- IR 05000416/1986037 + (03:30:40, 4 December 2024)
- 05000397/LER-1986-031, :on 860910,RCIC Inboard Steam Line Isolation Valves Closed on Erroneous RCIC Equipment Area High Temp Signal.Caused by Technicians Inadvertently Connecting Test Equipment to Wrong Circuit.Personnel Counseled + (03:30:42, 4 December 2024)
- ML20215F564 + (03:30:43, 4 December 2024)
- ML20215F563 + (03:30:43, 4 December 2024)
- U-600720, Forwards Summary of Results of Preoperational Phase Testing of Piping Vibration,Thermal Expansion & Dynamic Effects,Per FSAR Subsection 3.9.2.Tests Complete Preoperational Phase Evaluation of Piping Sys + (03:30:44, 4 December 2024)
- ML20215F559 + (03:30:44, 4 December 2024)
- ML20215F557 + (03:30:45, 4 December 2024)
- ML20215F552 + (03:30:46, 4 December 2024)
- ML20215F551 + (03:30:47, 4 December 2024)
- ML20215F549 + (03:30:48, 4 December 2024)
- ML20215F546 + (03:30:48, 4 December 2024)
- ML20215F545 + (03:30:49, 4 December 2024)
- RBG-25090, Responds to Re Effects of Potential Bankruptcy of Util on Facility.Util Continues to Fulfill All Financial Obligations + (03:30:49, 4 December 2024)
- 05000298/LER-1986-034, :on 861118,discovered That New Fuel Stored in Spent Fuel Storage Pool Contained U-235 Loading in Excess of Tech Specs.Caused by Newer GE-designed Pellets W/Higher Density.Design Will Be Reviewed + (03:30:52, 4 December 2024)
- ML20215F537 + (03:30:54, 4 December 2024)
- ML20215F534 + (03:30:55, 4 December 2024)
- ML20215F533 + (03:30:55, 4 December 2024)
- 05000321/LER-1986-037, :on 860906,one Half Primary Containment Isolation Sys Group 2 Isolation Occurred.Caused by Blown Fuse & Relay Coil Failure.Relay Coil Replaced & One Half Group 2 Signal Reset + (03:30:57, 4 December 2024)
- ML20215F527 + (03:30:58, 4 December 2024)
- ML20215F528 + (03:30:58, 4 December 2024)
- IR 05000259/1986037 + (03:30:59, 4 December 2024)
- ML20215F518 + (03:31:00, 4 December 2024)
- JAFP-86-0857, Monthly Operating Rept for Sept 1986 + (03:31:01, 4 December 2024)
- L-86-517, Forwards Rev 4 to Training & Qualification Plan.Rev Withheld (Ref 10CFR73.21) + (03:31:02, 4 December 2024)
- ML20215F511 + (03:31:02, 4 December 2024)
- 05000322/LER-1986-045, :on 861127,reactor Bldg Standby Ventilation Sys/Control Room Air Conditioning Sys Inadvertently Actuated During Change in Monitor Bulb.Caused by Personnel Error.Personnel Counseled + (03:31:04, 4 December 2024)
- ML20215F503 + (03:31:05, 4 December 2024)
- ML20215F504 + (03:31:05, 4 December 2024)
- 05000293/LER-1986-027, :on 861119,plant Experienced Loss of Offsite Power During Severe Winter Storm.Caused by Arcing of High Voltage Lines Due to Heavy Ice & Snow.All Safety Sys Performed as Expected + (03:31:07, 4 December 2024)
- 05000213/LER-1986-043, :on 861108,wide-range Noble Gas Stack Monitor RMS-14B Failed Low.Caused by Improper Setting for New Photomultiplier Tube Preventing Pulses from Passing Through & Being Registered by Electronics + (03:31:09, 4 December 2024)
- 05000220/LER-1986-028, :on 860910,discovered That Supply Valves to Sampling Points Utilized for Obtaining 12-h Grab Samples of Svc Water Discharge Closed.Cause Not Stated.Valves Reopened So That Representative Sample Could Be Taken + (03:31:11, 4 December 2024)
- ML20215F492 + (03:31:12, 4 December 2024)
- 05000366/LER-1986-023-01, :on 860903,reactor Protection Sys Scram Occurred.Caused by Leaking Oil Filter Gasket Initiating Main Turbine trip.Electro-hydraulic Control Leak Repaired, Procedures Revised & Personnel Counseled + (03:31:14, 4 December 2024)
- ML20215F484 + (03:31:14, 4 December 2024)
- IR 05000327/1986032 + (03:31:42, 4 December 2024)
- ML20215F479 + (03:31:45, 4 December 2024)
- 05000395/LER-1986-015, :on 860908 & 25,hourly Fire Watch Patrols Not Performed in Various Areas in Time Required by Tech Specs. Caused by Personnel Error.Personnel Counseled + (03:31:47, 4 December 2024)
- IR 05000327/1986057 + (03:31:48, 4 December 2024)
- ML20215F468 + (03:31:49, 4 December 2024)
- ML20215F470 + (03:31:49, 4 December 2024)
- ML20215F467 + (03:31:50, 4 December 2024)
- RBG-24508, Suppls 860514 Response to Item a of IE Bulletin 85-003.BWR Owners Group Efforts to Develop Generic Position for Meeting Item a Documented in 860902 Submittal.Completion of Items b-d Anticipated by 871115 + (03:31:50, 4 December 2024)
- ML20215F464 + (03:31:54, 4 December 2024)
- ML20215F463 + (03:31:55, 4 December 2024)
- ML20215F459 + (03:31:56, 4 December 2024)
- ML20215F460 + (03:31:56, 4 December 2024)
- 05000280/LER-1986-034, :on 861117,control/relay Room Chiller C Tripped Due to High Condenser Pressure,Leaving Only One Operable Chiller,In Violation of Tech Specs.Caused by Clogged Suction Strainer.Strainer Cleaned + (03:31:58, 4 December 2024)
- ML20215F457 + (03:31:59, 4 December 2024)
- ML20215F456 + (03:31:59, 4 December 2024)
- ML20215F455 + (03:32:00, 4 December 2024)
- ML20215F454 + (03:32:01, 4 December 2024)
- 05000325/LER-1986-030, :on 861120 & 1204,reactor Protection Sys Buses Deenergized on Units 2 & 1,respectively.Caused by Tripping of Motor Generator Set Output Breakers.Breaker Removed, Tested,Reinstalled & Returned to Svc + (03:32:02, 4 December 2024)