U-602803, Updates Previous Ltrs Providing Rationale That safety- Related Circuit Breakers Will Continue to Meet Requirements in Light of Recent Problems Identified W/W 4160-volt Circuit Breakers at Plant.Ltr Contains Listed Commitments

From kanterella
(Redirected from U-602803)
Jump to navigation Jump to search
Updates Previous Ltrs Providing Rationale That safety- Related Circuit Breakers Will Continue to Meet Requirements in Light of Recent Problems Identified W/W 4160-volt Circuit Breakers at Plant.Ltr Contains Listed Commitments
ML20217J615
Person / Time
Site: Clinton Constellation icon.png
Issue date: 08/01/1997
From: Romberg W
ILLINOIS POWER CO.
To: Beach A
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
U-602803, NUDOCS 9708140375
Download: ML20217J615 (12)


Text

,

t-

~s

}' ,

IIlesta Posvr Cwwy .

e

-Q C}nton ppwyf r,tAhM

o l

V o 60s 07ts )

Chim,IL 01r27 fet 3 7 W4T.'D i r., 2,7 men  :

ILLIN915 ..,,,. n n .a,.. .

NMR Ai ..c.***

- ^**+iv>c"'****"'"***'

i' U402803 4P.190 ,

1 August 1,1997 i

. P!tlORrrY ROUTING Firsi Second i k $A de 2_.11C  !

Docket No. 50-461 M99A LV24_ ElG _

Mr. A. Bill Beach nic:tI d (DRS A A? EGA Of Regional Administrator, Region 111 DNMS PAO "

t U S. Nuclear Regulatory Commission OfSAA l l

801 Warrenville Road Lisle, Illinois 605324351 FILE NLv *

Subject:

Update on Westinghouse 4160-Volt -

Citpuit Breakers at Clinton Power Stat ion  ;

i i

Dear Mr. Beach:

This letter is an update to previous letters providing rationale that our safety-related circuit breakers will continue to meet operational requicements in light of the recent problems we have identified with Westinghouse 4160-volt circuit breakers at Clinton Power Station. These problems were originally detailed in Illinois Power letter i U 602799 dated July 25,1997. The impact on circuit breaker operability from each of l' these problems is discussed below.

This letter contains the following commitments.

. - Drawings for the undervoltage relay seal in circuit will be revised to clearly show the removal of the internaljumper for the seal in circuit. This will be completed by August 30,1997. (

1

  • Maintenance and vendor personnel will review the Westinghouse circuit breaker

-vendor maintenance instructions against plant procedures for consistency. This ,

will_ be completed prior to startup Rom the current outage. -- t

  • Maintenance procedures that perform maintenance on ABB 480 volt and

_{ @k

_ q/ ,

General electric 4160-volt circuit breakers will be reviewed for consistency'with the vendor instructions. This will completed by August 30,1997. i

{-

l 13'00S0? '

IEpppppljp pr w ur,8slg, F 0,

U-603803 Page 2

+

A sample of electrical, mechanical, and control and instmmentation procedures will be reviewed for conformance with vendor instructions. This wi;l be completed by August 1,1998.

Westinghouse 4160 volt safety-related circuit breakers will be inspected dier switching operations to ensure they have operated completely and the charging springs are charged This inspection will be performed on each circuit breaker prior to startup from the current outage. Operating procedures will be revised to initiate this inspection.

The failed safety related Westinghouse circuit breaker will not be placed back in service unless the cause of the failure can be determined.

  • An independent circuit breaker expert will assist in determining the cause of the Westinghouse safety related circuit breaker failure.

En11nshauss Sakty Es. lated circuit 11rukstlillute To Trip On July 22,1997, a Westinghouse 4160 volt safety related circuit breaker failed to open when required. Failure of this circuit breaker during plant operation would not have caused the plant to trip offline. Inspection of the circuit breaker while it remained in the cubicle revealed it was in an intermediate position (photographs of the circuit breaker in the intermediate position are enclosed). In this position the circuit breaker is still able to carry electrical load. In order to remove the circuit breaker from the cubicle, it was fully closed and was successibily opened from that position.

