| title = LER 87-017-02:on 871113,six Leakage Pathways from Unit 1 Auxiliary Feedwater Pump Compartment 13 & One Pathway from Unit 2 Identified.Caused by Control of Design Requirements. Leakage Paths Sealed & Field Directive Will Be Issued
| title = LER 87-017-02:on 871113,six Leakage Pathways from Unit 1 Auxiliary Feedwater Pump Compartment 13 & One Pathway from Unit 2 Identified.Caused by Control of Design Requirements. Leakage Paths Sealed & Field Directive Will Be Issued
| author name = POLLACK M J
| author name = Pollack M
| author affiliation = PUBLIC SERVICE ELECTRIC & GAS CO. OF NEW JERSEY
| author affiliation = PUBLIC SERVICE ELECTRIC & GAS CO. OF NEW JERSEY
| addressee name =  
| addressee name =  
Line 17: Line 17:


=Text=
=Text=
{{#Wiki_filter:.. iillC forMJll IM:IJ LICENSEE EVENT REPORT (LEA) ' U.1, NUCLIAll llEOULATOllY c:a..i*ION -OVID OMI NO. 3110-41CM EX,.llES:
{{#Wiki_filter:..
1131
iillC forMJll                                                                                                                                   U.1, NUCLIAll llEOULATOllY c:a..i*ION IM:IJ
* PACILITY NAMI 111 Salem Generating Station -Unit 1 I DOCKIT Maalll 121 I
                                                                                                                                                          -OVID OMI NO. 3110-41CM EX,.llES: 1131
,.., o 15 IO IO Io I 21 71 211 loF 0 14 TITLI 1'1 Disc. Leak Paths From 13(23)AFW Pump Compartments  
* LICENSEE EVENT REPORT (LEA)                              '
-Control of Design Reqt IVINT CATI 1111 lllPOllT CATI 171 OTHlll PACIUTlll INVOLVID Ill MONTH QAY YEAR YEAR lt tt MONTH DAY YEAR FACILITY NAMU DOCltET NUMIERISI Salem Unit 2 o 1 s Io I o I o t3 11 11 l I 1 ll 3 s 1 s 11--o I 1 I 1 -o I 2 o I 12 16
DOCKIT Maalll 121                      I              r-~*         ,..,
* s 1 s THll llll'OllT 11 IUIMITTID l'UlllUANT TO THI lllQUllllMINTI OP 10 CPll §: (o-lt -°',,,,.,.of IN followlnf) 1111 Ol'lllATINO MODI Ill 6 20.40211tl 20.4Gl(ol I0.'7311112111*1 71.7111tl t----...---.._+--i i----10.al1IC11  
I PACILITY NAMI 111 Salem Generating Station - Unit 1                                                                                                 o 15 IO IO Io I 21 71               211 loF 0 14 TITLI 1'1 Disc. Leak Paths From 13(23)AFW Pump Compartments - Control of Design Reqt IVINT CATI 1111                   L!llN~llllll                              lllPOllT CATI 171                       OTHlll PACIUTlll INVOLVID Ill MONTH       QAY   YEAR     YEAR     lt u:;:;~~~~AL tt :~"1~                MONTH         DAY     YEAR           FACILITY NAMU                         DOCltET NUMIERISI Salem Unit 2                                     o 1s Io I o I o t3 11 11 l I 1 ll       3 s   1s    11- - o I 1 I1          -       oI 2 oI 12                 16
*.nc.11211*1 7:1.71111 i--eo.:.101121
* s 1s THll llll'OllT 11 IUIMITTID l'UlllUANT TO THI lllQUllllMINTI OP 10 CPll §: (o-lt -           °',,,,.,.of IN followlnf) 1111 Ol'lllATINO MODI Ill I
...... l'OWlll I 20 ...... 111,111 01 01 Q-20.4Glloll111MI 6'1.731eli.illll
t----...---.._+--i l'OWlll L~1L 6        20.40211tl 20......111,111 i--
-110.n1e11211w111  
i--
-1111.n1e11211w1111w
20.4Gl(ol 10.al1IC11 I0.'7311112111*1
::R OTHlll (Spclfy In Ab_,
                                                                                                                      *.nc.11211*1                         -::R  71.7111tl 7:1.71111 01 01 Q -       20.4Glloll111MI
Te:r, NflC f'r;;m --90.731elf2JUll IG.711811211111111111  
                                                                          ...... eo.:.101121                        110.n1e11211w111                             OTHlll (Spclfy In Ab_,
--Info Only I0.731ell2111111 ll0.7Jlell21f*I LICENIH CONTACT FOii THll LEll lt:lll NAME TELEPHONE NUMll!ll AREA COD! M. J. Pollack -LER Coordinator 61 0 I 9 31 31 9r 14 10 12 12 COMl'LITI ONE LINI FOii EACH COMPONENT PAILUlll DEIClllllD IN THll llll'OllT 11'1 CAUSE SYSTEM COMPONENT MANUFAC. TUR ER SYSTEM COMl'ONENT MANUFAC. TUR ER I I I I I I I I I I I I I I I I I I I I I I I I I I I I IUl'PLEMENTAL llEl'OllT l!XPECTID 11'1 EXPECTED MONTH DAY SUllMISSIDN DATE 11111 I YES,,, I'll. --EXl'ECTED  
