| title = Pilgrim, Response to Request for Additional Information - Exemption from the Requirements of 10 CFR 50.47 and Appendix E to 10 CFR Part 50
| title = Response to Request for Additional Information - Exemption from the Requirements of 10 CFR 50.47 and Appendix E to 10 CFR Part 50
| author name = Halter M K
| author name = Halter M K
| author affiliation = Entergy Nuclear Operations, Inc
| author affiliation = Entergy Nuclear Operations, Inc

Revision as of 15:28, 31 March 2019

Response to Request for Additional Information - Exemption from the Requirements of 10 CFR 50.47 and Appendix E to 10 CFR Part 50
ML18338A205
Person / Time
Site: Pilgrim
Issue date: 11/30/2018
From: Halter M K
Entergy Nuclear Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
2.18.066
Download: ML18338A205 (13)


Text

Entergy Nuclear Operations, Inc. 1340 Echelon Parkway Jackson, MS 39213 Tel 601-368-5573 Mandy K. Halter Director, Nuclear Licensing LETTER NUMBER: 2.18.066 November 30, 2018 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001

SUBJECT:

Response to Request for Additional Information

-Exemption from the Requirements of 10 CFR 50.47 and Appendix E to 10 CFR Part 50, Entergy Nuclear Operations, Inc. Pilgrim Nuclear Power Station Pilgrim Nuclear Power Station Docket 50-293 Renewed License No. DPR-35

REFERENCES:

1. Entergy Nuclear Operations, Inc. letter to NRC, "Request for Exemptions from Portions of 10 CFR 50.47 and 10 CFR Part 50 Appendix E," dated July 3, 2018 (ADAMS Accession No.

Dear Sir or Madam:

ML 18186A635)

2. NRC email to Entergy Nuclear Operations, Inc., RAls -Pilgrim EP Exemption," dated October 16, 2018 (ADAMS Accession No. ML 18289A407)

In Reference 1, Entergy Nuclear Operations, Inc. (ENO) submitted a request to the Nuclear Regulatory Commission (NRC) for exemption from portions of 10 CFR 50.47 and 10 CFR Part 50 Appendix E for Pilgrim Nuclear Power Station (PNPS). In Reference 2, the NRC requested additional information concerning the exemption request. Attachment 1 to this letter provides the ENO response to the NRC request for additional information (RAI). Attachment 2 provides revised pages of the exemption request. These revised pages supersede the original pages in their entirety.

This RAI response does not impact the conclusions of the no significant hazards evaluation or the environmental considerations evaluation presented in Reference

1. A copy of this submittal has been provided to the designated Commonwealth of Massachusetts officials.

If you have any questions or require additional information, please contact Mr. Peter J. Miner at (508) 830-7127.

Entergy Nuclear Operations, Inc. Pilgrim Nuclear Power Station Letter No. 2.18.066 Page 2 of 3 This letter contains no new commitments and no revisions to existing commitments.

Sincerely, Mandy K. Halter MKH/dd/mjp Attachments:

