801.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 32 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 3 of 244)
Access to this area for manual  firefighting is available as follows:
: a.                        Stairwell 4101 from the Turbine Building.
: b.                        Stairwell 1119 at the south end from El. 2000'-0".
: c.                          Stairwell 1127 at the north end from El. 2000'-0".
: d.                        Control Building through Access Control.
One 4-inch drain per 1,000 square feet of floor area is provided throughout this Fire Area.
The floor drains are piped to the Auxiliary Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.1.6                                                                                                        Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.1.7 Analysis
 
A.1.7.1 Fire Suppression
 
The automatic detection system will provide an early warning of a fire  in this area. Hose stations or portable extinguishers can be used to suppress the fire. The automatic sprinkler system installed over the  cable trays will actuate to control a fire below and to assist the  fire brigade by keeping the environment cool. The sprinkler actuation  or a malfunction will be identified by Control Room annunciation. In the event of a failure of the automatic system, the fire can be  extinguished manually, using hose stations and/or portable  extinguishers. Adequate floor drains are provided to remove the fire suppression system discharge.
 
A.1.7.2                                                                                                                                    Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-1 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-1.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 33 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 4 of 244)
Fire Area A-2 (Reference A-1801)
 
A.2.1                                                                                                        Fire Area Description
 
Auxiliary Building safety-related pump area Rooms 1111, 1112, 1113, and 1114.
 
A.2.2 Major Equipment
 
Centrifugal charging pump, safety-injection pump, RHR pump, containment spray pump, coolers for the above pump rooms, RHR room sump pumps, valves, and piping auxiliary lube oil pump for the centrifugal charging pump.
 
A.2.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.2.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.2.3-1 Fire Area A-2, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                    M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                  Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                                          Structural Steel Fireproofing unprotected thermal shorts
 
The Centrifugal Charging Pump Room 1114, is separated from the Safety-Injection Pump Room 1113, by a 2-foot-thick concrete wall with a 3 foot 4 inch x 7 foot 2 inch access way.
 
The RHR Pump Room 1111, is separated from the other rooms by 2-foot-thick concrete walls. A 3-hour fire door is provided for access to this room from Room 1112. However, Room 1111 is not credited as a separate Fire Area.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 34 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 5 of 244)
A.2.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-2 is Low.
 
A.2.5 Fire Protection
 
Smoke detectors are installed in each room. Manual-pull  fire alarm stations are located near the exit doorways for this  elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Hose stations and portable extinguishers are located in  Rooms 1101 and 1122 (corridors). In addition, portable fire extinguishers are located within the Fire Area, in Rooms 1112 and 1113. Specific fire hose and extinguisher locations are delineated on drawing A-1801.
 
Access to Room 1112 is from Room 1121  (corridor) through a watertight door. Access to Room 1111 is from Room 1112 through a 3-hour-rated fire door. Access to Rooms 1113 and 1114 is from Room 1101 through a watertight door.
 
Rooms 1113 and 1114 have two 4-inch floor drains per room. There is  one 4-inch floor drain in Rooms 1111 and 1112. A sump with two sump  pumps is located in Room 1111.
The floor drains are piped to this  sump. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.2.6                                                                                                        Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.2.7 Analysis
 
A.2.7.1 Fire Suppression
 
This area is protected from a fire in adjacent areas by 3-hour  barriers. A fire in this area will be detected and alarmed by the  automatic detection system. The fire can be extinguished manually,  using hose stations and/or portable extinguishers. A fire in this  area will be contained by the fire barriers, until extinguished  manually. Adequate drainage is provided in each room to drain away  the fire-fighting water. The watertight doors will protect the safe shutdown equipment from damage by water discharge from extinguishing systems in the adjacent areas.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 35 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 6 of 244)
A.2.7.2                                                                                                                                    Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-2 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-2 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-2.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 36 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 7 of 244)
Fire Area A-3 (Reference A-1801 and A-1803)
 
A.3.1                                                                                                        Fire Area Description
 
Boric Acid Tank Rooms 1116, 1117, and 1407.
 
A.3.2 Major Equipment
 
Boric acid tanks and transfer pumps, unit heaters, boric acid batching tank, boron injection makeup pump, and piping and valves. None are required for safe shutdown following a fire.
 
A.3.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.3.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.3.3-1 Fire Area A-3, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                            M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                                                Structural Steel Fireproofing unprotected thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 37 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 8 of 244)
The Fire Area extends from Elevation 1974 to the floor slab of Elevation 2047 feet - 6 inches. Room 1116 houses the Separation Group 4 boric acid tank and transfer pump.
The corresponding Separation Group 1 equipment is located in Room 1117. Rooms 1116 and 1117 are separated by a 6-foot-high, 12-inch-thick concrete barrier wall with no openings, which acts as a radiant heat shield. The redundant transfer pumps are located approximately 4 feet away from the barrier wall. A 6-foot-wide platform extending from the east to the west fire barrier is located at Elevation 2013. Steps are provided to Elevation 2026 from the platform with an intermediate landing at Elevation 2015 feet - 3 inches.
The boric acid batching tank and the boron injection makeup pumps are located on steel grating above Elevation 2026.
 
A.3.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-3 is Low.
 
A.3.5 Fire Protection
 
A smoke detector is installed under the Elevation 2026 slab in Rooms 1116 and 1117.
One infrared flame detector is installed on either side of the 6-foot-high barrier wall to provide early warning of a fire at the floor elevation. Manual-pull stations located at the exit doors on this floor can also provide warning in the event of a fire. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
A hose station and one portable extinguisher are located in the corridor (Room 1101),
outside Room 1116, and in Room 1122, as delineated on drawing A-1801. For fighting a fire from the platform or at Room 1407, the hose stations in Room 1408 can be used (see A-1803). Additional hose lengths can be added (if required) for manual fire fighting above the boric acid tanks. Access for manual fire fighting at the floor elevation is from Room 1122 for Room 1117 and from Room 1101 for Room 1116. For access to Rooms 1101 and 1122, see Fire Area A-1.
 
Access to Room 1407 and the platform is from Room 1408. For a description of access to Room 1408, see Fire Area A-16.
 
A 4-inch floor drain is provided in each room. The floor drains are located 10 feet away from the barrier wall. The floor drains discharge to a sump in the corridor area, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.3.6                                                                                                        Isolation and Smoke Removal
 
A fire in this area will be contained by the fire barriers. The  barrier wall will protect one room from a floor fire in the other. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 38 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 9 of 244)
A.3.7 Analysis
 
A.3.7.1 Fire Suppression
 
Due to the fire barrier separation, a fire in one of the adjacent areas cannot damage the equipment in this area. A fire in one of the rooms at Elevation 1974 will be detected and alarmed by the flame detectors and/or smoke detectors. The fire can be extinguished manually, using the hose stations and/or the portable extinguishers. A fire in this area will be contained by the fire barriers until extinguished. The combustible loading is low. Since the floor on either side of the barrier slopes to drains in the middle of each room, any transient combustible spill (such as lube oil) will flow away from the barrier wall.
 
Since there is no equipment requiring maintenance in the vicinity of  the platform, introduction of transient combustibles in such  quantities as to cause fire damage at this elevation is unlikely. A  fire in the cable tray will be detected and alarmed by the smoke  detector located in this fire area.
The fire can be extinguished from the  platform (or the steps leading to the platform) by manual hose stream  brought in from Room 1408. A fire in Room 1407 will be detected and alarmed by the detectors in the ceiling.
The fire can be extinguished  manually by hose stream brought in from Room 1408. The floor drains in Rooms 1116 and 1117 are adequate to drain the fire fighting water. The floor slopes away from the access doors and barrier walls to the floor drains in the corridor in these rooms.
Therefore, an extinguishing system discharge in one of the adjacent areas will not damage the equipment within this fire area.
 
A.3.7.2                                                                                                                                    Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-3 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-3 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-3.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 39 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 10 of 244)
Fire Area A-4 (Reference A-1801)
 
A.4.1                                                                                                        Fire Area Description
 
Auxiliary building safety-related pump area Rooms 1107, 1108, 1109, and 1110.
 
A.4.2 Major Equipment
 
Centrifugal charging pump, safety-injection pump, RHR pump, containment spray pump, coolers for the above pump rooms, RHR room sump pumps, and auxiliary lube oil pump for the centrifugal charging pump.
 
A.4.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.4.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.4.3-1 Fire Area A-4, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                    M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                  Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                                          Structural Steel Fireproofing unprotected thermal shorts
 
The Centrifugal Charging Pump Room, is separated from the Safety-Injection  Pump Room 1108, by a 2-foot-thick concrete wall with a 3 foot 4  inch x 7 foot 2 inch access way. The RHR Pump Room 1109, is separated from the other rooms by a 2-foot-thick concrete wall. A 3-hour fire door is provided for access to this room from Room 1110.
However, Room 1109 is not credited as a separate Fire Area.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 40 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 11 of 244)
A.4.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-4 is Low.
 
A.4.5 Fire Protection
 
Smoke detectors are installed in each room. Manual-pull fire alarm stations are located near the exit doorways for  this elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
A hose station and a portable extinguisher are located in Room 1101. In addition, portable extinguishers are located within the fire area, in Rooms 1110 and 1108. Hose stations and portable extinguishers are also located in Rooms 1120 and 1121 (corridors).
Specific fire hose and extinguisher locations are delineated on drawing A-1801.
 
Access to Room 1110 is from Room 1121  (corridor) through a watertight door. Access to Room 1109 is from Room 1110 through a 3-hour fire-rated door. Access to Rooms 1107 and 1108 is from Room 1101 through a watertight door.
 
Rooms 1107 and 1108 have two 4-inch floor drains each. There is one  4-inch floor drain in Rooms 1110 and 1109. A sump with two sump pumps  is located in Room 1109. The floor drains are piped to this sump. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.4.6                                                                                                        Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.4.7 Analysis
 
A.4.7.1 Fire Suppression
 
A fire in this area will be detected and  alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers. A fire in this area will be contained by the fire barriers until extinguished manually. Adequate drainage is provided  in each room to remove the fire-fighting water. The watertight doors  will protect the safe shutdown equipment from damage by water  discharge from extinguishing systems in the adjacent areas.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 41 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 12 of 244)
A.4.7.2                                                                                                                                    Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-4 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-4 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-4.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 42 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 13 of 244)
Fire Area A-5 (Reference A-1801 thru A-1804)
 
A.5.1                                                                                                        Fire Area Description
 
Auxiliary Building Stairway Room 1119, Elevator Shaft, and Elevator Penthouse Room 1601.
 
A.5.2 Major Equipment
 
Electric cable and elevator.
 
A.5.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.5.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.5.3-1 Fire Area A-5, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                        M-663-00017A Closure Component Category South personnel elevator doors and shaft                                                                        Fire Door Penetration seals that exceed the bounding                                    Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                                            Structural Steel Fireproofing unprotected thermal shorts
 
Since no Fire Areas are above the ceiling, it is not rated. Roof construction  is non-combustible concrete with built up Class A roofing. Therefore,  structural integrity will be maintained in the event of a fire.
 
A.5.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-5 is Low.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 43 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 14 of 244)
 
A.5.5 Fire Protection
 
A smoke detector is installed at the ceiling of the  stairwell. Smoke detectors are installed at the elevator lobby on  each floor. Manual-pull stations are located near the exit doors on each floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control  Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Hose stations and portable extinguishers are located outside the  stairway on each floor.
 
Access to the Fire Area is achieved from any floor elevation of the stairwell, as depicted on drawings A-1801 thru A-1804.
 
No drains are provided for this Fire Area, as manual fire water suppression efforts will be minimal, considering the limited combustible loading and equipment in the Fire Area.
Additionally, a floor drain is located in Fire Area  A-1 just outside the stairwell door at the 1974 elevation. There are no PFSSD equipment or circuits in this area. Therefore, water accumulation in the area would not affect safe shutdown capability.
 
A.5.6                                                                                                        Isolation and Smoke Removal
 
A fire in the stairway or elevator will be confined by the fire  barriers until extinguished.
Refer to Section 4.3.7.2 for smoke removal discussion.
 
A.5.7 Analysis
 
A.5.7.1 Fire Suppression
 
The stairwell and elevator will be protected from a fire in the  adjoining areas by the fire-rated barriers. A fire in the stairway  will be detected and alarmed by the smoke detector. The fire will  be contained by the fire-rated barrier until extinguished manually,  using the hose stations and/or portable extinguishers.
 
A.5.7.2                                                                                                                                    Safe Shutdown Capability
 
There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-5.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 44 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 15 of 244)
Fire Area A-6 (Reference A-1801 thru A-1804)
 
A.6.1                                                                                                        Fire Area Description
 
Auxiliary Building Stairway Room 1127
 
A.6.2 Major Equipment
 
Electric cable.
 
A.6.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.6.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.6.3-1 Fire Area A-6, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                M-663-00017A Closure Component Category 3-hour rated fire wrap protection for                                                Fire Wrap redundant PFSSD circuits Penetration seals that exceed the bounding                                          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                                                  Structural Steel Fireproofing unprotected thermal shorts
 
The ceiling in this area forms part  of the roof. Since no fire areas are above the ceiling, it is not rated. Roof construction is non-combustible concrete with built up  Class A roofing.
Therefore, structural integrity will be maintained  in the event of a fire.
 
A.6.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-6 is Low.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 45 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 16 of 244)
 
A.6.5 Fire Protection
 
A smoke detector is installed at the ceiling of the  stairway tower. The addressable detector alarms locally and in the Control Room. Manual-pull stations are located near the exit doors on each floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Hose stations and portable extinguishers are  located outside the stairwell on each floor.
 
Access to the Fire Area is achieved from any floor elevation of the stairwell, as depicted on drawings A-1801 thru A-1804.
 
No drains are provided for this Fire Area, as manual fire water suppression efforts will be minimal, considering the limited combustible loading and equipment in the Fire Area.
Additionally, a floor drain is located in Fire Area  A-1 just outside the stairwell door at the lowest (1974) elevation. There is no PFSSD equipment susceptible to water damage in this area. Therefore, water accumulation in the area would not affect safe shutdown capability.
 
A.6.6                                                                                                        Isolation and Smoke Removal
 
A fire in the stairway will be contained by the fire barriers until  extinguished. Refer to Section 4.3.7.2 for smoke removal discussion.
 
A.6.7 Analysis
 
A.6.7.1 Fire Suppression
 
The fire barriers will protect the stairwell from a fire in the  adjacent areas.
A fire in the stairway will be detected and alarmed  by the smoke detector.
The fire can be extinguished manually,  using the hose stations and portable extinguishers located at each  floor. A fire within the stairway will be contained by the fire  barriers until extinguished.
 
A.6.7.2                                                                                                                                    Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-6 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-6 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-6.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 46 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 17 of 244)
Fire Area A-7 (Reference A-1801)
 
A.7.1                                                                                                        Fire Area Description
 
Boron Injection Tank and Pump Room 1126.
 
A.7.2 Major Equipment
 
Boron injection tank, boron injection surge tank, boron injection recirculation pumps, piping, and valves.
 
A.7.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.7.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.7.3-1 Fire Area A-7, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                      M-663-00017A Closure Component Category Structural Steel Fireproofing with                                        Structural Steel Fireproofing unprotected thermal shorts
 
A.7.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-7 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 47 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 18 of 244)
A.7.5 Fire Protection
 
A smoke detector is installed at the ceiling of this area. A  manual-pull station is provided in the corridor adjacent to the  watertight door. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
A hose station and two portable extinguishers are located in Room 1122 (corridor),
adjacent to the access door.
 
Access to this area is from Room 1122 through a watertight door. For access  to Room 1122, see Fire Area A-1.
 
One 4-inch floor drain with a sealed  cover (to prevent back flooding) is located in this area. The drain is piped to the Auxiliary Building floor drain sump; however, it would  not be available during a fire. Fire-fighting water would drain from  the room through the open door and into the Auxiliary Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.7.6                                                                                                        Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.7.7 Analysis
 
A.7.7.1 Fire Suppression
 
The fire barriers protect the components within the area from a fire  in the adjacent areas. A fire in this area will be detected and  alarmed by the smoke detector. The fire can be extinguished  manually, using the hose station and/or portable extinguishers located  outside the area. The watertight door will protect the equipment in  this area against damage from a fire suppression system discharge in the adjacent area.
 
A.7.7.2                                                                                                                                    Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-7 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-7 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-7.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 48 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 19 of 244)
Fire Area A-8 (Reference A-1802)
 
A.8.1                                                                                                        Fire Area Description
 
Auxiliary building - El. 2000, general area Rooms 1301, 1302, 1306, 1307, 1308, 1311, 1312, 1313, 1314, 1315, 1318, 1319, 1320, and 1321.
 
A.8.2 Major Equipment
 
Volume control tank and associated piping and valves, containment spray additive tank, reactor coolant filter, seal water return filter, seal water injection filters (2), and boric acid filter, boron thermal regeneration demineralizers (5), cation bed demineralizer  and mixed bed demineralizers (2), resin charging tank, ground floor fan coil unit, auxiliary building sampling panel, and load center.
 
A.8.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.8.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 49 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 20 of 244)
Table A.8.3-1 Fire Area A-8, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                                                                    M-663-00017A Closure Component Category North equipment hatches                                                                                                                                                                                                                                                                                                                                                                                                  Hatch South equipment hatches                                                                                                                                                                                                                                                                                                                                                                                            Hatch Resin loading chute cover plate                                                                                                                                                                                                                                                                                    Hatch Hatches for RHR & containment spray valve                                                                                                  Hatch encapsulation tanks Containment post-tensioning hatch covers at                                                                                                Hatch C Buttress Dumbwaiter doors and shaft                                                                                                                                                                                                                                                                                                                                              Fire Door South personnel elevator doors and shaft                                                                                                          Fire Door Missile door 13331                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Fire Door Missile door 33044                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Fire Door 1-hour rated fire wrap protection for                                                                                                      Fire Wrap redundant PFSSD circuits Penetration seals that exceed the bounding                                                                                                  Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                                                              Structural Steel Fireproofing thermal shorts
 
The Volume Control Tank Room is separated from adjacent rooms by heavy concrete walls and a fire rated floor and ceiling. The wall separating the VCT from the seal water heat exchanger is fire rated for a minimum of 3 hours. Personnel access to the room is through a labyrinth opening with wire mesh doors.
 
Access to the Volume Control Tank Room is from Room 1320 through a door in Room 1318 and a labyrinth opening (Refer to A-1802). To promote radiological protection, an additional locked wire mesh door has been provided between Rooms 1313 and 1318.
The Volume Control Tank Room 1313 has the tank, piping, and two exposed conduits routed east-west 18 feet above the floor. The adjoining valve compartment, Room 1318, has two motor-operated valves, piping, manual valves, and five exposed conduits.
Therefore, the combustible loading in these two rooms is low. Since access from Room 1320 (corridor) is limited to these two rooms, the transient combustibles introduced into these rooms will be those required for maintenance of equipment located in these rooms.
Any cutting or welding operation will be administratively controlled. Therefore, the quantity of transient combustibles introduced into these rooms will be low and will not produce enough heat, in the event of a fire, to damage the tank, piping, and valves.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 50 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 21 of 244)
A.8.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-8 is Low.
 
The new resin for the demineralizers in Room 1319 will be brought in through the south end of the corridor and transported up to El. 2026 by the elevator in the south end. The resin will be in a hydrated  form  and therefore, does not ignite or sustain combustion easily. The demineralizers will be charged with new resin from the floor above. The demineralizers are ASME pressure vessels filled with water. Spent resin in the demineralizers is sluiced and piped to a spent resin storage tank located in the radwaste building. Consequently, the resin in the demineralizers do not pose a fire hazard.
 
The spent cartridges in the CVCS filters in Room 1302 will be moved to 55-gallon drums, sealed, and removed from the area. Administrative controls ensure that only new cartridges in quantities required for immediate use will be brought into this area and the containers are removed after they are emptied. The demineralizers and filters are not required for a safe shutdown of the plant.
 
A.8.5 Fire Protection
 
An automatic smoke detection system is  installed throughout the Fire Area except in several rooms with low combustible loading and no safe shutdown circuits or equipment (See Attachment A and XX-E-013). Manual-pull stations are  located at the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control    Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic preaction sprinkler system is installed over cable tray  concentrations in Rooms 1301, 1314, and 1320 as identified in Attachment  A. In the west corridor (Room 1301), additional sprinkler heads  are provided below the cable tray elevation between columns A-2 and A-4. These additional sprinkler heads are provided to protect the  cable trays from a transient fire located on the floor. This area  contains three racks of cable trays and other obstructions, which may  reduce the effectiveness of the ceiling-mounted sprinklers in controlling a transient  combustible fire. The system  also provides protection for the hatchways at the ceiling of this area  located at the north and south ends of the building. The hatches at  the center of the building are protected as detailed in M-663-00017A. Hose stations and portable extinguishers are located  throughout the area, as delineated on drawing A-1802.
 
Access to this area for manual fire fighting is available as follows:
: a.                        Stairwell 4101 from the Turbine Building.
: b.                        Stairwell 1119 (at the south end) from outside and other buildings.
: c.                          Stairwell 1127 (at the north end) from other elevations of the Auxiliary Building.
: d.                        Doors (at the south end) of Room 1301 from outside.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 51 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 22 of 244)
: e.                        Access to Room 1313 (Volume Control Tank Room) is through Room 1318 and Room 1320 (corridor).
: f.                                  Access to Room 1317 is from Room 1315 and Room 1316.
 
One 4-inch drain per 1,000 square feet of floor area is provided throughout this Fire Area.
Rooms 1313, 1318, 1311, and 1312 have one 4-inch floor drain per room. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974.
Sump pumps empty the sump. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.8.6                                                                                                        Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.8.7 Analysis
 
A.8.7.1 Fire Suppression
 
The smoke detection system installed throughout the Fire Area except where noted in Attachment A will provide early warning of a fire. Due to low combustible loading, detectors are not installed in the rooms where the CVCS demineralizers, filters, and volume control tank are located.
Hose stations and/or portable extinguishers can be used to extinguish a fire in these areas. The preaction sprinkler system installed over the cable tray concentration will actuate to control a fire below and keep the area cool for fire brigade entry. The sprinkler actuation or malfunction will be identified by Control Room annunciation. In the event of a failure of the automatic system, the fire can be extinguished manually using hose stations. Adequate floor drains are provided to remove the fire suppression system discharge. There is no safe shutdown equipment susceptible to water damage in this area.
 
The volume control tank in Room 1313 is enclosed by concrete walls of adequate thickness to prevent damage from a fire in the adjacent areas.
A water inventory is maintained within the tank at all times. The combustible loading in this area is low. Therefore, a fire in this room will not damage the tank.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 52 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 23 of 244)
A.8.7.2                                                                                                                                    Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-8 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-8 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-8.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 53 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 24 of 244)
Fire Area A-9 (Reference A-1802 and A-1803)
 
A.9.1                                                                                                        Fire Area Description
 
RHR Heat Exchanger Room 1309.
 
A.9.2 Major Equipment
 
RHR heat exchanger (B) and associated piping and valves.
 
A.9.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.9.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.9.3-1 Fire Area A-9, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                    M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                    Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                Structural Steel Fireproofing thermal shorts
 
This Fire area extends through two floor elevations. The ceiling forms the roof of the building and is not required to be fire rated. A hatch with a removable concrete cover is provided in the ceiling for pulling the tube bundle or the heat exchanger. A 1-foot-6-inch-thick, 8-foot-0-inch-high concrete partition wall is located within the Fire Area between the heat exchanger and the valve compartment.
 
A.9.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-9 is Low.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 54 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 25 of 244)
 
A.9.5 Fire Protection
 
Due to the low combustible loading in this area and the separation of redundant equipment by fire barriers, smoke detectors are not installed in this area. In the event of a fire in this area, plant notification can be made by the activation of a manual-pull station in the corridor.
 
Hose stations are located in Room 1301 outside the Fire Area. Two  portable extinguishers are located in Room 1301.
 
Access to this area  is from Room 1301 through a door. For access to Room 1301, see Fire Area A-8.
 
Two 4-inch floor drains, one on either side of the  partition wall, are provided. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974.
The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.9.6                                                                                                        Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.9.7 Analysis
 
A.9.7.1 Fire Suppression
 
The fire barriers protect the safe shutdown equipment from a  fire in adjacent areas. Hose stations or portable extinguishers are  available to manually extinguish a fire. A fire in this area will be  contained by the fire barriers. Adequate drainage is provided to  remove any fire-fighting water.
Since the floor in adjoining corridor  Room 1301 slopes away from the door to a floor drain, a fire suppression system discharge in the adjacent area cannot damage the equipment in this area.
 
A.9.7.2                                                                                                                                    Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-9 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-9 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-9.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 55 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 26 of 244)
Fire Area A-10 (Reference A-1802 and A-1803)
 
A.10.1                                                                                  Fire Area Description
 
RHR Heat Exchanger Room 1310.
 
A.10.2 Major Equipment
 
RHR heat exchanger (A) and associated piping and valves.
 
A.10.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.10.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.10.3-1 Fire Area A-10, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                      M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                      Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                  Structural Steel Fireproofing thermal shorts
 
This Fire Area extends through two floor elevations. The ceiling forms the roof of the building and is not required to be fire rated. A hatch with a removable concrete cover is provided in the ceiling for pulling the tube bundle or the heat exchanger. A 1-foot-6-inch-thick, 8-foot-0-inch-high concrete partition wall is located within the Fire Area between the heat exchanger and the valve compartment.
 
A.10.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-10 is Low.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 56 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 27 of 244)
 
A.10.5 Fire Protection
 
Due to low combustible loading and redundant train separation, smoke detectors are not installed in this area. In the event of a fire in this area, plant notification can be made by the activation of a manual-pull station in the corridor.
 
A hose station is located in Room 1301 outside the Fire Area. Two portable extinguishers are located in Room 1301.
 
Access to this area is from Room 1301 through a door. For access to Room 1301, see Fire Area A-8.
 
Two 4-inch floor drains, one on either side of the partition wall, are provided. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974.
The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.10.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.10.7 Analysis
 
A.10.7.1 Fire Suppression
 
The fire barriers protect the safe shutdown equipment from a  fire in adjacent areas. Hose stations or portable extinguishers can    be used to manually suppress a fire. The fire will be contained by  the fire barriers.
Adequate drainage is provided to remove the  fire-fighting water. Since the floor in the adjoining corridor Room  1301 slopes away from the door to a floor drain, a fire suppression  system discharge in the adjacent area cannot damage the equipment in this area.
 
A.10.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-10 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-10 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-10.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 57 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 28 of 244)
Fire Area A-11 (Reference A-1802)
 
A.11.1                                                                                  Fire Area Description
 
Cable Chase Room 1335, Auxiliary Building - El. 2000 to 2026.
 
A.11.2 Major Equipment
 
Electric cable only.
 
A.11.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.11.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.11.3-1 Fire Area A-11, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with unprotected                          Structural Steel Fireproofing thermal shorts
 
A.11.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-11 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 58 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 29 of 244)
A.11.5 Fire Protection
 
Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located at normal exits from this floor area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Room 1320 (Fire Area A-8).
 
Access to the chase is through a 3 foot 6 inch by 4 foot 0 inch, 3-hour-rated fire door. The access door is within 25 feet of the hose station.
 
Drainage in this area is by one 4-inch floor drain. This is more than adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Auxiliary Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.11.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.11.7 Analysis
 
A.11.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  hose streams can be directed through the access opening to extinguish  the fire.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 59 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 30 of 244)
A.11.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-11 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-11 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-11.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 60 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 31 of 244)
Fire Area A-12 (Reference A-1802)
 
A.12.1                                                                                  Fire Area Description
 
Cable Chase Room 1336, Auxiliary Building - El. 2000 to 2026.
 
A.12.2 Major Equipment
 
Electric cable only
 
A.12.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.12.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.12.3-1 Fire Area A-12, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with unprotected                          Structural Steel Fireproofing thermal shorts
 
A.12.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-12 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 61 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 32 of 244)
A.12.5 Fire Protection
 
Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located at normal exits from this floor area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Room 1314 (Fire Area A-8).
 
Access to the chase is through a 3 foot 6 inch by 4 foot,  3-hour-rated door. The access door is within 30 feet of the hose  station.
 
Drainage in this area is by one 4-inch floor drain. This is more than  adequate to handle maximum sprinkler system discharge or hose station  discharge. The drain discharges to the 1974 elevation and ultimately to the Auxiliary Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.12.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.12.7 Analysis
 
A.12.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers until extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
A.12.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-12 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-12 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-12.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 62 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 33 of 244)
Fire Area A-13 (Reference A-1802)
 
A.13.1                                                                                  Fire Area Description
 
Auxiliary Feedwater Pump Room 1325.
 