                                                                                                                                                                  ~-er.!!'"        Te:r, NflC               f'r;;m
:SVIMISSION DATE} I I AalTllACT (Limit ID 1400 -* I.&, _.,.1mno1y  
                                                                          --       6'1.731eli.illll 90.731elf2JUll                 --  1111.n1e11211w1111w IG.711811211111111111
,,_ r1,.,,, . .,,... ry,.,..,,mn llnmJ 1111 On 11/13/87 an NRC inspector identified leakage paths from the No. 13 Auxiliary Feedwater (AFW) Turbine .Driven Pump compartment  
                                                                                                                                                                  ~
{BAI. Subsequent investigation revealed six (6) unsealed openings from the Unit 1 pump and one unsealed opening from the Unit 2 pump. The compartment encloses the steam feed piping to the AFW Turbine Driven Pump such that a postulated pipe break would not damage adjacent vital electrical equipment located outside the compartment.
Info Only I0.731ell2111111                   ll0.7Jlell21f*I LICENIH CONTACT FOii THll LEll lt:lll NAME                                                                                                                                                     TELEPHONE NUMll!ll AREA COD!
The root cause of the Steam Driven AFW Pump compartment deficiencies has been attributed to control of design requirements.
M. J. Pollack - LER Coordinator                                                                                                         61 0 I 9 31 31 9r 14 10 12 12 COMl'LITI ONE LINI FOii EACH COMPONENT PAILUlll DEIClllllD IN THll llll'OllT 11'1 CAUSE SYSTEM       COMPONENT           MANUFAC.                                                      SYSTEM                          MANUFAC.
TUR ER                                                                 COMl'ONENT             TUR ER I       I I   I         I   I   I                                                     I         I   I     I       I     I   I I       I I     I         I   I   I                                                     I         I I       I       I     I   I                   l!l li!i!l i!il li ! i! !i! i!i! i!i!i!i i~l!i!i!
IUl'PLEMENTAL llEl'OllT l!XPECTID 11'1                                                                               MONTH           DAY                 V~AR EXPECTED
                                                                                        ~NO SUllMISSIDN I       YES,,, I'll. - - EXl'ECTED :SVIMISSION DATE}
DATE 11111 I                I                   I AalTllACT (Limit ID 1400 -
* I.&, _.,.1mno1y , , _     r1,.,,,..,,... ry,.,..,,mn llnmJ 1111 On 11/13/87 an NRC inspector identified leakage paths from the No. 13 Auxiliary Feedwater (AFW) Turbine .Driven Pump compartment {BAI.
Subsequent investigation revealed six (6) unsealed openings from the Unit 1 pump and one unsealed opening from the Unit 2 pump. The compartment encloses the steam feed piping to the AFW Turbine Driven Pump such that a postulated pipe break would not damage adjacent vital electrical equipment located outside the compartment. The root cause of the Steam Driven AFW Pump compartment deficiencies has been attributed to control of design requirements.                                                                       The leakage paths identified on the Salem Units 1 & 2 Steam Driven AFW Pump enclosures have been sealed. A review of other protective pipe rupture enclosures, to verify their integrity has been maintained, is continuing. To ensure that adequate attention is given to the maintenance of these structures in the future, the Program Analysis .c Group (PAG) will issue a Field Directive identifying the areas that-:
are designed to accommodate the effects of a pipe rupture.                                                                                              Based on the Field Directive, administrative controls to maintain protective structures in a condition that meets their design requirements will be reviewed and changes made as necessary.
8802090450 880126 PDR ADOCK 05000272 s                                    PDR
 
LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem-Generating Station        DOCKET NUMBER      LER NUMBER        PAGE Unit 1                            5000272          87-017-02        2 of 4 PLANT AND SYSTEM IDENTIFICATION:
Westinghouse  - Pressurized Water Reactor Energy Industry Identification System (EIIS) codes are identified in the text as f xxl IDENTIFICATION OF OCCURRENCE:
Discovered Leakage Paths From 13(23) Aux Feedwater Pump Compartment -
Control of Design Requirements Event Date:  11/13/87 Report Date: 01/26/88 This report was initiated by Incident Report No. 87-449.
CONDITIONS PRIOR TO OCCURRENCE:
Mode 6  Reactor Power    0% - Unit Load 0 MWe DESCRIPTION OF OCCURRENCE:
On 11/13/87 an NRC inspector identified leakage paths from the No. 13 Auxiliary Feedwater (AFW) Turbine Driven Pump compartment [BA} .
Subsequent investigation revealed six (6) leakage pathways from the Unit 1 pump compartment . and one pa.thway from the Unit 2 pump compartment. The compartment encloses the steam feed piping to the AFW Turbine Driven Pump such that a postulated pipe break would not damage adjacent vital electrical equipment located outside the compartment.
The Unit 1 pump compartment pathways consist of four (4) pipe penetrations where excessive annulus areas exist between the pipe and the compartment wall, one (1) hole cut to accommodate a protruding bolt~ and one (1) small hole cut through the steel compartment wall for no known reason. The Unit 2 pump compartment pathway is a pipe
    *penetration with an excessive annulus area between the pipe*and wall.
-APPARENT CAUSE OF OCCURRENCE:
The root cause of the Steam Driven AFW Pump compartment deficiencies is associated with control of design requirements.    "Notes" on the AFW Pump enclosure controlled drawings (bot~ Units) state that the compartment structure is designed for an internal pressure of 50 pounds per square foot (psf). Also, the drawing "Notes" indicate that gaps and cracks in the structure should be minimized during erection and plugged as required to ensure a reasonable degree of watertightness.
It cannot be conclusively determined what activities took place that resulted in these leakage paths whether from the original design configuration or as the result of design modifications.
 
DOCKET NUMBER LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem*Generating Station                        LER NUMBER      PAGE Unit 1                          5000272        87-017-02      3 of 4*
The Salem Unit 1 AFW Pump compartment was analyzed due to the greater open area than the Unit 2 AFW Pump enclosure. The total unsealed area for the Unit 1 and Unit 2 compartments was approximately 20 square inches and four square inches, respectively. The AFW Pump enclosure is designed to contain the steam release from a postulated steam pipe rupture such that adjacent vital electrical equipment is not damaged.
In the* event of a postulated pump steam supply line rupture (high energy line break} within the compartment, the compartment temperature and pressure would rise. At 0. 33 psi, exhaust dampers will op*en to vent steam into the adjacent Auxiliary Building pipe alley. The total effective free flow area provided by the dampers is 1265 in2
* The unsealed openings represented an increase in the available exhaust area of 1.6%. The total steam discharge rate from a *postulated break is 11.0 lb.ls of steam at an initial pressure.of 1020 psia, 547°F.
The amount of steam discharged.to the adjacent area of the enclose through the unsealed openings is 1.6% of 11.0 lb.ls which equals 0.17 lb./s. This will be an adiabatic expansion into the area at slightly less than atmosperic pressure. This process will reduce the temperature of t_he exiting steam to 300° F. The specific volume of steam.at these conditions (14.7 psia and 300°F) and a mass flow rate of O.i7 lb.ls will result in 300 cfm of steam exhausted into the area. Steam with a molecular weight of 18 will rise to the. ceiling.
The ceiling area has ventilation exhaust ducts with an exhaust
* capacity of 500 cfm. Therefore, the steam will be exhausted, via the Auxiliary Building Ventilation System, and will* not accumulate in the adjacent area. The operability of equipment adjacent to the enclosure will not be compromised by the steam release.
The adjacent area contains the 11(21) and 12(22) Motor Driven AFW Pumps,. various AFW valves, Main Steam System valves (Unit 2 only), the 1(2)A and 1(2}C West 230 V Vital Motor Control Centers (MCCs); and various electrical panels, including the Alternate Shutdown Panel (Panel 213). This equipment will remain operable during the postulated steam release.
The 230 V MCCs provide power and control to a variety of Emergency Core Cooling System (ECCS) valves, including one Residual Heat Removal (RHR) Pump Minimum Flow Valve (11RH29) (BPI, the Safety Injection Pump Minimum Flow Valves (SJ67 & 68), an RHR Loop Crosstie Valve (11RH19),
one suction valve from the Reactor Water Storage Tank to the Charging Pumps (lSJl),_ a Containment Sump Isolation Valve (11SJ44), and Component Cooling Water discharge valve from the RHR Heat Exchanger (11CC16).
Since an ECCS actuation is not expected to occur as a result of the postulated break, these ECCS valves would not be required to operate.
Also, since a fire is not postulated coincident with a pipe break, the Alternate Shutdown Panel would not be required. However, in the event of a break in the steam supply line to the AFW Turbine Driven Pump, the Motor Driven AFW Pumps and valves would be required to operate
 
LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem Generating Station          DOCKET NUMBER        LER NUMBER      PAGE u*n.i t 1                          5000272            87-017-02      4 of 4 ANALYS.LS OF    OCCURRENCE~  (cont'd)
                          -~~~~~
during normai plant cooldown to remove heat from the core until the RHR System could be placed in operation.
In summary, the equipment adjacent to the Steam Driven AFW Pump are necessary to normal plant operation as well as mitigation of design base accidents. They are required to be protected against the dynamic effects of a postulated pipe rupture. As discussed above, the operability of equipment adjacent to the Steam Driven AFW Pump compartment would not have been effected by a postulated steam supply line break.
_CORREC'IIVE _ACTION:
The leakage paths identified on the Salem Units 1 & 2 Steam Driven AFW Pump enclosures have been sealed. A review of other protective pipe rupture enclosures, to verify their integrity has been maintained, is continuing.
The leakage paths identified on the Salem Units 1 & 2 Steam Driven AFW Pump enclosures have been sealed. A review of other protective pipe rupture enclosures, to verify their integrity has been maintained, is continuing.
To ensure that adequate attention is given to the maintenance of these structures in the future, the Program Analysis .c Group (PAG) will issue a Field Directive identifying the areas that-: are designed to accommodate the effects of a pipe rupture. Based on the Field Directive, administrative controls to maintain protective structures in a condition that meets their design requirements will be reviewed and changes made as necessary.
8802090450 880126 PDR ADOCK 05000272 s PDR I LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem-Generating Station Unit 1 DOCKET NUMBER 5000272 PLANT AND SYSTEM IDENTIFICATION:
Westinghouse
-Pressurized Water Reactor LER NUMBER 87-017-02 PAGE 2 of 4 Energy Industry Identification System (EIIS) codes are identified in the text as f xxl IDENTIFICATION OF OCCURRENCE:
Discovered Leakage Paths From 13(23) Aux Feedwater Pump Compartment
-Control of Design Requirements Event Date: 11/13/87 Report Date: 01/26/88 This report was initiated by Incident Report No. 87-449. CONDITIONS PRIOR TO OCCURRENCE:
Mode 6 Reactor Power 0% -Unit Load 0 MWe DESCRIPTION OF OCCURRENCE:
On 11/13/87 an NRC inspector identified leakage paths from the No. 13 Auxiliary Feedwater (AFW) Turbine Driven Pump compartment
[BA} . Subsequent investigation revealed six (6) leakage pathways from the Unit 1 pump compartment . and one pa.thway from the Unit 2 pump compartment.
The compartment encloses the steam feed piping to the AFW Turbine Driven Pump such that a postulated pipe break would not damage adjacent vital electrical equipment located outside the compartment.
The Unit 1 pump compartment pathways consist of four (4) pipe penetrations where excessive annulus areas exist between the pipe and the compartment wall, one (1) hole cut to accommodate a protruding and one (1) small hole cut through the steel compartment wall for no known reason. The Unit 2 pump compartment pathway is a pipe *penetration with an excessive annulus area between the pipe*and wall. -APPARENT CAUSE OF OCCURRENCE:
The root cause of the Steam Driven AFW Pump compartment deficiencies is associated with control of design requirements. "Notes" on the AFW Pump enclosure controlled drawings Units) state that the compartment structure is designed for an internal pressure of 50 pounds per square foot (psf). Also, the drawing "Notes" indicate that gaps and cracks in the structure should be minimized during erection and plugged as required to ensure a reasonable degree of watertightness.
It cannot be conclusively determined what activities took place that resulted in these leakage paths whether from the original design configuration or as the result of design modifications.
* LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem*Generating Station Unit 1 DOCKET NUMBER 5000272 LER NUMBER 87-017-02 PAGE 3 of 4* The Salem Unit 1 AFW Pump compartment was analyzed due to the greater open area than the Unit 2 AFW Pump enclosure.
The total unsealed area for the Unit 1 and Unit 2 compartments was approximately 20 square inches and four square inches, respectively.