1. Response to Request for Additional Information

-Request for Exemptions from Portions of 1 O CFR 50.47 and 1 O CFR Part 50, Appendix E for the Pilgrim Nuclear Power Station 2. Revised Pages of the PNPS Request for Exemptions from Portions of 10 CFR 50.47 and 10 CFR Part 50 Appendix E l Entergy Nuclear Operations, Inc. Pilgrim Nuclear Power Station cc: Mr. David C. Lew Acting Regional Administrator, Region I U.S. Nuclear Regulatory Commission 2100 Renaissance Blvd, Suite 100 King of Prussia, PA 19406-2713 Mr. John Lamb, Senior Project Manager Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Mail Stop 0-9012 Washington, DC 20555-0001 Mr. John Giarrusso, Jr. Planning, Preparedness and Nuclear Section Chief Massachusetts Emergency Management Agency 400 Worcester Road Framingham, MA 01702 Mr. John Priest, Director Massachusetts Department of Public Health Radiation Control Program Commonwealth of Massachusetts 529 Main Street, Suite 1 M2A Charlestown, MA 02129-1121 NRG Senior Resident Inspector Pilgrim Nuclear Power Station Letter No. 2.18.066 Page 3 of 3 LETTER NO. 2.18.066 ATTACHMENT 1 Response to Request for Additional Information Request for Exemptions from Portions of 10 CFR 50.47 and 10 CFR Part 50, Appendix E for the Pilgrim Nuclear Power Station 5 pages follow LETTER NO. 2.18.066 ATTACHMENT 1 A Nuclear Regulatory Commission (NRC) request for additional information (RAI) regarding a request for exemptions from portions of 10 CFR 50.47 and 10 CFR Part 50, Appendix E for the Pilgrim Nuclear Power Station (PNPS) was received by Entergy Nuclear Operations, Inc. (ENO) via electronic mail (email) dated October 16, 2018. ENO responses to the RAI request are provided below. NRCREQUEST By letter dated July 3, 2018 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML 18186A635), Entergy Nuclear Operations, Inc. requested an exemption from specific emergency planning requirements of Title 10 of the Code of Federal Regulations (10 CFR) Part 50 for the Pilgrim Nuclear Power Station (PNPS), based on the proposed permanent cessation of power operations and removal of fuel from the reactor vessel, which is expected no later than June 1, 2019. The exemption request has been reviewed against the requirements in 10 CFR 50.47, "Emergency plans," and Appendix E to 10 CFR Part 50, "Emergency Planning and Preparedness for Production and Utilization Facilities," using the guidance provided in Interim Staff Guidance (ISG) NSIRIDPR-ISG-02, "Emergency Planning Exemption requests for Decommissioning Nuclear Power Plants" (ADAMS Accession No. ML 14106A057).

The review considered the storage of the spent nuclear fuel in the spent fuel pool (SFP) and the onsite independent spent fuel storage installation, and the low likelihood of any credible accident resulting in radiological releases requiring offsite protective measures.

Based on the NRG staff's initial review of PNPS's EP exemption request, the following requests for additional information (RA ls) are required to facilitate completion of the staff's technical review. NRC RAI-PNPS-1 The exemption for item 1 in Table 1 (Attachment 1), page 6 of 72, states: 10 CFR 50.47(b) The onsite aRd, except as provided iR paragraph (d) of this sectioR, offsite emergency response plans for nuclear power reactors must meet the following standards:

In the basi,s for the exemption PNPS states, that: PNPS maintains procedures and strategies for the movement of any necessary portable equipment that will be relied upon for mitigating the loss of SFP water. These mitigative strategies, addressing events involving a loss of SFP cooling and/or water inventory, include implementation of SFP inventory makeup strategies required under 10 CFR 50.54(hh)(2), which will continue to be maintained to satisfy applicable License Conditions of the Renewed Facility Operating License. These diverse strategies provide defense-in-depth and ample time to provide makeup water or spray to the SFP prior to the onset of zirconium Page 1 of 5 LETTER NO. 2.18.066 ATTACHMENT 1 cladding ignition when considering ve,y low probability beyond design basis events affecting the SFP. The on-shift individuals described in the Permanently Oefueled Emergency Plan will be able to implement the necessa,y tasks within the required timeframe.

Staff Decommissioning Assumptions (SDA) 1 in Table 5, "PNPS Compliance with NSIR!OPR-ISG-02 Staff Decommissioning Assumptions (SOAs)," (Attachment 1), page 61 of 72, states: Licensee's SFP cooling design will be at least as capable as that assumed in the risk assessment, including instrumentation.

Licensees will have at least one motor-driven and one diesel-driven fire pump capable of delivering invento,y to the SFP. Also, in the response to SDA 1 PNPS states, in part, that: The SFP has redundant cooling pumps, redundant heat exchangers, and multiple make-up sources, in addition to the normal condensate transfer system. The additional sources include tie-ins to the Firewater system, with Jockey pump P-146, Electric pump P-135, and diesel driven pump P-140. The make-up source for the firewater is a Municipal water system. Please provide additional details regarding the diverse mitigation strategies, to include the identification of the trained on-shift personnel designated for carrying out the necessary tasks and the timeframe for implementation of these diverse mitigation strategies.

ENO Response to RAI-PNPS-1 As indicated on Table 2.1, On-Shift and Emergency Response Organization Staffing Requirements, of the Pilgrim Nuclear Power Station Permanently Defueled Emergency Plan (PDEP) provided to the NRC in Reference 1, the Control Room Supervisor, Non-Certified Operator and Radiation Protection Technician are required to direct or perform site-specific mitigation strategies required for a catastrophic loss of SFP inventory.