A.13.2 Major Equipment
 
Motor-driven auxiliary feedwater pump B and pump room cooler.
 
A.13.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.13.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.13.3-1 Fire Area A-13, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                              M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                            Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                        Structural Steel Fireproofing thermal shorts
 
Watertight doors with 6-inch-high curb are located in the south and east fire barrier walls.
 
A.13.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-13 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 63 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 34 of 244)
A.13.5 Fire Protection
 
Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
A hose station and two portable extinguishers are located in the corridor  (Room 1329) outside this fire area. All areas are within reach of  this hose station.
 
Access for manual firefighting is through a  watertight door from Room 1329. Access to Room 1329 is from the Turbine Building.
 
Two 4-inch floor drains are provided in this area. The floor drain is piped to the Auxiliary Feedwater Room sump located in Room 1128 (El. 1974). The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
A.13.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.13.7 Analysis
 
A.13.7.1 Fire Suppression
 
This area is protected from a fire in the adjacent areas by fire barriers. A fire in the area will be detected and  alarmed by the automatic detection system. The fire can be extinguished manually, using the hose station and/or the portable extinguishers located in the adjoining corridor (Room 1329). A fire will be contained by the fire barriers until extinguished.
Adequate drainage is provided to drain the fire-fighting water. The watertight doors will protect the safe shutdown equipment from damage by water discharged by extinguishing systems in the adjacent areas.
 
A.13.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-13 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-13 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 64 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 35 of 244)
Fire Area A-14 (Reference A-1802)
 
A.14.1                                                                                  Fire Area Description
 
Auxiliary Feedwater Pump Room 1326.
 
A.14.2 Major Equipment
 
Motor-driven auxiliary feedwater pump A and pump room cooler.
 
A.14.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.14.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.14.3-1 Fire Area A-14, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                      M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                    Structural Steel Fireproofing thermal shorts
 
A watertight door with 6-inch-high curb is located in the east fire barrier walls.
 
A.14.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-14 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 65 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 36 of 244)
A.14.5 Fire Protection
 
Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
A hose station and two portable extinguishers are located in the corridor (Room 1329) outside this fire area. All areas are within reach of this hose station.
 
Access for manual fire fighting is through a watertight door from Room 1329. Access to Room 1329 is from the Turbine Building.
 
Two 4-inch floor drains are provided in this area. The floor drain is piped to the Auxiliary Feedwater Room sump located in Room 1128 (Elevation 1974). The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
A.14.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.14.7 Analysis
 
A.14.7.1 Fire Suppression
 
This area is protected from a fire in the adjacent areas by fire barriers. A fire in the area will be detected and  alarmed by the automatic detection system. The fire can be extinguished manually, using the hose station and/or the portable extinguishers located in the adjoining corridor (Room 1329). A fire will be contained by the fire barriers. Adequate drainage is provided to drain all fire-fighting water. The watertight doors will protect the safe shutdown equipment from damage by water discharge from extinguishing systems in the adjacent areas.
 
A.14.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-14 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-14 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 66 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 37 of 244)
Fire Area A-15 (Reference A-1802)
 
A.15.1                                                                                  Fire Area Description
 
Auxiliary Feedwater Pump Room 1331.
 
A.15.2 Major Equipment
 
Turbine-driven auxiliary feedwater pump.
 
A.15.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.15.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.15.3-1 Fire Area A-15, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                                  M-663-00017A Closure Component Category Blowout panel                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    Hatch Penetration seals that exceed the bounding                                                                Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                            Structural Steel Fireproofing thermal shorts
 
A watertight, missile-protection door with 6-inch- high curb is located in the west fire barrier wall.
 
A.15.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-15 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 67 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 38 of 244)
A.15.5 Fire Protection
 
Automatic smoke detection is provided in this area. Rate-compensated thermal detectors are also installed in this area. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
A hose station and two portable extinguishers are located in  the corridor (Room 1329) outside this Fire Area. All areas are within  reach of this hose station. In addition to the above, a manually charged fixed water spray system is installed to protect the turbine  and pump lubricating oil lines and bearings. A manual system  precludes any water damage to the turbine due to inadvertent  actuation. The manual valve to activate the system is located outside the Fire  Area in Room 1329 and is electrically supervised.
 
Access for manual fire fighting is through a watertight door from Room 1329. Access to Room 1329 is from the Turbine Building.
 
Two 4-inch floor drains are provided in this area. The floor drain is piped to the Auxiliary Feedwater Room sump located in Room 1128 (El. 1974). The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
A.15.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.15.7 Analysis
 
A.15.7.1 Fire Suppression
 
This area is protected from a fire in the adjacent areas by fire barriers. A fire in the area will be detected and  alarmed by the automatic detection system. The manual spray system  can be actuated to extinguish the fire.
In case of a malfunction of  the spray system, the hose station and/or the portable extinguishers  located in the adjoining corridor (Room 1329) will provide adequate backup for fire suppression. A fire will be contained by the fire barriers. Adequate drainage is provided to drain the fire-fighting water. The watertight doors will protect the safe shutdown equipment from damage by water discharged by extinguishing systems in the adjacent areas.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 68 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 39 of 244)
A.15.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-15 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-15 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 69 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 40 of 244)
Fire Area A-16 (Reference A-1803)
 
A.16.1                                                                                  Fire Area Description
 
Auxiliary Building El. 2026, general area Rooms 1401, 1402, 1406, and 1408.
 
A.16.2 Major Equipment
 
CCW heat exchangers, pumps, pump room coolers, piping, and valves.
 
A.16.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.16.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.16.3-1 Fire Area A-16, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                                              M-663-00017A Closure Component Category North equipment hatches                                                                                                                                                                                                                                                                                                                                                                                                  Hatch South equipment hatches                                                                                                                                                                                                                                                                                                                                                                                            Hatch Containment post-tensioning hatch covers at                                                                            Hatch C Buttress South personnel elevator doors and shaft                                                                                                          Fire Door Missile door 41015                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Fire Door Cable tray firestops and cable tray covers                                                                            Cable Tray Firestops & Cable Tray within Combustible Control Zone                                                                                        Covers Penetration seals that exceed the bounding                                                                            Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                                        Structural Steel Fireproofing thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 70 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 41 of 244)
Six-inch high curbs are installed around Rooms 1401 and 1406 containing the redundant CCW system equipment. These rooms are separated horizontally by 75 feet (minimum).
The fire barrier enclosure around Fire Areas A-9 and A-10 is located between these two rooms.
 
A.16.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-16 is Low.
 
A 20 ft. Combustible Control Zone separation area is administratively maintained to strictly control transient combustibles in the limiting separation area between redundant PFSSD circuits within the east corridor of 1408. Specifically, the Combustible Control Zone is located between columns A7 and A8 from the Containment wall to the east wall of RHR Heat Exchanger Room 1309. Insitu combustibles within the Combustible Control Zone do not pose a fire propagation path that would disable both trains of redundant PFSSD equipment.
 
A.16.5 Fire Protection
 
Automatic smoke detection is provided in this area. Manual-pull stations are located at exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic preaction-type sprinkler system is installed over cable tray concentrations in Rooms 1402 and 1408 as detailed in Attachment  A. The system also provides protection for the hatchways at the ceiling of this area.
 
In the east corridor (Room 1408), additional sprinkler heads are provided below the cable tray elevation between columns A-1 and A-4. These additional sprinkler heads are provided to protect the cable trays from a transient fire located on this floor. This area contains cable trays and other obstructions, which may reduce the effectiveness of the ceiling-mounted sprinklers in controlling a transient combustible fire.
 
Hose stations and portable extinguishers are located throughout the area, as delineated on drawing A-1803.
 
Access to this area for manual fire fighting is available as follows:
: a.                        Stairwell 4101 from the Turbine Building
: b.                        Stairwell 1119 (at the south end) from other elevations of the Auxiliary Building
: c.                          Stairwell 1127 (at the north end) from other elevations of the Auxiliary Building
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 71 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 42 of 244)
Steel cable tray covers are provided for cable trays within the Combustible Control Zone, while cable tray raceways 116J5B30, 116U5D30, and 116U5E30 are provided with a Silicone Foam RTV firestop. These cable tray covers and fire stops are administratively controlled.
 
One 4-inch drain per 1,000 square feet of floor area is provided in the corridor area (Rooms 1402 and 1408). Six 4-inch and two 4-inch drains are provided in Rooms 1401 and 1406, respectively. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.16.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. The 6-inch-high  curbing in Rooms 1401 and 1406 and the floor drains will prevent any  transient combustible spill (such as lube oil) from spreading from one room to the other. The curb will also protect Rooms 1401 and 1406 against a spill in the corridor (Room 1408). Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.16.7 Analysis
 
A.16.7.1 Fire Suppression
 
The fire barriers will contain a fire in this area and  will also protect this area from a fire in any of the adjoining areas. The smoke detectors will provide an early warning of a fire in  this area. The fire can be extinguished manually using the hose  stations and/or the portable extinguishers.
The Combustible Control Zone ensures that fire will not involve redundant PFSSD components within the Fire Area.
 
The automatic detection system will trip the sprinkler system deluge valve when a cable tray fire is detected. The automatic system will actuate to extinguish the fire. The sprinkler actuation or a malfunction will be identified by Control Room annunciation. In the event of a failure of the automatic system, the fire can be extinguished manually using the hose stations.
 
Adequate drainage is provided in each room to remove the  fire-fighting water. The 6-inch-high curb installed around Rooms 1401  and 1406 will protect the safe shutdown equipment against damage from  water discharged by the sprinkler system in Rooms 1402 and 1408.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 72 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 43 of 244)
A.16.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-16 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-16 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-16.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 73 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 44 of 244)
Fire Area A-17 (Reference A-1803)
 
A.17.1                                                                                  Fire Area Description
 
South Electrical Penetration Room 1409.
 
A.17.2 Major Equipment
 
Motor control centers, load center, switchgear, room cooler, electric cable, balance of plant computer cabinets.
 
A.17.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.17.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.17.3-1 Fire Area A-17, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                          M-663-00017A Closure Component Category Reactor Building electrical penetrations                                                                                                                                                Penetration Seal Structural Steel Fireproofing with unprotected                                    Structural Steel Fireproofing thermal shorts
 
A.17.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-17 is Low.
 
Internal panel surfaces of RJ160A/B/C/D are finished with paint of low fire rating. All cable in these panels meets the vertical flame requirements of IPCEA S-19-81 and/or IEEE 383 for flame resistance. The panels are provided with keylocks to control access to the panel interiors.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 74 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 45 of 244)
A.17.5 Fire Protection
 
This area is provided with a cross-zoned smoke detection system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
 
The Halon 1301 system serves the room, with the exception of the electrical chase area, and is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An actuation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation.
 
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
 
An automatic wet pipe sprinkler system serves the electrical chase area of Room 1409.
The system is equipped with closed head spray nozzles and a standard sprinkler, with deflector shield, at an intermediate level.
 
Access to the area is via adjacent Corridor 1408.
 
Two 4-inch floor drains are provided in this area. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.17.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.17.7 Analysis
 
A.17.7.1 Fire Suppression
 
The fire barriers enclosing the Fire Area will protect this area from a  fire in the adjoining areas and will contain a fire within this area  until extinguished. The fire will be detected, alarmed, and  suppressed by the Halon system or the wet pipe sprinkler system. The  Halon system discharge or a malfunction will be identified Control Room annunciation.
In the event of a malfunction of the  automatic systems, the hose station in Room 1408 can be used to extinguish the fire.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 75 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 46 of 244)
A.17.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-17 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-17 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-17.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 76 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 47 of 244)
Fire Area A-18 (Reference A-1803)
 
A.18.1                                                                                  Fire Area Description
 
North Electrical Penetration Room 1410.
 
A.18.2 Major Equipment
 
Motor control centers, load center, switchgear, room cooler, electric cable, balance of plant computer cabinets.
 
A.18.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.18.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.18.3-1 Fire Area A-18, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                            M-663-00017A Closure Component Category Reactor Building electrical penetrations                                                                                                                                                                                                                  Penetration Seal 1-hour rated fire wrap protection for redundant                                                            Fire Wrap PFSSD circuits Penetration seals that exceed the bounding                                                                  Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                              Structural Steel Fireproofing thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 77 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 48 of 244)
A.18.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-18 is Low.
 
Internal panel surfaces of RJ159A/B/C/D are finished with paint of low fire rating. All cable in these panels meets the vertical flame requirements of IPCEA S-19-81 and/or IEEE 383 for flame resistance. The panels are provided with keylocks to control access to the panel interiors.
 
A.18.5 Fire Protection
 
This area is provided with a cross-zoned smoke detection system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
 
The Halon 1301 system serves the room with the exception of the electrical chase area and is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An actuation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation.
 
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
 
An automatic wet pipe sprinkler system serves the electrical chase area of Room 1410.
The system is equipped with closed head spray nozzles and a standard sprinkler, with deflector shield, at an intermediate level.
 
A hose station and portable extinguishers are located outside the area in Room 1408 (corridor). Access for manual fire fighting is through the two doors from Room 1408. For access to Room 1408, see Fire Area A-16.
 
Access to the area is via adjacent Corridor 1408.
 
Two 4-inch floor drains are provided in this area. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.18.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 78 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 49 of 244)
A.18.7 Analysis
 
A.18.7.1 Fire Suppression
 
The fire barriers enclosing this Fire Area will protect this area from a  fire in the adjoining areas and will contain a fire within the area  until extinguished. The fire will be detected, alarmed, and  suppressed by the automatic Halon system or the wet pipe sprinkler  system. The Halon system discharge or a malfunction will be  identified by Control Room annunciation. In the event of a  malfunction of the automatic systems, the hose station in Room 1408  can be used to extinguish the fire.
 
Adequate drainage is provided to  drain the fire-fighting water. Should manual firefighting be required, water damage to the electrical equipment in this room could result (with or without associated fire damage);
however, the water damage would not adversely affect safe shutdown.
The redundant equipment is located in another fire area. Since the floor in Room 1408 (corridor) slopes away from the doors to this room, water damage due to a sprinkler discharge in adjoining areas is not possible.
 
A.18.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-18 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-18 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-18.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 79 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 50 of 244)
Fire Area A-19 (Reference A-1804)
 
A.19.1                                                                                  Fire Area Description
 
Auxiliary Building El. 2047'-6" general area Rooms 1504, 1506, and 1513.
 
A.19.2 Major Equipment
 
Auxiliary/fuel building normal exhaust filter, adsorber and exhaust fans, containment purge filter adsorber unit, containment minipurge and shutdown purge exhaust fans, access control exhaust filter adsorber unit and exhaust fans, condenser air removal filtration system filter adsorber unit and fans, control building air supply unit, control building exhaust fans, electrical equipment room cooler, auxiliary building supply air unit, containment purge and minipurge supply units, main steam enclosure supply unit, main steam enclosure building exhaust fans, unit heaters, hydrogen analyzers.
 
A.19.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.19.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.19.3-1 Fire Area A-19, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                                              M-663-00017A Closure Component Category North equipment hatch                                                                                                                                                                                                                                                                                                                                                                                                                                                    Hatch Containment post-tensioning hatch covers at                                                                        Hatch C Buttress Missile door 41017                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    Fire Door Reactor Building mechanical penetrations                                                                                                                                      Penetration Seal Penetration seals that exceed the bounding                                                                        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                                    Structural Steel Fireproofing thermal shorts Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 80 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 51 of 244)
 
A.19.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-19 is Low.
 
A small cylinder of hydrogen/nitrogen mix is located on the hydrogen analyzer skid. The skid is specifically designed for use with hydrogen. The cylinder, which contains 10%
hydrogen is used as a calibration gas. If the gas were to leak, it would quickly dissipate below the 4% LEL of hydrogen. Therefore, the small cylinder does not introduce any additional impact on safe shutdown capability.
 
A.19.5 Fire Protection
 
An automatic smoke detection system is installed in this area. A duct smoke detector is provided for the air intake of SGK02 in Room 1513. Manual-pull stations are located near the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
All charcoal adsorber units, except the containment purge filter adsorber, operate during normal plant operation. Downstream of each charcoal bed is a thermistor-type continuous thermal detector, which alarms in the control room at high air stream temperature. The bed temperature is therefore constantly monitored for the containment purge adsorber units and for the other units when not in use. The charcoal beds are equipped with a hose connection to provide manual water spray protection.
 
Hose stations and portable extinguishers are located throughout this area, as delineated on drawing A-1804.
 
Access to this area is as follows:
: a.                        From Turbine Building stairway (Room 4101)
: b.                        From Control Room A/C and Filtration Room 1512
: c.                          From the north and south stairways (Rooms 1127 and 1119)
 
One 4-inch floor drain per 1,000 square feet of floor area is provided in this area. The drains are piped to a sump at El. 1967 accessed from Auxiliary Building floor El. 1974.
The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.19.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 81 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 52 of 244)
A.19.7 Analysis
 
A.19.7.1 Fire Suppression
 
The fire barrier separation provided for this area will contain a fire until extinguished and will protect the area from a fire in any one of the adjoining areas. The automatic detection system will provide an early warning of a fire in this area. The fire can be extinguished manually, using the hose stations and/or portable extinguishers located throughout the area. Adequate drainage is provided to remove the fire-fighting water.
There is no safe shutdown equipment susceptible to water damage in this area.
 
A.19.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-19 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-19 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-19.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 82 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 53 of 244)
Fire Area A-20 (Reference A-1804)
 
A.20.1                                                                                  Fire Area Description
 
Personnel Hatch and CCW Surge Tank Area Rooms 1502, 1503, 1505, and 1507.
 
A.20.2 Major Equipment
 
CCW surge tanks, CCW chemical addition tank, piping and valves.
 
A.20.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.20.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.20.3-1 Fire Area A-20, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                                                                      M-663-00017A Closure Component Category South equipment hatch                                                                                                                                                                                                                                                                                                                                                                                                                                              Hatch Reactor Building personnel hatch                                                                                                                                                                                                                                                                              Hatch South personnel elevator doors and shaft                                                                                                                                            Fire Door Reactor Building mechanical penetrations                                                                                                                                      Penetration Seal Penetration seals that exceed the bounding                                                                                              Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                                                          Structural Steel Fireproofing thermal shorts
 
A 12-inch-thick concrete barrier wall extending 15 feet from the west barrier separates the redundant CCW surge tanks. The tank outside diameter is 8 feet.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 83 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 54 of 244)
A.20.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-20 is Low.
 
A small cylinder of hydrogen/nitrogen mix is located on the hydrogen analyzer skid. The skid is specifically designed for use with hydrogen. The cylinder, which contains 10%
hydrogen is used as a calibration gas. If the gas were to leak, it would quickly dissipate below the 4% LEL of hydrogen. Therefore, the small cylinder does not introduce any additional impact on safe shutdown capability.
 
A.20.5 Fire Protection
 
Smoke detectors are installed in the elevator lobby and over the cable trays in Rooms 1505 and 1507. Manual-pull stations are installed at the exit door to the stairway.
Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
A hose station and one portable extinguisher are installed in the elevator lobby within the Fire Area. If access to these are blocked by a fire in the area, the hose station located in Room 1504 (approximately 50 feet from the fire area) and portable extinguisher outside the area will provide backup fire-fighting capability (see drawing A-1804).
 
Access for manual fire fighting is as follows:
: a.                        From Room 1504 (see Fire Area A-19 for access to Room 1504)
: b.                        From stairway 1119
: c.                          From Fuel Building (Room 6301)
 
Four-inch floor drains are provided in this area as follows:
 
Room                                No. of Drains 1502 1 1503 1 Elevator lobby                                                                                                                                                                                                                                                                                                                                                                                            1 1505 1 1507 2
 
The drains are piped to a sump at El. 1967 accessed from Auxiliary Building floor El.
1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 84 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 55 of 244)
A.20.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.20.7 Analysis
 
A.20.7.1 Fire Suppression
 
The fire barrier separation provided will protect this area from a fire in adjacent areas and will also contain a fire within the area until extinguished. A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using the hose stations and/or portable  extinguishers located inside the area or in the adjacent Room 1504.
 
Adequate drainage is provided to remove the fire-fighting water. There is no safe shutdown equipment susceptible to  water damage in this area.
 
A.20.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-20 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-20 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-20.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 85 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 56 of 244)
Fire Area A-21 (Reference A-1804)
 
A.21.1                                                                                  Fire Area Description
 
Control Room AC and Filtration Units Room 1501.
 
A.21.2 Major Equipment
 
Control room ac unit (B), control room filtration system filter/adsorber unit (B), control filtration fan (B), motor control center.
 
A.21.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.21.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.21.3-1 Fire Area A-21, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                          M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                                                Structural Steel Fireproofing unprotected thermal shorts
 
A.21.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-21 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 86 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 57 of 244)
A.21.5 Fire Protection
 
Automatic smoke detectors are installed in this room. Manual-pull stations are installed at the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
A hose station is installed in this area. If access to this hose station is blocked by a fire, the hose station located in Room 1506 (corridor) can be used (see drawing A-1804). This hose station is approximately 20 feet away from the access door to this area. Two portable extinguishers are located in Room 1506.
 
The charcoal/adsorber unit is in the control room filtration system. Downstream of each charcoal bed is a thermistor-type continuous detector, which alarms in the Control Room at high airstream temperature. The charcoal filters are equipped with a hose connection to provide manual water spray protection.
 
Access to this fire area is as follows:
: a.                        From Room 1506 (see Fire Area A-19 for access to Room 1506)
: b.                        From Control Building through the adjacent Fire Area A 22 (Room 1512)
 
Two 4-inch floor drains are provided in this area. The drains are  piped to a sump at El.
1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.21.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.21.7 Analysis
 
A.21.7.1 Fire Suppression
 
The fire barrier separation provided for this area will contain a fire within the area until extinguished and will protect this area from a fire in adjacent areas. The automatic detection system will provide an early warning of a fire. The fire can be extinguished manually, using the hose stations and/or the portable extinguishers. Adequate drainage is provided to remove the fire-fighting water. Water or fire damage to the safe shutdown equipment will not prevent the safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 87 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 58 of 244)
A.21.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-21 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-21 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-21.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 88 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 59 of 244)
Fire Area A-22 (Reference A-1804)
 
A.22.1                                                                                  Fire Area Description
 
Control Room AC and Filtration Units Room 1512.
 
A.22.2 Major Equipment
 
Control room AC unit (A), control room filtration system filter/adsorber unit (A), control filtration fan (A), motor control center.
 
A.22.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.22.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.22.3-1 Fire Area A-22, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                    M-663-00017A Closure Component Category Fire dampers GKD0180 and GKD0182                                                            Fire Damper located beyond barrier plane Penetration seals that exceed the bounding                                                  Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                              Structural Steel Fireproofing thermal shorts
 
A.22.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-22 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 89 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 60 of 244)
A.22.5 Fire Protection
 
Automatic smoke detectors are installed in this room. Manual-pull stations are installed at the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
The charcoal/adsorber unit is in the control room filtration system. Downstream of each charcoal bed is a thermistor-type continuous detector, which alarms in the control room at high airstream temperature. The charcoal filters are equipped with a hose connection to provide manual water spray protection.
 
Two portable extinguishers are installed in this area. Additional portable extinguishers and a hose station are located in Room 1513 (see drawing A-1804).
 
Access to this fire area is as follows:
: a.                        From Room 1506 (see Fire Area A-19 for access to Room 1506)
: b.                        From Turbine Building through Room 1513
: c.                          From Control Building
 
Two 4-inch floor drains are provided in this area. The drains are piped to a sump at El.
1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.22.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.22.7 Analysis
 
A.22.7.1 Fire Suppression
 
The fire barrier separation provided for this area will contain a fire within the area until extinguished and will protect this area from a fire in adjacent areas. The automatic detection system will provide an early warning of a fire.
 
The fire can be extinguished manually, using the hose stations and/or    the portable extinguishers. Adequate drainage is provided to remove  the fire-fighting water. Water or fire damage  to the safe shutdown equipment will not prevent the safe shutdown of  the plant.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 90 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 61 of 244)
A.22.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-22 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-22 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-22.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 91 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 62 of 244)
Fire Area A-23 (Reference A-1803 and A-1804)
 
A.23.1                                                                                  Fire Area Description
 
Main Steam and Feedwater Valve Compartment Room 1508, 1509, 1411, and 1412.
 
A.23.2 Major Equipment
 
Main steam piping and isolation valves, feedwater piping and isolation valves, main steam safety relief valves, main steam atmospheric relief valves, steam generator blowdown isolation valves, auxiliary feedwater pump turbine steam supply valves, pressure transmitters, flow transmitters.
 
A.23.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.23.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.23.3-1 Fire Area A-23, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                                                              M-663-00017A Closure Component Category Emergency escape hatch                                                                                                                                                                                                                                                                                                                                                                                              Hatch 20 unsealed floor drains to Turbine Building                                                      Fire Barrier Missile Shield                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Fire Barrier Reactor Building mechanical penetrations                                                                                                    Penetration Seal Penetration seals that exceed the bounding                                                                                            Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                                                        Structural Steel Fireproofing thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 92 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 63 of 244)
The fire area below the 2065 elevation is divided into two compartments by a 2-foot-thick concrete wall. A 9-foot x 24-foot vent opening is located at the ceiling of each compartment. The barrier wall between the two compartments has a 27-foot wide x 23-foot high vent opening located approximately 34 feet above the floor. These vent openings are required to prevent over pressurization of the compartment in the event of a postulated break of main steam piping. Due to the existence of the vent opening, the barrier wall is not fire rated.
 
A.23.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-23 is Low.
 
A.23.5 Fire Protection
 
An automatic detection system consisting of infrared flame detectors is installed in this Fire Area. Manual-pull stations are installed in Room 1408. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a pull station alarm is point addressable, while detection is zoned, for a quick and easy means to identify the location associated with the device in alarm.
 
Portable extinguishers are located in each compartment. A hose station and additional portable extinguishers are located in Room 1506. The hose station is approximately 25 feet from the access door into Room 1508. All areas of the two compartments are within reach of this hose station. Additional hose length, if required, can be added from adjacent hose racks in Room 1506.
 
Access to this  area  is  through  an alarmed access door from stairway Room 1127.
Access openings in the barrier wall and platforms installed at El. 2042 and 2030 provide access between compartments. An intermediate platform is installed at El. 2037 feet              1/2 inches in each compartment; however, access between compartments at this elevation is not possible. An emergency escape hatch to the Turbine Building is located in the torsional restraint structure adjacent to this fire area. Access to this area is from the platform at El. 2030 in Room 1412.
 
Adequate fire water drainage is ensured by the two 20 diameter unsealed floor drains to the Turbine Building that are provided for drainage in the event of a feedwater pipe rupture within the area. Additionally, drainage is provided from the area by the oily waste drain system, which is piped to the Auxiliary Feedwater Room sump located in Room 1128 (El. 1974). The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
A.23.6                                                                                  Isolation and Smoke Removal
 
A fire in one of the compartments will be contained by the fire  barriers and the concrete barrier wall until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 93 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 64 of 244)
A.23.7 Analysis
 
A.23.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the detection system.
The fire can be extinguished manually, using the portable extinguishers and/or the hose station in Room 1506. The safe shutdown instrumentation in this area has watertight enclosures. All the safe shutdown equipment in these rooms is qualified to a steam environment and an ambient temperature of 320 F.
 
Since the access to this area is controlled and limited, the transient combustibles introduced into these rooms will be those associated with the maintenance of equipment located in these rooms. Any major maintenance work on the isolation valves or the atmospheric relief valves will require a plant shutdown. (Maintenance on these valves will normally be done during refueling outage). Any postulated transient fire will not damage the 2-foot-thick concrete wall. Due to low combustible loading and control on access and transient combustibles, this area is judged to require a degree of fire protection equivalent to the Reactor Building.
Therefore, the provisions of Appendix R, Section III.G.2.f are applied to this area.
 
A.23.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-23 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-23 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-23.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 94 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 65 of 244)
Fire Area A-24 (Reference A-1802)
 
A.24.1                                                                                  Fire Area Description
 
North Pipe Penetration Room 1323.
 
A.24.2 Major Equipment
 
Containment isolation valves and piping.
 