The cause of the circuit breaker to operate to the intermediate position could not be conclusively determined. The circuit breaker was inspected onsite by Westinghouse and lilinois Power personnel and dismantled offsite by Cutler llammer (the current manufacturer of the circuit breaker).

Illinois Power analyzed the as found intermediate position of the circuit breaker and determined the possible deficiencies that could cause the circuit breaker to be in this position. The possible deficiencies that would cause the circuit breaker to be in the intermediate position when operating in either the closed or open directions are: bent or misaligned operating linkages, degraded lubricant, binding of operating mechanism, debris preventing circuit breaker operation, weak closing or opening springs, malfunction of the trip latch.

During the offsite di: mantling of the circuit breaker the possible causes of the circuit breaker being in the intermediate position afler a trip signal was received (i.e.

failure in the opening direction.' were investigated. The operating linkages were checked for misalignment or physical damage. No damage of tbse linkages was noted. The puffer tube assembly was found slightly out of alignment. The pufTer tube assembly was readjusted with no affect on circuit breaker operation. The lubricated portions of the operating mechanism were inspected for degraded lubricant. Some dry, sticky lubricant was found on the pivot points for the circuit breaker's contact operating rods. However,

~ . -- - - - _ _ _ - . - - - - - . _ - -- - . - - _ _.

t

. U403803 Page 3 l

these pivot points have fairly loose tolerances and still operated freely. Inspection of the circuit breaker bearing lubricant disclosed that the lubricant was in like new condition.

Extensive examination and testing of the operating mechanism was conducted. No binding or abnormal operation was observed. No debris was found during the inspection '

which could have caused the circuit breaker to fail to operate. The spring strength and alignment were checked with no abnormalities noted.

During the offsite dismantling of the circuit breaker the possible causes of the circuit breaker being in the intennediate position afier a close signal (i.e., failure in the closing direction) was also investigated. The operating linkages were checked for misalignment or physical damage. No damage of these linkages was noted. The puffer ,

tube assembly was found slightly out of alignment. The puffer tube assembly was readjusted with no affect on circuit breaker operation. The lubricated portions of the operating mechanism were inspected for degraded lubricant. Some dry, sticky lubricant was found on the pivot points for the circuit breaker's contact operating re,ds. Ilowever, these pivot points have fairly loose tolerances and still operated freely, inspection of the circuit breaker bearing lubricant disclosed that the lubricant was in like-new condition.

Extensive examination and testing of the operating mechanism was conducted. No binding or abnormal operation was observed. No debris was found during the inspection which could have caused the circuit breaker to fail to operate. The spring strength and alignment were checked with no abnormalities noted. The trip latch was inspected for a condition which may have caused it to properly latch when attempting to close the circuit breaker. The inspection revealed that the trip latch was slightly out of specification but we could not make it fail to operate on several subsequent cycles.

During testing of the circuit breaker it was consistently demonstraced that if the circuit breaker was fully open or closed it would operate when required. Illinois Power believes that the circuit breaker was m the intermediate position when it was closed prior to the failure of the circuit breaker to open. A failure of the circuit breaker to completely close can be detected by a visual inspection of the circuit breaker local mechanical position )

indication.

l The vendor analysis of the condition of the circuit breaker afler testing and I

disassembly stated that the previous preventive maintenance activities performed on the circuit breaker were satisfactory to maintain the circuit breaker and should be continued. 1 The vendor also noted that, based on the condition of this circuit breaker, the other )

in service Westinghouse circuit breakers will operate satisfactory on demand. No l abnormalities were detected through tests or inspections that could have caused the circuit breaker to fall to open. (Attached is a copy of the Westinghouse preliminary report).

In order to ensure that circuit breakers at Clinton Power Station will operate when required the Westinghouse 4160-volt safety-related circuit breakers will be inspected aller switching operations and prior to startup from the current outage. This inspection will verify that the circuit breaker has operated completely to the expected position and that the charging springs are fully charged. Operating procedures will be revised to require  ;

notification of electrical maintenance to verify the mechanical indication of circuit breaker l

l

. i

. U 602803 Page 4 position and charging springs. Electrical maintenance personnel will conduct, document, and track this inspection in accordar cc with the maintenance work request procedure.