As indicated in the Response to IDC-4, provided in Table 4 of the Exemption Request (Reference 2), following permanent shut down and permanent removal of fuel from the reactor vessel, the on-shift plant operators, including Certified Fuel Handlers (CFH) and Non-Certified Operators, will be appropriately trained on the relevant procedures and on the various actions needed to provide makeup to the SFP to ensure appropriate personnel receive initial and continuing training on 8.5.b event-related procedures and strategies credited in applicable License Conditions required by 1 O CFR 50.54(hh)(2).

On May 22, 2018, Pilgrim performed a validation exercise demonstrating that the 8.5.b SFP Spray Strategy could be performed with designated personnel.

The timeframe was determined to be 95 minutes. The PDEP staffing table identifies the individuals in the on-shift crew responsible for implementing the mitigation activities.

Page 2 of 5 LETTER NO. 2.18.066 ATTACHMENT 1 NRC RAI-PNPS-2 The exemption for item 11 in Table 1, "Exemptions Requested from 10 CFR 50.47(b) and 50.47(c)(2)," (Attachment 1 ), page 9 of 72, states: 10 CFR 50.47(b)(10):

A range of protective actions has been developed for the plume exposuro pathv.ray EPZ for emergency workers and the public. IR elev-eloping this range of actions, consideration has been gi*/en to evacuation, sheltering, and, as a supplement to these, the prophylactic use of potassium iodide (Kl}, as appropriate.

Evacuation time estimates have been developed by applicants and licensees.

Licensees shall update the e*.tacuation time estimates on a periodic basis. Guidelines for the choice of protecti'/e actions during an emergency, consistent with Fede!'al guidance, are developed and in place, and protectiv-e actions for the ingestion exposure pathway EPZ appropriate to the locale ha*,.te been developed.

However, the guidance in Table 1, "Exemptions for Consideration," in NSIRIDPR-ISG-02 states: 10 CFR 50.47(b)(10):

A range of protective actions has been developed for the plume exposure pathway EPZ for emergency workers and the public. IR developing this range of actions, consideration has been gi*/en to evacuation, shelte!'!ng, and, as a supplement to these, the prophylactic use of potassium iodide (Kl}, as appropriate.

Evacuation time estimates have been developed by applicants and licensees.

Licensees shall update the evacuation time estimates on a periodic basis. Guidelines for the choice of protective actions during an emergency, consistent with Federal guidance, are developed and in place, and protectiv-e actions for the ingestion exposuro pathway EPZ appropriate to the locale have been developed.

Please provide justification for the exemption of the "and the public" as this is not consistent with the guidance and past precedent.

ENO Response to RAI-PNPS-2 The phrase "and the public" was unintentionally included in the proposed exemption language.

The Request for Exemptions from Portions of 10 CFR 50.47 and 10 CFR Part 50 Appendix E will be revised such that "and the public" is not included as part of the exemption request. This revision is included in Attachment 2 of this response.

Page 3 of 5 LETTER NO. 2.18.066 ATTACHMENT 1 NRC RAI-PNPS-3 The exemption for item 40 in Table 2, "Exemptions Requested from 10 CFR 50, Appendix E," (Attachment 1 ), page 24 of 72, states: C.2 By J1,me 20, 2012, nuclear power reactor licensees shall establish and maintain the capability to assess, classify, and declare an emergency condition within 15 mtm,tes after the availability of indications to plant operators that an emergency action level has been exceeded and shall promptly declare the emergency condition as soon as possible following identification of the appropriate emergency classification level. Also, the exemption for item 43 in Table 2 (Attachment 1), pages 26-27 of 72, states, in part: D. 3. A licensee shall have the capability to notify responsible State and local governmental agencies V'lithtn 15 minutes after declaring an emergency.

In the basis for the exemption for both item 40 and item 43, PNPS states, in part, that: During these meetings have included discussions of the regulatory exemption requests.

