ML20085E042

From kanterella
Jump to navigation Jump to search
Interim Deficiency Rept Re GE Akr Breakers.Initially Reported on 830620.Matter Still Under Evaluation.Status of Evaluation Will Be Reported by 831007
ML20085E042
Person / Time
Site: Wolf Creek 
Issue date: 07/20/1983
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Seidle W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, KMLNRC-83-094, KMLNRC-83-94, NUDOCS 8307290352
Download: ML20085E042 (1)


Text

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ -

KANSAS GAS AND ELECTRIC COMPANY T*4 E LECT 54*C COM*AN V OLENN L NOESTER vets pas s@ut pwctase July 20,1983 Mr. W.C. Seidle, Chief

- - m.

E.

Reactor Projects Branch 2 E

U.S. Nuclear Regulatory Commission i

3 Region IV 611 Ryan Plaza Drive, Suite 1000

\\

g g 2 1 %

.[ b Arlington, Texas 76011 i,

I l

J KMLNRC 83-094 Ret Docket No. STN 50-482 Subj: Potential 10CFR50.55(e) Report - General Electric AKR Breakers

Dear Mr. Scidle:

This letter provides an Interim report on a potential 10CFR50.55(e) l matter concerning General Electric (GE) AKR breakers being used in safety-related applications at Wolf Creek Generating Station. This item was initieilly reported by Mr. Gene Rathbun of Kansas Gas and Electric Company to Mr. Mike Murphy of the Nuclear Regulatory Com-mission, Region IV, on June 20, 1983.

During startup testing some safety-related GE AKR breakers were i

inspected at Wolf Creek and it was discovered that some of the l

l insulated couplings were cracked. The coupling is a 2" x 2" x 1" ceramic block which moves the breaker centacts into their closed position as the closing mechanism operates. The coupling travels through the breaker's are chute during the closing and opening cycle.

Several Wolf Creek AKR breakers exhibited the problem. The problem occurs when the coupling and are chute come into contact and pieces of the coupling break o.f.

This matter is still under evaluation. The status of this evaluation and the resolution of this concern will be reported to you on or before Octob,er 7, 1983. In the interim, please direct any questions on this subject to me or to Mr. Gene Rathbun of my staff.

Yours very truly, 8307290352 830720 I

PDR ADOCK 05000482 S

PDR f

GLK:bb cca RCDeYoung HRoberds/WSchum

.I E-2 7N 201 N. Market - WicNte, Kansas - Mel Address: RO. Box 200 l nEcNta, Kansas 67201 -Telephone: Area Code (316) 261-6451