A.24.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.24.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.24.3-1 Fire Area A-24, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                            M-663-00017A Closure Component Category 3-hour rated fire wrap protection for redundant                                                          Fire Wrap PFSSD circuits Reactor Building mechanical penetrations                                                                                                                                    Penetration Seal Penetration seals that exceed the bounding                                                                Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                            Structural Steel Fireproofing thermal shorts
 
A.24.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-24 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 95 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 66 of 244)
A.24.5 Fire Protection
 
An automatic smoke detection system is installed in this area. Manual-pull stations are located at the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
A hose station and portable extinguishers are located outside the area in Room 1320.
Access is from Room 1320 through a door.
 
For access to Room 1320, see Fire Area A-8.
 
Three 4-inch floor drains are provided in this area. These drains  are piped to a sump at El. 1967 accessed from Auxiliary Building floor El. 1974. This sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.24.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.24.7 Analysis
 
A.24.7.1 Fire Suppression
 
Due to low combustible loading, a fire in this area is unlikely. A fire will be detected by the smoke detection system  and can be extinguished manually, using the portable extinguishers  and/or the hose station in Room 1320. The fire barriers protect the  safe shutdown equipment from a fire in all adjacent areas. A fire  occurring in this area will be contained by the fire barriers.
 
Adequate drainage is provided to remove the fire-fighting water.
 
A.24.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-24 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-24 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-24.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 96 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 67 of 244)
Fire Area A-25 (Reference A-1802)
 
A.25.1                                                                                  Fire Area Description
 
South Pipe Penetration Room 1322.
 
A.25.2 Major Equipment
 
Containment isolation valves and piping.
 
A.25.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.25.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.25.3-1 Fire Area A-25, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                      M-663-00017A Closure Component Category Reactor Building mechanical penetrations                                                                                                    Penetration Seal Penetration seals that exceed the bounding                                                    Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                Structural Steel Fireproofing thermal shorts
 
A.25.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-25 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 97 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 68 of 244)
A.25.5 Fire Protection
 
An automatic smoke detection system is installed in this area. Manual pull    stations are located at the exit doors of this floor.
 
A hose station and two portable extinguishers are located outside the area in Room  1314.
Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Access is from Room 1314 through a 3-hour-rated fire door. For access to Room 1314, see Fire Area A-8.
 
Three 4-inch floor drains are provided in this area. The drains are piped to a sump at El.
1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.25.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.25.7 Analysis
 
A.25.7.1 Fire Suppression
 
Due to a low combustible loading, a fire in this area is highly  unlikely. A fire will be detected by the smoke detection system  and can be extinguished manually, using the portable extinguishers  and/or hose stations in Room 1314. The fire barriers protect  the safe shutdown equipment from a fire in all adjacent areas. A fire  occurring within this area will be contained by the fire barriers.
 
Adequate drainage is provided to remove any fire-fighting water.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 98 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 69 of 244)
A.25.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-25 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-25 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-25.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Page 99 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 70 of 244)
Fire Area A-26 (Reference A-1803)
 
A.26.1                                                                                  Fire Area Description
 
Room 1405 and Room 1415.
 
A.26.2 Major Equipment
 
Decontamination area scrubbers and I&C Hot Shop.
 
A.26.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.26.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.26.3-1 Fire Area A-26, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                          M-663-00017A Closure Component Category Resin loading chute cover plate                                                                                                                                                                                                                                                                                    Hatch Penetration seals that exceed the bounding                                                        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                    Structural Steel Fireproofing thermal shorts
 
A.26.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-26 is Low. Room 1405 is a designated combustible material staging area.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 100 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 71 of 244)
The resin loading chute for the demineralizers located in El. 2000 is located in this area.
Resins are received in a hydrated form, and, therefore, they do not readily ignite or sustain combustion. Administrative controls will ensure that resins only in quantities required for immediate use in recharging the demineralizers will be brought into this area.
In the event that the resins dehydrate and ignite, the fire barriers enclosing this area will contain the fire and prevent damage to equipment in adjacent areas.
 
A.26.5 Fire Protection
 
An automatic smoke detection system is installed in Rooms 1405 and 1415. Manual-pull stations are located at the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Two hose stations located in Room 1408 are within reach of this area. Two portable extinguishers are located in Room 1408 outside the area.
 
Access to Room 1405 is from 1408, through a 3-hour fire door, and  access to Room 1415 is from Room 1408 through a 3-hour fire door. Fire  separation between rooms 1405 and 1415 is not required. For access to  Room 1408, see Fire Area A-16.
 
One 4-inch floor drain is provided in  Room 1405 and two 4-inch drains in Room 1415.
The drains are piped to a sump  located at El. 1967 accessed from Auxiliary Building Floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.26.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.26.7 Analysis
 
A.26.7.1 Fire Suppression
 
The fire barrier separation provided for this area (Rooms 1405 and 1415) will contain a fire in this area and will protect this area from a fire in any of the adjoining areas. The detection system will provide an early warning of a fire. The fire can be extinguished manually, using the hose station and/or portable extinguishers located outside the fire area.
 
Adequate drainage is provided  to remove all fire-fighting water. There is no safe shutdown equipment susceptible to water damage in area A-26.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 101 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 72 of 244)
A.26.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-26 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-26 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-26.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 102 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 73 of 244)
Fire Area A-27 (Reference A-1803)
 
A.27.1                                                                                  Fire Area Description
 
Reactor Trip Switchgear Room 1403.
 
A.27.2 Major Equipment
 
Reactor trip switch gear, MG sets, load centers, rod control and rod-drive power supply control cabinets, 125-V dc panel.
 
A.27.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.27.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.27.3-1 Fire Area A-27, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                  M-663-00017A Closure Component Category Missile door 14032                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Fire Door Penetration seals that exceed the bounding                                                Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                            Structural Steel Fireproofing thermal shorts
 
A.27.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-27 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 103 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 74 of 244)
A.27.5 Fire Protection
 
This area is provided with a cross-zoned smoke detection system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
 
The Halon 1301 system installed is capable of attaining a minimal 5  percent concentration. The system is designed to maintain at least a  5-percent concentration at the level of the highest combustible for a  soak time of 10 minutes. An actuation station is provided to discharge the system manually. An activation by any automatic method  will sound a local alarm, close required ventilation dampers, shut off  associated ventilation and/or air conditioning fan motors, and  discharge the system after an adequate time delay for evacuation. The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system  controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
 
A hose station and three portable extinguishers are located within the  area. If access to these are blocked by a fire, additional hose  stations and portable extinguishers located outside the area in Rooms 1402 and 3503 (Communications Corridor) are available.
 
Access for manual fire-fighting is from Rooms 1402 and 3503. For access to Rooms 1402 and 3503, see Fire Areas A-16 and CC-1, respectively.
 
Four 4-inch floor drains are provided in this area. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
A.27.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.27.7 Analysis
 
A.27.7.1 Fire Suppression
 
The fire barriers enclosing this area will protect this area from a  fire in the adjoining areas and will contain a fire within the area  until extinguished.
The fire will be detected, alarmed, and  suppressed by the automatic Halon system. The Halon system discharge  or a malfunction will be identified by Control Room annunciation. In the event of a malfunction of the automatic system, the portable extinguishers and/or the hose stations can be used to extinguish the fire.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 104 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 75 of 244)
Adequate drainage is provided to drain the fire-fighting water. Should manual firefighting be required, water damage could result to  the electrical equipment in this room (with or without fire damage);  however, the water damage would not prevent safe shutdown. Since the  floor in Room 1402 (corridor) slopes away from the doors in this room,  water damage due to a sprinkler discharge in adjoining areas is not  possible.
 
A.27.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-27 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-27 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-27.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 105 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 76 of 244)
Fire Area A-28 (Reference A-1803)
 
A.28.1                                                                                  Fire Area Description
 
Auxiliary Shutdown Panel Room 1413.
 
A.28.2 Major Equipment
 
Auxiliary shutdown and control panels.
 
A.28.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature. In addition, within the room, the two auxiliary shutdown panels are separated by a fire barrier, which contains two normally closed fire rated doors. One door is located in front and one is located behind the panels.
 
Each auxiliary shutdown panel contains the controls and instrumentation for one safe shutdown train. Cable to the panels enter from the top for Separation Group 4 and from below for the redundant Separation Group 1. The Separation Group 1 circuits to the auxiliary shutdown panel enter the panel bottom directly through a penetration seal at the floor. Therefore, no exposed Separation Group 1 raceways appear in the room. The panels are provided with keylocks to control access to the panel interiors. Access to the Auxiliary Shutdown Panel Room is controlled and alarmed.
 
A.28.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-28 is Low. Due to the small floor area of the Auxiliary Shutdown Panel Room and the Security control of the room, combustibles are typically limited to those required for operation. Calculation XX-X-004 provides the bounding transient combustible package for this Fire Area.
(Reference 3.1, Section F.6)
 
Internal surfaces of the auxiliary shutdown panels are finished with paint of low flame spread. All cables in these panels meet the vertical flame spread requirements of IPCEA S-19-81 and/or IEEE 383-1974.
 
A.28.5 Fire Protection
 
Smoke detectors are installed at the ceiling of this fire area. Manual-pull stations are installed adjacent to the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.  (Reference 3.1, Section F.6)
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 106 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 77 of 244)
A hose station and one portable extinguisher are installed in Room 1408 (corridor) outside the area.  (Reference 3.1, Section F.6)
 
Access for manual firefighting is from Room 1408 through an alarmed access door. For access to Room 1408, see Fire Area A-16.
 
No drains are provided for this Fire Area, as manual fire water suppression efforts will be minimal, considering the limited combustible loading and small footprint of the Fire Area.
Additionally, a floor drain is located in Fire Area  A-16 just outside the access door to A-28.
 
A.28.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.28.7 Analysis
 
A.28.7.1 Fire Suppression
 
The fire barriers around the room will protect the panels from a  fire in one of the adjoining areas. The fire separation  between the panels will protect either auxiliary shutdown panel from a  fire postulated in the other. The smoke detectors will provide an  early warning of a fire either in a cabinet or in the room. The fire can be extinguished manually, using the portable extinguisher.
 
A.28.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-28 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-28 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-28.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 107 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 78 of 244)
Fire Area A-29 (Reference A-1802)
 
A.29.1                                                                                  Fire Area Description
 
Auxiliary Feedwater Pump Valve Compartment Rooms 1304, 1324, and 1327.
 
A.29.2 Major Equipment
 
Auxiliary feedwater piping and valves, backup compressed gas accumulator tanks.
 
A.29.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.29.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.29.3-1 Fire Area A-29, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                          M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                    Structural Steel Fireproofing thermal shorts
 
A.29.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-29 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 108 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 79 of 244)
A.29.5 Fire Protection
 
Due to low combustible loading in this area, a detection system  is not installed. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
 
Fire extinguishers are located in Rooms 1324 and  1329. A hose station is provided for this area in Room 1329. For specific locations, see A-1802.
 
Access to the area is via the Turbine Building.
 
One 4-inch drain is provided in each room. The drains are piped to a sump at El. 1974.
The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
A.29.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.29.7 Analysis
 
A.29.7.1 Fire Suppression
 
The fire barriers enclosing this area will protect this area from a  fire in the adjoining areas and will contain a fire within the area  until extinguished.
 
Adequate drainage is provided to drain any  fire-fighting water.
 
A.29.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-29 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-29 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 109 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 80 of 244)
Fire Area A-30 (Reference A-1802)
 
A.30.1                                                                                  Fire Area Description
 
Auxiliary Feedwater Pump Valve Compartment Rooms 1305, 1328, and 1330.
 
A.30.2 Major Equipment
 
Auxiliary feedwater piping and valves, backup compressed gas accumulator tanks.
 
A.30.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.30.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.30.3-1 Fire Area A-30, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                          M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                    Structural Steel Fireproofing thermal shorts
 
A.30.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-30 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 110 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 81 of 244)
A.30.5 Fire Protection
 
Due to low combustible loading in this area, a detection system  is not installed. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
 
Fire extinguishers are located in Rooms 1324 and  1329. A hose station is provided for this area in Room 1329. For specific locations, see drawing A-1802.
 
Access to the area is via the Turbine Building.
 
One 4-inch drain is provided in each room. The drains are piped to a sump at El. 1974.
The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
A.30.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.30.7 Analysis
 
A.30.7.1 Fire Suppression
 
The fire barriers enclosing this area will protect this area from a  fire in the adjoining areas and will contain a fire within the area  until extinguished.
 
Adequate drainage is provided to drain the  fire-fighting water.
 
A.30.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-30 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-30 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 111 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 82 of 244)
Fire Area A-33 (Reference A-1801 and A-1802)
 
A.33.1                                                                                  Fire Area Description
 
Auxiliary Building - El. 1989 and El. 2000, Rooms 1206, 1207, and 1329.
 
A.33.2 Major Equipment
 
Auxiliary feedwater piping, valves, and instrumentation.
 
A.33.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table A.33.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table A.33.3-1 Fire Area A-33, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                              M-663-00017A Closure Component Category Personnel hatch from Room 1129 to 1207                                                                                                                                Hatch 1-hour rated fire wrap protection for redundant                                                          Fire Wrap PFSSD circuits Penetration seals that exceed the bounding                                                                Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                            Structural Steel Fireproofing thermal shorts
 
A.33.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-33 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 112 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 83 of 244)
A portion of Room 1207 within this Fire Area is administratively maintained as a Combustible Control Zone to strictly control transient combustibles in the 20 ft. separation area between redundant PFSSD motor operated valves AL-HV-0032 and AL-HV-0033.
These valves provide a suction path for the turbine drive auxiliary feedwater pump. Insitu combustibles within the Combustible Control Zone do not pose a fire propagation path that would disable both trains of redundant PFSSD equipment.
 
A.33.5 Fire Protection
 
An automatic smoke detection system is installed in this area, except for Corridor 1329.
No detection is provided in this area due to low combustible loading. An automatic wet pipe sprinkler system is provided for Rooms 1206 and 1207. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. Sprinklers system actuation results in a local bell alarm and a point addressable Control Room alarm.
 
A hose station and portable extinguishers are located in the area, as delineated on drawings A-1801 and A-1802.
 
Access to this area for manual fire fighting is available as follows:
: a.                        Door 13291 from the Turbine Building
: b.                        Door 11281 from the Auxiliary Building through the personnel hatch between Rooms 1129 and 1207
 
One 4-inch drain per 1,000 square feet of floor area is provided throughout this fire area.
The floor drains are piped to the auxiliary feedwater pump rooms sump. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
A.33.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.33.7 Analysis
 
A.33.7.1 Fire Suppression
 
The automatic detection system will provide an early warning of fire in this area. The detection, automatic suppression, fire wrap, and combustible control within Rooms 1206 and 1207 ensure that a fire in this area will not involve redundant PFSSD components. The hose station in 1329 or portable extinguishers can also be used to suppress fire within this Fire Area.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 113 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 84 of 244)
A.33.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-33 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-33 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 114 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 85 of 244)
Fire Area A-34 (Reference A-1802)
 
A.34.1                                                                                  Fire Area Description
 
Auxiliary Building - El. 2000, Rooms 1316 and 1317.
 
A.34.2 Major Equipment
 
Seal water heat exchanger and associated piping and valves.
 
A.34.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
A.34.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area A-34 is Low.
 
A.34.5 Fire Protection
 
No detection or automatic suppression is provided in this fire area due to low combustible loading. Manual-pull fire alarm stations are located at normal exits from the Auxiliary Building. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Hose stations and portable extinguishers are located in an adjacent fire area, as delineated on drawing A-1802.
 
Access to this area for manual firefighting is available through door 13161 from room 1315.
 
One 4-inch floor drain is provided in rooms 1316 and 1317. The floor drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 115 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 86 of 244)
A.34.6                                                                                  Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
A.34.7 Analysis
 
A.34.7.1 Fire Suppression
 
The fire barriers enclosing this area will protect against a fire in the adjoining areas and will contain a fire within the area until extinguished.
Adequate drainage is provided to drain any firefighting water.
 
A.34.7.2                                                                                                              Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-34 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-34 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 116 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 87 of 244)
Fire Area AB-1 (Reference A-1802)
 
AB.1.1                                                                            Fire Area Description
 
Auxiliary Boiler Room 4315.
 
AB.1.2 Major Equipment
 
Auxiliary boiler.
 
AB.1.3 Design Features
 
The portions of this Fire Area that directly communicate with other Fire Areas are separated by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature. Stairwell T-6 enclosure is 2-hour fire rated. The roof, grade floor, and walls of the Auxiliary Boiler Room that communicate to the exterior are not credited fire boundaries.
 
AB.1.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area AB-1 is Low.
 
AB.1.5 Fire Protection
 
Infrared flame detectors are provided in this area. A manual-pull fire alarm station is located near the exit doorways from this area. An automatic wet-pipe sprinkler system is provided to protect the entire area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is zoned for a quick and easy means to identify the location associated with the device in alarm. Sprinklers system actuation results in a local bell alarm and a point addressable Control Room alarm.
 
Hose stations and portable extinguishers are provided just outside this area in the Turbine Building. In addition, a portable extinguisher is provided inside the area, near the exterior door.
 
The auxiliary boiler is provided with an emergency stop switch located in the Turbine Building just outside the Auxiliary Boiler Room.
 
Auxiliary boiler fuel oil tank 1FO01T has a capacity of 469,980 gallons and is located outside of the protected area in the southwest portion of the owner controlled area. A manual foam extinguishing system is provided with internal injection into the tank. It also supplies a hose station for external use. The tank is provided with a dike to contain fuel oil tank contents and fire suppression water.
 
Access to the Auxiliary Boiler Room is via the Turbine Building or the exterior or the room on the southeast side.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 117 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 88 of 244)
 
Floor drains in the area are piped to the Auxiliary Boiler Room sump. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
AB.1.6                                                                            Isolation and Smoke Removal
 
A fire in the area will be contained by the fire barriers until extinguished. No ventilation ductwork penetrates the fire barriers of this Fire Area. Fusible link operated smoke and heat venting is also provided in the roof of AB-1. Refer to Section  4.3.7.2 for smoke removal discussion.
 
AB.1.7 Analysis
 
AB.1.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event of the failure of the automatic sprinkler system, fire barriers will prevent fire spread to communicating Fire Areas. Fire may be extinguished manually, using a fire extinguisher and/or hose station.
 
AB.1.7.2                                                                                                          Safe Shutdown Capability
 
This area contains no PFSSD equipment or circuits and is separated from adjoining safe shutdown areas by a fire barrier construction. Therefore, a fire within Fire Area AB-1 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 118 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 89 of 244)
Fire Area C-1 (Reference A-1801)
 
C.1.1                                                                                                    Fire Area Description
 
Pipe Space and Tank Area Control Building, El. 1974 Room 3101 and 3104.
 
C.1.2 Major Equipment
 
ESW piping and motor-operated isolation valves, detergent drain tank and pumps, control building floor and equipment drain sump pumps, chemical equipment drain sump pumps.
 
C.1.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.1.3-1 Fire Area C-1, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                      M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                    Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                Structural Steel Fireproofing thermal shorts
 
Stairwell 3104 is separated by 3101 by a 2-hour rated fire barrier and where room 3104 interfaces with other fire areas the barrier is rated for 3-hours.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 119 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 90 of 244)
C.1.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-1 is Low.
 
A portion of Room 3101 within this Fire Area is administratively maintained as a Combustible Control Zone to strictly control transient combustibles in the 20 ft. separation area between redundant PFSSD motor operated valves for the essential service water (ESW) system. Insitu combustibles within the Combustible Control Zone do not pose a fire propagation path that would disable both trains of redundant PFSSD equipment.
 
C.1.5 Fire Protection
 
Room 3101 is provided with smoke detectors in the area of the ESW motor-operated isolation valves to provide early warning of a fire in this area. A manual-pull station is located at the north exit into Room 3102. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system is provided for Room 3101.
Two manual hose stations are located within the area as delineated on drawing A-1801.
Portable extinguishers are located within the area and in the corridor  outside access doors between the Control Building and the Auxiliary  Building (Room 1101).
Access to this area for manual  fire fighting is available via Auxiliary Building Corridor 1101 and Communications Corridor 3102.
Drainage in this area is by nine 4-inch floor drains. This is adequate to handle maximum sprinkler and hose station discharge. The drains discharge to the Control Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.1.6                                                                                                    Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.1.7 Analysis
 
C.1.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the smoke  detection system. In the event that a fire develops, it will be  contained by the fire barriers and extinguished by the wet pipe  system. The Combustible Control Zone ensures that fire will not involve redundant PFSSD components within the Fire Area. Should the automatic suppression system fail, manual hose  streams and extinguishers can be used to extinguish the fire.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 120 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 91 of 244)
C.1.7.2                                                                                                                                  Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-1 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in C-1.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 121 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 92 of 244)
Fire Area C-2 (Reference A-1801)
 
C.2.1                                                                                                    Fire Area Description
 
North vertical cable chase Room 3106, Control Building. El. 1974 to 1984.
 
C.2.2 Major Equipment
 
Electric cable only.
 
C.2.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.2.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.2.3-1 Fire Area C-2, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                    M-663-00017A Closure Component Category Structural Steel Fireproofing with unprotected                              Structural Steel Fireproofing thermal shorts
 
C.2.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-2 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 122 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 93 of 244)
C.2.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit  from the adjacent Room 3101. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler systems is by portable extinguishers and manual hose stations located in Fire Area C-1.
 
Access to the chase is through a 2 foot 8 inch by 4 foot 6 inch, 3-hour-rated fire  door.
 
No drains are provided for this Fire Area. Fire suppression water will escape under the rollup access fire door and into floor drains within Fire Area  C-1. There are no PFSSD equipment or circuits in this area. Therefore, water accumulation in the area would not affect safe shutdown capability.
 
C.2.6                                                                                                    Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.2.7 Analysis
 
C.2.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barrier and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.2.7.2                                                                                                                                  Safe Shutdown Capability
 
There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in C-2.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 123 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 94 of 244)
Fire Area C-3 (Reference A-1801)
 
C.3.1                                                                                                    Fire Area Description
 
South vertical cable chase Room 3105, Control Building. El. 1974 to 1984.
 
C.3.2 Major Equipment
 
Electric cable only.
 
C.3.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.3.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.  .
 
Table C.3.3-1 Fire Area C-3, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with unprotected                          Structural Steel Fireproofing thermal shorts
 
C.3.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-3 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 124 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 95 of 244)
C.3.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit  from the adjacent Room 3101. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler systems is by portable extinguishers and manual hose stations located in Fire Area C-1.
 
Access to the chase is through a 2 foot 8 inch by 4 foot 6 inch, 3-hour-rated fire  door.
 
No drains are provided for this Fire Area. Fire suppression water will escape under the rollup access fire door and into floor drains within Fire Area  C-1. There are no PFSSD equipment or circuits in this area. Therefore, water accumulation in the area would not affect safe shutdown capability.
 
C.3.6                                                                                                    Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.3.7 Analysis
 
C.3.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.3.7.2                                                                                                                                  Safe Shutdown Capability
 
There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in C-3.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 125 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 96 of 244)
Fire Area C-5 (Reference A-1801)
 
C.5.1                                                                                                    Fire Area Description
 
Access Control area above and below suspended ceiling Rooms 3206, 3212 through 3224, Pipe Chases, and Electrical Chase accessible from 3212.
 
C.5.2 Major Equipment
 
Electric cable, laundry machinery, medical supplies, and office equipment
 
C.5.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.5.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.5.3-1 Fire Area C-5, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                M-663-00017A Closure Component Category Fire door 32092                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Fire Door Penetration seals that exceed the bounding                                                  Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                              Structural Steel Fireproofing thermal shorts
 
C.5.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-5 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 126 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 97 of 244)
C.5.5 Fire Protection
 
Smoke detectors are installed above and below the suspended ceiling except as noted in Attachment A. Manual-pull fire alarm stations are located near the exit doorways from the Access Control area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system is provided in this area above  and below the suspended ceiling as detailed in Attachment  A. Water flow in the system is alarmed in the Control Room.
 
Hose stations and portable extinguishers are provided in the corridors within the Access Control area, as indicated on drawing A-1801.
 
Access to this area for manual firefighting is available via Communications Corridor 3225 and Auxiliary Building Corridor 1101 through Fire Area C-6.
 
Adequate floor drains are provided to remove sprinkler and hose station discharge without appreciable accumulation. Any sprinkler discharge in the area above the suspended ceiling will drain through the suspended ceiling to the Access Control  area below. Drainage is discharged to the Control Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.5.6                                                                                                    Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.5.7 Analysis
 
C.5.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire occurs, the automatic suppression system will actuate and extinguish the fire. In the event of failure of the automatic system, the manual hose stations provide the capability of extinguishing the fire.
 
The suspended ceiling panels may be removed as necessary during firefighting efforts involving the normally concealed space above the panels. The  majority of the cable  trays in this area are no more than 12 feet above the floor elevation,  and no trays are more than 14 feet above the floor. Consequently, a fire in these cable trays can be extinguished by manual hose stations from the floor (assuming failure of the automatic wet pipe sprinkler system above the  trays).
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 127 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 98 of 244)
C.5.7.2                                                                                                                                  Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-5 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-5 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 128 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 99 of 244)
Fire Area C-6 (Reference A-1801)
 
C.6.1                                                                                                    Fire Area Description
 
Access Control area above and below suspended ceiling Rooms 3201 through 3205 and 3207 through 3211, Pipe Chases, and Electrical Chase accessible from 3205.
 
C.6.2 Major Equipment
 
Electric cable, laundry machinery, medical supplies, and office equipment.
 
C.6.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
x                                      Have been evaluated as providing an equivalent level of protection.
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.6.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.6.3-1 Fire Area C-6, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                  M-663-00017A Closure Component Category Fire door 32015                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    Fire Door Fire door 32092                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    Fire Door Penetration seals that exceed the bounding                                            Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                                                    Structural Steel Fireproofing unprotected thermal shorts
 
The stairway enclosure at the 1984 elevation is 2-hour rated,  The remaining elevations are 3-hour rated with the exception of the ceiling. The ceiling of the stairway in this area forms part of the roof. Since no Fire Areas are above the ceiling, it is not rated. The roof is non-combustible concrete with built up Class A roofing. Therefore, structural integrity will be maintained in the event of a fire. Safe shutdown cable is separated from the Access Control area below by a noncombustible suspended ceiling.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 129 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 100 of 244)
C.6.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-6 is Low.
 
C.6.5 Fire Protection
 
Smoke detectors are installed above and below the suspended ceiling except as noted in Attachment A. Manual-pull fire alarm stations are located near the exit doorways from the Access Control area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system is provided in this area above  and below the suspended ceiling as detailed in Attachment  A. Water flow in the system is alarmed in the Control Room.
 
Hose stations and portable extinguishers are provided in the corridors within the Access Control area, as indicated on drawing A-1801.
 
Access to this area for manual firefighting is available via Communications Corridor 3225 through Fire Area C-5 and Auxiliary Building Corridor 1101.
 
Adequate floor drains are provided to remove sprinkler discharge without appreciable accumulation. Any sprinkler discharge in the area above the suspended    ceiling will drain through the suspended ceiling to the Access Control  area below. Drainage is discharged to the Control Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.6.6                                                                                                    Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.6.7 Analysis
 
C.6.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire occurs, the automatic suppression system will actuate and extinguish the fire. In the event of failure of the automatic system, the manual hose stations provide the capability of extinguishing the fire.
 
The suspended ceiling panels may be removed as necessary during firefighting efforts involving the normally concealed space above the panels. The  majority of the cable  trays in this area are no more than 12 feet above the floor elevation,  and no trays are more than 14 feet above the floor. Consequently, a fire in these cable trays can be extinguished by Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 130 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 101 of 244) manual hose stations from the floor (assuming failure of the automatic wet pipe sprinkler system above the  trays).
 
C.6.7.2                                                                                                                                  Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-6 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-6 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in C-6.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 131 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 102 of 244)
Fire Area C-7 (Reference A-1801)
 
C.7.1                                                                                                    Fire Area Description
 
North vertical cable chase Room 3230, Control Building. El. 1984 to 2000.
 
C.7.2 Major Equipment
 
Electric cable only
 
C.7.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.7.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.7.3-1 Fire Area C-7, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with                                    Structural Steel Fireproofing unprotected thermal shorts
 
C.7.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-7 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 132 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 103 of 244)
C.7.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit  from the adjacent area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler systems is by portable extinguishers and manual hose stations located in the Access Control area.
 
Access to the chase is through a 3-hour-rated fire door.
 
Drainage in this area is by one 4-inch floor drain. This is more than adequate  to handle maximum sprinkler system discharge and hose station  discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.7.6                                                                                                    Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.7.7 Analysis
 
C.7.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers until extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.7.7.2                                                                                                                                  Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-7 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-7 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 133 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 104 of 244)
Fire Area C-8 (Reference A-1801)
 
C.8.1                                                                                                    Fire Area Description
 
South vertical cable chase Room 3229, Control Building. El. 1984 to 2000.
 