PNPS will continue to meet with representatives from the Commonwealth of Massachusetts, local emergency preparedness personnel, and Regional leadership from FEMA. These discussions have addressed changes to onsite and offsite emergency preparedness throughout the decommissioning process, including the proposed 30-minute declaration time and the 60-minute notification time. Emergency management officials have not objected to the proposed changes. Please provide documentation that the Commonwealth of Massachusetts and the Town of Plymouth is in agreement with the proposed 30-minute declaration time and the 60-minute timeframe for notification.

ENO Response to RAI-PNPS-3 We have engaged representatives of the Town of Plymouth and the Commonwealth of Massachusetts to obtain written documentation of concurrence with the proposed 30-minute declaration time and the 60-minute timeframe for notification.

Although we have had further discussions subsequent to receipt of the request for information, we have not yet secured written documentation.

We anticipate providing concurrence from the Town of Plymouth and the Commonwealth of Massachusetts by February 15, 2019. Page 4 of 5 LETTER NO. 2.18.066 ATTACHMENT 1 NRC RAI-PNPS-4 The exemption for item 104 in Table 2 (Attachment 1), page 45 of 72, states: Footnotes 3, 4, 5, and 6 are proposed for exemption.

The basis for the exemption, states: ENO considers PNPS to be exempt from Footnotes 3, 4, 5, and 6 because PNPS will be exempt from the umbrella provisions of Section F.2. Please provide further justification for Footnote 3 as it is not exempt from the umbrella provisions of Section F. 2. ENO Response to RAI-PNPS-4 Footnote 3 will be removed from the exemption request. The Request for Exemptions from Portions of 10 CFR 50.47 and 10 CFR Part 50 Appendix E will be revised such that Footnote 3 is not included as part of the exemption request. This revision is included in Attachment 2 of this response.

References

1. Entergy Nuclear Operations, Inc. letter to NRC, "License Amendment Request to Revise the Pilgrim Nuclear Power Station Emergency Plan and Emergency Action Level Scheme to Address the Permanently Defueled Condition," dated August 1, 2018 (ADAMS Accession No. ML 18218184)
2. Entergy Nuclear Operations, Inc. letter to NRC, "Request for Exemptions from Portions of 10 CFR 50.47 and 10 CFR Part 50 Appendix E," dated July 3, 2018 (ADAMS Accession No. ML 18186A635)

Page 5 of 5 LETTER NO. 2.18.066 ATTACHMENT 2 Revised Pages of the PNPS Request for Exemptions from Portions of 10 CFR 50.47 and 10 CFR Part 50 Appendix E (Attachment 1 of the Exemption Request) 3 pages follow CNR0-2018-00031 ATTACHMENT 1 Table 1 Exemptions Requested from 10 CFR 50.47(b) and 50.47(c)(2)

Item# Regulation in 10 CFR 50.47 Basis for Exemption Also see the basis for 10 CFR 50.47 (b). 7 10 CFR 50.4 7(b)(6): Provisions exist for prompt See the basis for 10 CFR 50.47(b). communicat i ons among pr i ncipal response organ i zations to emergency personnel aAEl te tRe 13usliG. 8 10 CFR 50.47(b)(7):

IAfeFrnatieA is rnase availasle to tRe See the basis for 10 CFR 50.47(b). 13uslis oA a 13eFiosis sasis eA Row tRey will se Ratifies aAEl wRat tRei F iAitial astieAs sReuls se iA aA erneF§leAGY (e.§1., listeAiA§!

te a losal smassast statieA aAEl mrnaiA i A§! iAElems), [T)he principal points of contact with the news med i a for dissemination of information du r ing an emergency (iAGlusiA§!

tRe J:)Rysical losatioA OF lesatieAs) are estab l ished in advance , and procedures for coordinated dissem i nation of information to t he public are established.

9 10 CFR 50.47(b)(8)

Adequate emergency facilities and No exemption i s requested. equipment to support the emergency response are provided and maintained. 10 10 CFR 50.47 (b)(9): Adequate methods , systems , and See the bas i s fo r 10 CFR 50.47 (b). equipment fo r assessing and monitor i ng actual or potentia l e#site consequences of a radiologica l emergency condition are in use. 11 10 CFR 50.47 (b)(10): A range of protective act i ons has been In the unlikely event of a SFP accident , the iodine i sotopes which developed for tRe 13lurne ex:13osuFe 13atRway ePl feF emergency contribute to an offsite dose from an operat i ng reactor accident are workers and the p u blic aAEl tRe 13usliG. IA Elevelo13iA§!

