- 05000397/LER-1985-016, :on 850213,reactor Scrammed & HPCS Sys Automatically Initiated.Caused by Incorrect Differential Pressure Instrument Being Valved Into Svc.Instruments Verified for Proper Calibr + (11:11:19, 13 December 2024)
- ML20100A287 + (11:11:23, 13 December 2024)
- 05000373/LER-1985-020, :on 850214,gate to High Radiation Area Found Unlocked & Unattended.Caused by Individual Leaving High Radiation Gate Open & Unattended.Gate Closed & Secured & Personnel Counseled + (11:11:25, 13 December 2024)
- 05000388/LER-1985-008, :on 850216,logic Power Lost to HPCI & Loop B of Core Spray.Caused by Broken Lug on Negative Terminal.Lug Replaced.Power Restored + (11:11:27, 13 December 2024)
- W3P85-0664, Monthly Operating Rept for Feb 1985 + (11:11:28, 13 December 2024)
- 05000374/LER-1985-008-02, :on 850213,high Chlorine/Ammonia Concentration Alarm Received for Train B of HVAC Sys.Caused by Chemcassette Being Out of Tape.Exhausted Chemcassette Replaced & Trip Reset + (11:11:30, 13 December 2024)
- BSEP-84-2609, RO-2-84-12:on 841024,automatic Reactor Protection Sys High Pressure Scram Occurred When MSIVs Closed on Group 1 Isolation Signal.Investigation Still in Progress.Ler Will Be Delayed Until 841214 + (11:11:32, 13 December 2024)
- ML20100A238 + (11:11:34, 13 December 2024)
- ML20100A243 + (11:11:34, 13 December 2024)
- ML20100A237 + (11:11:35, 13 December 2024)
- ML20100A236 + (11:11:36, 13 December 2024)
- 05000483/LER-1985-004, :on 850125 & 0202,control Room Ventilation & Containment Purge Isolations Occurred.Caused by Incorrect High Radiation Signals Due to High Vacuum at Inlet Sample Line to Containment Process Monitor + (11:11:38, 13 December 2024)
- 05000413/LER-1985-011, :on 850207,safety Injection Trains a & B Inoperable.Caused by Personnel Error.Pump 1B Returned to Svc & Operator Update Issued Addressing Impact of Solid State Protection Sys Inoperability + (11:11:40, 13 December 2024)
- 05000454/LER-1984-041-01, :on 841031,ultraviolet Detector in Zone 38 Failed to Annunciate & Fire Catch Not Initiated Until 841212.Caused by Inoperability of Detector.Replaced Detector Not Proven Operable + (11:11:42, 13 December 2024)
- 05000237/LER-1985-007-03, :on 850215,weekly Operating Surveillances Not Completed.Caused by Operator Overlooking Surveillances on Weekly Schedule Due to Another Operator Incorrectly Recording Surveillances + (11:11:48, 13 December 2024)
- 05000237/LER-1985-006-04, :on 850217,reactor Scram Occurred During Undervoltage Tests.Caused by Misunderstanding of Ae Re Power Supply Divisionalization.Power Supplies Will Be Redesigned, Rewired & Tested + (11:11:50, 13 December 2024)
- 05000373/LER-1985-018-01, :on 850216,H2 Grab Sample Obtained for Unit Offgas Hydrogen Recombiner Effluent.Caused by Inoperability of Hydrogen Analyzers.Sample Obtained at Greater than Allowable Frequency + (11:11:53, 13 December 2024)
- ML20100A183 + (11:11:54, 13 December 2024)
- ML20100A178 + (11:11:55, 13 December 2024)
- ML20100A176 + (11:11:56, 13 December 2024)
- ML20100A173 + (11:11:57, 13 December 2024)
- 05000333/LER-1985-006, :on 850215 Turbine Trip & Reactor Scam Occurred.Caused by Closed Instrument Root Valve for Pressure Transmitter.Mod to Unbalance Circuit,Providing Indication of Circuit Failure Planned + (11:11:58, 13 December 2024)
- 05000220/LER-1985-002, :on 850214,auxiliary Control Room Fire Suppression Sys Inoperable.Caused by Inoperable Fire Dampers.Fire Dampers Repaired & Tested.Personnel Instructed in Tech Spec Requirements + (11:12:01, 13 December 2024)
- ML20100A154 + (11:12:02, 13 December 2024)
- ML20100A145 + (11:12:03, 13 December 2024)
