| issue date = 01/21/2004 | | issue date = 01/21/2004 | ||
| title = Auxiliary Feedwater Pump Recirculation Line Orifice Fouling - Potential Common Cause Failure | | title = Auxiliary Feedwater Pump Recirculation Line Orifice Fouling - Potential Common Cause Failure | ||
| author name = Beckner W | | author name = Beckner W | ||
| author affiliation = NRC/NRR/DIPM | | author affiliation = NRC/NRR/DIPM | ||
| addressee name = | | addressee name = | ||
Line 9: | Line 9: | ||
| docket = 05000266, 05000301 | | docket = 05000266, 05000301 | ||
| license number = DPR-024 | | license number = DPR-024 | ||
| contact person = Dozier J | | contact person = Dozier J, NRR/IROB 415-1014 | ||
| document report number = IN-04-001 | | document report number = IN-04-001 | ||
| document type = NRC Information Notice | | document type = NRC Information Notice | ||
| page count = 9 | | page count = 9 | ||
}} | }} | ||
{{#Wiki_filter:UNITED | {{#Wiki_filter:UNITED STATES | ||
NUCLEAR REGULATORY COMMISSION | |||
OFFICE OF NUCLEAR REACTOR REGULATION | |||
WASHINGTON, D.C. 20555 January 21, 2004 NRC INFORMATION NOTICE 2004-01: AUXILIARY FEEDWATER PUMP | |||
RECIRCULATION LINE ORIFICE FOULING - | |||
POTENTIAL COMMON CAUSE FAILURE | |||
==Addressees== | ==Addressees== | ||
:All holders of operating licenses or construction permits for nuclear power reactors, | : | ||
All holders of operating licenses or construction permits for nuclear power reactors, except | |||
those that have permanently ceased operations and have certified that fuel has been | |||
permanently removed from the reactor. | permanently removed from the reactor. | ||
==Purpose== | ==Purpose== | ||
:The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice to | : | ||
The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice to inform | |||
addressees of the potential common cause failure of auxiliary feedwater pumps because of | |||
fouling of pump recirculation line flow orifices. | fouling of pump recirculation line flow orifices. It is expected that recipients will review the | ||
information for applicability to their facilities and consider actions, as appropriate, to avoid | information for applicability to their facilities and consider actions, as appropriate, to avoid | ||
similar problems. However, suggestions in this information notice are not NRC requirements; | similar problems. However, suggestions in this information notice are not NRC requirements; | ||
therefore no specific action or written response is required.Background:Point Beach Nuclear Plant (PBNP) is a two unit site. | therefore no specific action or written response is required. | ||
Background: | |||
Point Beach Nuclear Plant (PBNP) is a two unit site. Each unit has a turbine-driven AFW pump | |||
(pumps 1P29 and 2P29) which can supply water to both steam generators. Additionally, the | |||
plant has two motor-driven AFW pumps (pumps P38A and P38B) each of which can be aligned | plant has two motor-driven AFW pumps (pumps P38A and P38B) each of which can be aligned | ||
to a steam generator in each unit. | to a steam generator in each unit. Each pump has a recirculation line back to the condensate | ||
storage tanks (CSTs) to ensure minimum flow to prevent hydraulic instabilities and dissipate | storage tanks (CSTs) to ensure minimum flow to prevent hydraulic instabilities and dissipate | ||
pump heat. | pump heat. The recirculation line contained a pressure reducing, flow restricting orifice. An | ||
arrow is pointing to the recirculation flow restricting orifice (RO) in the major flow path AFW | arrow is pointing to the recirculation flow restricting orifice (RO) in the major flow path AFW | ||
diagram provided in Figure 1 and a picture of the RO is provided in Figure 2. | diagram provided in Figure 1 and a picture of the RO is provided in Figure 2. | ||
The RO used a multi-stage, anti-cavitation trim package installed in the body of a globe valve to | |||
limit flow. This style of orifice or flow restrictor was installed in the AFW recirculation lines at | |||
PBNP in the past few years to eliminate cavitation caused by the old orifices. | PBNP in the past few years to eliminate cavitation caused by the old orifices. This type of flow | ||
restrictor used very small channels and holes in each stage combined with a tortuous path to | restrictor used very small channels and holes in each stage combined with a tortuous path to | ||
limit flow and prevent cavitation. Figure 1. | limit flow and prevent cavitation. | ||
Figure 1. AFW System - Major Flow Paths | |||
Figure 2. Recirculation Flow Restricting Orifice | |||