tRis not present , so potassium iodide (Kl) distribution offsite would no FaA§!e of astieAs , GoAsiseFatieA Ras seeA §!iveA to ei.,asuatieA , longer serve as an effective or necessary supplemental protective sRelteFiA§!, aAEl , as a su1313lerneAt to tRese , tRe J:lFOJ:)Rylast i s use action. Protective actions will be maintained for emergency workers Page 9 of 72 CNR0-2018-00031 ATTACHMENT 1 Table 2 Exemptions Requested from 10 CFR 50, Appendix E Item# Regulation in Part 50 , Appendix E Basis for Exemption fuel at the fac ilit y in a manner that is protective of public hea lt h and safety. PNPS will mainta i n a level of emergency r esponse tha t does not require add i tional response by headquarters personne l. The on-shift and eme r gency response positions are defined in the Permanently Defueled Emergency Plan and will be regular l y t ested through drills and exerc i ses , audited , and inspected by PNPS and the NRC. Also see the basis for 10 CFR 50.47 (b). Therefore , exempting licensee's headquarters personnel from training requirements i s considered to be reasonable. 78 F.1.i x. Security personne l. No e x emption is requested. 79 F.1. In addition , a radiological orientation train i ng program shall Because there will no longe r be any e x pected actions that must be be made available to local services personnel; e.g., local taken by the public during an emergency , it is no longer necessary to emergency services/Civ i l Defense , l ocal law enforcement pre-plan the dissemination of this informat i on to the public o r to personnel , local news med i a persons. provide radiolog i cal orientation tra i n i ng to local news media p e r sons. The phrase " C i v i l Defense" i s no longer a commonly used term and is no longer appl i cable as an example in the regulat i on. 80 F.2. The plan shall desc ri be provis i ons for the conduct of PNPS analyses demonstrate that 10 months after permanent emergency preparedness exercises as follows: cessation of power operations , no remaining postulated acc i dents at Exercises shall test the adequacy of timing and content of PNPS will result in radiological releases requiring offsite protective implementing procedures and methods , test emergency actions , or in the event of beyond des i gn basis accidents , 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> is equipment and communications networks , test the public alert ava i lable to take mitigative actions , and if needed , implemen t offsite protect i ve actions using a comprehensive emergency management and notification system , and ensure that emergency p l an. Therefore , the public alert and notification system will not be organization personnel are familiar with their dut i es.3 3 used and no testing would be required. Page 36 of 72



CNR0-2018-00031 ATTACHMENT 1 Table 2 Exemptions Requested from 10 CFR 50, Appendix E Item# Regulation in Part 50, Appendix E Basis for Exempt i on near real-time electronic data link between the licensee's onsite necessary to transmit safety system parameter data. No exemption is computer system a n d the NRC Operations Center that provides requested because this change in the EROS data requirement is for the automated transmission of a limited data set of selected identified in 10 CFR Part 50, Appendix E , Section Vl.2. parameters. The EROS supp l ements the ex i sting vo i ce transmission over the Emergency Notification System (ENS) by providing the NRC Operations Center with timely and accurate updates of a limited set of parameters from the licensee's installed onsite computer system i n the event of an emergency. When selected plant data are not available on the li censee's onsite computer system , retrofitting of data points is not required. The licensee shall test the EROS periodically to verify system availability and operability.

The frequency of EROS testing w ill be quarte r ly unless otherwise set by NRC based on demonstrated system performance. 2. Except for Big Rock Point and all nuclear power facilities that are shut down permanently or indefinitely, ons ite hardware shall be provided at each unit by the licensee to interface with the NRC receiving system. Software , which will be made available by the NRC, will assemble the data to be transmitted and transmit data from each unit via an output port on the appropriate data system. 104 10 CFR 50 Appendix E ENO co n siders PNPS to be exempt from Footnotes M , 5 , and 6 Footnotes M , 5, and 6 are proposed for exemption. because PNPS will be exempt from the umbrella provisions of Section F.2. :i Use of site specific simulators or computers is acceptable for any exercise. 4 i;:u1113articipation

  • ,¥Ren uses in conjunction witl=l emer§ency 13repareaness exercises for a particular site means appro13riate Page 45 of 72