This inspection will continue to be performed by electrical maintenance technicians that have been specifically trained for this inspection. This inspection will be performed until the Westinghouse 4160-volt safety-related circuit breakers have been replaced with new or refurbished circuit breakers. Ah.o, the circuit orcaker that failed on July 22,1997 will not be placed back into senice at Clinton Power Station unless the cause of the failure to open can be determined.

Illinois Power is continuing to pursue the cause of the failure of this circuit breaker. An independent circuit breaker expert will review the failure mode and inspection and test data to assist in cause determination.

As detailed in Illinois Power letter U 602787, dated July 16,1997, Illinois Power plans to have installed new or refurbished Westinghouse 4160 volt safety-related circuit breakers in scr ice in all Division 11 circuit breaker cubicles before the start of a planned mid cycle outage. This mid cycle outage is scheduled for April 1998. Nine of the ten Division I Westinghouse 4160-volt safety related circuit breakers will be replaced with new or refuibished circuit breakers by September 25,1998. The remaining Westinghouse 41t* wit safety related circuit breakers will be replaced with a new or refurbished circuit breaur during the next refueling outage. This outage is scheduled for the spring of 1999.

Hased on the opinion of the circuit breaker vendor that performed the tests and inspections,Illina's Power's review of the circuit breaker's condition, and compensatory actions lilinois Power is taking to ensure proper circuit breaker operation, there is reasonable assurance that the in service safety related Westingbouse 4160-volt circuit breakers wih operate when required.

Failure of Westinnhouse 4160-Volt Circuit Breaker Due to Relav Mis-Wiring in a separate event on July 22,1997, during restoration from an electrical bus outage, two non safety related Westinghouse 4160 volt circuit breakers failed to close on demand. The first failure of a Westinghouse non-safety related circuit breaker to close on demand was because a contact for a seal-in circuit in an undervoltage relay on the electrical bus was mis-wired. This caused the circuit breaker tu not receive the signal to close, it is suspected that the seal-in circuit mis wiring may have been caused by a lack of clarity in the design drawings. Removal of the contact from the scal in circuit can be accomplished by either moving the contact out of the way, so it does not make contact when the relay actuates, or removing an internaljumper in the relay. The drawings for this circuit do not show that the contacts for the scal-in function are enabled. The drawings also slo not describe the method to disable the seal-in function of the relay. The contact for this electrical bus undervoltage relay has been rewired (i.e. jumper removed) so the seal in function is disabled. The applicable drawings will be revised to clearly indicate that

- thejumper should be removed to disable the seal in function for these relays.

A review of the potential for the seal in function of this relay to be enabled on safety-related and non safety related electrical distribution systems was performed. There

. . _. _ . --- - - -- -= .

e

. U-603803 Page$

are seven relays in the safety-related electrical distribution system and forty six in the non-safety related electrical distribution systern that could cause this problem. The results of this review disclosed that the safety related electrical busses have had the internaljumper removed from the undervoltage relay to prevent the seal in ftmetion frora operating. The removal of thisjumper is periodically verified for the safety related relays during the performance of surveillance procedures. Ilowever, these surveillances are not performed on the non safety related distribution system. A maintenance work request has been issued to remove thejumper or verify that no jumper exists on all forty six of the affected non safety related relays. Because the safety-related relays are periodically verifled to not have the seal in circuit activated this condition does not affect the associated safety related Westinghouse circuit breakers.

Eailure ofWes1Lnghoms 4160-Volt Circuit Breaker Due to Latch Check Adjustmeal The cause of the second failure of a non safety related Westinghouse circuit breaker to close was that the contacts on the latch check switch, which provides a permissive to close the circuit breaker, did not make-up as required. This was caused by the latch check switch being out of adjustment. During preparation for the adjustment of the latch check switch it was discovered, with assistance frora Westinghouse personnel, that the method used in the plant procedure to adjust the latch check switch was incorrect.