C.8.2 Major Equipment
 
Electric cable only.
 
C.8.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.8.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.8.3-1 Fire Area C-8, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with                                    Structural Steel Fireproofing unprotected thermal shorts
 
C.8.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-8 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 134 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 105 of 244)
C.8.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit  from the adjacent area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in the Access Control area.
 
Access to the chase is through a 3-hour-rated door.
 
Drainage in this area is by one 4-inch floor drain. This is more than adequate  to handle maximum sprinkler system discharge and hose station  discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.8.6                                                                                                    Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.8.7 Analysis
 
C.8.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barrier and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.8.7.2                                                                                                                                  Safe Shutdown Capability
 
There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in C-8.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 135 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 106 of 244)
Fire Area C-9 (Reference A-1802)
 
C.9.1                                                                                                    Fire Area Description
 
North ESF Switchgear Room 3301.
 
C.9.2 Major Equipment
 
Electric cable, ESF switchgear, load center unit substations.
 
C.9.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.9.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.  (Reference 3.1, Section F.5)
 
Table C.9.3-1 Fire Area C-9, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                              M-663-00017A Closure Component Category Missile door 33012                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Fire Door Penetration seals that exceed the bounding                                              Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                          Structural Steel Fireproofing thermal shorts
 
Cables which enter the Switchgear Room without terminating there are minimized.
(Reference 3.1, Section F.5)
 
C.9.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-9 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 136 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 107 of 244)
C.9.5 Fire Protection
 
This area is provided with a cross-zoned smoke detection system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
 
The Halon 1301 system installed is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An activation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation.  (Reference 3.1, Section F.5)
 
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
 
Manual-pull fire alarm stations are located near the exit doorway from this area. The pull stations alarm locally and in the Control Room.
 
Hose stations and portable extinguishers are provided in this Fire Area, as delineated on drawing A-1802.  (Reference 3.1, Section F.5)
 
The area is accessible through two double doorways in the south wall and one  double doorway in the north wall.
 
Three 4-inch floor drains are provided in this area. The drains discharge to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
C.9.6                                                                                                    Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.9.7 Analysis
 
C.9.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the detection  system.
Normally, since this is an unoccupied area, both zones of  smoke detection would trip during a fire and the Halon system  would discharge.
 
In the event of the failure of the Halon system  (identified by Control Room annunciation) the fire can be  extinguished manually with the portable extinguishers and/or hose  stations.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 137 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 108 of 244)
 
C.9.7.2                                                                                                                                  Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-9 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-9 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 138 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 109 of 244)
Fire Area C-10 (Reference A-1802)
 
C.10.1                                                                              Fire Area Description
 
South ESF Switchgear Room 3302.
 
C.10.2 Major Equipment
 
Electric cable, ESF switchgear, load center unit substations.
 
C.10.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.10.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.  (Reference 3.1, Section F.5)
 
Table C.10.3-1 Fire Area C-10, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                        M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                    Structural Steel Fireproofing thermal shorts
 
Cables which enter the Switchgear Room without terminating there are minimized.
(Reference 3.1, Section F.5)
 
C.10.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-10 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 139 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 110 of 244)
C.10.5 Fire Protection
 
This area is provided with a cross-zoned smoke detection system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
 
The Halon 1301 system installed is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An activation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation.  (Reference 3.1, Section F.5)
 
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
 
A manual-pull fire alarm station is located near the south stairwell exit and the north exit from Room 3301. The pull stations alarm locally and in the Control Room.
 
Hose stations and portable extinguishers are provided in this Fire Area, as delineated on drawing A-1802.  (Reference 3.1, Section F.5)
 
The area is accessible through the southwest stairwell and the two double doorways in the north wall.
 
Three 4-inch floor drains are provided in this area. The drains discharge to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
C.10.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.10.7 Analysis
 
C.10.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by either zone of  detection.
Normally, since this is an unoccupied area, both smoke detection zones would trip during the fire and the Halon system  would discharge.
 
In the event of a failure of the Halon system  (identified by Control Room annunciation) the fire can be  extinguished manually with the portable extinguishers and/or hose  stations.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 140 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 111 of 244)
 
C.10.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-10 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-10 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 141 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 112 of 244)
Fire Area C-11 (Reference A-1802)
 
C.11.1                                                                              Fire Area Description
 
South vertical cable chase Room 3305, Control Building. El. 2000 to 2016.
 
C.11.2 Major Equipment
 
Electric cable only.
 
C.11.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.11.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.11.3-1 Fire Area C-11, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with                                    Structural Steel Fireproofing unprotected thermal shorts
 
C.11.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-11 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 142 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 113 of 244)
C.11.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit  from the adjacent area (C-10). Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and the manual hose stations located in Fire Area C-10.
 
Access to the chase is through a 3-hour-rated fire door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle  maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.11.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.11.7 Analysis
 
C.11.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barrier and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.11.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-11 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-11 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 143 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 114 of 244)
Fire Area C-12 (Reference A-1802)
 
C.12.1                                                                              Fire Area Description
 
North vertical cable chase Room 3306, Control Building. El. 2000 to 2016.
 
C.12.2 Major Equipment
 
Electric cable only.
 
C.12.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.12.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.12.3-1 Fire Area C-12, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with                                    Structural Steel Fireproofing unprotected thermal shorts
 
C.12.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-12 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 144 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 115 of 244)
C.12.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit  from the adjacent area (C-9). Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-9.
 
Access to the chase is through a 3-hour-rated fire door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.12.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.12.7 Analysis
 
C.12.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.12.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-12 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-12 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 145 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 116 of 244)
Fire Area C-13 (Reference A-1802)
 
C.13.1                                                                              Fire Area Description
 
Class IE Air Conditioning Equipment Room No. 1 (Room 3415).
 
C.13.2 Major Equipment
 
Class IE electrical AC unit, control room pressurization fan, and control room pressurization system filter adsorber unit
 
C.13.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.13.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.13.3-1 Fire Area C-13, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                          M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                    Structural Steel Fireproofing thermal shorts
 
C.13.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-13 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 146 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 117 of 244)
C.13.5 Fire Protection
 
Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located near the exit  doorways from this elevation of the Control Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are provided in the corridors just outside this Fire Area, as indicated on drawing A-1802.
The charcoal adsorber unit is provided with thermistor-type temperature detectors downstream of the charcoal bed, which alarm in the Control Room at  high airstream temperature. The charcoal bed is equipped with a hose connection to provide manual water spray protection.
The area is accessible through the door from the adjacent corridor.
Drainage in this area is by two 4-inch floor drains. These drains are adequate to handle hose station discharge. The drains discharges to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
C.13.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.13.7 Analysis
 
C.13.7.1 Fire Suppression A fire in this area will be detected and alarmed by the automatic  detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers. Water or fire damage to the safe shutdown equipment will not prevent the safe shutdown of the plant.
A filter fire in the charcoal adsorber unit will be extinguished utilizing the manual spray system.
 
C.13.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-13 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-13 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 147 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 118 of 244)
Fire Area C-14 (Reference A-1802)
 
C.14.1                                                                              Fire Area Description
 
Class IE Air Conditioning Equipment Room No. 2 (Room 3416).
 
C.14.2 Major Equipment
 
Class IE electrical equipment AC unit, control room pressurization fan, and control room pressurization system filter adsorber unit.
 
C.14.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.14.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.14.3-1 Fire Area C-14, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                M-663-00017A Closure Component Category Ceramic fiber and sheet metal fire barrier                                                  Fire Barrier segment Penetration seals that exceed the bounding                                                  Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                              Structural Steel Fireproofing thermal shorts
 
C.14.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-14 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 148 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 119 of 244)
C.14.5 Fire Protection
 
Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located near the exit  doorways from this elevation of the Control Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are provided in the corridors just outside this Fire Area, as indicated on drawing A-1802.
The charcoal adsorber unit is provided with thermistor-type temperature detectors downstream of the charcoal bed, which alarm in the control room at  high airstream temperature. The charcoal bed is equipped with a hose connection to provide manual water spray protection.
The area is accessible through the door from the adjacent corridor.
Drainage in this area is by one 4-inch floor drain. This drain is adequate to handle hose station discharge. The drain discharges to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
C.14.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.14.7 Analysis
 
C.14.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers. Water or fire damage to the safe shutdown equipment will not prevent the safe shutdown of the plant.
A filter fire in the charcoal adsorber unit will be extinguished utilizing the manual spray system.
 
C.14.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-14 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-14 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 149 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 120 of 244)
Fire Area C-15 (Reference A-1802)
 
C.15.1                                                                              Fire Area Description
 
Battery and Switchboard Rooms (south), Control Building. El. 2016. Rooms 3403, 3404, 3405, 3410, and 3411.
 
C.15.2 Major Equipment
 
Switchgear, batteries, battery chargers, panels, inverters, transformers, and electric cable
 
C.15.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.15.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.  (Reference 3.1, Section F.7)
 
Table C.15.3-1 Fire Area C-15, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                    M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                    Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                Structural Steel Fireproofing thermal shorts
 
The area contains five rooms (including two battery rooms) that are separated by 3-hour fire barrier construction.  (Reference 3.1, Section F.7)
 
C.15.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-15 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 150 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 121 of 244)
C.15.5 Fire Protection
 
Except for the Battery Rooms (Rooms 3405 and 3411), a cross-zoned smoke detection system is installed in this area. The Battery Rooms are provided with one smoke detection zone. Manual-pull fire alarm stations are located near the exit doorways from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Hose stations and portable extinguishers are provided in the corridors just outside this Fire Area, as indicated on drawing A-1802. The hose stations can reach all rooms in this area.  (Reference 3.1, Section F.7)
 
Those areas provided with a cross-zoned detection system are also protected with an automatic Halon 1301 extinguishing system. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
 
The Halon 1301 system installed is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An actuation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation.
 
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
 
This area is accessible through any of the four doors  opening into the access corridor.
 
Each room within the Fire Area is provided with one 4-inch drain. These drains are adequate to handle hose station discharge. The drains discharge to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
C.15.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 151 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 122 of 244)
The Battery Rooms in this Fire Area serving each of the safeguards equipment trains in the safe shutdown areas are served by two systems--the Control Building supply air system and the Class IE AC unit. Loss of either or both of these systems will be alarmed in the Control Room via the plant computer. These ventilation systems are capable of maintaining the hydrogen concentration well below two-volume percent. Additionally, each Battery Room is also provided with a hydrogen detector which will alarm in the Control Room whenever the hydrogen concentration exceeds 1 volume percent in any one of the Battery Rooms.  (Reference 3.1, Section F.7)
 
The Control Building supply air system supplies outside air to each of the four DC Switchgear Rooms. This air is exhausted from the Switchgear Rooms through the Battery Rooms by the Control Building exhaust system. The supply air system and the exhaust system provide approximately one air change per hour in each Battery Room.
(Reference 3.1, Section F.7)
 
Battery Rooms 1, 3 and 2, 4 are each served by the Class IE ac system. Each Battery Room is supplied and exhausted separately. The Class IE  AC systems each operate in a completely recirculating mode at all  times. These systems also serve their respective ESF Switchgear and DC Switchgear Rooms. It has been conservatively calculated that with no fresh air the system can operate for approximately 3 days before  the hydrogen concentration reaches 3 volume percent.  (Reference 3.1, Section F.7)
 
C.15.7 Analysis
 
C.15.7.1 Fire Suppression
 
A fire in any of the rooms in this area will be detected and alarmed  by the smoke detection system. In those areas protected with a  Halon 1301 extinguishing system, the system will provide fire suppression of the fire.
In the event of a failure of the halon system or  in areas not provided with an extinguishing system, the fire can be  extinguished manually with the portable extinguishers and/or hose  streams.
 
C.15.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-15 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-15 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 152 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 123 of 244)
Fire Area C-16 (Reference A-1802)
 
C.16.1                                                                              Fire Area Description
 
Battery and Switchboard Rooms (north), Control Building. El. 2016 Rooms 3407, 3408, 3409, 3413, and 3414.
 
C.16.2 Major Equipment
 
Switchgear, batteries, battery chargers, panels, inverters, transformers, and electric cable.
 
C.16.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
x                                      Have been evaluated as providing an equivalent level of protection.
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.16.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.  (Reference 3.1, Section F.7)
 
Table C.16.3-1 Fire Area C-16, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                              M-663-00017A Closure Component Category Door 34071                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door Penetration seals that exceed the bounding                                                Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                            Structural Steel Fireproofing thermal shorts
 
The area contains five rooms (including two battery rooms) that are separated by 3-hour fire barrier construction.  (Reference 3.1, Section F.7)
 
C.16.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-16 is Low.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 153 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 124 of 244)
C.16.5 Fire Protection
 
Except for the Battery Rooms (Rooms 3407 and 3413), a cross-zoned smoke detection system is installed in the area. One zone of smoke detectors is installed in the Battery Rooms. Manual-pull fire alarm stations are located near the exit doorways from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Hose stations and portable extinguishers are provided in the corridors just outside this fire area, as indicated on drawing A-1802. The hose stations can reach all the various rooms in this area.  (Reference 3.1, Section F.7)
 
Those areas provided with a cross-zoned smoke detection system are also protected with an automatic Halon 1301 extinguishing system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
 
The Halon 1301 system installed is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An actuation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation.
 
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
 
This area is accessible through any of the four doors  opening into the access corridor.
 
Each room within the Fire Area is provided with one 4-inch drain. These drains are adequate to handle hose station discharge. The drains discharge to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
C.16.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
The Battery Rooms in this Fire Area serving each of the safeguards equipment trains in the safe shutdown areas are served by two systems--the Control Building supply air system and the Class IE AC unit. Loss of either or both of these systems will be alarmed in the Control Room via the plant computer. These ventilation systems are capable of maintaining the hydrogen concentration well below two-volume percent. Additionally, Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 154 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 125 of 244) each Battery Room is also provided with a hydrogen detector which will alarm in the Control Room whenever the hydrogen concentration exceeds 1 volume percent in any one of the Battery Rooms.  (Reference 3.1, Section F.7)
 
The Control Building supply air system supplies outside air to each of the four DC Switchgear Rooms. This air is exhausted from the Switchgear Rooms through the Battery Rooms by the control Building exhaust system. The supply air system and the exhaust system provide approximately 1 air change per hour in each Battery Room.
(Reference 3.1, Section F.7)
 
Battery Rooms 1, 3 and 2, 4 are each served by the Class IE AC system. Each Battery Room is supplied and exhausted separately. The Class IE  ac systems each operate in a completely recirculating mode at all  times. These systems also serve their respective ESF Switchgear and DC Switchgear Rooms. It has been conservatively calculated that with no fresh air the system can operate for approximately 3 days before  the hydrogen concentration reaches 3 volume percent.  (Reference 3.1, Section F.7)
 
C.16.7 Analysis
 
C.16.7.1 Fire Suppression
 
A fire in any of the rooms in this area will be detected and alarmed  by the smoke detection system. In those areas protected with a  Halon 1301 extinguishing system, the system will provide fire suppression of the fire.
In the event of a failure of the Halon system or in areas  not provided with an extinguishing system, the fire can be  extinguished manually with the portable extinguishers and/or hose  streams.
 
C.16.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-16 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-16 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 155 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 126 of 244)
Fire Area C-17 (Reference A-1802)
 
C.17.1                                                                              Fire Area Description
 
South Vertical Cable Chase (Room 3418), Control Building El. 2016 to 2032.
 
C.17.2 Major Equipment
 
Electric cable only
 
C.17.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.17.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.17.3-1 Fire Area C-17, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with                                    Structural Steel Fireproofing unprotected thermal shorts
 
C.17.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-17 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 156 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 127 of 244)
C.17.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in the access corridor (3401) at this elevation.
 
Access to the chase is through a 3-hour-rated fire  door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.17.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.17.7 Analysis
 
C.17.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.17.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-17 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-17 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 157 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 128 of 244)
Fire Area C-18 (Reference A-1802)
 
C.18.1                                                                              Fire Area Description
 
North Vertical Cable Chase (Room 3419), Control Building  El. 2016 to 2032.
 
C.18.2 Major Equipment
 
Electric cable only
 
C.18.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.18.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.18.3-1 Fire Area C-18, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with                                    Structural Steel Fireproofing unprotected thermal shorts
 
C.18.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-18 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 158 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 129 of 244)
C.18.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in the access corridor (3401) at this elevation.
 
Access to the chase is through a 3-hour-rated  door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.18.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.18.7 Analysis
 
C.18.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.18.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-18 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-18 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 159 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 130 of 244)
Fire Area C-19 (Reference A-1802)
 
C.19.1                                                                              Fire Area Description
 
Cable Chase at column line CA-C3, Control Building El. 2016 to 2032.
 
C.19.2 Major Equipment
 
Electric cable only.
 
C.19.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
C.19.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-19 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
C.19.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in the access corridor (3401) at this elevation.
Access to the chase is through a 3-hour-rated  door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.19.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 160 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 131 of 244)
C.19.7 Analysis
 
C.19.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.19.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-19 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-19 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 161 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 132 of 244)
Fire Area C-20 (Reference A-1802)
 
C.20.1                                                                              Fire Area Description
 
Cable Chase at column line C-6, Control Building El. 2016 to 2032.
 
C.20.2 Major Equipment
 
Electric cable only.
 
C.20.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.20.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.20.3-1 Fire Area C-20, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with                                    Structural Steel Fireproofing unprotected thermal shorts
 
C.20.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-20 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 162 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 133 of 244)
C.20.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in the access corridor (3401) at this elevation.
 
Access to the chase is through a 3-hour-rated fire door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.20.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.20.7 Analysis
 
C.20.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.20.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-20 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-20 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 163 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 134 of 244)
Fire Area C-21 (Reference A-1803)
 
C.21.1                                                                              Fire Area Description
 
Lower Cable Spreading Room 3501.
 
C.21.2 Major Equipment
 
Electric cable.
 
C.21.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
x                                      Have been evaluated as providing an equivalent level of protection.
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.21.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.  (Reference 3.1, Section F.3.a)(3))
 
Table C.21.3-1 Fire Area C-21, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                                            M-663-00017A Closure Component Category Cable trenches                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  Fire Barrier Door 32015                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            Fire Door Missile door 35021                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Fire Door Penetration seals that exceed the bounding                                                                            Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                                        Structural Steel Fireproofing thermal shorts
 
Stairwell C-1 is separated from this area by fire rated barriers.
 
C.21.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-21 is Low.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 164 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 135 of 244)
C.21.5 Fire Protection
 
Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located near the exit doorways from this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
This area is provided with partial coverage automatic preaction sprinkler system installed at the ceiling. Location of the closed sprinkler heads considers cable tray sizing and arrangement. Cables are designed to allow wetting down with suppression water without electrical faulting.  (Reference 3.1, Section F.3.a)(1))
 
Hose stations and portable extinguishers are provided in this fire area for backup protection, as indicated on drawing A-1803.  (Reference 3.1, Section F.3.a)(2))
 
This area is accessible from the stairway at the south end and the Communications Corridor at the north end of the area. These entrances to the area are remote and separate. Generally, aisle separation between tray stacks is 3 feet wide by 7 feet high.
(Reference 3.1, Section F.3.a)(4) and F.3.a)(5))
 
Adequate floor drainage capacity is provided in this area to remove sprinkler system and hose station discharge without  appreciable accumulation. Specifically, four 6-inch drains are provided throughout this Fire Area. The floor drains are piped to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
C.21.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.21.7 Analysis
 
C.21.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. Detector actuation will also open the sprinkler  system deluge valve, thus charging the system piping. In the event  that a fire occurs, the automatic sprinkler system will discharge and  suppress the fire. Should the automatic system fail to operate (identified by Control Room annunciation), or fail to completely extinguish the fire, it would be extinguished by utilizing the manual hose stations.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 165 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 136 of 244)
C.21.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-21 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-21 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 166 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 137 of 244)
Fire Area C-22 (Reference A-1804)
 
C.22.1                                                                              Fire Area Description
 
Upper Cable Spreading Room 3801.
 
C.22.2 Major Equipment
 
Electric cable.
 
C.22.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.22.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.  (Reference 3.1, Section F.3.a)(3))
 
Table C.22.3-1 Fire Area C-22, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                    M-663-00017A Closure Component Category Missile door 38011                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Fire door Structural Steel Fireproofing with unprotected                              Structural Steel Fireproofing thermal shorts
 
The ceiling is the roof of the control building and is not rated. It is however constructed of concrete with built up Class A roofing. In addition, the structural steel supporting the roof is protected with 3-hour fire proofing material. Therefore, building structural integrity is maintained.  (Reference 3.1, Section F.3.a)(3))
 
Stairwell C-1 is separated from this area by fire rated barriers.
 
Floor penetrations in this area are  provided with raised sleeves or curbs, and all penetrations have watertight seals to prevent water damage in the Control Room below during fire-fighting operations in this area.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 167 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 138 of 244)
C.22.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-22 is Low.
 
C.22.5 Fire Protection
 
Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located near the exit doorways from this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
This area is provided with partial coverage automatic preaction sprinkler system installed at the ceiling. Location of the closed sprinkler heads considers cable tray sizing and arrangement. Cables are designed to allow wetting down with suppression water without electrical faulting.  (Reference 3.1, Section F.3.a)(1))
 
Hose stations and portable extinguishers are provided in this fire area for backup protection, as indicated on drawing A-1804.  (Reference 3.1, Section F.3.a)(2))
 
This area is accessible from the stairway at the south end and the Communications Corridor at the north end of the area. These entrances to the area are remote and separate. Generally, aisle separation between tray stacks is 3 feet wide by 7 feet high.
(Reference 3.1, Section F.3.a)(4) and F.3.a)(5))
 
Adequate floor drainage capacity is provided in this area to remove sprinkler system and hose station discharge without  appreciable accumulation. Specifically, four 6-inch drains are provided throughout this Fire Area. The floor drains are piped to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
C.22.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.22.7 Analysis
 
C.22.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. Detector actuation will also open the sprinkler system deluge valve, thus charging the system piping. In the event that a fire occurs, the automatic sprinkler system will discharge and suppress the fire. Should the automatic system fail to operate (identified by Control Room annunciation), or fail to completely extinguish the fire, it would be extinguished by utilizing the manual hose stations.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 168 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 139 of 244)
C.22.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-22 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-22 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 169 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 140 of 244)
Fire Area C-23 (Reference A-1803)
 
C.23.1                                                                              Fire Area Description
 
South Vertical Cable Chase (Room 3505), Control Building. El. 2032 to 2047-6.
 
C.23.2 Major Equipment
 
Electric cable only.
 
C.23.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.23.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.23.3-1 Fire Area C-23, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                        M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                      Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                  Structural Steel Fireproofing thermal shorts
 
C.23.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-23 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 170 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 141 of 244)
C.23.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the exits  from the adjacent Room 3501. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-21.
 
Access to the chase is through a 3-hour-rated door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.23.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.23.7 Analysis
 
C.23.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
 
C.23.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-23 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-23 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 171 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 142 of 244)
Fire Area C-24 (Reference A-1803)
 
C.24.1                                                                              Fire Area Description
 
North Vertical Cable Chase (Room 3504), Control Building. El. 2032 to 2047-6.
 
C.24.2 Major Equipment
 
Electric cable only.
 
C.24.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.24.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.24.3-1 Fire Area C-24, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category Structural Steel Fireproofing with                                    Structural Steel Fireproofing unprotected thermal shorts
 
C.24.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-24 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 172 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 143 of 244)
C.24.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the exits  from the adjacent Room 3501. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-21.
 
Access to the chase is through a 3-hour-rated door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.24.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.24.7 Analysis
 
C.24.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
 
C.24.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-24 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-24 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 173 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 144 of 244)
Fire Area C-25 (Reference A-1803)
 
C.25.1                                                                              Fire Area Description
 
Cable Chase at column line CA-C6, Control Building. El. 2032 to 2047-6.
 
C.25.2 Major Equipment
 
Electric cable only.
 
C.25.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.25.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.24.3-1 Fire Area C-25, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                    M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                    Penetration Seal limitations of M-663-00017
 
C.25.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-25 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 174 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 145 of 244)
C.25.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the exits  from the adjacent Room 3501. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-21.
 
Access to the chase is through a 3-hour-rated door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.25.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.25.7 Analysis
 
C.25.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.25.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-25 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-25 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 175 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 146 of 244)
Fire Area C-26 (Reference A-1803)
 
C.26.1                                                                              Fire Area Description
 
Vertical Cable Chase at column line CA-C3, Control Building El. 2032 to 2047-6.
 
C.26.2 Major Equipment
 
Electric cable only.
 
C.26.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
C.26.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-26 is High.
 
C.26.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the exits  from the adjacent Room 3501. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-21.
 
Access to the chase is through a 3-hour-rated door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.26.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 176 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 147 of 244)
C.26.7 Analysis
 
C.26.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. In the event that a fire develops, it will be  contained by the fire barriers and extinguished by the automatic  suppression system. Should the automatic suppression system fail,  manual hose streams can be directed through the access opening to  extinguish the fire.
 
C.26.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-26 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-25 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 177 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 148 of 244)
Fire Area C-27 (Reference A-1804)
 
C.27.1                                                                              Fire Area Description
 
Control Room area, Rooms 3601, 3603-3606, and 3616.
 
C.27.2 Major Equipment
 
Main control board equipment cabinets, electric cable.
 
C.27.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.27.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.  (Reference 3.1, Section F.2)
 
All penetration seals are relatively airtight, as demonstrated by periodic Control Room pressurization testing.  (Reference 3.1, Section F.2)
 
Table C.27.3-1 Fire Area C-27, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                              M-663-00017A Closure Component Category Cable trenches                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  Fire Barrier Missile door 36042                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Fire Door Penetration seals that exceed the bounding                                                              Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                          Structural Steel Fireproofing thermal shorts
 
The following rooms at this elevation of the Control Building are considered peripheral rooms and are not part of the Control Room. These rooms are separated from this Fire Area by fire rated barriers.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 178 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 149 of 244)
: a.                                                        3609, SAS room (See Fire Area C-29)
: b.                                                        3602, Pantry (See Fire Area C-28)
: c.                                                          3607, Toilet (See Fire Area  C-28)
: d.                                                        3608, Janitor's closet (See Fire Area  C-28)
 
Some electric cable is routed above the suspended ceiling over Room 3601. However, none of these circuits are required for a safe shutdown. The floor of Room 3601 contains nine cable trenches (approximately 3-1/4 inches deep), which continue up the height of the west wall in the Control Room. The trenches are covered by steel plates, and the vertical chases are faced with sheet rock (not rated). Access panels are provided for each chase at several elevations within the Control Room, and the steel covers on the trenches are removable for manual fire-fighting access. The floor of 3605 contains two cable trenches (approximately 3-1/4 inches deep). These two trenches are covered by steel cover plates that are removable for firefighting access.
 
Electrical cables of redundant safety-related equipment trains are physically separated within the Control Room. Redundant safety-related circuits enter the Control Room from the Upper and Lower Cable Spreading Rooms. Circuits from the Lower Cable Spreading Room, which are in separation groups 1, 3, and 5 enter the control panels and cabinets directly. Circuits from the Upper Cable Spreading Room, which are in separation groups 2, 4, and 6 are routed to the control panels and cabinets through conduit, vertical wall trays, and under floor cable trenches. Within the control panels, safety-related wiring is separated from redundant circuits and protected in accordance with the guidelines of Regulatory Guide 1.75.
 
C.27.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-27 is Low.
 
Internal surfaces of control panels are finished with paint of low flame spread. All cables in these panels meet the vertical  flame requirements of ICEA S-19-81 and/or IEEE 383-1974 for flame resistance.
 
The carpet material used in the control room is 100 percent nylon. This material meets or exceeds the surface flammability requirements per ASTM E84 or CPSC Standard FF1-70, the static propensity rating per ASTM D2679 or AATCC-134, smoke development rating per ASTM E662, and the critical radiant flux rating per ASTM E-648 or NFPA 253.
 
The suspended acoustical ceiling consists of panels with a maximum flame spread of 25 when tested in accordance with ASTM E 84.
 