==Description of Circumstances== | ==Description of Circumstances== | ||
:On October 24, 2002, during post-maintenance surveillance testing of the P38A motor- | : | ||
On October 24, 2002, during post-maintenance surveillance testing of the P38A motor-driven | |||
AFW pump at PBNP, the licensee observed AFW recirculation line flow to be 64.5 gpm, which | |||
was less than the 70 gpm acceptance criterion. Normal flow through the recirculation line was | |||
75 gpm. Suspecting instrument error, plant personnel vented and recalibrated the flow | |||
was | instrument. The P38A AFW pump was then started and tested again; however, the observed | ||
recirculation flow was essentially unchanged. Following that test run, the recirculation flow | |||
orifice was removed and inspected. | |||
After removal of the orifice internals, partial blockage was observed in 24 of the 54 holes in the | |||
outermost sleeve. No particles were found on any of the inner sleeves. Samples of the | |||
particles removed from the orifice were retained for analysis. | particles removed from the orifice were retained for analysis. A boroscope inspection of the | ||
recirculation piping at the orifice location revealed no evidence of debris. | recirculation piping at the orifice location revealed no evidence of debris. Following cleaning | ||
and reassembly, the orifice was reinstalled and the P38A AFW pump was successfully retested. | and reassembly, the orifice was reinstalled and the P38A AFW pump was successfully retested. | ||
Line 72: | Line 105: | ||
Testing was successfully completed on the other three AFW pumps to verify acceptable | Testing was successfully completed on the other three AFW pumps to verify acceptable | ||
recirculation flow by October 25, 2002.During the next several days, PBNP personnel evaluated the implications of the orifice | recirculation flow by October 25, 2002. | ||
During the next several days, PBNP personnel evaluated the implications of the orifice plugging | |||
event. An apparent cause evaluation was initiated with specific directions to assess and | |||
evaluate the potential extent of condition. | evaluate the potential extent of condition. An action plan was developed to identify the source | ||
of the debris found in the orifice and to determine what other testing or flushing would be | of the debris found in the orifice and to determine what other testing or flushing would be | ||
required to assure that future plugging did not occur. As the investigations continued, questions developed concerning the operability of the | required to assure that future plugging did not occur. | ||
As the investigations continued, questions developed concerning the operability of the AFW | |||
system while supplied by its safety-related water supply, the service water (SW) system. | |||
Although the service water supply was provided through a basket strainer, it was recognized | Although the service water supply was provided through a basket strainer, it was recognized | ||
Line 84: | Line 125: | ||
that the strainer mesh was larger than the much finer RO channel holes and could allow debris | that the strainer mesh was larger than the much finer RO channel holes and could allow debris | ||
to pass that could clog the RO. | to pass that could clog the RO. These concerns culminated in a meeting on October 29, 2002, at which PBNP personnel concluded that there was no longer a reasonable assurance that | ||
operation of the AFW system using its safety-related suction source of service water would not | operation of the AFW system using its safety-related suction source of service water would not | ||
result in potential AFW recirculation line orifice clogging.In a worst case scenario, Point Beach personnel determined that it may be possible, | result in potential AFW recirculation line orifice clogging. | ||
In a worst case scenario, Point Beach personnel determined that it may be possible, although | |||
unlikely, for each of the four flow control orifices, each associated with one of the four AFW | |||
pumps, to restrict the flow through the associated recirculation line. | pumps, to restrict the flow through the associated recirculation line. Under such conditions, it | ||
was hypothesized that if the discharge valves for the AFW pumps were throttled, adequate flow | was hypothesized that if the discharge valves for the AFW pumps were throttled, adequate flow | ||
Line 96: | Line 141: | ||
might be unavailable through the recirculation line and pump damage could occur due to | might be unavailable through the recirculation line and pump damage could occur due to | ||