The AFW Pump enclosure is designed to contain the steam release from a postulated steam pipe rupture such that adjacent vital electrical equipment is not damaged. In the* event of a postulated pump steam supply line rupture (high energy line break} within the compartment, the compartment temperature and pressure would rise. At 0. 33 psi, exhaust dampers will op*en to vent steam into the adjacent Auxiliary Building pipe alley. The total effective free flow area provided by the dampers is 1265 in 2
* The unsealed openings represented an increase in the available exhaust area of 1.6%. The total steam discharge rate from a *postulated break is 11.0 lb.ls of steam at an initial pressure.of 1020 psia, 547°F. The amount of steam discharged.to the adjacent area of the enclose through the unsealed openings is 1.6% of 11.0 lb.ls which equals 0.17 lb./s. This will be an adiabatic expansion into the area at slightly less than atmosperic pressure.
This process will reduce the temperature of t_he exiting steam to 300° F. The specific volume of steam.at these conditions (14.7 psia and 300°F) and a mass flow rate of O.i7 lb.ls will result in 300 cfm of steam exhausted into the area. Steam with a molecular weight of 18 will rise to the. ceiling. The ceiling area has ventilation exhaust ducts with an exhaust
* capacity of 500 cfm. Therefore, the steam will be exhausted, via the Auxiliary Building Ventilation System, and will* not accumulate in the adjacent area. The operability of equipment adjacent to the enclosure will not be compromised by the steam release. The adjacent area contains the 11(21) and 12(22) Motor Driven AFW Pumps,. various AFW valves, Main Steam System valves (Unit 2 only), the 1(2)A and 1(2}C West 230 V Vital Motor Control Centers (MCCs); and various electrical panels, including the Alternate Shutdown Panel (Panel 213). This equipment will remain operable during the postulated steam release. The 230 V MCCs provide power and control to a variety of Emergency Core Cooling System (ECCS) valves, including one Residual Heat Removal (RHR) Pump Minimum Flow Valve (11RH29) (BPI, the Safety Injection Pump Minimum Flow Valves (SJ67 & 68), an RHR Loop Crosstie Valve (11RH19), one suction valve from the Reactor Water Storage Tank to the Charging Pumps (lSJl),_ a Containment Sump Isolation Valve (11SJ44), and Component Cooling Water discharge valve from the RHR Heat Exchanger (11CC16).
Since an ECCS actuation is not expected to occur as a result of the postulated break, these ECCS valves would not be required to operate. Also, since a fire is not postulated coincident with a pipe break, the Alternate Shutdown Panel would not be required.
However, in the event of a break in the steam supply line to the AFW Turbine Driven Pump, the Motor Driven AFW Pumps and valves would be required to operate LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem Generating Station u*n.i t 1 DOCKET NUMBER 5000272 ANALYS.LS OF (cont'd)
LER NUMBER 87-017-02 PAGE 4 of 4 during normai plant cooldown to remove heat from the core until the RHR System could be placed in operation.
In summary, the equipment adjacent to the Steam Driven AFW Pump are necessary to normal plant operation as well as mitigation of design base accidents.
They are required to be protected against the dynamic effects of a postulated pipe rupture. As discussed above, the operability of equipment adjacent to the Steam Driven AFW Pump compartment would not have been effected by a postulated steam supply line break. _CORREC'IIVE
_ACTION: The leakage paths identified on the Salem Units 1 & 2 Steam Driven AFW Pump enclosures have been sealed. A review of other protective pipe rupture enclosures, to verify their integrity has been maintained, is continuing.
To ensure that adequate attention is given to the maintenance of these structures in the future, the Program Analysis Group (PAG) will issue a Field Directive (by February 16, 1988) identifying the areas that are.designed to accommodate the effects of a pipe rupture. Based on the Field Directive, administrative controls to maintain protective structures in a condition that meets their design requirements will be reviewed and changes made as necessary.
To ensure that adequate attention is given to the maintenance of these structures in the future, the Program Analysis Group (PAG) will issue a Field Directive (by February 16, 1988) identifying the areas that are.designed to accommodate the effects of a pipe rupture. Based on the Field Directive, administrative controls to maintain protective structures in a condition that meets their design requirements will be reviewed and changes made as necessary.
i1Jl-':pc SORC Mtg. 88-009 (]AA 9 Salerr, Operation!':}}
G~~~~er ~
(]AA          9 Salerr, Operation!':
i1Jl-':pc SORC Mtg. 88-009}}