This correct method was used to check and readjust the switch as necessary on both safety and non safety related circuit breakers. Ilowever, prior to the procedure being revised in April 1997, the instructions in the procedure were correct and consistent with those in the vendor manual. Review of maintenance history showed that only one circuit breaker was checked for proper latch check switch adjustment using the deficient procedure. This circuit breaker was subsequently checked for proper latch check switch adjustment.

Adjustment of this latch check switch was not required.

Because the latch check switch was found out of adjustment on the non safety

related circuit breaker, and CPS procedures are the same for safety related circuit breakers, all of the safety-related circuit breakers that are needed to actively close to perform their safety function (twenty-two of twenty four in service safety related circuit breakers) have been checked for proper latch check switch adjustment. Those that were not properly adjusted have been corrected. To date, the check of the adjustment of the latch check switches has revealed that twenty of twenty-eight checked (this includes some non-safety related circuit breakers) were out of adjustment. The procedure that checks this adjustment has been revised to reflect the correct method of performing this task and is nonually performed during circuit breaker preventive maintenance activities.

Therefore, since this condition has been corrected on those circuit breakers that are needed to actively close to perform their safety function there is no impact on the ability of these circuit breakers to perform their safety function.

Illinois Power is also taking actions to determine if there are additional problems with maintenance procedures that implement vendor instructions. Maintenance personnel will review the Westinghouse circuit breaker vendor maintenance instructions against the instructions in the maintenance procedure to determine if there are other instances where the circuit breaker maintenance procedures are not consistent with those in the vendor i . -

. i U403803 I Page 6 l manual. Also, an independent contractor will perform the review described above separately from maintenance personnel. Any discrepancies found will be reviewed for potentialimpact on circuit breaker operability. This review will be complete prior to start-up from the current outage. In addition, the procedures that perform maintenance on the AllB 480 volt and General Electric 4160-volt circuit breakers will be reviewed in the same manner to that of the Westinghouse circuit breakers. This review will be complete by August 30,1997. l In an overall effort to improve the quality of maintenance procedures a sample of electrical, mechanical, and control and instrumentation procedures will be reviewed for '

confonnance with vendor instructions. The results of this review will determine the necessity to increase the scope of this review to include all or some additional portion of maintenance procedures based on vendor instructions. The review of the sample of procedures will be complete by August 1,1998.

In summary, in light of our recent corrective actions and plant'ed compensatory measures, Illinois Power has reasonable assurance that our 4160 volt circuit breakers will perform their safety function, if you have any questions about the resolution of these circuit breaker problems please contact me at (217) 935 8881 extension 3400.

Sincerely yours, (D a y."

g ;L,b,f Wayne D. Romberg Assistant Vice President MRS/krk Enclosure ec: J. L Caldwell, USNRC, Region ill G. C. Wright, USNRC, Region til M. A. Ring, USNRC, Region 111 NRC Resident Omce, V 690 Document Control Desk, USNRC Dave Zemel, T-31Z

u. a v , a , . . eu - me,.e m o . , .,m, m__ ,. m

{\ s\

V

: : ;- m  :::asatcownon Electric Corporation g,'% ' ' * * '% "  ;

aucww chseed.Pa 150N 1386 l

.Wy N.1997 ' ,

RRs/AosT(st)oss '

Mr. Don Lukach Illinois Power and Light Company Clinton Station ,

P.O. Box 678 Clinton,IL 61727

  • o

Subject:

Prelissinary Report DHP Breaker Failure Analysis Illinois Power Co. Clinton Power Plant .

Sleop Order 01YN005B4 Serial #2 De.4r Mr. Lukach:

This is a preliminary failure analysis report. His analysis was conducted in the Greenwood manufacturing plant, Greenwood, South Caroline on Saturday, July 25, 1997.

De scope of the failure analysis was performed following purchase order instructions (P.O. # 705276), General Order # ST30665. N.3.E.D. Attachment #1,90356 Rev. #1.