The majority of the paper is stored in steel cabinets, book cases and drawers, which reduces the fire loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 179 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 150 of 244)
C.27.5 Fire Protection
 
As delineated in Attachment  A. Automatic smoke detectors are installed in each room containing fixed combustibles and in panels, which contain both trains of redundant safety-related conduit, cable, or wire required for safe shutdown. Smoke detection is also provided for the cable trenches in 3601 and the area above the Control Room proper suspended ceiling.  (Reference 3.1, Section F.2)
 
Manual-pull fire alarm stations are located near the exit doorways from this area.
Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.  (Reference 3.1, Section F.2)
 
Automatic smoke detection is provided for the outside air intakes to  the Control Room ventilation system. This detection is alarmed in the  Control Room, and the Control Room ventilation system can be manually  isolated.  (Reference 3.1, Section F.2)
 
An automatic Halon 1301 extinguishing system is provided for the nine cable trench/wall chase combinations in the floor and west wall of Room 3601. The system is designed to maintain a minimum 5-percent concentration for approximately 7 minutes by utilizing an extended discharge following the initial release of Halon agent. This design configuration was accepted in SSER 5.  (Reference 3.1, Section F.2)
 
The Halon cylinders and the control panel are located outside the cable trench protected area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A release button is provided on the control panel to discharge the system manually. Automatic activation will sound a local alarm and discharge the system following a brief time delay. One hundred percent capacity reserve cylinders are provided for connection to the system.
 
Hose stations and portable extinguishers are provided adjacent to the Control Room area, as indicated on drawing A-1804. Hose stations are equipped with Class "C" spray nozzles with rubber bumpers. These hose stations permit coverage of the area above the suspended ceiling.  (Reference 3.1, Section F.2)
 
The area is accessible for manual firefighting from Communications Corridor Room 3611, Southwest Stairwell 3201, and Auxiliary Building Room 1512. Breathing apparatus are available for Control Room operators.  (Reference 3.1, Section F.2)
 
Drainage in this area is by four 4-inch floor drains. This is adequate to handle maximum hose station discharge. The floor drains are piped to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 180 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 151 of 244)
C.27.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion. Air packs are provided for operating  personnel to permit them to remain in the Control Room when smoke is  present.
 
C.27.7 Analysis
 
C.27.7.1 Fire Suppression
 
Personnel access to the Control Room is limited to necessary  personnel, and strict administrative controls exist to limit transient  combustibles within the Control Room. For these reasons, it is highly  improbable that any fire more severe than an electrical fire within a  control panel or cabinet could occur.
 
The fixed paper combustibles are  necessary for the safe operation of the plant and are not stored in  the immediate vicinity of the panels containing redundant safe shutdown circuits. Nevertheless, exposure fires sufficiently large to destroy any single control panel, before being extinguished, have been  postulated. The ability to take the plant to a safe shutdown condition under such a circumstance is addressed in Section C.27.7.2.
 
The physical separation discussed in Section C.27.3 for redundant cable separation groups prevents an electrically-initiated fire from propagating to the point that it could adversely affect redundant trains. This is based on the limited energy density associated with an electrical fire, the minimum separation distances within any control panel, the physical barriers provided within the panel, and the fire detection and suppression systems provided. Further, since there are no power cables in safety-related control panels, the probability of an electrical fire is low.
 
Additionally, consistent with the conclusions of NUREG/CR-4527, an internal cabinet fire is not postulated to propagate to an adjacent cabinet when the following are satisfied:
 
x                                    Cabinet of fire origin is protected by a predominantly noncombustible external shell.
 
x                                    Adjacent cabinet is protected by a predominantly noncombustible external shell.
 
x                                    At least a 1 air gap is provided between the cabinet of fire origin and the adjacent cabinet of concern.
 
The cabinet fire testing documented in NUREG/CR-4527 demonstrated that significant smoke obscuration did not occur until approximately six minutes following cabinet fire ignition.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 181 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 152 of 244)
 
The automatic Halon system will suppress a fire originating in a cable trench. Portable fire extinguishers and hose stations in the foyer to the Control Room and the vestibule to Stairway C-1 provide    means of extinguishing any fire that may occur.
 
C.27.7.2                                                                                                            Safe Shutdown Capability
 
A detailed study, entitled "SNUPPS Control Room Fire Hazards Analysis,"
was submitted to the NRC by letter SLNRC 82-046 dated November 15, 1982. That report addressed transient fires originating between the Control Room panels. Based on revised NRC positions, a report, "Fire Protection Review" was submitted to the NRC by letter SLNRC 84-109, dated August 23, 1984. This report provides the response plan necessary to ensure achievement and maintenance of hot standby conditions from outside the Control Room with postulated Control Room fire damage.
Modifications to the facility and procedure changes have resulted in enhancements to the original response plan identified in SLNRC 84-109.
However, the letters objective to achieve and maintain hot standby in a systematic, prioritized manner is preserved.
 
In the event that the Control Room is made uninhabitable by smoke, as a consequence of a fire, and there is no damage to safety-related circuits within the Control Room, the plant can be taken to and controlled in a safe hot standby condition from the auxiliary shutdown panel in the Auxiliary Building. The plant can be taken to a cold shutdown condition from outside the Control Room using the auxiliary shutdown panel and local controls at equipment locations and cabinets containing safety related equipment as described in USAR Section 7.4.3.
 
If, as a consequence of a fire, there is the potential for damage affecting safety-related circuits within Control Room panels, there are switches and contacts on the train B auxiliary shutdown panel (RP118B) that would be used to isolate Control Room circuits. With control at RP118B and following completion of specific actions at other locations outside the Control Room, the plant can be taken to and maintained at a safe hot standby condition. Refer to USAR Table 7.4-1 for the list of selected instrumentation and controls on RP118B that have the isolation feature.
Transition to hot standby as a result of a Control Room fire necessitating Control Room evacuation is procedurally controlled by OFN RP-017.
 
With the plant in a safe hot standby condition, controls and instrumentation for systems required to take the plant to cold shutdown can be evaluated for operability and cold shutdown activities can be performed from the auxiliary shutdown panels, and locally, as required.
 
Refer to letter SLNRC 84-109 for further discussion on safe shutdown following a Control Room fire. XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 182 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 153 of 244)
Fire Area C-28 (Reference A-1804)
 
C.28.1                                                                              Fire Area Description
 
Service area by Control Room, Rooms 3602, 3607, and 3608.
 
C.28.2 Major Equipment
 
None.
 
C.28.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
C.28.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-28 is Low.
 
C.28.5 Fire Protection
 
Automatic smoke detection is installed in the janitors closet Room 3608. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A stand-alone heat detector/door closer system is installed in the pantry, room 3602, which actuates closure of the pantry to Control Room door which is normally in the open position. The heat detector actuates the door closer and a strobe located in the Control Room near the pantry door.
Hose stations and portable extinguishers are provided in the foyers of  Fire Area C-27 as indicated on drawing A-1804.
The area is accessible for manual firefighting from Communications Corridor Room 3611, Southwest Stairwell 3201, and Auxiliary Building Room 1512.
A sanitary drain is provided in the floor of the restroom for this area. This is acceptable since manual fire water suppression efforts will be minimal, considering the small footprint of the area.
 
C.28.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 183 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 154 of 244)
C.28.7 Analysis
 
C.28.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic  detection system. The fire can be extinguished manually with the  portable extinguishers and/or hose station located in the adjacent  area.
Continuous occupancy of the adjacent Control room ensures a  rapid response to a fire in this area.
 
C.28.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-28 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-28 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 184 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 155 of 244)
Fire Area C-29 (Reference A-1804)
 
C.29.1                                                                              Fire Area Description
 
SAS Room 3609.
 
C.29.2 Major Equipment
 
SAS panel.
 
C.29.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
C.29.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-29 is Low.
 
C.29.5 Fire Protection
 
Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located near the exit doorways from the adjacent area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Hose stations and portable extinguishers are provided in the foyers of Fire Area C-27, as indicated on drawingA-1804.
 
The area is accessible for manual fire fighting from Communications Corridor Room 3611, Southwest Stairwell 3201, and Auxiliary Building Room 1512.
 
No drains are provided for this Fire Area, as manual fire water suppression efforts will be minimal, considering the small footprint of the area.
 
C.29.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 185 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 156 of 244)
C.29.7 Analysis
 
C.29.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually with the portable extinguishers and/or hose station located in the adjacent area.
Continuous occupancy of the adjacent control room ensures a rapid response to a fire in this area.
 
C.29.7.2                                                                                                            Safe Shutdown Capability
 
There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 186 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 157 of 244)
Fire Area C-30 (Reference A-1804)
 
C.30.1                                                                              Fire Area Description
 
South Vertical Cable Chase (Room 3617), Control Building. El. 2047-6 to 2073-6.
 
C.30.2 Major Equipment
 
Electric cable only.
 
C.30.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.30.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.30.3-1 Fire Area C-30, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                        M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                      Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                  Structural Steel Fireproofing thermal shorts
 
C.30.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-30 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 187 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 158 of 244)
C.30.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent area (C-27). Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-27 and Stairwell Vestibule 3616.
 
Access to the chase is through a 3-hour-rated fire door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.30.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.30.7 Analysis
 
C.30.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
 
C.30.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-30 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-30 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 188 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 159 of 244)
Fire Area C-31 (Reference A-1804)
 
C.31.1                                                                              Fire Area Description
 
North Vertical Cable Chase (Room 3618), Control Building. El. 2047-6 to 2073-6.
 
C.31.2 Major Equipment
 
Electric cable only.
 
C.31.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.31.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.31.3-1 Fire Area C-31, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                  M-663-00017A Closure Component Category Structural Steel Fireproofing with                                      Structural Steel Fireproofing unprotected thermal shorts
 
C.31.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-31 is Low. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 189 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 160 of 244)
C.31.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent area (C-27). Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-27.
 
Access to the chase is through a 3-hour-rated door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.31.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.31.7 Analysis
 
C.31.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
 
C.31.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-31 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-31 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 190 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 161 of 244)
Fire Area C-32 (Reference A-1804)
 
C.32.1                                                                              Fire Area Description
 
Vertical Cable Chase at column line CA-C6, Control Building El. 2047-6 to 2073-6.
 
C.32.2 Major Equipment
 
Electric cable only.
 
C.32.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.32.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.32.3-1 Fire Area C-32, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                          M-663-00017A Closure Component Category Penetration seals that exceed the                              Penetration Seal bounding limitations of M-663-00017
 
C.32.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-32 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 191 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 162 of 244)
C.32.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent area (C-27). Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-27 and Stairwell Vestibule 3616.
 
Access to the chase is through a 3-hour-rated door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.32.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.32.7 Analysis
 
C.32.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barrier and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
 
C.32.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-32 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-32 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 192 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 163 of 244)
Fire Area C-33 (Reference A-1804)
 
C.33.1                                                                              Fire Area Description
 
South Vertical Cable Chase (Room 3804), Control Building El. 2073-6.
 
C.33.2 Major Equipment
 
Electric cable only.
 
C.33.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature. Since this is the highest elevation, the ceiling of the Fire Area is not rated.
 
C.33.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-33 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
C.33.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent Room 3801. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-22.
 
Access to the chase is through a 3-hour-rated door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.33.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 193 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 164 of 244)
 
C.33.7 Analysis
 
C.33.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
 
C.33.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-33 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-33 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 194 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 165 of 244)
Fire Area C-34 (Reference A-1804)
 
C.34.1                                                                              Fire Area Description
 
Vertical Cable Chase at column line CA-C6, Control Building El. 2073-6.
 
C.34.2 Major Equipment
 
Electric cable only.
 
C.34.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature. Since this is the highest elevation, the ceiling of the Fire Area is not rated.
 
C.34.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-34 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
C.34.5 Fire Protection
 
Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent Room 3801. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-22.
 
Access to the chase is through a 3-hour-rated door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.34.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 195 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 166 of 244)
C.34.7 Analysis
 
C.34.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
 
C.34.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-34 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-34 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 196 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 167 of 244)
Fire Area C-35 (Reference A-1802)
 
C.35.1                                                                              Fire Area Description
 
Control Building corridor, El. 2016 Rooms 3401, 3406, and 3412.
 
C.35.2 Major Equipment
 
None.
 
C.35.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.35.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.35.3-1 Fire Area C-35, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                                              M-663-00017A Closure Component Category Ceramic fiber and sheet metal fire barrier                                                                            Fire Barrier segment Missile door 34021                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Fire Door Fire door 34071                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    Fire Door 3-hour rated fire wrap protection for                                                                                  Fire Wrap redundant PFSSD circuits Penetration seals that exceed the bounding                                                                            Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                                                        Structural Steel Fireproofing thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 197 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 168 of 244)
C.35.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-35 is Low.
 
C.35.5 Fire Protection
 
Due to low combustible loading in this area, a detection system is not installed. Manual-pull stations are located at exit doors. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Fire extinguishers and hose stations are located in this area, as delineated on drawing A-1802.
 
Access to the area for manual fire fighting is via Communications Corridor 3402 and Stairwell 3201.
 
There are four floor drains located in this area (a fifth drain in the area is capped). These drains are adequate to handle hose station discharge. The floor drains are piped to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps.
Refer to drawing series M-12LE for further information on the oily waste drain system.
 
C.35.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.35.7 Analysis
 
C.35.7.1 Fire Suppression
 
The fire barriers enclosing this area will protect this area from a fire in the adjoining areas and will contain a fire within this area until extinguished. A fire in this area would be extinguished manually using the hose stations and extinguishers shown on drawing A-1802.
 
C.35.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-35 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-35 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 198 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 169 of 244)
Fire Area C-36 (Reference A-1802)
 
C.36.1                                                                              Fire Area Description
 
Cable Chase at column line CA-C6, Control building El. 2000 to 2016.
 
C.36.2 Major Equipment
 
Electric cable only.
 
C.36.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.36.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.36.3-1 Fire Area C-36, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                  M-663-00017A Closure Component Category Structural Steel Fireproofing with                                      Structural Steel Fireproofing unprotected thermal shorts
 
C.36.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-36 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 199 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 170 of 244)
C.36.5 Fire Protection
 
A manual-pull fire alarm station is located at the normal exit from this floor elevation. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and a manual hose station located in the ESF Switchgear Room (3302) at this elevation.
 
Access to the chase is through a 3-hour-rated fire door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.36.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.36.7 Analysis
 
C.36.7.1 Fire Suppression
 
In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
 
C.36.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-36 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-36 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 200 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 171 of 244)
Fire Area C-37 (Reference A-1802)
 
C.37.1                                                                              Fire Area Description
 
Cable Chase at column line CA-C3, Control building El. 2000 to 2016.
 
C.37.2 Major Equipment
 
Electric cable only.
 
C.37.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table C.37.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table C.37.3-1 Fire Area C-37, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                  M-663-00017A Closure Component Category Structural Steel Fireproofing with                                      Structural Steel Fireproofing unprotected thermal shorts
 
C.37.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area C-37 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 201 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 172 of 244)
C.37.5 Fire Protection
 
A manual-pull fire alarm station is located at the normal exit from this floor elevation. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and a manual hose station located in the ESF Switchgear Room (3301) at this elevation.
 
Access to the chase is through a 3-hour-rated door.
 
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
C.37.6                                                                              Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
C.37.7 Analysis
 
C.37.7.1 Fire Suppression
 
In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
 
C.37.7.2                                                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-37 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-37 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 202 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 173 of 244)
Fire Area CC-1 (Reference A-1801 through A-1804)
 
CC.1.1                                                                        Fire Area Description
 
Communications corridor (all elevations) Rooms 3102, 3103, 3225, 3226 3227, 3228, 3303, 3304, 3402 3502, 3503, 3611 3612, 3613 3614, 3619, 3701, 3702, 3703, 3704, 3705, 3802, 3803, and OP-6.
 
CC.1.2 Major Equipment
 
Plant computer, central chilled and hot water package, and HVAC equipment, batteries, hydrogen monitor, power distribution equipment.
 
CC.1.3 Design Features
 
With the exception of the open communication with the Turbine Building on the east end, this Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table CC.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table CC.1.3-1 Fire Area CC-1, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                                            M-663-00017A Closure Component Category Missile door 14032                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door Missile door 33012                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door Missile door 33044                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door Missile door 34021                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door Missile door 35021                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door Missile door 36042                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door Missile door 38011                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door Penetration seals that exceed the                                                                                Penetration Seal bounding limitations of M-663-00017
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 203 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 174 of 244)
The ceiling of this area is the building roof, and the bottom floor is on grade. At floor El.
2000 feet and above, this area is open to the Turbine Building. However, Rooms 3702 and 3703 are separated from all of the adjacent rooms within the Communication Corridor and Turbine Building by fire rated barriers; floor, walls and ceiling. The floor of the Rooms (3702, 3703) are at EL. 2061'-6" and the ceiling is at EL. 2074'-2".
 
CC.1.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area CC-1 is Low. This includes the combustible gas cylinder rack in Room 3102 that is necessary for laboratory analysis activities in the Health Physics Hot Laboratory.
 
The combustible loading associated with Rooms 3702 and 3703 is not considered to contribute to a fire in this Fire Area due to the fire barriers provided for each of these rooms.
 
CC.1.5 Fire Protection
 
Automatic smoke detectors are installed in areas which contain appreciable quantities of combustibles. Attachment  A identifies the specific rooms in this Fire Area that contain detection. Manual-pull fire alarm stations are located near the exit doorways from each elevation of this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
At the floor elevations below the turbine operating floor where the Communications Corridor opens into the Turbine Building, an automatic pre-action sprinkler system is provided in the Turbine Building to protect this area from a fire in the Turbine Building.
 
Access to this area is from the Control Building through doors at each elevation, from the Turbine Building, and from the exterior through doors in the north wall of the building.
 
Adequate drainage is provided to handle maximum hose station discharge. The drains discharge to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
CC.1.6                                                                        Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
CC.1.7 Analysis
 
CC.1.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In all areas, the fire can be extinguished, using hose stations and/or portable extinguishers.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 204 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 175 of 244)
 
CC.1.7.2                                                                                                      Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an CC-1 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area CC-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in CC-1.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 205 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 176 of 244)
Fire Area D-1 (Reference A-1802 through A-1804)
 
D.1.1                                                                                                    Fire Area Description
 
Diesel Generator Room 5203 (east).
 
D.1.2 Major Equipment
 
Standby diesel generator package, associated auxiliaries, and fuel oil day tank.
 
D.1.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table D.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.  (Reference 3.1, Section F.9)
 
Table D.1.3-1 Fire Area D-1, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                    M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                    Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                Structural Steel Fireproofing thermal shorts
 
To minimize property damage, the 18 concrete slab roof is also a fire rated boundary, with the exception of the ventilation openings. No safety-related equipment is located above the buildings ceiling.  (Reference 3.1, Section F.9)
 
A curb is provided at the interconnecting door between this area and the ESF Switchgear Room (Fire Area C-10) to prevent the sprinkler system discharge from passing into Fire Area C-10.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 206 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 177 of 244)
The trench between the two Diesel Generator Rooms (P511W0018) is sealed with full depth grout at the communicating wall (column line DB). This seal configuration provides at least a 3-hour fire resistance rating.
 
D.1.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area D-1 is Moderate.
 
The diesel fuel oil day tank has a nominal capacity of 550 gallons. The dike around the base of the tank will hold at least 110 percent of the tank contents. The dike area is drained by gravity to a 900-gallon, covered sump in the same Diesel Generator Room.
The oil can be pumped outdoors to a truck connection for removal from the building.
 
Each diesel fuel oil tank is provided with protection features to preclude the uncontrolled leakage of diesel fuel. The design features provided for the day tank were reviewed and accepted by the NRC at the Wolf Creek Fire Protection Audit of February 6 to 9, 1984.
(Reference 3.1, Section F.9)
 
Diesel fuel is stored in underground tanks. The diesel fuel storage tanks are buried approximately 23 feet from the Diesel Generator Building wall. The storage tanks are set on a firm foundation, backfilled with noncorrosive sand surrounding the tank (6 inches minimum) and provided with a covering of 2 feet (minimum) of earth. This bulk storage of flammable liquids is remote from PFSSD SSCs.  (Reference 3.1, Section F.10)
 
D.1.5 Fire Protection
 
Automatic thermal detectors and infrared detectors are provided in this area. Manual-pull fire alarm stations are located near the exit doorways from this area. Detector or pull station activation alarms locally and in the Control Room. The Control Room annunciation is zoned for quick identification of the specific area in alarm.  (Reference 3.1, Section F.9)
 
An automatic preaction sprinkler system is provided for this area. The system is charged by thermal detector alarm or by manual activation of the suppression release station located in Room 3302, (outside the north exit from Fire Area D-1). Thermal detector or suppression release station activation will also lockout the emergency diesel generator fuel oil transfer pump, unless the pump is running. This configuration is provided to preclude a spurious fire protection system trip under accident conditions that would present a negative consequence to emergency diesel generator performance.
(Reference 3.1, Section F.9)
 
A hose station and portable extinguishers are provided just outside this Fire Area, and portable extinguishers are located within the area, as indicated on drawing A-1802. The hose station is equipped with 100 feet of hose for effective coverage of this Fire Area.
 
The area is accessible for manual fire fighting from the south ESF Switchgear Room 3302.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 207 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 178 of 244)
Adequate floor drains are provided in the area to remove sprinkler and hose station discharge without appreciable accumulation. The drainage is collected in a sump within the area. The sump is emptied by sump pumps. The sump pump discharge lines from the two Diesel Generator Room sumps are connected outside of the Diesel Generator Building. It is not possible for a flame to spread through the pumps, valves, and piping from one sump to another. Refer to drawing series M-12LE for further information on the oily waste drain system.  (Reference 3.1, Section F.9)
 
D.1.6                                                                                                    Isolation and Smoke Removal
 
A fire in this area will be contained by the fire barriers. Heat and smoke venting for each Diesel Generator Room is provided by utilizing the exhaust air flow path. The free area of the exhaust air flow path provides at least 1.0 square feet of venting area for each 200 square feet of floor area. Smoke exhaust fans per se are not employed. Normal ventilation exhaust systems are utilized throughout for smoke removal.  (Reference 3.1, Section F.9)
 
D.1.7 Analysis
 
D.1.7.1 Fire Suppression
 
Early warning fire detection is by infrared detectors, which will readily detect the type of fire caused by the burning of fuel and lube oils. In the event of a large fire, thermal detectors will charge the sprinkler system and the fusible link heads will open to extinguish the fire.
 
In the event the automatic system fails (identified by Control Room annunciation), the hose stream available will control the fire. As previously discussed, a thermal fire detection signal stops the emergency diesel generator fuel oil transfer pump, unless it is running. Depending upon the quantity of oil involved in the fire at this point, manual extinguishment with portable extinguishers and/or the hose station may be possible. If additional hose streams are required, the room is accessible from the yard hose hydrant system.
 
D.1.7.2                                                                                                                                  Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an D-1 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area D-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in D-1.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 208 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 179 of 244)
Fire Area D-2 (Reference A-1802 through A-1804)
 
D.2.1                                                                                                    Fire Area Description
 
Diesel Generator Room 5201 (west).
 
D.2.2 Major Equipment
 
Standby diesel generator package, associated auxiliaries, and fuel oil day tank.
 
D.2.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table D.2.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.  (Reference 3.1, Section F.9)
 
Table D.2.3-1 Fire Area D-2, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                    M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                    Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                Structural Steel Fireproofing thermal shorts
 
To minimize property damage , the 18 concrete slab roof is also a fire rated boundary, with the exception of the ventilation openings. No safety-related equipment is located above the buildings ceiling.  (Reference 3.1, Section F.9)
 
A curb is provided at the interconnecting door between this area and the ESF Switchgear Room (Fire Area C-10) to prevent the sprinkler system discharge from passing into Fire Area C-10.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 209 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 180 of 244)
The trench between the two Diesel Generator Rooms (P511W0018) is sealed with full depth grout at the communicating wall (column line DB). This seal configuration provides at least a 3-hour fire resistance rating.
 
D.2.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area D-2 is Moderate.
 
The diesel fuel oil day tank has a nominal capacity of 550 gallons. The dike around the base of the tank will hold at least 110 percent of the tank contents. The dike area is drained by gravity to a 900-gallon, covered sump in the same Diesel Generator Room.
The oil can be pumped outdoors to a truck connection for removal from the building.
 
Each diesel fuel oil tank is provided with protection features to preclude the uncontrolled leakage of diesel fuel. The design features provided for the day tank were reviewed and accepted by the NRC at the Wolf Creek Fire Protection Audit of February 6 to 9, 1984.
(Reference 3.1, Section F.9)
 
Diesel fuel is stored in underground tanks. The diesel fuel storage tanks are buried approximately 23 feet from the Diesel Generator Building wall. The storage tanks are set on a firm foundation, backfilled with noncorrosive sand surrounding the tank (6 inches minimum) and provided with a covering of 2 feet (minimum) of earth. This bulk storage of flammable liquids is remote from PFSSD SSCs.  (Reference 3.1, Section F.10)
 
D.2.5 Fire Protection
 
Automatic thermal detectors and infrared detectors are provided in this area. Manual-pull fire alarm stations are located near the exit doorways from this area. Detector or pull station activation alarms locally and in the Control Room. The Control Room annunciation is zoned for quick identification of the specific area in alarm.  (Reference 3.1, Section F.9)
 
An automatic preaction sprinkler system is provided for this area. The system is charged by thermal detector alarm or by manual activation of the suppression release station located in Room 3302, (outside the north exit from Fire Area D-2). Thermal detector or suppression release station activation will also lockout the emergency diesel generator fuel oil transfer pump, unless the pump is running. This configuration is provided to preclude a spurious fire protection system trip under accident conditions that would present a negative consequence to emergency diesel generator performance.
(Reference 3.1, Section F.9)
 
A hose station and portable extinguishers are provided just outside this Fire Area, and portable extinguishers are located within the area, as indicated on drawing A-1802. The hose station is equipped with 100 feet of hose for effective coverage of this Fire Area.
 
The area is accessible for manual fire fighting from the south ESF Switchgear Room 3302.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 210 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 181 of 244)
Adequate floor drains are provided in the area to remove sprinkler and hose station discharge without appreciable accumulation. The drainage is collected in a sump within the area. The sump is emptied by sump pumps. The sump pump discharge lines from the two Diesel Generator Room sumps are connected outside of the Diesel Generator Building. It is not possible for a flame to spread through the pumps, valves, and piping from one sump to another. Refer to drawing series M-12LE for further information on the oily waste drain system.  (Reference 3.1, Section F.9)
 
D.2.6                                                                                                    Isolation and Smoke Removal
 
A fire in this area will be contained by the fire barriers. Heat and smoke venting for each Diesel Generator Room is provided by utilizing the exhaust air flow path. The free area of the exhaust air flow path provides at least 1.0 square feet of venting area for each 200 square feet of floor area. Smoke exhaust fans per se are not employed. Normal ventilation exhaust systems are utilized throughout for smoke removal.  (Reference 3.1, Section F.9)
 
D.2.7 Analysis
 
D.2.7.1 Fire Suppression
 
Early warning fire detection is by infrared detectors, which will readily detect the type of fire caused by the burning of fuel and lube oils. In the event of a large fire, thermal detectors will charge the sprinkler system and the fusible link heads will open to extinguish the fire.
 
In the event the automatic system fails (identified by Control Room annunciation), the hose stream available will control the fire. As previously discussed, a thermal fire detection signal stops the emergency diesel generator fuel oil transfer pump, unless it is running. Depending upon the quantity of oil involved in the fire at this point, manual extinguishment with portable extinguishers and/or the hose station may be possible. If additional hose streams are required, the room is accessible from the yard hose hydrant system.
 
D.2.7.2                                                                                                                                  Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an D-2 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area D-2 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in D-2.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 211 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 182 of 244)
Fire Area ESWA (Reference M-KG080, E-KF0231 and E-KR0231)
 
ESWA.1                                              Fire Area Description
 
Essential Service Water Pumphouse Room K105, Access Vaults MHE1 through MHE5 and Train A ESW Electrical Duct Banks Room K105A.
 
ESWA.2 Major Equipment
 
Essential Service Water Pumps, Traveling Screens, Strainers, Pre-Lube Storage Tank, Ventilation Fans, Electric Cable and ESW Electrical Duct Banks and Access Vaults.
 
ESWA.3 Design Features
 
This Fire Area is separated from adjacent Fire Area ESWB by a common concrete wall and penetration closure assemblies that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, UL-555, or IEEE-634) for the respective barrier assembly protective feature. No door is present in this fire boundary.
 
Buried raceways containing electrical cabling associated with the Essential Service Water System are routed from the ESW Pump House to the Control Building. The raceways are embedded below grade except where they transition through a total of five access vaults.
At these locations a buried concrete vault containing two cells is provided to separate the redundant raceways. Each cell within a vault physically separates redundant train cable by a minimum of 18 concrete construction on all sides. The vault equipment hatches have an 18 overlap with vault interior walls and the manway hatches have at least an 11 overlap. All penetrations into the vaults are adequately sealed to minimize in leakage of air or water.
 