overheating.On October 29, 2002, all four AFW pumps were declared inoperable. | overheating. | ||
On October 29, 2002, all four AFW pumps were declared inoperable. Both units entered their | |||
technical specification action statements and required actions which directs immediate action to | |||
restore an AFW system to operable status. | restore an AFW system to operable status. Immediate corrective actions consisted of briefing | ||
the on-shift crew of the potential consequences of restricted recirculation flow and initiating | the on-shift crew of the potential consequences of restricted recirculation flow and initiating | ||
procedure changes. | procedure changes. The operators were also directed to secure a running AFW pump if the | ||
pump discharge flows should be decreased to less than 50 gpm for the motor-driven pumps or | pump discharge flows should be decreased to less than 50 gpm for the motor-driven pumps or | ||
75 gpm for the turbine-driven pumps. | 75 gpm for the turbine-driven pumps. These flow rates were substantially above the point at | ||
which pump damage could occur. Information tags were placed at the AFW pump flow | which pump damage could occur. Information tags were placed at the AFW pump flow | ||
indicators on the main control boards to convey that information. | indicators on the main control boards to convey that information. With these administrative | ||
controls in place, operations declared the AFW system operable, about four hours after the pumps had been declared inoperable. An incident investigation was initiated to collect and | |||
confirm the facts of this event description beginning with the discovery of the P-38A AFW pump | |||
degraded recirculation flow during post-maintenance testing and concluding with the decision to | degraded recirculation flow during post-maintenance testing and concluding with the decision to | ||
declare the AFW system inoperable.In accordance with 10 CFR 50.72(b)(3)(v), an eight-hour ENS notification (EN #39330) | declare the AFW system inoperable. | ||
In accordance with 10 CFR 50.72(b)(3)(v), an eight-hour ENS notification (EN #39330) was | |||
made on October 29, 2002. The LER is available in ADAMS (Accession Number | |||
ML032890115). | |||
A PBNP multi-discipline event resolution team was formed to identify and resolve the issues | |||
associated with the discovery of this condition. Activities included initiation of a root cause | |||
evaluation (RCE) to determine the root and contributing causes for the postulated | evaluation (RCE) to determine the root and contributing causes for the postulated | ||
Line 124: | Line 183: | ||
common-mode failure that would render all AFW pump recirculation lines with restricted | common-mode failure that would render all AFW pump recirculation lines with restricted | ||
flow rates. | flow rates. The RCE concluded that this event had a direct root cause and an organizational | ||
root cause. | root cause. The direct root cause was the failure by design engineering to properly evaluate | ||
the potential for orifice plugging within the design process. | the potential for orifice plugging within the design process. Instead of revisiting the design for | ||
adequacy and evaluating the potential for plugging of the proposed orifices within the rigor of | adequacy and evaluating the potential for plugging of the proposed orifices within the rigor of | ||
Line 134: | Line 193: | ||
the design process, the 10 CFR 50.59 safety evaluation was revised to justify the proposed | the design process, the 10 CFR 50.59 safety evaluation was revised to justify the proposed | ||
design. | design. The organizational root cause was less than adequate management oversight of the | ||
design modification process. | |||
Also, in January and February 2003, a specially fabricated orifice was tested at a contractor | |||
laboratory in an effort to determine a plugging probability with service water. Definitive testing | |||
occurred on February 21 when a debris mixture of sand, silt, and zebra mussel shells, representative of what would exist in the Point Beach SW system, was injected into a closed | occurred on February 21 when a debris mixture of sand, silt, and zebra mussel shells, representative of what would exist in the Point Beach SW system, was injected into a closed | ||
loop configuration of piping, an orifice, and a centrifugal pump. | loop configuration of piping, an orifice, and a centrifugal pump. The orifice plugged in much | ||
