- 05000395/LER-1983-068-03, /03L-0:on 830620,snubber FWH-1109 (Feedwater Sys) Declared Inoperable Due to Bearing Offset.Caused by Maint Activity in Immediate Area.Bearing Centered,Restaked,Tested & Declared Operable on 830620 + (ML20085D907)
- ML20085D909 + (ML20085D909)
- ML20085D911 + (ML20085D911)
- ML20085D912 + (ML20085D912)
- ML20085D913 + (ML20085D913)
- 05000261/LER-1983-015-01, /01T-0:on 830622,w/unit at 80% Power,Increase in Total Primary Sys Leakage to 1.19 Gpm Identified.Caused by Defective Sensing Line Fitting.Abnormal Degradation of RCPB Declared on 830705.Fitting Replaced + (ML20085D914)
- ML20085D916 + (ML20085D916)
- 05000302/LER-1983-023, Updated LER 83-023/01T-1:on 830613,fire Damper Discovered Missing.Approx 55 Addl Dampers & Chase Connecting Control Complex 108 & 165 Ft Elevations Degraded Due to Incorrect Fire Rating.Caused by Personnel Error + (ML20085D918)
- ML20085D919 + (ML20085D919)
- 05000395/LER-1983-069-03, /03L-0:on 830620,snubber FWH-0265 Declared Inoperable Due to Misalignment & Bent Paddle Plate.Caused by Transient Loading During Startup.Snubber Replaced W/Unit Modified to Suit Dimensional Requirements + (ML20085D921)
- 05000339/LER-1983-051-03, /03L-0:on 830627 & 0702,RCS Subcoolant Margin Monitor a Failed to Operate Correctly.Cause on 830627 Due to Failed Low Level Data Board & on 830702 Due to Failed Computation Board.Monitor Will Be Relocated + (ML20085D922)
- ML20085D923 + (ML20085D923)
- 05000338/LER-1981-062-03, Util Notified That 15 Block Walls in Fuel Bldg Did Not Meet Design Requirements of IE Bulletin 80-11.Caused by Refinement in Masonry Wall Design.Block Walls to Be Replaced + (ML20085D925)
- ML20085D926 + (ML20085D926)
- ML20085D930 + (ML20085D930)
- ML20085D931 + (ML20085D931)
- ML20085D932 + (ML20085D932)
- ML20085D937 + (ML20085D937)
- ML20085D939 + (ML20085D939)
- ML20085D947 + (ML20085D947)
- 05000416/LER-1983-070-03, Reactor Water Cleanup Sys Isolated When Standby Liquid Control Pump Breaker B Closed. Caused by Procedural Inadequacy.Standby Liquid Control Operating Instruction Revised + (ML20085D948)
- ML20085D952 + (ML20085D952)
- ML20085D959 + (ML20085D959)
- ML20085D965 + (ML20085D965)
- ML20085D986 + (ML20085D986)
- ML20085D992 + (ML20085D992)
- ML20085E001 + (ML20085E001)
- HL-1682, Rev 2 to Special Rept 1-91-005:on 910515,discovered That Cable Penetration Seal Assembly Not Installed Per Mfg Instructions & Barrier Inoperable for More than 14 Days. Hourly Fire Watch Established & Thermolag Barrier Installed + (ML20085E039)
- ML20085E042 + (ML20085E042)
- ML20085E046 + (ML20085E046)
- 05000414/LER-1991-010-02, :on 910911,diesel Generator 2A Tripped When Lube Oil Outlet Temp Setpoint Reached.Caused by Mild Crankcase Explosion & Failure of Thermostatic Control Valve.Power Elements in Valve Replaced + (ML20085E050)
- ML20085E052 + (ML20085E052)
- ML20085E053 + (ML20085E053)
- 05000413/LER-1991-019, :on 910911,reactor Trip Occurred as Result of Turbine Trip Above P-9 & Feedwater Control/Bypass Valves Closed Rapidly.Caused by Loss of Feedwater Pumps on High Discharge Pressure.Four Second Delay Added + (ML20085E068)
- 05000366/LER-1991-019, :on 910906,primary Containment Isolation Valves Failed to Close During Quarterly Stroke Time Testing.On 910912,oily,sticky Substance Found on Valve Internals.Caused by Inadequate Design.Valves Replaced + (ML20085E089)
- ML20085E092 + (ML20085E092)
- ML20085E098 + (ML20085E098)
- B13903, Application for Amend to License DPR-65,changing Index & Tech Spec Sections 3.1.3.6,3.4.11,3.9.18,3.9.19 & 3.9.20 & Bases Sections 3/4.9.17,3/4.9.18.3/4.9.19 & 3/4.9.20 to Resolve Editorial Errors & Typos + (ML20085E103)
- ML20085E106 + (ML20085E106)
- 05000321/LER-1991-017-01, :on 910911,reactor Feedwater Pumps & Main Turbine Tripped on False High Reactor Water Level Signal, Resulting in Reactor Scram.Caused by Personnel Error.Health Physics Technician Counseled + (ML20085E112)
- HL-1865, Forwards Rev 11 to Ei Hatch Nuclear Plant Units 1 & 2 Emergency Plan. Amend Clarifies Terminology & Editorial Corrections to Emergency Classification Tables & Updates Population Figures in Agreement W/State of Ga Plan + (ML20085E115)
- 05000321/LER-1991-013, :on 910809,generator Field Ground Detecting Relay Actuated,Causing Main Turbine Trip & Reactor Scram on Turbine Stop Valve Closure.Caused by Short Duration Ground. Generator Tested & Relay Replaced + (ML20085E119)
- ML20085E123 + (ML20085E123)
- ML20085E125 + (ML20085E125)
- ML20085E134 + (ML20085E134)
- ML20085E142 + (ML20085E142)
- ML20085E143 + (ML20085E143)
- ML20085E149 + (ML20085E149)
- ML20085E150 + (ML20085E150)
- ML20085E152 + (ML20085E152)
- ML20085E158 + (ML20085E158)