Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- SNRC-1986, Requests Approval of Decommissioning Plan Changes W/Regard to in-core Guide Tubes & Dryer/Separator Guide Rods + (ML20114A027)
- ML20114A033 + (ML20114A033)
- ML20114A045 + (ML20114A045)
- 05000364/LER-1984-016-01, :on 841220,reactor Trip Occurred Due to Manual Tripping of Main Turbine.Caused by Failure of Heater Drain Tank 2A Level Control Sys.Unit Returned to Power Operation + (ML20114A048)
- ML20114A056 + (ML20114A056)
- ML20114A060 + (ML20114A060)
- 05000275/LER-1984-035, :on 841215,turbine Trip & Feedwater Isolation Occurred.Caused by hi-hi Steam Generator Water Level Signal. Steam Generator 1-2 Feedwater Restored & Turbine Relatched + (ML20114A062)
- ML20114A063 + (ML20114A063)
- ML20114A071 + (ML20114A071)
- L-92-182, Forwards Plant Attribute & Data Point Libraries for Turkey Point Units 3 & 4 to Support Implementation by NRC of Erds,Submitted by Ltr + (ML20114A075)
- ML20114A076 + (ML20114A076)
- 05000373/LER-1984-091, :on 841220,train B ammonia-chlorine Alarm Tripped.Caused by Broken Chemcassette Tape.Chemcassette Replaced W/New Tape & Detector Reset + (ML20114A077)
- ML20114A080 + (ML20114A080)
- 05000483/LER-1984-064, :on 841217,reactor Trip Received on Rapidly Decreasing Pressurizer Pressure.Caused by Lifting of PORVs & Fully Opened Pressurizer Spray Valves.Test Procedure Revised & Test Repeated Successfully + (ML20114A091)
- ML20114A094 + (ML20114A094)
- ML20114A096 + (ML20114A096)
- ML20114A102 + (ML20114A102)
- 05000237/LER-1984-025-05, :on 841220,4-kV Main Feed Breaker 152-2430 on Bus 24-1 Failed to Trip Open.Caused by Dirty Auxiliary Breaker Contacts in Trip Control Logic.Contacts Cleaned & Breaker Returned to Svc After Testing + (ML20114A108)
- 05000374/LER-1984-093, :on 841220,reactor Water Cleanup Sys Isolated on High Differential Flow.Caused by Sys Flow Perturbations Combined W/Water Temp,Pressure & Density Differences.Sys Restarted + (ML20114A118)
- 1CAN018501, Confirms 850104 Telcon Re Potentially Fraudulent Records of Inservice Insp During Refueling Outage 1R6.Util Knows of No Discrepancies in First 10-yr Interval of Inservice Insp Program.List of Insps Performed by Contractor Encl + (ML20114A121)
- 05000374/LER-1984-088-01, :on 841228,vacuum Breaker Valve Opened to Equalize Pressure Difference Between Suppression Pool & Drywell.Caused by Operating Hydrogen Recombiner.No Further Action Required + (ML20114A124)
- IR 05000313/1984037 + (ML20114A150)
- ML20114A160 + (ML20114A160)
- ML20114A172 + (ML20114A172)
- RBG-19879, Final Deficiency Rept DR-203 Re Arc Strikes & Weld Spatter on Interior of Four Diesel Starting Airtanks Supplied by Tdi.Air Start Sys Adequate to Perform Safety Function. Condition Not Reportable Under 10CFR50.55(e) + (ML20114A183)
- ML20114A188 + (ML20114A188)
- 05000321/LER-1984-020-01, :on 841216,Group 2 Isolation Occurred for No Apparent Reason.Two Other Group 2 Isolations Occurred on 841219 & 28.Caused by Normal Grid Voltage Swings + (ML20114A190)
- ML20114A192 + (ML20114A192)
- RBG-19888, Final Deficiency Rept DR-168 Re Stainless Steel Welds Repaired W/Filler Metal in Excess of 1/16-inch Diameter.Item Not Reportable Per 10CFR50.55(e) + (ML20114A198)
- RBG-19880, Final Deficiency Rept DR-75 Re Error in GHOSH-WILSON Computer Program.Initially Reported on 841211.Program Corrected.Hardware Mods Resulting from Reanalysis Listed + (ML20114A199)
- ST-HL-AE-1168, Second Interim Deficiency Rept Re Containment Spray Ph Levels That Exceed Equipment Qualification Limits.Initially Reported on 840821.Spray Additive Tanks Will Be Isolated. Next Rept by 850422 + (ML20114A202)
- ML20114A214 + (ML20114A214)
- ML20114A256 + (ML20114A256)
- 05000395/LER-1984-048, :on 841217,w/plant in Mode 3,unmonitored Liquid Release Occurred.Caused by Improper Valve Lineup.Operations Procedure for Liquid Radwaste Discharge Being Revised to Clarify Valve & Switch Alignment + (ML20114A261)
- ML20114A265 + (ML20114A265)
- BSEP-84-2619, Forwards Monthly Operating Repts for Nov 1984 & Corrected Monthly Operating Repts for Aug,Sept & Oct 1984 for Unit 1 + (ML20114A267)
- ML20114A271 + (ML20114A271)
- ML20114A274 + (ML20114A274)
- RBG-19856, Final Part 21/deficiency Rept Re Installation of Pacific Scientific Snubbers & Associated Bergen Paterson Clamps. Initially Reported on 841206.Nonconformance & Disposition Rept 6992 Generated + (ML20114A280)
- ML20114A282 + (ML20114A282)
- ML20114A292 + (ML20114A292)
- ML20114A301 + (ML20114A301)
- TXX-4397, Requests Relief from Diesel Generator Operating Restrictions & Elimination of Related Documents as Fuel Load Requirements.Justification for Relief Request Provided + (ML20114A305)
- RBG-19854, Revised Final Deficiency Rept DR-172 Re Rupture of Jacket Water Shroud for Standby Diesel Generator a Supplied by Tdi. General Flush Procedure 1-GFP-1 Revised + (ML20114A306)
- ML20114A308 + (ML20114A308)
- ML20114A312 + (ML20114A312)
- RBG-19855, Revised Final Deficiency Rept DR-191 Re Improperly Sized Gould Buchanan Stacking Terminal Blocks for Power Cables. Blocks Removed & Scrapped.Util Notified Gould of Conditions Requesting Investigation to Prevent Recurrence + (ML20114A318)
- 05000483/LER-1984-065, :on 841217 & 18,ESFs Actuated by Steam Generator Level Oscillations.First Event Caused by Failed Current Pressure Converter.Second Event Caused by Control Valve Not Seating Properly + (ML20114A335)
- ML20114A338 + (ML20114A338)
- RBG-19871, Interim Deficiency Rept DR-156 Re GE Conductivity Cells & Indicators.Next Rept Will Be Provided by 850226 + (ML20114A341)
- ST-HL-AE-1167, First Interim Deficiency & Part 21 Rept Re Failure of Ruskin Fire Dampers to Close.Initially Reported on 841211. Revised Locking Mechanism Considered for Horizontal Dampers. Next Rept by 850308 + (ML20114A354)