less than one minute after the mixture was injected into the loop. | less than one minute after the mixture was injected into the loop. These results were contrary | ||
to those of a previously performed computational particle fouling model analysis that indicated | to those of a previously performed computational particle fouling model analysis that indicated | ||
Line 150: | Line 213: | ||
shear forces in the holes and channels of the orifices developed with the minimum flow required | shear forces in the holes and channels of the orifices developed with the minimum flow required | ||
through the orifice for pump cooling. | through the orifice for pump cooling. | ||
Discussion: | |||
A special inspection was conducted by the NRC to evaluate the facts, circumstances, and | |||
licensee actions, and documented in NRC Inspection Report 50-266/02-15 and 50-301/02-15 (Accession Number ML030920128). This issue was determined to be of Yellow risk | |||
significance for Unit 1, an issue with substantial importance to safety, and Red risk significance | significance for Unit 1, an issue with substantial importance to safety, and Red risk significance | ||
for Unit 2, an issue of high importance to safety. | for Unit 2, an issue of high importance to safety. The difference in significance between the | ||
Units was a result of the longer period of time that the AFW recirculation line pressure reduction | Units was a result of the longer period of time that the AFW recirculation line pressure reduction | ||
orifices were installed in Unit 2. | orifices were installed in Unit 2. (See Final Determination Letter, dated December 11, 2003, Accession Number ML033490022). This information notice requires no specific action or written response. If you have any | ||
questions regarding the information notice, please contact the technical contacts listed below or | |||
the appropriate Office of Nuclear Reactor Regulation (NRR) project manager. | |||
/Original signed by: Terrence Reis/ | |||
William D. Beckner, Chief | |||
Reactor Operations Branch | |||
Division of Inspection Program Management | Division of Inspection Program Management | ||
Office of Nuclear Reactor | Office of Nuclear Reactor Regulation | ||
Technical contacts: Jerry Dozier, NRR Paul Krohn, Region III | |||
(301) 415-1014 (920) 755-2309 E-mail: jxd@nrc.gov E-mail: pgk1@nrc.gov | |||
Attachment: List of Recently Issued NRC Information Notices This information notice requires no specific action or written response. If you have any | |||
questions regarding the information notice, please contact the technical contacts listed below or | |||
the appropriate Office of Nuclear Reactor Regulation (NRR) project manager. | |||
/Original signed by: Terrence Reis/ | |||
William D. Beckner, Chief | |||
Reactor Operations Branch | |||
Division of Inspection Program Management | Division of Inspection Program Management | ||
Office of Nuclear Reactor | Office of Nuclear Reactor Regulation | ||
Technical contacts: Jerry Dozier, NRR Paul Krohn, Region III | |||
(301) 415-1014 (920) 755-2309 E-mail: jxd@nrc.gov E-mail: pgk1@nrc.gov | |||
Attachment: List of Recently Issued NRC Information Notices | |||
DISTRIBUTION: | |||
ADAMS | |||
IN File | |||
DOCUMENT NAME: G:\RORP\OES\Staff Folders\Dozier\InformationNoticeonPointBeachOrifice.wpd | |||
Adams Accession No.:ML040140460 | |||
OFFICE OES:IROB:DIPM Tech Editor DLPM SRI:RIII | |||
NAME IJDozier PKleene DWSpaulding PKrohn | |||
DATE 12/03/2003 12/09/2003 01/14/2004 01/13/2004 OFFICE BC:RIII SC:OES:IROB:DIPM C:IROB:DIPM | |||
NAME AVegel TReis WDBeckner | |||
DATE 01/13 /2004 01/14/2004 01/21/2004 OFFICIAL RECORD COPY | |||
Attachment LIST OF RECENTLY ISSUED | |||
NRC INFORMATION NOTICES | |||
_____________________________________________________________________________________ | |||
Information Date of | |||
Notice No. Subject Issuance Issued to | |||
_____________________________________________________________________________________ | |||
2002-26, Sup 2 Additional Failure of Steam 01/09/2004 All holders of an operating license | |||
Dryer After A Recent Power or a construction permit for | |||
nuclear power reactors, except | Uprate nuclear power reactors, except | ||
those that have permanently | those that have permanently | ||
Line 194: | Line 308: | ||
permanently removed from the | permanently removed from the | ||
reactor.2003-11, Sup | reactor. | ||
2003-11, Sup 1 Leakage Found on Bottom- 01/08/2004 All holders of operating licenses | |||
Mounted Instrumentation or construction permits for | |||
nuclear power reactors, except | Nozzles nuclear power reactors, except | ||