Latest revision as of 07:46, 3 February 2020

LER 87-017-02:on 871113,six Leakage Pathways from Unit 1 Auxiliary Feedwater Pump Compartment 13 & One Pathway from Unit 2 Identified.Caused by Control of Design Requirements. Leakage Paths Sealed & Field Directive Will Be Issued
ML18093A625
Person / Time
Site: Salem PSEG icon.png
Issue date: 01/26/1988
From: Pollack M
Public Service Enterprise Group
To:
Shared Package
ML18093A627 List:
References
LER-87-017, LER-87-17, NUDOCS 8802090450
Download: ML18093A625 (4)


Text

..

iillC forMJll U.1, NUCLIAll llEOULATOllY c:a..i*ION IM:IJ

-OVID OMI NO. 3110-41CM EX,.llES: 1131

  • LICENSEE EVENT REPORT (LEA) '

DOCKIT Maalll 121 I r-~* ,..,

I PACILITY NAMI 111 Salem Generating Station - Unit 1 o 15 IO IO Io I 21 71 211 loF 0 14 TITLI 1'1 Disc. Leak Paths From 13(23)AFW Pump Compartments - Control of Design Reqt IVINT CATI 1111 L!llN~llllll lllPOllT CATI 171 OTHlll PACIUTlll INVOLVID Ill MONTH QAY YEAR YEAR lt u:;:;~~~~AL tt :~"1~ MONTH DAY YEAR FACILITY NAMU DOCltET NUMIERISI Salem Unit 2 o 1s Io I o I o t3 11 11 l I 1 ll 3 s 1s 11- - o I 1 I1 - oI 2 oI 12 16

  • s 1s THll llll'OllT 11 IUIMITTID l'UlllUANT TO THI lllQUllllMINTI OP 10 CPll §: (o-lt - °',,,,.,.of IN followlnf) 1111 Ol'lllATINO MODI Ill I

t----...---.._+--i l'OWlll L~1L 6 20.40211tl 20......111,111 i--

i--

20.4Gl(ol 10.al1IC11 I0.'7311112111*1

  • .nc.11211*1 -::R 71.7111tl 7:1.71111 01 01 Q - 20.4Glloll111MI

...... eo.:.101121 110.n1e11211w111 OTHlll (Spclfy In Ab_,

~-er.!!'" Te:r, NflC f'r;;m

-- 6'1.731eli.illll 90.731elf2JUll -- 1111.n1e11211w1111w IG.711811211111111111

~

Info Only I0.731ell2111111 ll0.7Jlell21f*I LICENIH CONTACT FOii THll LEll lt:lll NAME TELEPHONE NUMll!ll AREA COD!