ESWA.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area ESWA is Low. This combustible loading applies to Room K105 only. Combustible loading for the access vaults and electrical duct banks (Room K105A) is not quantified.
 
The ESW system is manually treated for organic fouling with a microbial control agent (biocide) that is a combustible liquid. The liquid is piped within the ESWA where it taps into the ESW system piping.
 
ESWA.5 Fire Protection
 
Room K105 (Train A ESW Pumphouse)
 
Automatic smoke detectors are installed at the ceiling of the area. A manual-pull fire alarm station is located at the exit from this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.  (Reference 3.1, Section F.11)
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 212 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 183 of 244)
Portable extinguishers and hose stations are provided for manual fire suppression. Water for the hose stations is taken from the ESW piping, however these stations are pressurized by the service water system from the Circulating Water Screen House unless a low suction pressure signal in the Auxiliary Feedwater System, an SIS or loss of off-site power signal has caused the ESW pumps to start. Under these conditions water is taken from the ESW System. Any water used in this area for fire suppression would flow to the ultimate heat sink. Refer to Figure  ESWA.5-1 for the ESW Pump House hose station configuration.  (Reference 3.1, Section F.11)
 
Access for manual firefighting is via exterior access through door K1051.
 
Figure ESWA.5-1, ESW Hose Stations
 
Room K105A (Train A ESW Duct Banks and Access Vaults)
 
Fire hydrants are located in the vicinity of the vaults for manual firefighting. The cooling lake is also in the vicinity for manual firefighting.
 
ESWA.6                                              Isolation and Smoke Removal
 
Room K105 - The fire barrier will contain a fire within the Fire Area until extinguished.
Refer to Section 4.3.7.2 for smoke removal discussion.
 
Room K105A - A fire in any one of the cells within a vault will be contained to the cell of origin and will not propagate to the adjacent cell within a vault. The 18 thick concrete walls and ceilings, along with the hatch cover overlap, will help to prevent a fire from propagating into another vault or the surrounding area. Refer to Section    4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 213 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 184 of 244)
ESWA.7 Analysis
 
ESWA.7.1 Fire Suppression
 
Room K105
 
The fire hazard associated with the injection process for ESW chemical treatment is the undiluted combustible liquid filled piping located in ESWA.
 
Leakage from the pipe containing concentrated biocide within the ESWA is not anticipated, as the material is compatible with the pipe type, and the piping stresses are within ANSI B31.1 allowable values considering an operation basis earthquake and safe shutdown earthquake loads.
Additionally, the piping will only contain the combustible liquid concentration under pressure during periods of chemical injection. During periods of chemical injection inactivity, only residual biocide will remain in the distribution piping to ESW. In the unlikely event of a leak within the piping containing concentrated biocide, only Fire Area ESWA would be affected, as the fire barrier between the pump rooms prevent the same fire from damaging redundant ESW trains.
 
Due to the complete solubility of the biocide product in water and the very small concentrations of product in ESW system, there is no fire hazard concern associated with the product after it is diluted with ESW water in Fire Area ESWA.
 
Manual fire suppression equipment is available to extinguish a fire in this area.  (Reference 3.1, Section F.11)
 
Room K105A
 
Manual fire protection equipment is available to control and extinguish any postulated vault fire.
 
ESWA.7.2                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an ESWA fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area ESWA will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 214 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 185 of 244)
Fire Area ESWB (Reference M-KG080, E-KF0231 and E-KR0231)
 
ESWB.1                                              Fire Area Description
 
Essential Service Water Pumphouse Room K104, Access Vaults MHE1 through MHE5 and Train B ESW Electrical Duct Banks Room K104A.
 
ESWB.2 Major Equipment
 
Essential Service Water Pumps, Traveling Screens, Strainers, Pre-Lube Storage Tank, Ventilation Fans, Electric Cable and ESW Electrical Duct Banks and Access Vaults.
 
ESWB.3 Design Features
 
This Fire Area is separated from adjacent Fire Area ESWA by a common concrete wall and penetration closure assemblies that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, UL-555, or IEEE-634) for the respective barrier assembly protective feature. No door is present in this fire boundary.
 
Buried raceways containing electrical cabling associated with the Essential Service Water System are routed from the ESW Pump House to the Control Building. The raceways are embedded below grade except where they transition through a total of five access vaults.
At these locations a buried concrete vault containing two cells is provided to separate the redundant raceways. Each cell within a vault physically separates redundant train cable by a minimum of 18 concrete construction on all sides. The vault equipment hatches have an 18 overlap with vault interior walls and the manway hatches have at least an 11 overlap. All penetrations into the vaults are adequately sealed to minimize in leakage of air or water.
 
ESWB.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area ESWB is Low. This combustible loading applies to Room K104 only. Combustible loading for the access vaults and electrical duct banks (Room K104A) is not quantified.
 
The ESW system is manually treated for organic fouling with a microbial control agent (biocide) that is a combustible liquid. The liquid is piped within the ESWA where it taps into the ESW system piping.
 
ESWB.5 Fire Protection
 
Room K104 (Train B ESW Pumphouse)
 
Automatic smoke detectors are installed at the ceiling of the area. A manual-pull fire alarm station is located at the exit from this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.11)
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 215 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 186 of 244)
Portable extinguishers and hose stations are provided for manual fire suppression. Water for the hose stations is taken from the ESW piping, however these stations are pressurized by the service water system from the Circulating Water Screen House unless a low suction pressure signal in the Auxiliary Feedwater System, an SIS or loss of off-site power signal has caused the ESW pumps to start. Under these conditions water is taken from the ESW System. Any water used in this area for fire suppression would flow to the ultimate heat sink. Refer to Figure  ESWB.5-1 for the ESW Pump House hose station configuration. (Reference 3.1, Section F.11)
 
Access for manual firefighting is via exterior access through door K1041.
 
Figure ESWB.5-1, ESW Hose Stations
 
Room K104A (Train B ESW Duct Banks and Access Vaults)
 
Fire hydrants are located in the vicinity of the vaults for manual firefighting. The cooling lake is also in the vicinity for manual firefighting.
 
ESWB.6                                              Isolation and Smoke Removal
 
Room K104 - The fire barriers will contain a fire within the Fire Area until extinguished.
Refer to Section 4.3.7.2 for smoke removal discussion.
 
Room K104A - A fire in any one of the cells within a vault will be contained to the cell of origin and will not propagate to the adjacent cell within a vault. The 18 thick concrete walls and ceilings, along with the hatch cover overlap, will help to prevent a fire from propagating into another vault or the surrounding area. Refer to Section    4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 216 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 187 of 244)
ESWB.7 Analysis
 
ESWB.7.1 Fire Suppression
 
Room K104
 
The fire hazard associated with the injection process for ESW chemical treatment is the undiluted combustible liquid filled piping located in ESWA.
Due to the complete solubility of the biocide product in water and the very small concentrations of product in ESW system, there is no fire hazard concern associated with the product after it is diluted with ESW water in Fire Area ESWA. ESWB only contains diluted biocide.
 
In the unlikely event of a leak within the piping containing concentrated biocide, only Fire Area ESWA would be affected, as the fire barrier between the pump rooms prevent the same fire from damaging redundant ESW trains.
 
As discussed above, the fire barrier between the pump rooms prevents a single fire from damaging ESW trains. Therefore, a fire originating in ESWB will not impact ESWA. Manual fire suppression equipment is available to extinguish a fire in this area.  (Reference 3.1, Section F.11)
 
Room K104A
 
Manual fire protection equipment is available to control and extinguish any postulated vault fire.
 
ESWB.7.2                                                                            Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an ESWB fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area ESWB will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 217 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 188 of 244)
Fire Area ESWV (Reference  M-KX9002, C-K230, C-K231, C-K232, C-K233, C-K234)
 
ESWV.1                                              Fire Area Description
 
Essential Service Water Yard Pipe Access Vaults AV1 (Z118A), AV2 (Z118B), AV3 (Z118C), AV4 (Z118D), AV5 (Z118E), and AV6 (Z118F).
 
ESWV.2 Major Equipment
 
ESW Piping Access Vaults.
 
ESWV.3 Design Features
 
Each of the two redundant trains of Essential Service Water System, supply and return piping, pass through buried vaults located in the yard. The vaults are physically independent structures, recessed at grade elevation. All penetrations into the vaults are adequately sealed to minimize in leakage of air or water.
 
ESW Access Vault AV1 (Z118A) is broken up into two chambers separated by a 2 foot thick concrete wall. Each chamber is 19 feet-3 inches by 24 feet and the access vault has a vault height of 10 feet-9 inches. Details for AV1 are shown on drawing C-K230.
 
ESW Access Vaults AV2 (Z118B) and AV5 (Z118E) measure approximately 10 feet-6 inches by 24 feet and have a vault height of 11 feet-3 inches. Details for AV2 and AV5 are shown on drawing C-K231.
 
ESW Access Vault AV3 (Z118C) has a main vault area that measures 44 feet by 12 feet-3 inches and has a vault height of 11 feet-6 inches. There is a small 6 foot by 5 foot valve operations compartment separated from the main AV3 vault chamber by a 2 foot thick concrete wall. Details for vault AV3 are shown on drawing C-K232.
 
ESW Access vault AV4 (Z118D) has a main vault area that measures 46 feet by 17 feet-9 inches and has a vault height of 10 feet-6 inches. There is a small 6 foot by 5 foot valve operations compartment from the main AV4 vault chamber by a 2 foot thick concrete wall.
Details for vault AV4 are shown on drawing C-K233.
 
ESW Access Vault AV6 (Z118F) is broken up into two chambers separated by a 2 foot thick concrete wall. Each chamber is 14 feet-3 inches by 27 feet and the access vault has a vault height of 10 feet. Details for AV6 are shown on drawing C-K234.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 218 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 189 of 244)
For all of the ESW access vaults the roof panels have a 2 foot overlap and lineup flush with the vault walls. The man-way access cover panels have a 5 foot - 6 inch overlap.
Vault AV1 has two instrument penetrations in the roof panel. The instruments are used for indication only, no control functions. Vault AV5 has one instrument penetration in the roof panel. The instrument is used for indication only, no control function. Vault AV3, Train B only, has one instrument penetration in the roof panel that is used for indication only, no control functions. Vault AV3 has another instrument penetration that is used for access to instruments in the pipe area, no control functions. Vault AV4, Train A only, has one instrument penetration in the roof panel that is used for indication only, no control functions. Vault AV4 has another instrument penetration that is used for access to instruments in the pipe area, no control functions. Vaults AV3 and AV4 have 120VAC routed into the vault that is used for flow and temperature instrumentation, indication only, no control functions.
 
ESWV.4 Combustible Loading
 
The cumulative combustible loading classification for each vault is Low.
 
ESWV.5 Fire Protection
 
Fire hydrants are located in the vicinity of the vaults for manual firefighting. The cooling lake is also in the vicinity for manual firefighting.
 
ESWV.6                                              Isolation and Smoke Removal
 
A fire in any one of the pipe access vaults will be contained to the vault and will not propagate to the surrounding area. The two foot thick concrete walls and ceilings, along with the hatch cover overlap, will help to prevent a fire from propagating into another vault or the surrounding area. Refer to Section  4.3.7.2 for smoke removal discussion.
 
ESWV.7 Analysis
 
ESWV.7.1 Fire Suppression
 
There are no ignition sources located within vaults AV1, AV2, AV5, and AV6. The vaults are unheated. Vaults AV3 and AV4 have 120VAC routed into the vault that is used for flow and temperature instrumentation, indication only with no control functions. Manual fire protection equipment is available to control and extinguish any postulated vault fires.
 
ESWV.7.2                                                                            Safe Shutdown Capability
 
A vault fire will not impact safe shutdown capability. There are no electrically powered safe shutdown components or circuits located in any of the vaults to be damaged by fire. Redundant trains of the Essential Service Water System will not be affected by a single fire in any one of the vaults. Physical separation of the vaults precludes the possibility of a single fire in any one of the vaults from affecting the redundant train vault.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 219 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 190 of 244)
Fire Area F-1 (Reference A-1802 through A-1804)
 
F.1.1                                                                                                          Fire Area Description
 
Fuel Building General Area all elevations, Rooms 6101, 6102, 6103, 6106, 6201, 6204, 6205, 6210, 6301, and 6302.
 
F.1.2 Major Equipment
 
Fuel storage pool bridge crane and cask handling crane.
 
F.1.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table F.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table F.1.3-1 Fire Area F-1, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                M-663-00017A Closure Component Category No structural steel fireproofing                                                                                                                                                                                                                                                          Structural Steel Fireproofing Fuel transfer tube penetration                                                                                                                                                                                                                                                                    Penetration Seal Penetration seals that exceed the                                      Penetration Seal bounding limitations of M-663-00017
 
The bottom floor of this area is on soil and, consequently, is not rated. The structural steel of the Fuel Building is not structurally tied into the Auxiliary Building.
 
New fuel storage is designed for optimum moderation conditions. Refer to USAR Section 9.1 for further discussion.  (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 220 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 191 of 244)
F.1.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area F-1 is Low.
 
F.1.5 Fire Protection
 
Thermal detectors are installed in the Railroad bay area, while infrared flame detectors are also provided for Refueling Floor El 2047 feet 6 inches. The detection system alarms locally and in the Control Room. The Control Room annunciation is zoned for quick identification of the area in alarm. Manual-pull fire alarm stations are located near the exit doorways from this area. The pull stations also alarm locally and in the Control Room.
(Reference 3.1, Section F.12 and F.13)
 
An automatic preaction sprinkler system is provided for Room 6102, Railroad Bay/Laydown area.
 
Hose stations and portable extinguishers are provided throughout this fire area, as indicated on drawings A-1802 and A-1804.  (Reference 3.1, Section F.12 and F.13)
 
This area is accessible through one personnel door and one railroad door from the exterior and through a personnel door at each floor elevation at the northwest corner of the building from the Auxiliary Building.
 
Adequate floor drains (21 total) are provided in the area to remove sprinkler and hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
(Reference 3.1, Section F.12)
 
F.1.6                                                                                                          Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
F.1.7 Analysis
 
F.1.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers. The preaction sprinkler system in Room 6102, is activated by thermal detection. It does not protect safe shutdown equipment. Consequently, failure of this system to operate will not prevent safe shutdown.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 221 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 192 of 244)
F.1.7.2                                                                                                                                      Safe Shutdown Capability
 
No fire could cause structural damage to the fuel storage racks in the Fuel Storage Pool. A fire during fuel handling operations could cause damage to either of the fuel handling cranes; however, both cranes are designed to fail safe.
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an F-1 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area F-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-1.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 222 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 193 of 244)
Fire Area F-2 (Reference A-1802)
 
F.2.1                                                                                                          Fire Area Description
 
Fuel Pool Cooling Heat Exchanger Room 6104 (west), El. 2000-0.
 
F.2.2 Major Equipment
 
Fuel pool cooling heat exchanger B, fuel pool cooling pump B, room cooler, and fuel pool cleanup pumps.
 
F.2.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table F.2.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table F.2.3-1 Fire Area F-2, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                              M-663-00017A Closure Component Category Trench cover panels                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Fire Barrier Penetration seals that exceed the bounding                                              Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                          Structural Steel Fireproofing thermal shorts
 
F.2.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area F-2 is Low.    (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 223 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 194 of 244)
F.2.5 Fire Protection
 
An automatic smoke detection system  is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control  Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.  (Reference 3.1, Section F.12)
 
Hose stations and portable extinguishers are provided just outside this Fire Area, as indicated on drawing A-1802.  (Reference 3.1, Section F.12)
 
This area is accessible through a door at the south end of the room and a door at the northwest corner.
 
Adequate floor drains (3 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in the room. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.  (Reference 3.1, Section F.12)
 
F.2.6                                                                                                          Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
F.2.7 Analysis
 
F.2.7.1 Fire Suppression
 
A fire in the area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
 
F.2.7.2                                                                                                                                      Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an F-2 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area F-2 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-2.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 224 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 195 of 244)
Fire Area F-3 (Reference A-1802)
 
F.3.1                                                                                                          Fire Area Description
 
Fuel Pool Cooling Heat Exchanger Room 6105 (east), ), El. 2000-0.
 
F.3.2 Major Equipment
 
Fuel pool cooling heat exchanger A, fuel pool cooling pump A, and room cooler.
 
F.3.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table F.3.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table F.3.3-1 Fire Area F-3, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                        M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                      Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                  Structural Steel Fireproofing thermal shorts
 
F.3.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area F-3 is Low.  (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 225 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 196 of 244)
F.3.5 Fire Protection
 
An automatic smoke detection system  is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control  Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.  (Reference 3.1, Section F.12)
 
Hose stations and portable extinguishers are provided just outside this Fire Area, as indicated on drawing A-1802.  (Reference 3.1, Section F.12)
 
This area is accessible through a door at the south end of the room.
 
Adequate floor drains (3 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.  (Reference 3.1, Section F.12)
 
F.3.6                                                                                                          Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
F.3.7 Analysis
 
F.3.7.1 Fire Suppression
 
A fire in the area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
 
F.3.7.2                                                                                                                                      Safe Shutdown Capability
 
There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-3.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 226 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 197 of 244)
Fire Area F-4 (Reference A-1803)
 
F.4.1                                                                                                          Fire Area Description
 
Air Handling Equipment Room 6203, El. 2026.
 
F.4.2 Major Equipment
 
Fuel Building supply air units, Fuel Building heating coil unit, fuel handling area cooling coil.
 
F.4.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table F.4.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table F.4.3-1 Fire Area F-4, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                      M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                      Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                  Structural Steel Fireproofing thermal shorts
 
F.4.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area F-4 is Low.    (Reference 3.1, Section F.12)
 
F.4.5 Fire Protection
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 227 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 198 of 244)
An automatic smoke detection system  is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control  Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.  (Reference 3.1, Section F.12)
 
A hose station and portable extinguishers are provided within this Fire Area. If access to these is blocked by a fire within the area, the hose station and portable extinguishers in Room 1408 of the Auxiliary Building can be used.  (Reference 3.1, Section F.12)
 
This area is accessible through doors from the adjacent room and from the Auxiliary Building (Room 1408).
 
Adequate floor drains (3 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.  (Reference 3.1, Section F.12)
 
F.4.6                                                                                                          Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
F.4.7 Analysis
 
F.4.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
 
F.4.7.2                                                                                                                                      Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an F-4 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area F-4 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-4.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 228 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 199 of 244)
Fire Area F-5 (Reference A-1803)
 
F.5.1                                                                                                          Fire Area Description
 
Electrical Equipment Room 6202, El. 2026.
 
F.5.2 Major Equipment
 
Load centers and motor control centers.
 
F.5.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table F.5.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table F.5.3-1 Fire Area F-5, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                    M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                                  Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                              Structural Steel Fireproofing thermal shorts
 
F.5.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area F-5 is Low.  (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 229 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 200 of 244)
F.5.5 Fire Protection
 
An automatic smoke detection system  is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control  Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.  (Reference 3.1, Section F.12)
 
A portable extinguisher is provided in this Fire Area and hose stations and portable extinguishers are provided just outside this Fire Area, as indicated on drawing A-1803.
(Reference 3.1, Section F.12)
 
The area is accessible through double doors in the north and south walls of the area.
 
Adequate floor drains (2 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.  (Reference 3.1, Section F.12)
 
F.5.6                                                                                                          Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
F.5.7 Analysis
 
F.5.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
 
F.5.7.2                                                                                                                                      Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an F-5 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area F-5 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-5.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 230 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 201 of 244)
Fire Area F-6 (Reference A-1804)
 
F.6.1                                                                                                          Fire Area Description
 
Emergency Exhaust Equipment Room 6304 (east), El. 2047-6.
 
F.6.2 Major Equipment
 
Emergency exhaust filter/adsorber unit and emergency exhaust fan.
 
F.6.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table F.6.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table F.6.3-1 Fire Area F-6, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                        M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                      Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                  Structural Steel Fireproofing thermal shorts
 
F.6.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area F-6 is Low.    (Reference 3.1, Section F.12)
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 231 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 202 of 244)
F.6.5 Fire Protection
 
An automatic smoke detection system  is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control  Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.  (Reference 3.1, Section F.12)
 
Hose stations and portable extinguishers are provided just outside this Fire Area, as indicated on drawing A-1804.  (Reference 3.1, Section F.12)
 
The emergency exhaust filter adsorber unit does not normally operate. Downstream of the charcoal bed is a thermistor-type continuous thermal detector, which alarms in the Control Room at high air stream temperature. This unit is equipped with a hose connection to provide manual water spray protection.
 
Access to this area is through a door at the south end of the room.
 
Adequate floor drains (3 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.  (Reference 3.1, Section F.12)
 
F.6.6                                                                                                          Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
F.6.7 Analysis
 
F.6.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
 
F.6.7.2                                                                                                                                      Safe Shutdown Capability
 
This area contains no PFSSD equipment or circuits and is separated from adjoining Fire Areas by fire barrier construction. Therefore, a fire within Fire Area F-6 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-6.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 232 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 203 of 244)
Fire Area F-7 (Reference A-1804)
 
F.7.1                                                                                                          Fire Area Description
 
Emergency Exhaust Equipment Room 6303 (west), El. 2047-6.
 
F.7.2 Major Equipment
 
Emergency exhaust filter/adsorber unit and emergency exhaust fan.
 
F.7.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table F.7.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table F.7.3-1 Fire Area F-7, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                        M-663-00017A Closure Component Category Penetration seals that exceed the bounding                                      Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected                                  Structural Steel Fireproofing thermal shorts
 
F.7.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area F-7 is Low.    (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 233 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 204 of 244)
F.7.5 Fire Protection
 
An automatic smoke detection system  is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control  Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.  (Reference 3.1, Section F.12)
Hose stations and portable extinguishers are provided just outside this Fire Area, as indicated on drawing A-1804.  (Reference 3.1, Section F.12)
The emergency exhaust filter adsorber unit does not normally operate. Downstream of the charcoal bed is a thermistor-type continuous thermal detector, which alarms in the Control Room at high air stream temperature. This unit is equipped with a hose connection to provide manual water spray protection.
Access to this area is through a door at the south end of the room.
Adequate floor drains (3 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.  (Reference 3.1, Section F.12)
 
F.7.6                                                                                                          Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
F.7.7 Analysis
 
F.7.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
 
F.7.7.2                                                                                                                                      Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an F-7 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area F-7 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-7.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 234 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 205 of 244)
Fire Area HMS-1 (Reference A-1802)
 
HMS.1.1                                          Fire Area Description
 
Hot Machine Shop Rooms 1332, 1333, and 1334.
 
HMS.1.2 Major Equipment
 
Decontamination equipment, laboratory equipment, and machine tools.
 
HMS.1.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire door, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table HMS.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table HMS.1.3-1 Fire Area HMS-1, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                      M-663-00017A Closure Component Category Missile door 13331                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door Trench cover panels                                                                                                                                                                                                                                                                                                                                                                                                                                    Fire Barrier
 
The structural steel of the Hot Machine Shop is not structurally tied into the Auxiliary Building. The ceiling of this area is the building roof, and the building floor is on grade with the exception of the pipe chase communicating with Fire Area F-2. Consequently, only the building walls and the concrete trench cover plugs provide fire boundary protection.
 
HMS.1.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area HMS-1 is Low.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 235 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 206 of 244)
HMS.1.5 Fire Protection
 
An automatic smoke detection system is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
The combustible loading in the Hot Machine Shop is low. The  Hot Machine Shop is not a safety-related area and is separated from adjacent safety-related areas by fire barrier construction. Therefore, an automatic sprinkler system is not provided for the Hot Machine Shop.
 
A hose station and portable extinguishers are provided within this Fire Area, as indicated on drawing A-1802.
 
Access to this area is through the exterior door in the west wall or through the interior doors at the north wall.
 
Adequate floor drains are provided in the area to remove hose station discharge without appreciable accumulation. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
HMS.1.6                                          Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section  4.3.7.2 for smoke removal discussion.
 
HMS.1.7 Analysis
 
HMS.1.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using the hose station and/or portable extinguishers.
 
HMS.1.7.2                                                                      Safe Shutdown Capability
 
This area contains no PFSSD equipment or circuits and is separated from adjoining Fire Areas by fire barrier construction. Therefore, a fire within Fire Area HMS-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in HMS-1.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 236 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 207 of 244)
Fire Area RB (Reference A-1801 through A-1804)
 
RB.1                                                                                                            Fire Area Description
 
Reactor Building (Containment).
 
RB.2 Major Equipment
 
Reactor coolant pumps, steam generators, reactor, pressurizer, regenerative heat exchanger, reactor coolant drain tank and pumps, pressurizer relief tank, accumulator tanks excess letdown heat exchanger, cavity cooling fans, rod positioning indicator cabinets, incore instrumentation drive units, hydrogen recombiners, CRDM cooling fans, hydrogen mixing fans, dry waste compactor, polar crane, RCP lube oil drain tanks, containment coolers
 
RB.3 Design Features
 
This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table RB.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table RB.3-1 Fire Area RB, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                    M-663-00017A Closure Component Category Flanges for encapsulated valve                                                          Fire Barrier tanks Reactor Building personnel hatch                                                                                                                                                                                                    Hatch Radiant energy shield fire wrap                                                                                                                                                                                                                                          Fire Wrap Electrical penetrations                                                                                                                                                                                                                                                                                                                                                                                                    Penetration Seal Mechanical penetrations                                                                                                                                                                                                                                                                                                                                                                    Penetration Seal Fuel transfer tube penetration                                                                                                                                                                                                                                                                    Penetration Seal
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 237 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 208 of 244)
The 4-foot-thick Reactor Building walls serve as the fire barrier separation from adjacent buildings. There are no physical boundaries enclosing localized fire hazards within the Reactor Building. However, for purposes of this analysis, the Reactor Building is divided in the following zones as delineated on drawings A-1801 through A-1804.
 
Zone No.                          Area RB-1                                                                                                                                                                                                        Area within the secondary shield wall RB-2                                                                                                                                                                                                        Area outside the secondary shield wall - El. 2000 RB-3                                                                                                                                                                                                        North electrical penetration area - El. 2026 RB-4                                                                                                                                                                                                        South electrical penetration area - El. 2026 RB-5                                                                                                                                                                                                        Cable tray area - El. 2047'-6" RB-6                                                                                                                                                                                                        Reactor building - El. 2068'-8" RB-7                                                                                                                                                                                                        West area - El. 2026 RB-8                                                                                                                                                                                                        East area - El. 2026 RB-9                                                                                                                                                                                                        Tendon access gallery area RB-10                                                                                                                                                                                  Reactor building - El. 2047'-6" areas, except cable tray area RB-11                                                                                                                                                                                  Area within primary shield wall
 
RB.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area RB is Low.
 
RB.5 Fire Protection
 
Linear heat detection is installed above each reactor coolant pump and in areas where cable trays are concentrated. Duct smoke detection is provided for each containment cooler. Manual-pull fire alarm stations are located near hose stations. Detector or pull activation alarms locally and in the Control Room. The Control Room alarms are zoned for quick identification of the area in alarm.  (Reference 3.1, Section F.1a))
 
Portable extinguishers and manual hose stations are permanently installed inside the Reactor Building as shown on drawings A-1801 through A-1804. The hose stations are spaced at no more than 100-foot intervals. The hose station locations are such that all accessible areas of the Reactor Building are adequately covered by at least one hose stream. A fire at any hose station may be extinguished by using an adjacent hose station. An extra length of hose can be added, if required, to the adjacent hose station.
(Reference 3.1, Section F.1b))
 
A fixed, manually charged, closed head sprinkler system is provided over the cable trays in Zones RB-3 and RB-4. A manual system is installed to prevent an inadvertent actuation of the sprinklers during normal plant operation. To protect the chloride sensitive piping and equipment from fire protection system leakage, the standpipes inside the Reactor Building are also normally dry.  (Reference 3.1, Section F.1.a))
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 238 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 209 of 244)
All fire water system piping within the Reactor Building is maintained dry by two normally closed isolation valves located in series on the same supply line. The motor operated isolation valve (KCHV0253) can be operated from the Control Room while the manual valve (KCV0427) can be manipulated locally in Room 1322. Opening both of these valves will charge fire water system piping within the Reactor Building, including the two sprinkler systems. All the isolation valves associated with the standpipe and sprinkler system are electrically supervised.
 