Psior to beginning the failure analysis, the analysis steps to be performed were reviewed and approved by Illinois power and Cutler.liammer representatives.

The circuit breaker was removed from tbc shipping container and visually inspected.

He breaker appeared to be in good condition and the only noticeable sign the breaker had failed was the blackened open coil. The circuit breaker operations counter indicated

$51 operations. The breaker was exercised mechanically without failure. Main contact gaps were checked and found to be slightly wider than outlined in DlIP circuit breaker 1.L 32 2534B. Main contacu and arching contacts showed minimal wear, contact alignment was good, contact synchronization good and contact penetration good. The puffer adjust,nent was checked and found to be slightly over the recommended setting.

He contacts were not adjusted for this analysis. De mechanism mechanically operated freely which is a good measure of the effectiveness of past preventative maintenance.

The open coil (tip coil) was replaced including the complete trip solenoid assembly.

Tais was done because the open coil could not be removed from the assembly without further damaging the assembly. The close coil was also replaced because it had a black mark on the coil insulation caused when the open coil overheated and open. The breaker was electrically operated,5 times at normal voltage,5 times at maximum voltaBe, S

,,, m -va o u . - ~ --

times at minimum voltage and 5 this at normal voltage to verify tbc anti pump feature.

All electrical operations were crisp and without failure.

The circuit breaker opening and closing intervals were recorded using a PROGRAMA Circuit Breaker Test Device. Tbc close interval was wit * ' ' in sp- .ific-tion and the trip interval was just out (or stichtly slower) than the specifuden tiraits.

In order to detennine if any mechanical component may have contnbuted to the failure o! the breaku, we changed opening springs, main contact Lick off spnng;, adjusted the main contact hinge bolts and puffer. These replacements and adjustments were cnade in ,

sequence and timing was performed after each event. The results were inconclusive in that tbc effect of each adjustamt of par 1 change had very little effect on the opening or closing speed of the mechanism. The snain contacts we e not adjusted for this anal >ils because the slightly wider main contact gaps would promote quicker releap and contact opening, ne mechanism was dismantled and each part associated upth tbc opening or closing of

^

the main contacts visually inspected. We found that the main shaA bearings were still in very good condition with original factory lubrkation (breaker was manufactured in -

1978). The pint connecting the main shaft to the main contact push rods were removed and found to have some lubricant on the pins, but,the lubrication felt st;cky indicating the lubrication was drying. We found the same condition on the puffer operating lirJc pivot pins. The re maining parts in the snechanism were visually inspected and found to be in very good condition.

Conclusion 1he circutt breaker was operated a total of $1 times without failure. Part replacement and mechanism tear down d.d not provide evidence that would identify one particular cause for the in service failure There is r.o evidence found to indicate a mechanical deficiency or a generic problem with this circuit breaker or with the existing preventative maintenance program. The cause of the breaker failure to open has not boca determined at this time.

We will continue the analysis by mearunnF mechanism parts to determine if any part associated with the opening of the mechanism is out of tolerance or wom to the point where replacement would be recommended. The analysis should be completed by the end of this week with a final repoti a few days later.

.,w a v , o , . , m w, - - c . . - . . . a ~a . u , .,- - - - . mm s a .

I ItsiB N t j At th's point, based on the prelkainey la@ of this ckcuit breaker, k 1s my opinion the reventet.5 maintenance pwformed on this circuit tweaker was adequate to maintain the propw oparadon of the breaker. Using this circuit breaks as a aanple of one, I believe 'hst the remaining circuit breakers at the Clinton Power Plant. maintained under de same program should provide safe and eNective operation. ,

l r

No recornmendatlots at this time. Continue to operate under existing procedures and  ;

guidelmes.

