- ML20077M663 + (06:15:28, 15 December 2024)
- 05000317/LER-1983-042-03, /03L-0:on 830729,auxiliary Feedwater Flow Indicator to Steam Generator 11 Found Reading Incorrectly. Caused by Zero Ref Shifting Low on Flow Transmitter 1-FT-4509.Transmitter Recalibr + (06:15:30, 15 December 2024)
- ML20077M650 + (06:15:31, 15 December 2024)
- 05000251/LER-1983-009-03, /03L-0:on 830803,steam Generator 4A Blowdown Isolation Valve CV-4-6275A Failed to Close Upon Blowdown Isolation Signal.Caused by Instrument Air Isolation to Valve Actuator.Instrument Air Supply Restored + (06:15:33, 15 December 2024)
- 05000321/LER-1983-076-03, /03L-0:on 830806,w/reactor Cleanup Pumps Out of Svc,Determined That Conductivity Monitor Failed Downscale. Caused by Plugged Monitor Sample Line.Pumps Returned to Svc + (06:15:35, 15 December 2024)
- ML20077M638 + (06:15:36, 15 December 2024)
- 05000366/LER-1983-078-03, /03L-0:on 830804,five Drywell Pneumatic Sys Drain Valves Closed But Not Locked & Sealed.Caused by Personnel Error.Valves Immediately Locked & Sealed + (06:15:37, 15 December 2024)
- 05000361/LER-1983-103-03, /03L-0:on 830730,w/unit Operating at 92%,rapid Reduction in Power Commenced to Clean Debris from Traveling Screen Sys.W/Power at 52% During Xenon Transient,Tc Observed Outside Limits of Limiting Conditions + (06:15:39, 15 December 2024)
- L-94-325, Comment on Proposed Rule 10CFR50 Re Fracture Toughness Requirements for LWR Pressure Vessels.Endorses NEI Comments & Recommendations + (06:15:40, 15 December 2024)
- ML20077M622 + (06:15:44, 15 December 2024)
- ML20077M618 + (06:15:48, 15 December 2024)
- 05000315/LER-1983-078-01, /01T-0:on 830831,adequately Designed tie-down Features Not Installed on Pressurizer Ventilation Sys Inside Containment.Caused by Inadequate Administrative Controls During Design Mod + (06:15:49, 15 December 2024)
- 05000251/LER-1983-007-03, /03L-0:on 830803,during Routine Temp Reduction on Pressurizer Relief Tank Prior to Pumping,High Level Alarm Received Followed by Rupturing of Rupture Discs.Caused by Overpressurization.Ruptured Disc Replaced + (06:15:51, 15 December 2024)
- BECO-95-001, Forwards Reformatted Version of TS & Bases,Allowing Access of Document in Electronic Form for Review & Concurrence + (06:15:52, 15 December 2024)
- ML20077M605 + (06:15:53, 15 December 2024)
- AECM-83-0535, Updated RO 83-006/2:on 830210,fire Penetrations AE-382C & AE-384C Opened to Allow Performance of Planned Maint.Work Completed & Limiting Condition for Operation Lifted 830827 + (06:15:54, 15 December 2024)
- 05000316/LER-1983-076-01, /01T-0:on 830830,discovered Leak on Nonessential Svc Water Header Supplying Reactor Coolant Pump Fire Protection Sys.Caused by Leaking Strainer Blowdown Connection Isolation Valve + (06:15:56, 15 December 2024)
- ML20077M579 + (06:15:57, 15 December 2024)
- ML20077M583 + (06:15:57, 15 December 2024)
- ML20077M573 + (06:15:58, 15 December 2024)
- AECM-83-0531, RO 83-054/1:on 830608,fire Rated Doors Blocked Open to Support Planned Maint in Auxiliary & Control Bldgs.All Doors Restored to Operability.Limiting Condition for Operation Lifted 830822 + (06:15:59, 15 December 2024)
- DCL-95-001, Comment on Proposed Changes to Reactor Pressure Vessel Integrity Rule 10CFR50.Endorses NEI Comments + (06:15:59, 15 December 2024)
- AECM-83-0530, RO 83-046/1:on 830515,during Surveillance Testing,Fire Door OC103 Found Damaged & in Constant Alarm State.Caused by Damage from Heavy Use.Hourly Fire Watch Conducted Until Door Restored to Operability on 830825 + (06:16:00, 15 December 2024)
- ML20077M547 + (06:16:01, 15 December 2024)
- 05000316/LER-1983-073-01, /01T-0:on 830815,evaluation of Field Insp Findings Re safety-related Electrical Cabinets Revealed Battery Charges for Train AB Not Adequately Anchored.Caused by Nuts Not Being Installed.Nuts Installed + (06:16:02, 15 December 2024)
- ML20077M531 + (06:16:03, 15 December 2024)
- ML20077M518 + (06:16:04, 15 December 2024)
- ML20077M515 + (06:16:04, 15 December 2024)
- ML20077M508 + (06:16:05, 15 December 2024)
- ML20077M503 + (06:16:06, 15 December 2024)
- 05000346/LER-1983-042-03, /03L-0:on 830801 & 06,main Steam Line Room Doors 601 & 602 Found Open & Unattended.Caused by Personnel Error. Personnel Counseled + (06:16:08, 15 December 2024)
- B10887, Forwards Amend 1 to Probabilistic Safety Study + (06:16:09, 15 December 2024)
- ML20077M480 + (06:16:13, 15 December 2024)
- 05000315/LER-1983-076-03, /03L-0:on 830807,during Refueling Shutdown,Fire Detection Sys Alarm for Zone 3 in Auxiliary Bldg Received in Control Room.Caused by Faulty Detector Setpoint.New Detector Installed + (06:16:15, 15 December 2024)
- ML20077M475 + (06:16:16, 15 December 2024)
- ML20077M472 + (06:16:16, 15 December 2024)
- ML20077M469 + (06:16:17, 15 December 2024)
- ML20077M458 + (06:16:18, 15 December 2024)
- 05000244/LER-1983-022-03, /03L-0:on 830725,while Performing Procedure S-16.2 Nitrogen Makeup to Accumulators,Containment Isolation Valve AOV-846 for Nitrogen Supply to Containment Seized in Mid Position.Caused by Galling Plug + (06:16:20, 15 December 2024)
- ML20077M447 + (06:16:21, 15 December 2024)
- ML20077M444 + (06:16:21, 15 December 2024)
- ML20077M437 + (06:16:22, 15 December 2024)
- ML20077M436 + (06:16:22, 15 December 2024)
- ML20077M431 + (06:16:25, 15 December 2024)
- ML20077M427 + (06:16:25, 15 December 2024)
- ML20077M426 + (06:16:26, 15 December 2024)
- ML20077M421 + (06:16:27, 15 December 2024)
- ML20077M425 + (06:16:27, 15 December 2024)
- ML20077M418 + (06:16:28, 15 December 2024)
- ML20077M416 + (06:16:29, 15 December 2024)
- 0CAN089108, Provides Response to Suppl 2 to NRC Bulletin 89-001, Failure of Westinghouse Steam Generator Tube Mechanical Plugs + (06:16:30, 15 December 2024)
- ML20077M412 + (06:16:31, 15 December 2024)