Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML18139A870 + (02:16:43, 6 January 2025)
- ML18139A869 + (02:16:45, 6 January 2025)
- ML18139A868 + (02:16:46, 6 January 2025)
- ML18139A867 + (02:16:48, 6 January 2025)
- 05000281/LER-1980-036-03, /03L-0:on 801101,discovered That MOV-FW-251B Could Not Be Closed from Control Room.Caused by Misplacement of Limitorque Cover & Three Broken Control Wires.Cover & Wires Replaced + (02:16:50, 6 January 2025)
- 05000281/LER-1980-036, Forwards LER 80-036/03L-0 + (02:16:52, 6 January 2025)
- 05000280/LER-1980-070-01, /01T-0:on 801114,S&W Informed Util That Out of Phase Transfer Might Occur When Emergency Buses Transferred from Offsite Source.Caused by Undeterminable Design Error. Time Delay Circuit Installed + (02:16:54, 6 January 2025)
- 05000280/LER-1980-070, Forwards LER 80-070/01T-0 + (02:16:56, 6 January 2025)
- ML18139A858 + (02:16:57, 6 January 2025)
- ML18139A860 + (02:16:57, 6 January 2025)
- ML18139A857 + (02:16:59, 6 January 2025)
- ML18139A856 + (02:17:00, 6 January 2025)
- ML18139A855 + (02:17:01, 6 January 2025)
- 05000280/LER-1980-069-03, /03L-0:on 801022,PT-27D Revealed Low Amp Reading for Panel 8,circuit 13A (Boron Injection Recirculation to Boric Acid Tanks).Caused by Excessive Heat.Failed Heat Tape Replaced + (02:17:02, 6 January 2025)
- 05000280/LER-1980-069, Forwards LER 80-069/03L-0 + (02:17:04, 6 January 2025)
- ML18139A851 + (02:17:05, 6 January 2025)
- ML18139A849 + (02:17:06, 6 January 2025)
- ML18139A850 + (02:17:06, 6 January 2025)
- ML18139A848 + (02:17:07, 6 January 2025)
- 05000280/LER-1980-062-03, /03L-0:on 801019,w/unit at Cold Shutdown & Defueled,Pt 26.1 Showed RM-CC-105/106 Alarm Setpoint to Be Greater than Twice Background Radiation Levels.Caused by Decrease in Background Radiation Levels.Setpoints Reduced + (02:17:08, 6 January 2025)
- 05000280/LER-1980-032-03, /03L-0:on 801020,during Check of Low Heat Tracing Alarms,Circuit 2A Panel 11 Found to Have Low Amps.Caused by Damage to Heat Tracing Tape.Operation of Redundant Heat Tracing Circuit Verified & Tape Replaced + (02:17:10, 6 January 2025)
- 05000280/LER-1980-033-03, /03L-0:on 801024,w/unit at 100% Power,Positive Pressure of Greater That 0.05 Inches of Water Could Not Be Maintained in Control Room.Caused by Deterioration of Door Seals.Defective Doors Repaired + (02:17:12, 6 January 2025)
- ML18139A842 + (02:17:13, 6 January 2025)
- ML18139A843 + (02:17:13, 6 January 2025)
- ML18139A841 + (02:17:14, 6 January 2025)
- IR 05000280/1980031 + (02:17:15, 6 January 2025)
- ML18139A838 + (02:17:17, 6 January 2025)
- ML18139A837 + (02:17:18, 6 January 2025)
- ML18139A836 + (02:17:19, 6 January 2025)
- ML18139A834 + (02:17:20, 6 January 2025)
- ML18139A832 + (02:17:21, 6 January 2025)
- ML18139A830 + (02:17:22, 6 January 2025)
- 05000281/LER-1980-035-01, /01T-0:on 801101,electrical Transient Tripped Breaker & Two Emergency Generators Started & Loaded.Caused by Contact of Jackhammer with Power Cable.Emergency Diesel Generators Verified Operating & Supplying Emergency Buses + (02:17:24, 6 January 2025)
- 05000281/LER-1980-031-03, /03L-0:on 801015,pipe Support in Alternate Charging Header Found in Overstressed Condition Per IE Bulletin 79-14,Suppl 2.Caused by Faulty Installation. Modified Support & Returned Subsys to Svc + (02:17:25, 6 January 2025)
- ML18139A826 + (02:17:26, 6 January 2025)
- ML18139A825 + (02:17:28, 6 January 2025)
- ML18139A824 + (02:17:29, 6 January 2025)
- ML18139A822 + (02:17:30, 6 January 2025)
- ML18139A820 + (02:17:31, 6 January 2025)
- 05000281/LER-1980-029-03, /03L-0:on 801012,svc Water Pump 2-SW-P-10A Developed Low Discharge Pressure.Caused by Eel Lodged in Impeller.Eel Removed,Pump Returned to Svc + (02:17:32, 6 January 2025)
- 05000281/LER-1980-029, Forwards LER 80-029/03L-0 + (02:17:34, 6 January 2025)
- 05000280/LER-1980-067-01, /01T-0:on 801028,indications Found on All Three Steam Generators.Caused by Original Const.Weld Areas Will Be Completely Machined Out & Replaced + (02:17:36, 6 January 2025)
- 05000280/LER-1980-067, Forwards LER 80-067/01T-0 + (02:17:37, 6 January 2025)
- ML18139A813 + (02:17:39, 6 January 2025)
- ML18139A812 + (02:17:40, 6 January 2025)
- ML18139A811 + (02:17:41, 6 January 2025)
- ML18139A810 + (02:17:42, 6 January 2025)
- 05000281/LER-1980-030-03, /03L-0:on 801013,at 100% power,PT-27B Indicated Low Amp Reading on Circuit 6A,boric Acid to Blender Panel 10.Caused by Heat Tracing Failure Due to Mechanical Damage Sustained from Erecting Scaffolding + (02:17:43, 6 January 2025)
- 05000281/LER-1980-030, Forwards LER 80-030/03L-0 + (02:17:45, 6 January 2025)
- ML18139A806 + (02:17:46, 6 January 2025)
- ML18139A805 + (02:17:47, 6 January 2025)