M. J. Pollack - LER Coordinator 61 0 I 9 31 31 9r 14 10 12 12 COMl'LITI ONE LINI FOii EACH COMPONENT PAILUlll DEIClllllD IN THll llll'OllT 11'1 CAUSE SYSTEM COMPONENT MANUFAC. SYSTEM MANUFAC.

TUR ER COMl'ONENT TUR ER I I I I I I I I I I I I I I I I I I I I I I I I I I I I l!l li!i!l i!il li ! i! !i! i!i! i!i!i!i i~l!i!i!

IUl'PLEMENTAL llEl'OllT l!XPECTID 11'1 MONTH DAY V~AR EXPECTED

~NO SUllMISSIDN I YES,,, I'll. - - EXl'ECTED :SVIMISSION DATE}

DATE 11111 I I I AalTllACT (Limit ID 1400 -

  • I.&, _.,.1mno1y , , _ r1,.,,,..,,... ry,.,..,,mn llnmJ 1111 On 11/13/87 an NRC inspector identified leakage paths from the No. 13 Auxiliary Feedwater (AFW) Turbine .Driven Pump compartment {BAI.

Subsequent investigation revealed six (6) unsealed openings from the Unit 1 pump and one unsealed opening from the Unit 2 pump. The compartment encloses the steam feed piping to the AFW Turbine Driven Pump such that a postulated pipe break would not damage adjacent vital electrical equipment located outside the compartment. The root cause of the Steam Driven AFW Pump compartment deficiencies has been attributed to control of design requirements. The leakage paths identified on the Salem Units 1 & 2 Steam Driven AFW Pump enclosures have been sealed. A review of other protective pipe rupture enclosures, to verify their integrity has been maintained, is continuing. To ensure that adequate attention is given to the maintenance of these structures in the future, the Program Analysis .c Group (PAG) will issue a Field Directive identifying the areas that-:

are designed to accommodate the effects of a pipe rupture. Based on the Field Directive, administrative controls to maintain protective structures in a condition that meets their design requirements will be reviewed and changes made as necessary.

8802090450 880126 PDR ADOCK 05000272 s PDR

LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem-Generating Station DOCKET NUMBER LER NUMBER PAGE Unit 1 5000272 87-017-02 2 of 4 PLANT AND SYSTEM IDENTIFICATION:

Westinghouse - Pressurized Water Reactor Energy Industry Identification System (EIIS) codes are identified in the text as f xxl IDENTIFICATION OF OCCURRENCE:

Discovered Leakage Paths From 13(23) Aux Feedwater Pump Compartment -

Control of Design Requirements Event Date: 11/13/87 Report Date: 01/26/88 This report was initiated by Incident Report No.87-449.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 6 Reactor Power 0% - Unit Load 0 MWe DESCRIPTION OF OCCURRENCE:

On 11/13/87 an NRC inspector identified leakage paths from the No. 13 Auxiliary Feedwater (AFW) Turbine Driven Pump compartment [BA} .

Subsequent investigation revealed six (6) leakage pathways from the Unit 1 pump compartment . and one pa.thway from the Unit 2 pump compartment. The compartment encloses the steam feed piping to the AFW Turbine Driven Pump such that a postulated pipe break would not damage adjacent vital electrical equipment located outside the compartment.

The Unit 1 pump compartment pathways consist of four (4) pipe penetrations where excessive annulus areas exist between the pipe and the compartment wall, one (1) hole cut to accommodate a protruding bolt~ and one (1) small hole cut through the steel compartment wall for no known reason. The Unit 2 pump compartment pathway is a pipe

  • penetration with an excessive annulus area between the pipe*and wall.

-APPARENT CAUSE OF OCCURRENCE:

The root cause of the Steam Driven AFW Pump compartment deficiencies is associated with control of design requirements. "Notes" on the AFW Pump enclosure controlled drawings (bot~ Units) state that the compartment structure is designed for an internal pressure of 50 pounds per square foot (psf). Also, the drawing "Notes" indicate that gaps and cracks in the structure should be minimized during erection and plugged as required to ensure a reasonable degree of watertightness.

It cannot be conclusively determined what activities took place that resulted in these leakage paths whether from the original design configuration or as the result of design modifications.