The fire protection supply piping to the Reactor Building is protected from the effects of a single active failure. The inside Containment isolation valve is a check valve which is highly reliable by design and considered exempt from active failures due to the lack of any external electrical signals which may be disabled due to a fire inside the containment.
Refer to USAR Section 3.1.1 for a discussion of the single failure criteria. Even though a fire inside the Containment would not disable the outside isolation valve, a random failure of the outside valve may be postulated with a fire inside the Containment. In this case, the accessibility of the outside isolation valve is not impaired, and the valve may be operated manually.
 
The Containment atmospheric control filter-adsorber units are provided with a thermistor-type continuous detector which alarms in the Control Room on high airstream temperature downstream of the charcoal bed. The charcoal beds are equipped with a hose connection to provide manual water spray protection.
 
A system is provided to collect and contain lubricating oil for each reactor coolant pump (RCP). The RCP oil spillage protection and control system consists of a package of splash guards, catch basins, and enclosure assemblies as attachments to the RCP motors at strategic locations to preclude the possibility of oil making contact with hot components and pipe. High pressure portions of the lube oil system are totally enclosed with low point drain connections. Low pressure portions of the system are provided with drip pans with low point connections. Remote lube oil fill lines for the upper and lower bearing reservoirs on each reactor coolant pump motor are not protected by drip pans.
Due to the design of the fill lines, no lube oil leakage is postulated. The RTD Conduit Boxes (3 per motor) are not provided with drip pans, however, conduit seals and leak tight fittings are used to minimize lube oil leakage. Oil leakage at the RDT Conduit Box does not represent a fire hazard.  (Reference 3.1, Section F.1.a) and Reference 3.2, Section III.O)
 
Low points of the collection systems are piped to two collection tanks (each tank serves two RCPs) located in the Reactor Building as shown on Figure  RB.5-1. Each of the two oil collection tanks has a capacity of 311 gallons (usable), compared to 265 gallons of oil in the lube oil system of each pump. It is unlikely that common failure would occur that would cause the entire inventory of oil in two RCP motors to leak out. The collection tanks are provided with level indication and high level alarm in the Control Room.
Therefore, the plant operators would have an early indication of a significant oil leak and could initiate corrective action. The tanks are manually drained as required. Should leakage exceed collection tank capacity before corrective actions are completed, the tank would overflow onto the Containment floor. Any such leakage would flow to the containment normal sumps via the drainage trenches located adjacent to the tanks (see drawing M-1G022). This oil would not come into contact with hot surfaces and create a fire hazard.  (Reference 3.1, Section F.1.a) and Reference 3.2, Section III.O)
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 239 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 210 of 244)
The tanks are constructed to the requirements of ASME Section VIII and have flame arrestors on the vents. The drain piping is ANSI B31.1. The tanks and piping are seismically supported in accordance with the requirements of Paragraph C.2 of Regulatory Guide 1.29. Additionally, the oil collection tanks were sized to accommodate any reasonable amount of leakage that might result from an SSE. The oil collection devices mounted on the RCPs have been seismically analyzed and qualified in accordance with the requirements of Paragraph C.2 of Regulatory Guide 1.29.
(Reference 3.1, Section F.1.a) and Reference 3.2, Section III.O)
 
Refer to drawing M-12LF09 for a piping and instrument diagram of the RCP lube oil collection system. The location of cable trays in the vicinity of the reactor coolant pumps is identified in Figure RB.5-1.  (Reference 3.1, Section F.1.a) and Reference 3.2, Section III.O)
 
Access to the Containment is via the personnel hatch at El. 2047 feet 6 inches. This hatch opens to Room 1507 of the Auxiliary building. For access to Room 1507, see Fire Area A-20. An emergency personnel hatch for evacuation purposes is located at El. 2013 feet 5 inches. The hatch opens to a stairway leading to the outside grade elevation. The tendon access gallery can be reached from a hatch at the outside grade at El. 2000 leading to the tendon gallery access shaft, and through door 21011 at El. 1974 of Fire Area A-1. Stairways and one elevator are located at Zone RB-2, as shown on drawing A-1802, and provide access to all elevations up to 2068 feet 8 inches.
 
Self-contained breathing apparatus are available for use inside Containment. They are stored near the entrance to the RCA.  (Reference 3.1, Section F.1.b)
 
Adequate drainage capability exists in the Reactor Building to prevent the accumulation of fire-fighting water. Refer to drawing series M-12LE and M-12LF and for further information on the drain systems applicable to the Reactor Building.
 
RB.6                                                                                                            Isolation and Smoke Removal
 
A fire within the reactor building will be contained by the fire barriers until extinguished.
Smoke may be removed by the containment purge system. Refer to Section  4.3.7.2 for smoke removal discussion.
 
RB.7 Analysis
 
RB.7.1 Fire Suppression
 
The automatic detection system, above the reactor coolant pumps, over areas where cable trays are concentrated and in the containment cooling system ducts, will alarm in the Control Room upon detection of a fire. The standpipes and sprinkler systems are manually charged by a combination of Control Room and local action to open the two normally closed isolation valves for Containment fire water supply. A fire in the cable trays at zones RB-3 or RB-4 would be suppressed by the respective sprinkler system. A fire can be extinguished manually, using the portable extinguishers and/or the hose stations.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 240 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 211 of 244)
The reactor coolant pumps are approximately 50 feet apart and a totally enclosed system to collect and contain the lube oil is provided for each pump. An oil fire is not postulated since this would require a failure in the pump lube oil system and another failure in the lube oil collection system in combination with the presence of an ignition source. Any  major maintenance work on the pumps will require a plant shutdown. Therefore, an introduction of transient combustibles into this zone during normal plant operation is not postulated. The reactor coolant pumps are not required for a safe shutdown. For these reasons, an automatic suppression system is not provided to extinguish an oil fire in this zone.
 
The probability of a fire occurrence is greater during refueling and maintenance operations, when transient combustibles could be in the Reactor Building. However, the area would be occupied, and any potential fire would be quickly detected. Again, fire fighting could be performed manually using the hose stations and extinguishers shown on drawings A-1801 through 1804.
 
RB.7.2                                                                                                                                        Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an RB fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area RB will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in RB.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 241 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 212 of 244)
 
Figure RB.5-1, RCP Cable Trays in Proximity to RCPs Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 242 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 213 of 244)
 
Figure RB.5-1 (Contd), RCP Cable Trays in Proximity to RCPs Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 243 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 214 of 244)
Fire Area RW (Reference A-1801 through A-1804, A-1347 through A-1350, and Z007A-M-0008)
 
Note:
The RW FHA encompasses the Fire Areas identified as RW A, RW B, and RW C in E-15000.
 
RW.1                                                                                                Fire Area Description
 
Entire Radwaste Building and Radwaste Storage Building - Rooms 7101, 7102, 7103, 7104, 7105, 7106, 7107, 7108, 7109, 7110, 7111, 7112, 7113, 7114, 7115, 7116, 7117, 7118, 7119, 7120, 7121, 7122, 7123, 7124, 7125, 7126, 7127, 7128, 7129, 7130, 7131, 7132, 7135, 7201, 7202, 7203, 7204, 7205, 7206, 7207, 7208, 7209, 7210, 7211, 7212, 7213, 7214, 7215, 7216, 7217, 7218, 7219, 7220, 7221, 7222, 7223, 7224, 7225, 7226, 7227, 7228, 7229, 7230, 7231, 7232, 7233, 7301, 7302, 7303, 7304, 73057401, 7402, 7403, 7404, 7405, 7406, 7407, 7408, 7409, 7410, 7411, 7413, 7501, 7502, 7503, and 7504.
 
RW.2 Major Equipment
 
SG blowdown surge tank, SG blowdown surge pumps, aux steam condensate recovery tank, Aux steam condensate transfer pumps, gas decay tanks, catalytic hydrogen recombiner, waste gas compressors, floor drain tanks, floor drain pumps, waste hold-up tank, waste evaporator feed pump, thb04, chemical drain tank, chemical drain pump, waste evaporator condensate tank, waste evaporator condensate pump, waste monitor tank, waste monitor pump, re-cycle hold-up tanks, recycle evaporator feed pumps, primary waste evaporator bottoms tank, gas analyzer racks, oil water separator, radiation monitors, oil water separator pumps, load centers, motor control centers, solidification control cabinet, SLWS monitor tanks, spent resin storage tanks, control room control panels, hold-up tanks,  evaporators, fan coil units, equipment hoist radwaste, Radwaste Building exhaust fans, Radwaste Building exhaust filter adsorber unit, SLWS monitor tanks.
 
RW.3 Design Features
 
Fire Area RW to RW-1 is not separated by a physical fire barrier boundary. The south end of the Radwaste Tunnel at Column R1 has been established as a theoretical zone boundary between RW and RW-1 for analysis purpose only. For life safety purposes, fire barriers are provided for the stairwell enclosures within the Radwaste Building. The Radwaste Building is a concrete structure, while the Radwaste Storage Building is constructed of sheet metal siding over unprotected structural steel. The drum storage building is a combination of concrete and sheet metal construction. Although the majority of the barriers within the Radwaste Building are not credited as fire barriers, they do present a substantial impediment to fire propagation within the structure.
 
RW.4 Combustible Loading
 
Calculation XX-X-004 does not maintain a combustible loading classification for Fire Area RW. The predominate combustible hazards associated with this area is that presented by Class A and B radwaste materials that a stored for ultimate processing or disposal.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 244 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 215 of 244)
RW.5 Fire Protection
 
Automatic smoke detectors are installed in the area, except as noted in Attachment    A.
Manual-pull fire alarm stations are located near exit doorways. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
An automatic wet pipe sprinkler system is provided for the Radwaste Storage Building and the Dry Waste Compactor area (Room 7228) of the Radwaste Building.
 
The charcoal filter adsorber unit is provided with a thermistor-type continuous detector which alarms in the Control Room at high airstream temperature. The adsorber unit is equipped with a hose connection to provide manual water spray protection.
 
Hose stations and fire extinguishers are strategically located throughout the area.
 
The area is accessible for firefighting from the exterior and the Radwaste Tunnel.
 
Floor drains that discharge to the Radwaste Building sump are provided for removal of firefighting water. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
RW.6                                                                                                Isolation and Smoke Removal
 
A fire in this area is isolated from the Auxiliary Building by fire barrier construction. Refer to Section 4.3.7.2 for smoke removal discussion.
 
RW.7 Analysis
 
RW.7.1 Fire Suppression
 
A fire in the Radwaste Building will be detected and alarmed by the automatic detection system. A fire in the Radwaste Storage Building will be alarmed following sprinkler system water flow. Fire in the Radwaste Storage Building or Dry Waste Compactor area will be suppressed by the respective automatic sprinkler system. A fire can be extinguished manually, using hose stations and/or portable extinguishers in the event automatic suppression fails, or the fire is located in an area where automatic suppression is not provided.
 
A filter fire in the charcoal adsorber unit will be extinguished utilizing the manual spray system.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 245 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 216 of 244)
RW.7.2                                                                                                                              Safe Shutdown Capability
 
Four hand switches and associated cables are located in fire areas RW and RW-1 that are used to close the Steam Generator blowdown valves BMHV0001 through BMHV0004 in the case of a fire that renders the primary circuit incapable of controlling the valves. In the case of a fire in Fire Area RW or RW-1, the primary circuit will be available to control these valves. Therefore, a fire in this area will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in RW.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 246 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 217 of 244)
Fire Area RW-1 (Reference A-1801)
 
RW.1.1                                                                Fire Area Description
 
Radwaste Pipe Tunnel and Cable Chase to Auxiliary Building (below grade) Rooms 7133 and 7134.
 
RW.1.2 Major Equipment
 
Electric cable.
 
RW.1.3 Design Features
 
This Fire Area is separated from the Auxiliary Building by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table RW.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table RW.1.3-1 Fire Area RW-1, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                      M-663-00017A Closure Component Category Penetration seals that exceed the                          Penetration Seal bounding limitations of M-663-00017
 
The ceiling, floor, and east west side walls of this area are against soil. The fire area is divided into two rooms by a 2-foot-thick concrete wall. Room 7133 is the Nonradioactive Tunnel, while Room 7134 contains radioactive piping.
 
Ventilation air for the tunnel is provided by transferring air from the Radwaste and Auxiliary Buildings by means of transfer fans. The tunnel is exhausted by Radwaste and Auxiliary Building exhaust systems. More air is exhausted than supplied to prevent exfiltration from the tunnel. Air is supplied to the nonradioactive portion of the tunnel and exhausted from the radioactive side of the tunnel.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 247 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 218 of 244)
RW.1.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area RW-1 is Low.
 
RW.1.5 Fire Protection
 
An automatic smoke detection system is installed in Room 7133. Manual-pull fire alarm stations are located near the exit doorways from adjacent areas. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. Detection is not installed in the Radioactive Pipe Tunnel (Room 7134) due to low installed combustibles.
 
Hose stations are not located inside the tunnel since a fire in the tunnel may render them inaccessible. Hose stations, located approximately 30 feet away from either end of the tunnel in the Auxiliary and Radwaste Buildings, are available for manual firefighting.
Each hose rack has 75 feet of hose, and the tunnel is approximately 140 feet along.
Therefore, all areas of the tunnel are within reach of these hose stations. Portable extinguishers are provided inside and outside of the tunnel. Refer to drawing A-1801 for hose stations and extinguisher locations.
 
The area is accessible for firefighting from both the north and south ends of the tunnel.
 
A 4 foot x 4 foot x 4 foot sump with two 50 gpm submersible pumps is located in the Nonradioactive Tunnel  midway between the Auxiliary and Radwaste Buildings. The sump pumps discharge to the floor drain tank located in the Radwaste building. The Radioactive Pipe Tunnel has a 3 foot x 3 foot x 3 foot sump, which is connected to the Nonradioactive Tunnel sump by a 4-inch embedded pipe.
 
RW.1.6                                                                Isolation and Smoke Removal
 
A fire in this area is isolated from the Auxiliary Building by fire barrier construction. Fire dampers will isolate HVAC openings in the fire barrier communicating with the Auxiliary Building. Refer to Section 4.3.7.2 for smoke removal discussion.
 
RW.1.7 Analysis
 
RW.1.7.1 Fire Suppression
 
Due to the low installed combustibles in the Radioactive Pipe Tunnel and limited credible ignition sources, a fire in this area is not postulated.
 
A fire in the Nonradioactive Tunnel area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 248 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 219 of 244)
RW.1.7.2                                                                                            Safe Shutdown Capability
 
Four hand switches and associated cables are located in fire areas RW and RW-1 that are used to close the Steam Generator blowdown valves BMHV0001 through BMHV0004 in the case of a fire that renders the primary circuit incapable of controlling the valves. In the case of a fire in Fire Area RW or RW-1, the primary circuit will be available to control these valves. Therefore, a fire in this area will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in RW-1.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 249 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 220 of 244)
Fire Area SBO (Reference M-1G074)
 
SBO.1                                                                          Fire Area Description
 
Station Blackout (SBO) diesel generator missile shield structure. The concrete structure has four (4) bays. The North and South ends of the bays are open to atmosphere and enclosed with steel grating.
 
SBO.2 Major Equipment
 
Three 3250 kW/4063 kVA diesel generator enclosures and one Power Equipment Center (PEC) enclosure. The PEC enclosure contains the switchgear (PB005) for the generator sets and power output to the plant.
 
SBO.3 Design Features
 
This Fire Area is outside the protected area and is remote to the power block structures.
Due to the spatial separation, there is no exposure hazard to this Fire Area. The missile shield structure is constructed with non-combustible, fire resistive, materials. The structure is comprised of 1-foot thick concrete walls on the ends with 1-foot thick separation walls between the bays. The North and South sides of the building is enclosed with steel grating. The roof has removable concrete shield plugs that are 1-foot thick. The building is lightning protected per NFPA 780. The doors between the bays are 3-hour fire rated. The PEC has 2-hour fire rated walls between the switchgear room and the control room. The wall surrounding the battery room within the PEC is 2-hour fire rated. The diesel driven generator sets and PEC are each housed within an enclosure designed to withstand 150 mph winds. UL Listed double walled fuel tanks are provided with the generator sets. The fuel tanks are equipped with overfill protection. The PEC battery compartment is equipped with redundant hydrogen ventilation fans. The vent fan is started on detection of a 1% hydrogen concentration. An alarm is initiated on detection of a 2% hydrogen level.
 
SBO.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area SBO is High. This area is not a safety related area nor is it adjacent to a safety related area so it is not included in Calculation XX-X-004, Combustible Fire Loading For Each Room In The Various Fire Areas At WCNOC. The following is included for information.
 
Each individual fuel oil tank for the SBO diesels has a nominal capacity of 6512 gallons.
The tank is a UL #142 listed double walled fuel tank. Each Diesel engine contains 104 gallons of lube oil. The PEC has 60 lead acid batteries (LSe450). The overall square footage of the fire area is 6500 sqft. Each individual bay has a square footage of 1625 sqft.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 250 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 221 of 244)
Room Combustible                                                                                      Heat Rate                                        Quantity                                  Room Area                                            Load (Btu/sqft)
Material                                                    (Btu/lb)                                            (gal)                                        (sqft)
SBO-A                                                                                      Diesel Fuel
* 20000                                                                                                                                        6187*                                                                                                                                                  1625                                                                                                                                                                                                523896 Lube Oil **                                                                                                                                                                  20000                                                                                                                                            104**                                                                                                                                                      1625                                                                                                                                                                                                                    9114 SBO-B                                                                                      Diesel Fuel
* 20000                                                                                                                                        6187*                                                                                                                                                  1625                                                                                                                                                                                                523896 Lube Oil **                                                                                                                                                                  20000                                                                                                                                            104**                                                                                                                                                      1625                                                                                                                                                                                                                    9114 SBO-                                  Diesel Fuel
* 20000                                                                                                                                        6187*                                                                                                                                                  1625                                                                                                                                                                                                523896 C                                  Lube Oil **                                                                                                                                                                  20000                                                                                                                                            104**                                                                                                                                                      1625                                                                                                                                                                                                                    9114 SBO-E Batteries Class A 18000  650 lbs  1625        7200 Misc Class A 18000 ~150 lbs 1625    1662
* Specific Gravity of Diesel Fuel - 0.86
                                                                                                                                                                                                                                                                                                      ** Specific Gravity of lube oil - 0.89
 
Fire                              Combustible                                                  Heat Rate                                        Quantity                                  Room Area                                            Load (Btu/sqft)
Area                                        Material                                                  (Btu/lb)                                            (gal)                                        (sqft)
SBO                                                                                                        Diesel Fuel
* 20000                                                                                                                                      18561                                                                                                                                                6500                                                                                                                                                                                                392922 Lube Oil **                                                                                                                                                  20000                                                                                                                                                          312                                                                                                                                                                    6500                                                                                                                                                                                                                    6836 Misc Class A 18000 750 lbs 6500      2077 Total                                                                                                                                                                                            401835
* Specific Gravity of Diesel Fuel - 0.86
                                                                                                                                                                                                                                                                                                      ** Specific Gravity of lube oil - 0.89
 
SBO.5 Fire Protection
 
An automatic heat detection system  is installed in the separate diesel enclosures in this fire area. Automatic smoke detection is installed in the PEC enclosure in this fire area.
Manual-pull stations are located at exit doors from the three Diesel Generator and PEC enclosures. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the WCNOC Control Room.
 
Attachment A summarizes the automatic detection and suppression coverage provided for this fire area. Specifically, automatic detection coverage is only provided within the three Diesel Generator and PEC enclosures.
 
Portable extinguishers are located within the three Diesel Generator and PEC enclosures.
 
Access to this area for manual  firefighting is available from outside of the structure at ground level. A fire hydrant and hose house will be installed in the future adjacent to the structure.
 
The structure is open to the outside on the North and South side through steel grating on each of the four bays of the structure, which will facilitate drainage of firewater.
 
SBO.6                                                                              Isolation and Smoke Removal
 
There are no mechanical smoke isolation or smoke removal features within the fire area.
The structure is open to the outside on the North and South side through steel grating on each of the four bays of the structure, which will facilitate smoke removal due to natural ventilation.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 251 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 222 of 244)
SBO.7 Analysis
 
SBO.7.1 Fire Suppression
 
The automatic detection system installed in the Diesel Generator and PEC enclosures will provide an early warning of a fire  in this area. The fire can be extinguished manually, using hose lines and/or portable  extinguishers.
Adequate drainage is provided to remove the fire  suppression water discharge.
 
SBO.7.2                                                                                                            Safe Shutdown Capability
 
There are no cables or components within the SBO fire area that are credited for Post Fire Safe Shutdown (PFSSD).
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 252 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 223 of 244)
Fire Area T-1 (Reference A-1801 through A-1804, A-1806, A-1807, and A-1812 )
 
T.1.1                                                                                                          Fire Area Description
 
Turbine Building Stairway Room 4101.
 
T.1.2 Major Equipment
 
Electric cable.
 
T.1.3 Design Features
 
This Fire Area is separated from the Auxiliary Building by fire barrier construction and penetration closure assemblies (fire doors and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table T.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table T.1.3-1 Fire Area T-1, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                              M-663-00017A Closure Component Category Missile door 41015                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door Missile door 41017                                                                                                                                                                                                                                                                                                                                                                                                                                                              Fire Door
 
Remaining walls of the stairwell enclosure are 2-hour rated.
 
T.1.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area T-1 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 253 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 224 of 244)
T.1.5 Fire Protection
 
Automatic smoke detection is provided at the top of the stairwell. Manual-pull fire alarm stations are located just outside the doorway at each floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control  Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Hose stations and portable extinguishers are provided just outside this fire area at each floor elevation.
 
The area is accessible for fire fighting from each communicating elevation with the Auxiliary Building and Turbine Building.
 
No drains are provided for this Fire Area, as manual fire water suppression efforts will be minimal, considering the limited combustible loading and equipment in the Fire Area.
There are no PFSSD equipment or circuits in this area. There is no PFSSD equipment susceptible to water damage in this area. Therefore, water accumulation in the area would not affect safe shutdown capability.
 
T.1.6                                                                                                          Isolation and Smoke Removal
 
The fire barriers will contain a fire within the Fire Area until extinguished. Refer to Section 4.3.7.2 for smoke removal discussion.
 
T.1.7 Analysis
 
T.1.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
 
T.1.7.2                                                                                                                                      Safe Shutdown Capability
 
One cable for the trip circuit for the main feedwater pump turbine runs through this Fire Area. This cable needs to function when the MSIV's are rendered incapable of closing due to a fire. For a fire in this area, the MSIV's will function normally. Therefore, a fire in any portion of Fire Area T-1 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 254 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 225 of 244)
Fire Area T-2 (Reference A-1806 through A-0808)
 
T.2.1                                                                                                          Fire Area Description
 
Turbine Building - 50 feet north of Auxiliary Building wall. Rooms 4301, 4302, 4303, 4304, 4305, 4306, 4322, 4351, 4401, 4501, and 4504.
 
T.2.2 Major Equipment
 
Condenser vacuum pumps, air compressors feedwater heaters, turbine building supply air units, S.G. blowdown flash tank, S.G. blowdown non-regenerative heat exchanger, load centers and motor control centers.
 
T.2.3 Design Features
 
This Fire Area is separated from the Auxiliary Building and Fire Areas T-4 and T-10 by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
Table T.2.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Table T.2.3-1 Fire Area T-2, Unique or Unbounded Fire Barrier Features Unique or Unbounded Feature                                                                      M-663-00017A Closure Component Category Blowout panel                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  Hatch Emergency escape hatch                                                                                                                                                                                                                                                                                                                                            Hatch Missile Shield                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        Fire Barrier 20 unsealed floor drains from A-23                                                                                                                                                                Fire Barrier Penetration seals that exceed the                                                        Penetration Seal bounding limitations of M-663-00017
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 255 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 226 of 244)
The Communication Corridor (Fire Area CC-1) is open to this area at El. 2000 and 2016, but separated from the adjacent Control Building by a fire boundary wall. The turbine lube oil area located approximately 38 feet north of the Auxiliary Building wall consists of two rooms (4308 and 4403), one above the other, which are both enclosed by fire barriers. Due to the fire boundaries for each of these rooms the areas are not considered part of Fire Area T-2. The FHA for Room 4308 is provided in Section  T.4.1 (Fire Area T-4), while the FHA for 4403 (Fire Area T-10) is provided in Section  T.10.1.
 
Fire Area T-2 to TURB is not separated by a physical boundary. The 50 point north of the Auxiliary Building wall has been established as a theoretical zone boundary between T-2 and TURB for fire hazard analysis purpose only.
 
A pipe trench extends from the Auxiliary Building wall to the Condenser Pit area. The trench is sloped away from the Auxiliary building.
 
T.2.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area T-2 is Low.
 
T.2.5 Fire Protection
 
The T-2 areas below the turbine operating floor (El. 2065) are protected by an automatic detection system, using rate compensated thermal detectors. The detection system alarms locally and in the Control Room and also charges the preaction sprinkler system in the area. The Control Room detection annunciation is zoned for quick identification of the specific area in alarm. Manual-pull fire alarm stations are located near the emergency exit doorways from this area. The pull stations alarm locally and in the Control Room.
Control Room annunciation of a pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Hose stations and portable extinguishers are provided throughout this area. Adjacent hose stations are separated by no more than 100 feet.
 
Automatic preaction sprinkler protection is provided for T-2 areas below the operating floor, El. 2065. Each of the two systems is charged by actuation of any one of the thermal detectors located in the area protected by that system.
 
The entire area is readily accessible through several interior and exterior doors and fire-rated stairways.
 
Adequate floor drains are provided in the Turbine Building area to remove sprinkler and hose station discharge without appreciable accumulation. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 256 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 227 of 244)
T.2.6                                                                                                          Isolation and Smoke Removal
 
A fire in this area will be isolated from the Auxiliary Building and Fire Areas T-4 and T-10 by fire barrier construction. Fire dampers will isolate the HVAC ducts from the Auxiliary Building, and Fire Areas T-4 and T-10. The roof of the Turbine Building is fitted with spring loaded vents which are held closed by fusible links. In the event of a fire in the Turbine Building, these vents will open to relieve smoke and heat. The vents are sized to provide 1 square foot of vent area for each 100 square feet of floor area. Refer to Section 4.3.7.2 for additional smoke removal discussion.
 
T.2.7 Analysis
 
T.2.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. The automatic suppression systems will discharge shortly after the automatic alarm signal occurs. In the event of failure of the automatic suppression system or a delay in discharge, the fire can be manually extinguished, using the portable extinguishers, manual hose stations, and/or the manual water spray systems, where provided.
Collapse of the Turbine Building roof or even a Turbine Building roof truss is not credible and is not postulated because of the fire protection provided, low fire loadings above the operating deck of the Turbine Building, and the construction of the roof which meets FM Class I UL Class A requirements. Even though the roof trusses will not collapse, it has been verified that a free-falling roof truss has less energy than tornado missiles considered in the design of safety-related buildings.
Fires on or above the operating deck within the T-2 area would be extinguished manually. The combustible loading above the operating floor is low and administrative controls limit the introduction and storage of transient combustibles on the operating floor. Fires starting on or above the operating floor will not damage the roof or roof trusses. The resultant heat and smoke will be vented through the roof vents.
Fire starting below the operating deck in an open area will be automatically detected and extinguished by an automatic preaction sprinkler system. Therefore, fires below the operating deck within the T-2 area will not damage the roof or the roof trusses. Failure of the automatic extinguishing system is alarmed in the Control Room.
 
T.2.7.2                                                                                                                                      Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an T-2 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area T-2 will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 257 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 228 of 244)
Fire Area T-4 (Reference A-1806)
 
T.4.1                                                                                                          Fire Area Description
 
Turbine Building 2000, Lube Oil Storage Tanks Room 4308.
 
T.4.2 Major Equipment
 
Main lube oil storage tanks, oily waste sumps, main lube oil conditioner, and main lube oil transfer pump.
 
T.4.3 Design Features
 
This Fire Area is separated from other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, fire damper, and penetration seals) that satisfy at least one of the following criteria:  (Reference 3.1, Section F.8)
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
The doorway of the room has an 8-inch curb to contain oil spillage in the room.
 
T.4.4 Combustible Loading
 
Calculation XX-X-004 does not maintain a combustible loading classification for Fire Area T-4. The combustible hazard associated with this area is that presented by stored lubrication oil. The maximum capacity of each tank (TCF01A and TCF01B) is approximately 15,122 gallons.
 
T.4.5 Fire Protection
 
An automatic infrared flame detector is installed in this Fire Area. Manual-pull stations are located at Turbine Building Exits. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
The area is protected by an automatic wet pipe sprinkler system.  (Reference 3.1, Section F.8)
 
Hose stations and portable extinguishers are located outside the area to ensure accessibility. Refer to drawing A-1806 for specific hose station and fire extinguisher locations.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 258 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 229 of 244)
 
The area is accessible for fire fighting efforts via Turbine Building Room 4322.
 
