- ML20071H306 + (ML20071H306)
- ML20071H310 + (ML20071H310)
- 05000280/LER-1982-012-03, /03L-0,on 820131,amp Readings for Heat Tracing Circuits 23A & C on Panels 8 & 9 Found Below Acceptance Criteria.Apparently Caused by Inadvertent Damage to Heat Tracing Tape During Cleanup Operations.Tape Replaced + (ML20071H318)
- ML20071H325 + (ML20071H325)
- 05000280/LER-1982-015-03, /03L-0,on 820129,while Performing PT-33,low Control Room Envelope Pressure of .045 Inches of Water Found.Caused by Deterioration of Weather Stripping Around Doors.Weather Stripping Replaced + (ML20071H328)
- ML20071H340 + (ML20071H340)
- ML20071H342 + (ML20071H342)
- ML20071H345 + (ML20071H345)
- ML20071H348 + (ML20071H348)
- ML20071H349 + (ML20071H349)
- ML20071H354 + (ML20071H354)
- ML20071H356 + (ML20071H356)
- ML20071H357 + (ML20071H357)
- ML20071H363 + (ML20071H363)
- 05000296/LER-1982-002, Forwards LER 82-002/03L-0 + (ML20071H367)
- ML20071H368 + (ML20071H368)
- 05000364/LER-1982-007, Forwards LER 82-007/03L-0 + (ML20071H384)
- 05000364/LER-1982-007-03, /03L-0:on 820118,boron Concentration in 2C Accumulator Fell Below Min Required in Tech Specs.Sampling Yielded Results Both Below & Above 1900 Ppm Limit.Cause of Fluctuation Not Determined.Accumulator Will Be Monitored + (ML20071H390)
- ML20071H392 + (ML20071H392)
- 05000338/LER-1983-023-03, /03L-0:on 830423,low Head Safety Injection Pump 1-SI-P-1B Suction Isolation Valve Failed to Open.Caused by Lack of Lubrication on Valve Stem to Operator Nut Area.Stem Lubricated & Stroked + (ML20071H394)
- 05000369/LER-1982-008, Forwards LER 82-008/03L-0.Detailed Event Analysis Encl + (ML20071H395)
- ML20071H397 + (ML20071H397)
- 05000369/LER-1982-010, Forwards LER 82-010/03L-0.Detailed Event Analysis Encl + (ML20071H401)
- ML20071H404 + (ML20071H404)
- 05000369/LER-1982-008-03, /03L-0:on 820115,exam of Programs on Operator Computer Revealed Equipment Run Time on Fuel Pool Ventilation Sys Exceeded Tech Specs W/O Sample Being Taken from Charcoal Absorber.Caused by Lack of Procedure + (ML20071H406)
- ML20071H411 + (ML20071H411)
- 05000369/LER-1982-007, Forwards LER 82-007/03L-0.Detailed Event Analysis Encl + (ML20071H412)
- ML20071H415 + (ML20071H415)
- ML20071H416 + (ML20071H416)
- 05000369/LER-1982-010-03, /03L-0:on 820120,while in Mode 1,all Digital Rod Position Indications for Control Rod K-8 Lost.Caused by Cabling to Detectors Susceptible to Conductor Damage Due to Own Weight.Bulkhead Connector Cable Replaced + (ML20071H422)
- ML20071H425 + (ML20071H425)
- ML20071H427 + (ML20071H427)
- 05000335/LER-1983-026-09, /09T-0:on 830513,67 of 264 Bergen Paterson EA-3 Clamps Discovered Oriented Improperly.Caused by Vendor Catalog Interpreted Improperly.Clamps Will Be Replaced During Present Outage + (ML20071H429)
- 05000328/LER-1982-011, Forwards LER 82-011/03L-0 + (ML20071H430)
- DCL-94-135, Comment Supporting Petition for Rulemaking PRM-50-59 Re Proposed Amend to 10CFR50.54(p) Concerning Frequency W/Which Licensee Conducts Independent Reviews of Security Programs + (ML20071H431)
- 05000369/LER-1982-007-03, /03L-0:on 820111,many Instrument Lines Froze W/ Instruments Declared Inoperable Leading to Inadvertent Actuation of ESF Causing Safety Injection,Steamline Isolation & Reactor Trips.Caused by Cold Weather + (ML20071H435)
- ML20071H436 + (ML20071H436)
- 05000296/LER-1982-003, Forwards LER 82-003/03L-0 + (ML20071H440)
- 05000296/LER-1982-002-03, /03L-0:on 820121,during Surveillance Test SI 4.11.C.1 & 5 Smoke Detector in Auxiliary Instrument Room 3 Would Not Alarm.Caused by Loose Annunciator Point Card Due to Incorrect Installation of Retainer Bar + (ML20071H443)
- ML20071H445 + (ML20071H445)
- 05000296/LER-1982-003-03, /03L-0:on 820123,during Refueling Outage,While Performing SI 4.2.A-39,temp Switches TS-69-30A,B,C & E on Reactor Cleanup Sys Floor Drain High Temp,Operated at Less than 160 F.Caused by Improper Calibr or Instrument Drift + (ML20071H449)
- ML20071H453 + (ML20071H453)
- ML20071H456 + (ML20071H456)
- ML20071H457 + (ML20071H457)
- ML20071H459 + (ML20071H459)
- 05000244/LER-1982-003, RO 82-007/01T:on 820125,unit Experienced Event Described in LER 82-003 Leading to RCS Cooldown Rate Greater than 100 F/H.Further Info Will Be Submitted w/14-day Written Rept + (ML20071H460)
- ML20071H462 + (ML20071H462)
- ML20071H463 + (ML20071H463)
- ML20071H465 + (ML20071H465)
- ML20071H466 + (ML20071H466)
- 05000328/LER-1982-011-03, /03L-0:on 820122,performance of SI-16 Revealed Boron Injection Tank Records Not Kept.Caused by Inadequate Procedures.Revisions to SI-16 Recordkeeping Procedures Include Boron Injection Tank Heat Tracing + (ML20071H470)