- 3F1191-08, Responds to NRC Re Violations Noted in Insp Rept 50-302/90-18.Corrective actions:PM-126, Electrical Checks of CRD Power Train Performed Correctly on 910905 +
- SNRC-1860, Informs of Plans to Continue Using NRC Approved Plans Entitled Snps Security Training... W/Rev Through 900918 & Snps Safeguards... W/Revs Through 880513,per 911104 Request for Exemption from 10CFR73.55 +
- HL-1916, Special Rept 1-91-008:on 911014,four Suppression Sys Flooding Valves in Fixed Water Suppression Sys Not Surveilled Once Per 18 Months.Caused by Less than Adequate Procedure.Valves Tested & Inspected Per Revised Procedures +
- HL-1902, Forwards Results of Insp of IGSCC in Susceptible Welds, Performed During Current Refueling Outage,Per Generic Ltr 88-01 & Rev 2 to NUREG-0313.New crack-like Indications Noted in One 28 Category C Weld +
- RBG-35924, Forwards Criteria for Evaluating Potential Effect of Scaffolding on Safety Related Equipement as Supplemental Response to Violation Noted in Insp Rept 50-458/91-18 on 910619-0730 & 911009 Request for Addl Info +
- PY-CEI-NRR-1414, Forwards LERs 91-021-00 & 91-022-00 +
- ML20261K316 +
- ML20217M594 +
- 05000265/LER-1991-011-06, :on 911015,HPCI Gland Seal Hotwell Pump Observed to Be Cycling on & Off & Sys Declared Inoperable. Caused by High Level Switch for Pump Slipping Out of C-clip. Switch Repaired & Sys Succesfully Tested +
- 05000301/LER-1991-002-01, :on 911014,insp of SG Hot Leg Revealed Degraded Tubes.Results of 800 Psig Leak Test Were Satisfactory.All Tubes in Both a & B SGs Plugged +
- 05000301/LER-1991-003-01, :on 911010,containment Hatch Temporary Third Door Blocked Open During Fuel Movement Due to Personnel Error.Outer Third Door Shut & Refueling Procedure Revised.W/ +
- 05000285/LER-1991-022, :on on 911009,evaluation Initiated in Response to 910912 Neutron Flux Channel Concerns,Per Rev 2 to Reg Guide 1.97.Caused by Failure to Follow Procedure PED-QP-5. Memo Issued.Also Reported Per Part 21 +
- 05000293/LER-1991-021, :on 911009,RCIC Declared Inoperable Due to Lack of Sufficient Battery Charger Test Data.Caused by Unavailability of Backup Battery Charger.Alarm Response Procedure for Alarm Window I4 Changed +
- 05000368/LER-1991-017-01, :on 911011,discovered That TS Surveillance Test for Station Batteries Not Performed within Max Allowable Time Limit.Caused by Lack of Oversight of Surveillance Activity.Tests Highlighted on Shop Schedule +
- 05000361/LER-1991-016-01, :on 911010,control Room Isolation Sys,Train B, Spurious Actuation Occurred.Caused by Momentary Instrument Failure of Train B Particulate/Iodine Channel.Filtering Circuit Added to Ac Input to Monitor Module +
- 05000498/LER-1991-021, :on 911010,power from 1J Bus Lost When Electrician Misapplied Multimeter Test Leads in Energized Circuit,Resulting in Reactor Trip.Caused by Personnel Error. Pump Reenergized & Training Session Held +
- ML20086D946 +