those that have permanently | those that have permanently | ||
Line 208: | Line 324: | ||
permanently removed from the | permanently removed from the | ||
reactor.2003- | reactor. | ||
2003-22 Heightened Awareness for 12/09/2003 All medical licensees and NRC | |||
Patients Containing Detectable Master Materials License medical | |||
Amounts of Radiation from use permittees. | |||
Medical Administrations | |||
2003-21 High-Dose-Rate-Remote- 11/24/2003 All medical licensees. | |||
Afterloader Equipment Failure | |||
2003-20 Derating Whiting Cranes 10/22/2003 All holders of operating licenses | |||
Purchased Before 1980 for nuclear power reactors, except those who have | |||
permanently ceased operations | permanently ceased operations | ||
Line 227: | Line 354: | ||
facilities, and independent spent | facilities, and independent spent | ||
fuel storage installations.Note:NRC generic communications may be received in electronic format shortly after they | fuel storage installations. | ||
Note: NRC generic communications may be received in electronic format shortly after they are | |||
issued by subscribing to the NRC listserver as follows: | |||
To subscribe send an e-mail to <listproc@nrc.gov >, no subject, and the following | |||
command in the message portion: | |||
subscribe gc-nrr firstname lastname | |||
______________________________________________________________________________________ | |||
OL = Operating License | |||
}} | CP = Construction Permit}} | ||
{{Information notice-Nav}} | {{Information notice-Nav}} |
Latest revision as of 02:22, 24 November 2019
ML040140460 | |
Person / Time | |
---|---|
Site: | Point Beach |
Issue date: | 01/21/2004 |
From: | Beckner W NRC/NRR/DIPM |
To: | |
Dozier J, NRR/IROB 415-1014 | |
References | |
IN-04-001 | |
Download: ML040140460 (9) | |
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555 January 21, 2004 NRC INFORMATION NOTICE 2004-01: AUXILIARY FEEDWATER PUMP
RECIRCULATION LINE ORIFICE FOULING -
POTENTIAL COMMON CAUSE FAILURE
Addressees
All holders of operating licenses or construction permits for nuclear power reactors, except
those that have permanently ceased operations and have certified that fuel has been
permanently removed from the reactor.
Purpose
The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice to inform
addressees of the potential common cause failure of auxiliary feedwater pumps because of
fouling of pump recirculation line flow orifices. It is expected that recipients will review the
information for applicability to their facilities and consider actions, as appropriate, to avoid
similar problems. However, suggestions in this information notice are not NRC requirements;
therefore no specific action or written response is required.
Background:
Point Beach Nuclear Plant (PBNP) is a two unit site. Each unit has a turbine-driven AFW pump
(pumps 1P29 and 2P29) which can supply water to both steam generators. Additionally, the
plant has two motor-driven AFW pumps (pumps P38A and P38B) each of which can be aligned
to a steam generator in each unit. Each pump has a recirculation line back to the condensate
storage tanks (CSTs) to ensure minimum flow to prevent hydraulic instabilities and dissipate
pump heat. The recirculation line contained a pressure reducing, flow restricting orifice. An
arrow is pointing to the recirculation flow restricting orifice (RO) in the major flow path AFW
diagram provided in Figure 1 and a picture of the RO is provided in Figure 2.
The RO used a multi-stage, anti-cavitation trim package installed in the body of a globe valve to
limit flow. This style of orifice or flow restrictor was installed in the AFW recirculation lines at
PBNP in the past few years to eliminate cavitation caused by the old orifices. This type of flow
restrictor used very small channels and holes in each stage combined with a tortuous path to
limit flow and prevent cavitation.
Figure 1. AFW System - Major Flow Paths
Figure 2. Recirculation Flow Restricting Orifice
Description of Circumstances
On October 24, 2002, during post-maintenance surveillance testing of the P38A motor-driven
AFW pump at PBNP, the licensee observed AFW recirculation line flow to be 64.5 gpm, which
was less than the 70 gpm acceptance criterion. Normal flow through the recirculation line was
75 gpm. Suspecting instrument error, plant personnel vented and recalibrated the flow
instrument. The P38A AFW pump was then started and tested again; however, the observed
recirculation flow was essentially unchanged. Following that test run, the recirculation flow
orifice was removed and inspected.