An 8 curb and sump are provided within the area to contain and remove sprinkler and hose station discharge without appreciable accumulation. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
T.4.6                                                                                                          Isolation and Smoke Removal
 
A fire in this area will be isolated from adjacent safe shutdown areas of the plant by fire barriers. Fire dampers will isolate the HVAC ducts from the adjacent safe shutdown areas. Refer to Section 4.3.7.2 for smoke removal discussion.
 
T.4.7 Analysis
 
T.4.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be  contained by the fire barriers and suppressed by the wet pipe  system. Should the automatic suppression system fail, manual hose  streams and extinguishers can be used to extinguish the fire.
 
T.4.7.2                                                                                                                                      Safe Shutdown Capability
 
There are no PFSSD equipment or circuits in this area. Therefore fire damage to this area will not prevent safe shutdown.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 259 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 230 of 244)
Fire Area T-10 (Reference A-1807)
 
T.10.1                                                                                    Fire Area Description
 
Turbine Building 2033, Lube Oil Reservoir Room 4403.
 
T.10.2 Major Equipment
 
Lube oil reservoir.
 
T.10.3 Design Features
 
This Fire Area is separated from other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, fire dampers, and penetration seals) that satisfy at least one of the following criteria:  (Reference 3.1, Section F.8)
 
x                                      Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
 
x                                      Have been evaluated as providing an equivalent level of protection.
 
x                                      Have been evaluated as providing protection commensurate with the fire hazards present.
 
T.10.4 Combustible Loading
 
Calculation XX-X-004 does not maintain a combustible loading classification for Fire Area T-10. The combustible hazard associated with this area is that presented by lubrication oil within the main turbine lube oil tank (TCB01). The tank has a maximum capacity of approximately 12,450 gallons.
 
T.10.5 Fire Protection
 
An automatic infrared flame detector is installed in this Fire Area. Manual-pull stations are located at Turbine Building Exits. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
The area is protected by an automatic wet pipe sprinkler system.  (Reference 3.1, Section F.8)
 
Hose stations and portable extinguishers are located outside the area to ensure accessibility. Refer to drawing A-1807 for specific hose station and fire extinguisher locations.
 
The area is accessible for firefighting efforts via Turbine Building Room 4401.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 260 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 231 of 244)
Floor drains are provided within the area to contain and remove sprinkler and hose station discharge without appreciable accumulation. The drains discharge to the oily waste sump located in Room 4308. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
T.10.6                                                                                    Isolation and Smoke Removal
 
A fire in this area will be isolated from adjacent safe shutdown areas of the plant by fire barriers. Fire dampers will isolate the HVAC ducts from the adjacent safe shutdown areas. Refer to Section 4.3.7.2 for smoke removal discussion.
 
T.10.7 Analysis
 
T.10.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be  contained by the fire barriers, with the exception of the potential fire communication path to Fire Area T-4 via the floor drain system. The automatic sprinkler system will suppress a fire in the area. Should the automatic suppression system fail, manual hose streams and extinguishers can be used to extinguish the fire.
 
As identified in Section T.10.5, floor drains in the area discharge to the oily waste sump located in Room 4308 (Fire Area T-4). This presents a potential combustible liquid communication path between the two Fire Areas. However, each Fire Area is protected from other Fire Areas by fire barrier construction and a wet pipe sprinkler system ensuring that a fire originating in T-10 and communicating to T-4 through the drainage system, would be maintained within the fire barrier confines of T-4.
Additionally, Fire Area T-4 does not contain any PFSSD equipment or circuits. Therefore, a fire involving both T-10 and T-4 will have the same overall impact on plant safe shutdown capability.
 
T.10.7.2                                                                                                                Safe Shutdown Capability
 
One cable for the control of valve ABHV031 runs through this Fire Area.
This cable needs to function when the MSIV's are rendered incapable of closing due to a fire. For a fire in this area, the MSIV's will function normally. Therefore, a fire in any portion of Fire Area T-10 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 261 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 232 of 244)
Fire Area TURB (Reference A-1806 through A-0808)
 
Note:
The TURB FHA encompasses Fire Zones T-3, T-5, T-6, T-7, T-8, and T-9 identified in AP 10-106, Fire Preplans.
 
TURB.1                                                      Fire Area Description
 
Entire Turbine Building north of Fire Area T-2. Rooms 4201, 4203, 4204, 4205, 4309, 4310, 4312, 4313, 4314, 4316, 4317, 4318, 4319, 4320, 4321, 4323, 4324, 4325, 4326, 4402, 4404, 4405, 4502, 4503, 4505, 4601, 4301E, 4301W, 4401E, 4401W, 4501E,4501W, OP-1, OP-2, and OP-7.
 
TURB.2 Major Equipment
 
Condensate pumps, heater drain pumps, low, intermediate and high pressure condensers, steam generator feedwater pump lube oil pumps and conditioners, lube oil filter pump, process sample rack, condenser drain pump, auxiliary steam boiler blowdown flash tank,  demineralized water transfer pump, low TDS transfer pumps, high TDS transfer pumps, SLW oil interceptor transfer pumps, SLW oil interceptor, oily waste sump pumps, miscellaneous condensate drain pump and tank, condensate demineralizer hot water tank, condensate demineralizer control panel, steam generator feedwater pump and turbine, acid day tank, caustic day tank, condensate demineralizers, high TDS tanks, high TDS collection pumps, hydrazine chemical addition skid, ammonia chemical addition skid, high pressure feedwater heaters, motor control centers, moister separator/reheater drain tank, reheater drain tank, 125 volt dc electrical busses, 125 volt batteries, 125 volt battery chargers, 13.8 kv electrical busses, 4.16 kv electrical busses, 480 volt load centers, isophase bus duct cooling system, exciter control panel, main generator relay panels \\ main generator potential relay cabinets, waterbox vent tank, waterbox venting pumps, moister separator/reheater drain tank, reheater drain tanks, main turbine generator, alternator, intercept and control valves, and closed cooling water surge tank.
 
TURB.3 Design Features
 
Fire Area TURB to T-2 is not separated by a physical fire barrier boundary. The 50 mark north of the Auxiliary Building wall has been established as a theoretical zone boundary between T-2 and TURB for analysis purpose only. Fire barriers are provided for Battery Rooms 4402 and 4404 for commercial property protection.
 
The Communication Corridor (Fire Area CC-1) is open to this area via T-2. However, CC-1 is separated from the adjacent Control Building by a fire boundary wall.
 
TURB.4 Combustible Loading
 
Calculation XX-X-004 does not maintain a combustible loading classification for Fire Area TURB. The predominate combustible hazards associated with this area is that presented by lubrication oil and hydrogen within the main generator.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 262 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 233 of 244)
TURB.5 Fire Protection
 
Battery Rooms 4402 and 4404 are protected by automatic smoke detectors. Remaining TURB areas below the turbine operating floor (El. 2065), with the exception of the Condenser Pit and Observation Posts are protected by an automatic detection system, using rate compensated thermal detectors. The detection system alarms locally and in the Control Room. Thermal detection activation and also charges the preaction sprinkler system in the area. The Control Room thermal detector alarm annunciation is zoned for quick identification of the specific area in alarm. Manual-pull fire alarm stations are located near the emergency exit doorways from this area. The pull stations alarm locally and in the Control Room. Control Room annunciation of a smoke detector and pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
Automatic preaction sprinkler systems are provided to protect TURB areas below the turbine operating floor (excluding room enclosures and the Condenser Pit area). Each system is charged by actuation of any one of the thermal detectors located in the area protected by that system. Each floor elevation in the Turbine Building with the exception of 1983 and 2065 is protected by two independent sprinkler systems with each system serving approximately one-half of the floor area. A preaction sprinkler system, actuated by thermal detection, is also provided for the main turbine generator bearings
 
The area under the condenser in the Condenser Pit is protected by an automatic wet pipe sprinkler system. The steam generator feedwater pump turbines are protected by a manually actuated water spray system. Detection is by thermal detectors which alarm locally and in the Control Room. A manual system is installed to prevent damage due to inadvertent operation. The hydrogen seal oil unit and is protected by an automatic water spray system actuated by thermal detectors, which alarm locally and in the Control Room.
An automatic wet pipe sprinkler system is provided for the Outage office and storage area located in the northwest corner of the turbine operating floor.
 
The entire area is readily accessible through several interior and exterior doors and fire-rated stairways.
 
Adequate floor drains are provided in the Turbine Building area to remove sprinkler and hose station discharge without appreciable accumulation. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
TURB.6                                                      Isolation and Smoke Removal
 
A fire in this area will be isolated from the Auxiliary Building, Control Building, Fire Area T-4, and Fire Area T-10 by fire barriers. Fire dampers will isolate the HVAC ducts from the these areas. The roof of the Turbine Building is fitted with spring loaded vents which are held closed by fusible links. In the event of a fire in the Turbine Building, these vents will open to relieve smoke and heat. The vents are sized to provide 1 square foot of vent area for each 100 square feet of floor area. Refer to Section  4.3.7.2 for additional smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 263 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 234 of 244)
TURB.7 Analysis
 
TURB.7.1 Fire Suppression
 
A fire in this area will be detected and alarmed by the automatic detection system. In areas where preaction suppression systems are installed, the design is such that the system will discharge shortly after the automatic alarm signal occurs. The wet pipe sprinkler systems will automatically activate as sprinklers heads are opened by the fire. In the event of an automatic suppression system failure, complete extinguishment is not achieved by the automatic systems, or there is a delay in discharge, the fire can be manually extinguished, using the portable extinguishers, manual hose stations, and/or the manual water spray systems, where provided.
 
Collapse of the Turbine Building roof or even a Turbine Building roof truss is not credible and is not postulated because of the fire protection provided, low fire loadings above the operating deck of the Turbine Building, and the construction of the roof which meets FM Class I UL Class A requirements. Even though the roof trusses will not collapse, it has been verified that a free-falling roof truss has less energy than tornado missiles considered in the design of safety-related buildings.
 
A fire involving the Outage Office or storage area on the operating floor would be suppressed by the sprinkler system. All other fires on or above the operating deck would be extinguished manually. The combustible loading above the operating floor is low and administrative controls limit the introduction and storage of transient combustibles on the operating floor. Fires starting on or above the operating floor will not damage the roof or roof trusses. The resultant heat and smoke will be vented through the roof vents.
 
Fire starting below the operating deck in an open area will be automatically detected and suppressed by an automatic sprinkler system.
Should an automatic fire extinguishing system fail to operate or is not entirely successful, manual fire fighting could still be accomplished to extinguish the fire. The resultant heat and smoke would be vented through the roof vents. Therefore, fires below the operating deck will not damage the roof or the roof trusses. Failure of the automatic extinguishing system is alarmed in the Control Room.
 
TURB.7.2                                                                                    Safe Shutdown Capability
 
There are several components located in Fire Area TURB that are needed for a fire that renders the MSIVs incapable of closing. For a fire in this area, the MSIV's will function normally. Cables for several components that are needed for a fire that renders the MSIVs incapable of closing are located in Fire Area T-2 and CC-1. For a fire in these areas, the MSIV's will function normally.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 264 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 235 of 244)
The main turbine stop valves and steam bypass valves are located in Fire Area TURB. In addition to a fire that renders the MSIVs incapable of closing, these valves are needed in the case of a fire in the Control Room.
The procedure that governs the safe shutdown of the plant in the case of a fire in the Control Room assures that these valves will close.
 
Fire in this area and CC-1 can cause loss of off site power. However, redundant on-site power sources are available.
 
In summary, a fire in any portion of Fire Area TURB will not prevent safe shutdown of the plant, even in the unlikely event that fire propagation to T-2 and/or CC-1 occurs.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 265 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 236 of 244)
Fire Area CST & RWST (Reference A-1802)
 
CST/RWST.1                                                        Fire Area Description
 
Yard Areas around Condensate Storage Tank and Refueling Water Storage Tank (areas are identified as Fire Areas Y-01 and Y-02 in XX-X-004).
 
CST/RWST.2 Major Equipment
 
Condensate Storage Tank, Refueling Water Storage Tank, Demineralized Water Tank, Reactor Makeup Water Tank, and Emergency Fuel Oil Storage Tanks.
 
CST/RWST.3 Design Features
 
The water storage tanks are located in areas containing low combustible loading.
The walls of the two buildings adjacent to the Refueling Water Storage Tank are of concrete for the Fuel Building and metal siding for the Hot Machine Shop. The walls of the buildings adjacent to the Condensate Storage Tank are concrete for the Reactor Building and metal siding for the Auxiliary Boiler Room. Neither the below grade emergency fuel oil storage tanks or the diked heating oil storage tank present an exposure hazard to the CST or RWST.
 
CST/RWST.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area CST/RWST is Low.
 
CST/RWST.5 Fire Protection
 
Yard hydrants and hose houses are located throughout the Power Block area.
 
CST/RWST.6                                                        Isolation and Smoke Removal
 
Smoke will be removed by natural means for these outdoor structures.
 
CST/RWST.7 Analysis
 
CST/RWST.7.1 Fire Suppression
 
Manual fire suppression equipment is available to extinguish a fire in this area.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 266 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 237 of 244)
CST/RWST.7.2                                                                                      Safe Shutdown Capability
 
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a CST/RWST fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area CST/RWST will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in CST/RWST.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 267 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 238 of 244)
Fire Area YARD-ESF (Reference E-0F0221)
 
Note:
Fire Area YARD-ESF is identified as YARD1 in E-15000.
 
YARD-ESF.1                                                                Fire Area Description
 
ESF Transformers XNB01, XNB02, and surrounding yard area
 
YARD-ESF.2 Major Equipment
 
ESF Transformers XNB01 and XNB02.
 
YARD-ESF.3 Design Features
 
The two ESF Transformers are located outdoors west of the Turbine Building and north of the Communications Corridor. The units set approximately 9-6 apart with an 13-3 tall by 20-8 long by 12 thick concrete barrier provided between the transformers for fire exposure protection. Overhead cable raceways exiting the transformers into the Communications Corridor are separated by a horizontal distance of approximately 20 ft.
 
Due to spatial separation, the Communications Corridor, Turbine Building, and Station Service Transformers, do not present an exposure hazard to XNB01 or XNB02.
 
YARD-ESF.4 Combustible Loading
 
The predominate combustible material is the transformer oil (approximately 4,205                              12 gallons for XNB01 and approximately 4,205 gallons for XNB02). The oil is a Class IIIB combustible liquid.
 
YARD-ESF.5 Fire Protection
 
Each transformer is provided with automatic thermal detectors that upon activation will trip the open spray head deluge sprinkler system protecting the corresponding unit. The system may also be manually actuated by an electrical manual pull station in the area or by activation of a pneumatic manual release station on the deluge system riser. Detector or pull station activation will annunciate locally and in the Control Room. The Control Room annunciation of a detection or release station alarm is zoned for a quick and easy means to identify the location associated with the device in alarm.
 
Hydrants and hose hoses are accessible in the area for manual firefighting efforts.
 
The transformers area accessible from the yard area of the Power Block for firefighting efforts.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 268 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 239 of 244)
A curbed gravel pit is located beneath the transformers. The pit is sized to contain the oil from a transformer as well as water from both ESF transformer deluge sprinkler systems operating for approximately 10 minutes. Drainage is provided by a manual valve controlled 6 drain that discharges to the Turbine Building drainage system. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
YARD-ESF.6                                                                Isolation and Smoke Removal
 
The concrete barrier between the two transformers provides exposure protection from a fire originating in either transformer. Smoke will be removed by natural means for the outdoor transformers.
 
YARD-ESF.7 Analysis
 
YARD-ESF.7.1 Fire Suppression
 
A fire in either transformer unit would be detected by the automatic heat detectors, which would automatically actuate the open head spray deluge system to suppress the fire. In the event that the deluge system does not extinguish the fire or the system fails to operate, the fire can be  extinguished manually by utilizing an area fire hydrant.
 
YARD-ESF.7.2                                                                                            Safe Shutdown Capability
 
The ESF transformers have been included as PFSSD equipment because they are the normal power supplies to the emergency busses. An analysis has been performed that shows the areas where these transformers can be lost and is included in calculation XX-E-013. In all areas where fire can cause the loss of these transformers, the emergency diesel generators will be available. Therefore, a fire in that causes the loss of ESF transformers XNB01 and XNB02 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 269 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 240 of 244)
Fire Area YARD-SU (Reference E-0F0221)
 
Note:
Fire Area YARD-SU is identified as YARD3 in E-15000.
 
YARD-SU.1                                                                                      Fire Area Description
 
Startup Transformers XMR01 and surrounding yard area.
 
YARD-SU.2 Major Equipment
 
Startup Transformer XMR01.
 
YARD-SU.3 Design Features
 
The Startup Transformer is located outdoors west of the Turbine Building.
Overhead cable raceways exiting the transformers into the Communications
 
Due to spatial separation, the Turbine Building and Station Service Transformers, do not present an exposure hazard to XMR01.
 
YARD-SU.4 Combustible Loading
 
The predominate combustible material is the transformer oil (approximately 10,850 gallons). The oil is a Class IIIB combustible liquid.
 
YARD-SU.5 Fire Protection
 
The transformer is provided with cross zoned automatic thermal detectors.
Detection by either zone will alarm locally and in the Control Room. Activation by both zones will trip the open spray head deluge sprinkler system protecting the transformer. A deluge system trip signal also deenergizes XMR01. Activation of the electrical manual pull station in the area results in an single zone only alarm. It will not trip the deluge system. Manual deluge system actuation may be accomplished by activation of the pneumatic manual release station on the deluge system riser or key activated switch at the control panel. The Control Room annunciation of a detection or manual pull station alarm is zoned for a quick and easy means to identify the location associated with the device in alarm.
Hydrants and hose hoses are accessible in the area for manual firefighting efforts.
The transformer area accessible from the yard area of the Power Block for firefighting efforts.
A curbed gravel pit is located beneath the transformer. The pit is sized to contain the oil from the transformer as well as water from the deluge sprinkler system operating for approximately 10 minutes. Drainage is provided by a manual valve controlled 6 drain that discharges to the Turbine Building drainage system. Refer to drawing series M-12LE for further information on the oily waste drain system.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 270 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 241 of 244)
YARD-SU.6                                                                                      Isolation and Smoke Removal
 
Smoke will be removed by natural means for the outdoor transformer.
 
YARD-SU.7 Analysis
 
YARD-SU.7.1 Fire Suppression
 
A fire in the transformer unit would be detected by the automatic heat detectors, which would automatically actuate the open head spray deluge system to suppress the fire. In the event that the deluge system does not extinguish the fire or the system fails to operate, the fire can be  extinguished manually by utilizing an area fire hydrant.
 
YARD-SU.7.2                                                                                                                  Safe Shutdown Capability
 
The startup transformer XMR01 is required to provide power to equipment in the Turbine Building that is needed when a fire renders the MSIVs incapable of closing. Any fire that can cause the loss of the startup transformer will not cause the MSIVs to be incapable of closing. Therefore, a fire in that causes the loss of startup transformer XMR01 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 271 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 242 of 244)
Fire Area ESWC (Reference A-1324 through A-1327)
 
ESWC.1                                            Fire Area Description
 
ESW Vertical Loop Chase, West of Control Building, Elevations 1974 to 2087-2, Room 8000.
 
ESWC.2 Major Equipment
 
A and B train essential service water (ESW) piping and vacuum breakers.
 
ESWC.3 Design Features
 
The ESW Vertical Loop Chase is a Seismic Category I structure that is attached to the west exterior wall of the Control Building. The exterior walls of the Chase below grade are concrete. Above grade, the walls are 1/2 thick steel plate with the exception of the east wall, which is the Control Building concrete wall at column line CF. The approximate area footprint of the Chase is  23 x 13. The Chase extends from 1974 to the top of the Control Building (2087-2). Access/egress is provided by an exterior door at 2000 (grade) and a personnel hatch on the Chase roof.
 
This fire area is separated from all other fire Areas by 3-hour rated fire barrier construction and penetration closure assemblies. No structural steel fireproofing is provided for the Chase due to low combustible loading. An additional consideration for not providing fireproofing was thermal expansion/contraction of the steel enclosure, from seasonal temperature changes, which would challenge fireproofing bond integrity. The exterior walls of the Chase are not fire rated, as there are no significant exterior fire exposure hazards in close proximity to the Chase.
 
ESWC.4 Combustible Loading
 
The cumulative combustible loading classification for Fire Area ESWC is Low, with minimal fixed combustibles and no combustible continuity. As an added defense in depth feature, the fire area is maintained as a Combustible Control Zone. This administrative control requires that transient combustibles be constantly attended, or a transient combustible materials (TCM) permit is required. The TCM will specify required compensatory measures commensurate with the hazard presented by the transient combustible material package.
 
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 272 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 243 of 244)
ESWC.5 Fire Protection
 
Area smoke detection is provided for the Chase. A manual-pull fire alarm station is located at each exit. Smoke detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a fire alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
 
A dry standpipe connection is provided south of the Chase at grade level. The standpipe feeds open head spray nozzles located below the Chase roof. Fire water is provided to the system by connecting the standpipe to an area fire hydrant with fire hose located in the hydrant hose house. The nozzles provide water spray protection for the Chase footprint, including the structural steel vertical columns.
 
Manual fire water suppression capability also includes hose stream application via area fire hydrants that are provided with fire hose and nozzle stored within the fire hydrant hose house.
 
Portable fire extinguishers are provided within the Chase for incipient fire response.
 
Drainage for the Chase is by a sump located on the 1974 elevation. Fire water discharge into the chase will not impact safe shutdown capability, as there are no electrical safe shutdown components within the Chase.
 
ESWC.6                                            Isolation and Smoke Removal
 
The fire barrier separating the Chase from the Control Building will prevent fire propagation to a communicating fire area. No ventilation ductwork penetrates the fire barrier separating the Chase from the Control Building. Louvered vents are provided in the exterior walls of the chase to provide natural ventilation.
 
Refer to Section 4.3.7.2 for smoke removal discussion.
 
ESWC.7 Analysis
 
ESWC.7.1 Fire Suppression
 
In the event that a fire occurs within the Chase, it will be detected by area smoke detection. Fire severity will be low considering the limited amount of fixed combustibles and the administratively controlled transient combustibles within the Chase. Fire suppression will be via portable fire extinguishers, manual operation of the water spray system, or hose stream from an area yard fire hydrant. This protection approach Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 273 of 275 Fire Hazard Analysis
 
ATTACHMENT B FIRE HAZARD ANALYSIS (Page 244 of 244) ensures that Chase structural integrity will not be challenged by an ESW Vertical Loop Chase fire.
 
ESWC.7.2                                                                          Safe Shutdown Capability
 
As previously identified, there is no electrical safe shutdown equipment within the fire area. Protection of the Chase and  vertical structural steel with the manual water spray system ensures that the building structure will not impact the performance of the ESW piping internal to the Chase. Per the section 3.2.1.2 assumption from NEI 00-01,  Guidance for Post-Fire Safe Shutdown Circuit Analysis,  (Rev. 2), exposure fire damage to manual valves and piping does not adversely impact their ability to perform their pressure boundary or safe shutdown function. Therefore, a fire within ESWC will not prevent safe shutdown of the plant.
Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 274 of 275 Fire Hazard Analysis
 
ATTACHMENT C NON-SAFETY RELATED SITE STRUCTURES (Page 1 of 2)
 
Structures & Equipment                                                                                                Nearest Structure Containing PFSSD                                                                                                      Approximate Equipment/Circuits                                                                                                                      Distance (ft) 345 KV Switchyard and 69 KVA                                                                                        Turbine Building                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      1155 Substation Concentrate Acid Storage Tank Area                                                                      ESW Mechanical Vault 675 Unit Aux. Transformer XMA02                                                                                                                                                                                    Turbine Building 20 Main Phase A Transformer XMA01A Turbine Building 62 Main Phase B Transformer XMA01B                                                                            Turbine Building 62 Main Phase C Transformer XMA01B                                                                          Turbine Building 62 Spare Transformer                                                                                                                                                                                                                                                                                                                                                                      Turbine Building 62 Station Service Transformer XPB03                                                                                        Turbine Building 63 Station Service Transformer XPB04                                                                                        Turbine Building 63 Admin. Services Shop                                                                                                                                                                                                                                                                                                                  ESW Mechanical Vault 354 Cable Reel Shop                                                                                                                                                                                                                                                                                                                                                                                                    Start-Up Transformer XMR01                                                                                                                                                                                                                                                                                                                    744 Walter P. Chrysler Support Complex                                                                              Turbine Building 112 Charles Curtis Development Center                                                                                          ESW Mechanical Vault 477 Circulating Water Screen House                                                                                                                                                ESW Pump House                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              849 Dosimetry Building Start-Up Transformer XMR01 58 Dimineralized Water Storage                                                                                                                                                                                              CST & Valve House                                                                                                                                                                                                                                                                                                                                                                                                                                                                          21 Dwight D. Eisenhower Learning Center                                                                                Turbine Building                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      14070 (Emergency Operations Center)
Ron Evans Outage Processing Center                                                  Turbine Building 1041 Fire Training Building ESW Pumphouse      645 Clyde Cessna Administration Building CST                                                                                                277 High Ammonia Chemistry Building Turbine Building 504 Hazardous Waste Storage Radwaste Storage Building 507 Hydrogen Storage Turbine Building 747 Kelly Building #7                                                                                                                                                                                                                                                                                                                                                                                                          Start-Up Transformer XMR01                                                                                                                                                                                                                                                                                                                    1080 Edward P. Macabe Support Building Turbine Building 448 NDE/Civil Test Center                                                                                                                                                                                                                                                                                                                    ESW Mechanical Vault 234 North Storage Building Turbine Building 1245 Olive Ann Beech - Ops Admin. Building CST                                                                                                                                                                128 Arthur Capper OJT Center                                                                                                                                                                                                                                              ESW Mechanical Vault 531 Outage Support Building                                                                                                                                                                                                                                                                            Start-Up Transformer XMR01                                                                                                                                                                                                                                                                                                                    52 Owens Corning Warehouse                                                                                                                                                                                                                          Radwaste Building 513 Nitrogen / Oxygen Storage                                                                                                                                                                                                                                          Diesel Generator Building 255 Pump House Northeast                                                                                                                                                                                                                                                                                    ESW Pumphouse                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              1506 Paint Shop                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Radwaste Building 945 Paint Storage Radwaste Building 1092 Pole Barns East, Middle, & West                                                                                                                                          Start-Up Transformer XMR01                                                                                                                                                                                                                                                                                                                  1348 Charles Evans Whittaker Security                                                                                    Reactor Building                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  192 Building Security Diesel Generator Building Fuel Building 197 Secondary Access                                                                                                                                                                                                                                                                                                                                                                          Turbine Building 1290 Badge Check Point to Owner                                                                                          Turbine Building                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      2994 Controlled Area Vehicle Inspection Building Turbine Building 2970 William Allen White Skills Training                                                                                  Turbine Building                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      909 Center Technical Support Center                                                                                                                                                                                                                                                            Turbine Building 183 Vehicle Maintenance Shop                                                                                                                                                                                                                                        ESW Mechanical Vault 513 Amelia Earhart Warehouse                                                                                                                                                                                                                                    ESW Pumphouse                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              882 Wolf Creek Nuclear Operating Corporation                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Page 275 of 275 Fire Hazard Analysis
 
ATTACHMENT C NON-SAFETY RELATED SITE STRUCTURES (Page 2 of 2)
Structures & Equipment                                                                    Nearest Structure Containing PFSSD                                                                        Approximate Equipment/Circuits                                                                                        Distance (ft)
Amelia Earhart Warehouse (West) Control Building 822 Waste Oil Storage Radwaste Building 216 Heating Oil Pumphouse and Storage                                                        Radwaste Building                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                417 Tank Area Sewage Lagoon Turbine Building 3444 Circ. Water Discharge                                                                                                                                                                                                                                                                                                            Start-Up Transformer XMR01                                                                                                                                                                                                                                                                                                                    984 Waste Water Treatment Turbine Building 885 SBO Diesel Generator Structure                                                                                                                                                Control Building 240
 
                                                                                                                -END-}}

Latest revision as of 17:00, 4 October 2024

Redacted Updated Safety Analysis Report (WCGS Usar), Revision 37, E-1F9905, Rev. 12, Fire Hazard Analysis
ML24114A185
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 04/15/2024
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
References
000347
Download: ML24114A185 (1)


Text