Sincerely, i

n ^- - - - - k.- o, _

' Thomat R. Critchlow, Enpirwe, Distribet)Srues :Engiercing ,

/eks i i Attachments (2) .;.

cc: Rick Redding Clinton Station Linda DeGrofft Clinton Station John Dence Cutler Hammer Chuck Kelley Cutler Hammer ,

Bob Folino Westinghouse i Dale Rygg Westinghouse Tom Moser Westinghouse <

Dick Miller Westinghouse

s elu l-* 2 9 9 7 013300A* . . . . . . ... .. ..,..ws .ww....-~~.~ . ~ ww P.OG e, , JtA. ns

  • y/ 141W W C* r$.0 CLA.!TY 0@
  • 9649426419 TO 814172753189--43 P.e5/95 I,

Cutler Hammer i

Westinghouse & Cutler Hammer Products l Afr.errnarket Product Center I 2210 Laurens Highway Gro6nwood, SC 29649 l Type _Sonap 360 _ _ Amps /4o _ sye No. _o I Y d a a aA A EAT N l

serw No. J .

I 0 0, No. _ diYonon04 w s.o.No. C / V A/Oof/N namoheniset vwir,oetien

i. Nam.,w.e verision. ion

/

t

f. InitialVoederCounterMeeding
s. Manus one,,e, oi.ee, one r,v OTE! _

/

4. Audiery ownen operosion -
s. Prima 7 Disconnect Ahenment

/

s. steshw P Ween interlook Funonon
7. Ground contact ^7 ;w.t b
8. Ptoor Tripper Operation [
s. Cose Pwe veruicamon O

. 10. Fren Pand inesensson -

V-

, b \1. Genesel Appoorsnee end Clooniness

\

. Doettleel verifleetlen

' it. Vefify Motor. C8oos and THp Voltagee

13. Ceese et Minimum, Nomirk', and Mesimum Voltagee 1 14. Tito at Minimum. Nominal and Maximum Vollegee #

1s. Contant Meelesence's in Mien 4hme et 100 Ampa D C.

i Phase 11 Phase 2 44 Phase s lfi., Derdh

18. Centml Wiring Conelnuity ' FQuV
17. VerWy Brasher WirtAg Manchee 6.0. SchemeWo it. Aunthery Swllch Wirtng P it. Operation of Crei;: Trip #

l 30. Opemelon of Antipurvy Meisti N 4 .

21. Generalf;; r.xm and Cleanlinese 1 St. Mnes ve54r Coumer Reeding
23. Hi Pet Tese

_o05 I3 , _

l 94, leur Yeltage 8meher Trip Urdt Thet Dghtt#Anyte<ter

- - 4 Tale oW brasher enoots oil cluelay seendente in eccentence w6th the Ahormert stooeduees. ,

em inspecaer

' 1/ 7% VO 7 seei, ion,ree,er _ 71 4 oeie 7/E8/77 r r i D. _ 7- a t, - t 7 I ,]

}

ATTACHMENT 3 1

1 ;'." h "* '9' , l' =. ^ ... - . .. . . . . :.:. ::. .- = '- :.:.::.; '; ; ====  ; = =

. 1

~ TEST REPORT

, TY PE. DH P \ R. C'I RC u lT B R EA.KE.R  !

ttvrem er C-Ao- o ut.

es.c n, w tr g?-

2. 1 \ DEhl7\FK.AT10N : C -@ -

m n,,, g i TYPE OF BKR. b og, 360 '

CLASING V6LTAGE 10-1303 M A X . KV. 5 CLOSING AMPS 5 HERT7_ 40 TRIP V61.TAGE 'to"W086 g RATED 5.C.CORREMT 41 TRIP AMPS 5

" STYLE No.01740 W . MOTOR V6LTAGE 12,6%

CONT)Mubus AHPS laso 1. B . N o. 5.1 -85.4 A.

j$;

. C&L KA gm,, . us 78 m DATE mm .OF MAMUF. 5/'7f

tl

~~

32tp.(o we 3 8 H T.

4.2 ABJOSTMENTS

G-Jo h

t.AM.M CMEN St.A.