After removal of the orifice internals, partial blockage was observed in 24 of the 54 holes in the
outermost sleeve. No particles were found on any of the inner sleeves. Samples of the
particles removed from the orifice were retained for analysis. A boroscope inspection of the
recirculation piping at the orifice location revealed no evidence of debris. Following cleaning
and reassembly, the orifice was reinstalled and the P38A AFW pump was successfully retested.
Testing was successfully completed on the other three AFW pumps to verify acceptable
recirculation flow by October 25, 2002.
During the next several days, PBNP personnel evaluated the implications of the orifice plugging
event. An apparent cause evaluation was initiated with specific directions to assess and
evaluate the potential extent of condition. An action plan was developed to identify the source
of the debris found in the orifice and to determine what other testing or flushing would be
required to assure that future plugging did not occur.
As the investigations continued, questions developed concerning the operability of the AFW
system while supplied by its safety-related water supply, the service water (SW) system.
Although the service water supply was provided through a basket strainer, it was recognized
that the strainer mesh was larger than the much finer RO channel holes and could allow debris
to pass that could clog the RO. These concerns culminated in a meeting on October 29, 2002, at which PBNP personnel concluded that there was no longer a reasonable assurance that
operation of the AFW system using its safety-related suction source of service water would not
result in potential AFW recirculation line orifice clogging.
In a worst case scenario, Point Beach personnel determined that it may be possible, although
unlikely, for each of the four flow control orifices, each associated with one of the four AFW
pumps, to restrict the flow through the associated recirculation line. Under such conditions, it
was hypothesized that if the discharge valves for the AFW pumps were throttled, adequate flow
might be unavailable through the recirculation line and pump damage could occur due to
overheating.
On October 29, 2002, all four AFW pumps were declared inoperable. Both units entered their
technical specification action statements and required actions which directs immediate action to
restore an AFW system to operable status. Immediate corrective actions consisted of briefing
the on-shift crew of the potential consequences of restricted recirculation flow and initiating
procedure changes. The operators were also directed to secure a running AFW pump if the
pump discharge flows should be decreased to less than 50 gpm for the motor-driven pumps or
75 gpm for the turbine-driven pumps. These flow rates were substantially above the point at
which pump damage could occur. Information tags were placed at the AFW pump flow
indicators on the main control boards to convey that information. With these administrative
controls in place, operations declared the AFW system operable, about four hours after the pumps had been declared inoperable. An incident investigation was initiated to collect and
confirm the facts of this event description beginning with the discovery of the P-38A AFW pump
degraded recirculation flow during post-maintenance testing and concluding with the decision to
declare the AFW system inoperable.
In accordance with 10 CFR 50.72(b)(3)(v), an eight-hour ENS notification (EN #39330) was
made on October 29, 2002. The LER is available in ADAMS (Accession Number
A PBNP multi-discipline event resolution team was formed to identify and resolve the issues
associated with the discovery of this condition. Activities included initiation of a root cause
evaluation (RCE) to determine the root and contributing causes for the postulated
common-mode failure that would render all AFW pump recirculation lines with restricted
flow rates. The RCE concluded that this event had a direct root cause and an organizational
root cause. The direct root cause was the failure by design engineering to properly evaluate
the potential for orifice plugging within the design process. Instead of revisiting the design for
adequacy and evaluating the potential for plugging of the proposed orifices within the rigor of
the design process, the 10 CFR 50.59 safety evaluation was revised to justify the proposed
design. The organizational root cause was less than adequate management oversight of the
design modification process.
Also, in January and February 2003, a specially fabricated orifice was tested at a contractor
laboratory in an effort to determine a plugging probability with service water. Definitive testing
occurred on February 21 when a debris mixture of sand, silt, and zebra mussel shells, representative of what would exist in the Point Beach SW system, was injected into a closed
loop configuration of piping, an orifice, and a centrifugal pump. The orifice plugged in much
less than one minute after the mixture was injected into the loop. These results were contrary
to those of a previously performed computational particle fouling model analysis that indicated
that plugging was unlikely because of the particle size distribution of debris in SW and the
shear forces in the holes and channels of the orifices developed with the minimum flow required
through the orifice for pump cooling.