- ML20100A144 + (11:12:04, 13 December 2024)
- 05000237/LER-1984-025, :on 841220,main Feed Breaker 152-2430 on Bus 24-1 Failed to Trip Open.Caused by Dirty Auxiliary Breaker Contacts.Contact Cleaned,Tested & Returned to Svc + (11:12:05, 13 December 2024)
- ML20100A124 + (11:12:07, 13 December 2024)
- RBG-42311, Responds to RAI Pertaining to LAR 95-04,Changes to TS Re Fuel Handling Accident Conditions + (11:12:07, 13 December 2024)
- ML20100A120 + (11:12:08, 13 December 2024)
- 05000382/LER-1985-005, :on 850216 & 18,automatic Actuation of ESF Portion of Control Room Ventilation Sys Occurred.Caused by Air Intake Radiation Monitors Spiking High.Electrocubes Installed to Filter Noise Spikes + (11:12:10, 13 December 2024)
- ML20100A095 + (11:12:11, 13 December 2024)
- 05000275/LER-1985-009, :on 850213,steam Line Differential Pressure Injection Signal Received,Resulting in Safety Injection, Turbine Trip & Reactor Trip.Caused by Frequency Interference from Radio.Procedure Revised + (11:12:13, 13 December 2024)
- ML20100A086 + (11:12:14, 13 December 2024)
- ML20100A075 + (11:12:15, 13 December 2024)
- 05000325/LER-1985-009, :on 850215,monthly Channel Functional Testing of Reactor Bldg Roof Ventilation Monitor Revealed Annunciator Card for Monitor Control Room Alarm Not Installed.Cause Unknown + (11:12:16, 13 December 2024)
- 05000370/LER-1985-005-02, :on 850212,diesel Generator 2B Experienced Invalid Automatic Start.Caused by Electrical Storm Causing Voltage Dip on Train B Essential Switchgear.Mod to Undervoltage Relays Will Be Installed + (11:12:18, 13 December 2024)
- 05000305/LER-1985-004, :on 850210,control Room Operator Noticed Reactor Coolant Pump 1B Running.Caused by Grounded Condition in Actuation Circuitry Due to Water Accumulation in Pressure Switch.Hardware Mod Being Evaluated + (11:12:20, 13 December 2024)
- 05000250/LER-1985-005-01, :on 850205,during Work Order to Clean Four Batteries for Diesel Driven Fire Protection Pump,Battery Acid Fluid Noticed Forced Out of Four Batteries.Caused by Standby Charging Sys Overcharging + (11:12:26, 13 December 2024)
- 05000328/LER-1985-004-02, :on 850215 & 17,reactor Trips Occurred Due to lo-lo Steam Generator Water Level.Caused by Personnel Error & Failed Filter Cartridge Cover.New Cover Installed & Personnel Counseled + (11:12:28, 13 December 2024)
- 05000373/LER-1985-013-01, :on 850212,while Finishing Precoating of Filter Demineralizer,Reactor Water Cleanup Sys Isolated on High Differential Flow.Caused by Internal Accumulated Sys Leakage & Flow Perturbations + (11:12:30, 13 December 2024)
- ML20100A052 + (11:12:32, 13 December 2024)
- 05000373/LER-1985-019-01, :on 850212,Door 606 to High Radiation Area Boundary Found Ajar W/Radiation Protection Sign Between Door & Jamb.Caused by Equipment Attendant Opening Door.Alarm Reset.Sign Reposted + (11:12:33, 13 December 2024)
- 05000352/LER-1985-025, :on 850211,spurious Isolation of Reactor Water Cleanup Sys Occurred.Cause of Isolation Under Investigation. Disturbance Analyzer Will Be Installed in Inboard & Outboard Reactor Water Cleanup Sys Isolation Logics + (11:12:35, 13 December 2024)
- ML20100A041 + (11:12:36, 13 December 2024)
- 05000528/LER-1985-007, :on 850210,automatic Activation of NSSS ESF Actuation Sys Auxiliary Relay Cabinet Occurred Due to Train a Power Supply Failure.Caused by Faulty Transformer. Power Supply Replaced + (11:12:38, 13 December 2024)
- ML20100A036 + (11:12:40, 13 December 2024)
- ML20100A032 + (11:12:41, 13 December 2024)
- ML20100A029 + (11:12:42, 13 December 2024)
- ML20100A025 + (11:12:44, 13 December 2024)