Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20215F444 + (ML20215F444)
- ML20215F447 + (ML20215F447)
- ML20215F448 + (ML20215F448)
- ML20215F450 + (ML20215F450)
- ML20215F452 + (ML20215F452)
- 05000325/LER-1986-030, :on 861120 & 1204,reactor Protection Sys Buses Deenergized on Units 2 & 1,respectively.Caused by Tripping of Motor Generator Set Output Breakers.Breaker Removed, Tested,Reinstalled & Returned to Svc + (ML20215F453)
- ML20215F454 + (ML20215F454)
- ML20215F455 + (ML20215F455)
- ML20215F456 + (ML20215F456)
- ML20215F457 + (ML20215F457)
- 05000280/LER-1986-034, :on 861117,control/relay Room Chiller C Tripped Due to High Condenser Pressure,Leaving Only One Operable Chiller,In Violation of Tech Specs.Caused by Clogged Suction Strainer.Strainer Cleaned + (ML20215F458)
- ML20215F459 + (ML20215F459)
- ML20215F460 + (ML20215F460)
- ML20215F463 + (ML20215F463)
- ML20215F464 + (ML20215F464)
- RBG-24508, Suppls 860514 Response to Item a of IE Bulletin 85-003.BWR Owners Group Efforts to Develop Generic Position for Meeting Item a Documented in 860902 Submittal.Completion of Items b-d Anticipated by 871115 + (ML20215F466)
- ML20215F467 + (ML20215F467)
- ML20215F468 + (ML20215F468)
- ML20215F470 + (ML20215F470)
- IR 05000327/1986057 + (ML20215F475)
- 05000395/LER-1986-015, :on 860908 & 25,hourly Fire Watch Patrols Not Performed in Various Areas in Time Required by Tech Specs. Caused by Personnel Error.Personnel Counseled + (ML20215F477)
- ML20215F479 + (ML20215F479)
- IR 05000327/1986032 + (ML20215F481)
- ML20215F484 + (ML20215F484)
- 05000366/LER-1986-023-01, :on 860903,reactor Protection Sys Scram Occurred.Caused by Leaking Oil Filter Gasket Initiating Main Turbine trip.Electro-hydraulic Control Leak Repaired, Procedures Revised & Personnel Counseled + (ML20215F487)
- ML20215F492 + (ML20215F492)
- 05000220/LER-1986-028, :on 860910,discovered That Supply Valves to Sampling Points Utilized for Obtaining 12-h Grab Samples of Svc Water Discharge Closed.Cause Not Stated.Valves Reopened So That Representative Sample Could Be Taken + (ML20215F493)
- 05000213/LER-1986-043, :on 861108,wide-range Noble Gas Stack Monitor RMS-14B Failed Low.Caused by Improper Setting for New Photomultiplier Tube Preventing Pulses from Passing Through & Being Registered by Electronics + (ML20215F497)
- 05000293/LER-1986-027, :on 861119,plant Experienced Loss of Offsite Power During Severe Winter Storm.Caused by Arcing of High Voltage Lines Due to Heavy Ice & Snow.All Safety Sys Performed as Expected + (ML20215F500)
- ML20215F503 + (ML20215F503)
- ML20215F504 + (ML20215F504)
- 05000322/LER-1986-045, :on 861127,reactor Bldg Standby Ventilation Sys/Control Room Air Conditioning Sys Inadvertently Actuated During Change in Monitor Bulb.Caused by Personnel Error.Personnel Counseled + (ML20215F505)
- L-86-517, Forwards Rev 4 to Training & Qualification Plan.Rev Withheld (Ref 10CFR73.21) + (ML20215F509)
- ML20215F511 + (ML20215F511)
- JAFP-86-0857, Monthly Operating Rept for Sept 1986 + (ML20215F512)
- ML20215F518 + (ML20215F518)
- IR 05000259/1986037 + (ML20215F525)
- ML20215F527 + (ML20215F527)
- ML20215F528 + (ML20215F528)
- 05000321/LER-1986-037, :on 860906,one Half Primary Containment Isolation Sys Group 2 Isolation Occurred.Caused by Blown Fuse & Relay Coil Failure.Relay Coil Replaced & One Half Group 2 Signal Reset + (ML20215F530)
- ML20215F533 + (ML20215F533)
- ML20215F534 + (ML20215F534)
- ML20215F537 + (ML20215F537)
- ML20215F538 + (ML20215F538)
- IR 05000259/1986029 + (ML20215F541)
- 05000298/LER-1986-034, :on 861118,discovered That New Fuel Stored in Spent Fuel Storage Pool Contained U-235 Loading in Excess of Tech Specs.Caused by Newer GE-designed Pellets W/Higher Density.Design Will Be Reviewed + (ML20215F542)
- ML20215F543 + (ML20215F543)
- RBG-25090, Responds to Re Effects of Potential Bankruptcy of Util on Facility.Util Continues to Fulfill All Financial Obligations + (ML20215F544)
- ML20215F545 + (ML20215F545)
- ML20215F546 + (ML20215F546)
- ML20215F549 + (ML20215F549)