DOCKET NUMBER LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem*Generating Station LER NUMBER PAGE Unit 1 5000272 87-017-02 3 of 4*

The Salem Unit 1 AFW Pump compartment was analyzed due to the greater open area than the Unit 2 AFW Pump enclosure. The total unsealed area for the Unit 1 and Unit 2 compartments was approximately 20 square inches and four square inches, respectively. The AFW Pump enclosure is designed to contain the steam release from a postulated steam pipe rupture such that adjacent vital electrical equipment is not damaged.

In the* event of a postulated pump steam supply line rupture (high energy line break} within the compartment, the compartment temperature and pressure would rise. At 0. 33 psi, exhaust dampers will op*en to vent steam into the adjacent Auxiliary Building pipe alley. The total effective free flow area provided by the dampers is 1265 in2

  • The unsealed openings represented an increase in the available exhaust area of 1.6%. The total steam discharge rate from a *postulated break is 11.0 lb.ls of steam at an initial pressure.of 1020 psia, 547°F.

The amount of steam discharged.to the adjacent area of the enclose through the unsealed openings is 1.6% of 11.0 lb.ls which equals 0.17 lb./s. This will be an adiabatic expansion into the area at slightly less than atmosperic pressure. This process will reduce the temperature of t_he exiting steam to 300° F. The specific volume of steam.at these conditions (14.7 psia and 300°F) and a mass flow rate of O.i7 lb.ls will result in 300 cfm of steam exhausted into the area. Steam with a molecular weight of 18 will rise to the. ceiling.

The ceiling area has ventilation exhaust ducts with an exhaust

  • capacity of 500 cfm. Therefore, the steam will be exhausted, via the Auxiliary Building Ventilation System, and will* not accumulate in the adjacent area. The operability of equipment adjacent to the enclosure will not be compromised by the steam release.

The adjacent area contains the 11(21) and 12(22) Motor Driven AFW Pumps,. various AFW valves, Main Steam System valves (Unit 2 only), the 1(2)A and 1(2}C West 230 V Vital Motor Control Centers (MCCs); and various electrical panels, including the Alternate Shutdown Panel (Panel 213). This equipment will remain operable during the postulated steam release.

The 230 V MCCs provide power and control to a variety of Emergency Core Cooling System (ECCS) valves, including one Residual Heat Removal (RHR) Pump Minimum Flow Valve (11RH29) (BPI, the Safety Injection Pump Minimum Flow Valves (SJ67 & 68), an RHR Loop Crosstie Valve (11RH19),

one suction valve from the Reactor Water Storage Tank to the Charging Pumps (lSJl),_ a Containment Sump Isolation Valve (11SJ44), and Component Cooling Water discharge valve from the RHR Heat Exchanger (11CC16).

Since an ECCS actuation is not expected to occur as a result of the postulated break, these ECCS valves would not be required to operate.

Also, since a fire is not postulated coincident with a pipe break, the Alternate Shutdown Panel would not be required. However, in the event of a break in the steam supply line to the AFW Turbine Driven Pump, the Motor Driven AFW Pumps and valves would be required to operate

LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem Generating Station DOCKET NUMBER LER NUMBER PAGE u*n.i t 1 5000272 87-017-02 4 of 4 ANALYS.LS OF OCCURRENCE~ (cont'd)

-~~~~~

during normai plant cooldown to remove heat from the core until the RHR System could be placed in operation.

In summary, the equipment adjacent to the Steam Driven AFW Pump are necessary to normal plant operation as well as mitigation of design base accidents. They are required to be protected against the dynamic effects of a postulated pipe rupture. As discussed above, the operability of equipment adjacent to the Steam Driven AFW Pump compartment would not have been effected by a postulated steam supply line break.

_CORREC'IIVE _ACTION:

The leakage paths identified on the Salem Units 1 & 2 Steam Driven AFW Pump enclosures have been sealed. A review of other protective pipe rupture enclosures, to verify their integrity has been maintained, is continuing.

To ensure that adequate attention is given to the maintenance of these structures in the future, the Program Analysis Group (PAG) will issue a Field Directive (by February 16, 1988) identifying the areas that are.designed to accommodate the effects of a pipe rupture. Based on the Field Directive, administrative controls to maintain protective structures in a condition that meets their design requirements will be reviewed and changes made as necessary.

G~~~~er ~

(]AA 9 Salerr, Operation!':

i1Jl-':pc SORC Mtg.88-009