5. ELE (TRICA\. 6PERATIONS TEST .E.3o Mc/Tese S. 2 MIN. CONTROL VOLTAGE 100 '/ Doc voers
5. A MAX. CONTROL VDLTAGE t)cac h eoc.. votTs % .
5. 4 NON. (DNTROL Yo E - ANTL POMP TEST tarer/iara 5.S NtM.C.0NTRol. V E 74 4 / erne vetTsie=/> c votTs

~7 IN50LATibNB TEdiS Se a.o 7.3 7A TEST Al.L SECONDARY MtlNG /bR l Niu. AT IS06votTs Go Hz.

TEST Al.l. PR1 MARY INSul.ATl0R ALL So DHP BREAKERS FOR 1 MlN. Go 42.

19 KV Au 7t>!CO N P APrn ses xc yu 8 TtMWG TESTS .f:!Lo y um e

Fhn. Titre '

J.

PRIMARYmA CohlDBCTAhKE TESTS G- @ - *o ma ec 3

.23 11 i

.2.S. l tD. DC. UhlDERVMT. 9/A bRoP OUT VOLTAGE ME TRIP TtESTS9/A PKW UP V0LTAGE 35 4 lo 60Y.

/A B6%

, I. ' NGTE'5 : , ba y.u y

.. :n Dm ,hsM -r -

, i, n y .fp +t..

., c %g.e .'

w

. ::e ..g s z.

. . ..E,cgg'm,3 ,i ~

j i

i t .

I l

As found condition of Westinghouse 4160 volt safety-related circuit breaker l i

W-w '

\ , v f ;, llg i V'ay'  :,

  • ^.

c ,

y i< r3 n

  • y , o% ,
.' ~* ,

d .,> {> 4 g.g.  ;

,m gr . , i, r

^ a

+  : *

,[;

a #

_9  ;

f , . - F ~ \

G Y, .

h

, * @ L g 4 a \

%. y 1 g  ; t. 4 - , q; ; w

?*

tjo'

.yS

. . j sa ' ;,l. ht 9, y 5, % '

p 4 'm. ,a

    • 4 1 m ;. . -
Q ?.. ' ~j.

ih k

e

. $" } }

~

a. ~ ~

?%.y; q'  ;, -.<..

' _ v f, ] I-J -

1 '! . ' pI [W , h, 0.[

J

' I Y.5 h 4 [f #

n , .. ;% hh

-c ,

s Qj' ,y,

! y

-- k_ l e-? g' :., yn u l

  • y

\. e

n. , f a..

<ri

'b

)

Q 8

i

",22kfhe s. . lib,%%J t

", .. * '. , . ' ) f b

{-

Y ( [

?, ?

l  ? h I -l

' q q. ',

, s. s' . 99 . > . . it . . . .

4 g 1

. .$5i{'s ?ui fW pN,oin;,'g 4 %, ?ti$D,f{rf-h [Nf? ] f : ' D;7 :;

j' T: d ' ' .-'h '.

,.w.' '

I -

f

.. s . o . m
.h . . mL
  • 5g 241 % .bi4#w.w.-r 4:Giy '

.fll;-l -l ' .., .'. rx.n a ' i: . rt-lf i

. l !)}

^

, a{p.. . . s ;, c, . .

-. w. .

i ,

1

,, l =

                                                                    * ~                                                                                                                                                                                                                     '
                                                                                                                                                                                     ....           v.

I , t . ..  ; ( -c 4 - .- .. essa 4 . l e ,

                                                    .                                p.
                                                                                                                    .:           e. .

l ' ~ h f i e 4 Y{a a g

                                               ,                                                                   ,.           % ^
                                          ,s-                                                                      c.                                                                       .                                                                      r           .

ey, a T y *

  • 3 .
                                                                                                                                                                                                                                                                           %?( o 3

. c. - .

                                                                                                                                                       -                                                    w..
                                                                                                                                                                                                                                                                  ,                                 3, 4                                                                                                                                                                                                                 P                                    4 ...

i ~ -

                                                                                                                                                                                                                                                      .'44       #    E Mw:ed .wh .* a- p .

b d

 ;I a

l j ' s 1 i i l _ _ _ ___ . ._ , _ . _ . . - _ - _ . _ _ . . _ . . _ _ _ . _ . _ _ _ _ . __._.__ . _ _ . _}}