Discussion:
A special inspection was conducted by the NRC to evaluate the facts, circumstances, and
licensee actions, and documented in NRC Inspection Report 50-266/02-15 and 50-301/02-15 (Accession Number ML030920128). This issue was determined to be of Yellow risk
significance for Unit 1, an issue with substantial importance to safety, and Red risk significance
for Unit 2, an issue of high importance to safety. The difference in significance between the
Units was a result of the longer period of time that the AFW recirculation line pressure reduction
orifices were installed in Unit 2. (See Final Determination Letter, dated December 11, 2003, Accession Number ML033490022). This information notice requires no specific action or written response. If you have any
questions regarding the information notice, please contact the technical contacts listed below or
the appropriate Office of Nuclear Reactor Regulation (NRR) project manager.
/Original signed by: Terrence Reis/
William D. Beckner, Chief
Reactor Operations Branch
Division of Inspection Program Management
Office of Nuclear Reactor Regulation
Technical contacts: Jerry Dozier, NRR Paul Krohn, Region III
(301) 415-1014 (920) 755-2309 E-mail: jxd@nrc.gov E-mail: pgk1@nrc.gov
Attachment: List of Recently Issued NRC Information Notices This information notice requires no specific action or written response. If you have any
questions regarding the information notice, please contact the technical contacts listed below or
the appropriate Office of Nuclear Reactor Regulation (NRR) project manager.
/Original signed by: Terrence Reis/
William D. Beckner, Chief
Reactor Operations Branch
Division of Inspection Program Management
Office of Nuclear Reactor Regulation
Technical contacts: Jerry Dozier, NRR Paul Krohn, Region III
(301) 415-1014 (920) 755-2309 E-mail: jxd@nrc.gov E-mail: pgk1@nrc.gov
Attachment: List of Recently Issued NRC Information Notices
DISTRIBUTION:
IN File
DOCUMENT NAME: G:\RORP\OES\Staff Folders\Dozier\InformationNoticeonPointBeachOrifice.wpd
Adams Accession No.:ML040140460
OFFICE OES:IROB:DIPM Tech Editor DLPM SRI:RIII
NAME IJDozier PKleene DWSpaulding PKrohn
DATE 12/03/2003 12/09/2003 01/14/2004 01/13/2004 OFFICE BC:RIII SC:OES:IROB:DIPM C:IROB:DIPM
NAME AVegel TReis WDBeckner
DATE 01/13 /2004 01/14/2004 01/21/2004 OFFICIAL RECORD COPY
Attachment LIST OF RECENTLY ISSUED
NRC INFORMATION NOTICES
_____________________________________________________________________________________
Information Date of
Notice No. Subject Issuance Issued to
_____________________________________________________________________________________
2002-26, Sup 2 Additional Failure of Steam 01/09/2004 All holders of an operating license
Dryer After A Recent Power or a construction permit for
Uprate nuclear power reactors, except
those that have permanently
ceased operations and have
certified that fuel has been
permanently removed from the
reactor.
2003-11, Sup 1 Leakage Found on Bottom- 01/08/2004 All holders of operating licenses
Mounted Instrumentation or construction permits for
Nozzles nuclear power reactors, except
those that have permanently
ceased operations and have
certified that fuel has been
permanently removed from the
reactor.
2003-22 Heightened Awareness for 12/09/2003 All medical licensees and NRC
Patients Containing Detectable Master Materials License medical
Amounts of Radiation from use permittees.
Medical Administrations
2003-21 High-Dose-Rate-Remote- 11/24/2003 All medical licensees.
Afterloader Equipment Failure
2003-20 Derating Whiting Cranes 10/22/2003 All holders of operating licenses
Purchased Before 1980 for nuclear power reactors, except those who have
permanently ceased operations
and have certified that fuel has
been permanently removed from
the reactor vessel; applicable
decommissioning reactors, fuel
facilities, and independent spent
fuel storage installations.
Note: NRC generic communications may be received in electronic format shortly after they are
issued by subscribing to the NRC listserver as follows:
To subscribe send an e-mail to <listproc@nrc.gov >, no subject, and the following
command in the message portion:
subscribe gc-nrr firstname lastname
______________________________________________________________________________________
OL = Operating License
CP = Construction Permit