Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20069A580 + (ML20069A580)
- ML20069A582 + (ML20069A582)
- ML20069A585 + (ML20069A585)
- ML20069A592 + (ML20069A592)
- ML20069A593 + (ML20069A593)
- ML20069A598 + (ML20069A598)
- 05000318/LER-1983-008, Forwards LER 83-008/03L-0 + (ML20069A599)
- ML20069A603 + (ML20069A603)
- ML20069A610 + (ML20069A610)
- 05000318/LER-1983-008-03, /03L-0:on 830131,containment Spray Header 21 Isolation Valve CV-4150 Found to Stroke Only Partially, Rendering Containment Spray Header 21 Inoperable.Caused by Improper Adjustment of Spring Adjuster.Adjustment Corrected + (ML20069A612)
- 05000247/LER-1983-003, Forwards LER 83-003/01T-0 + (ML20069A618)
- 05000281/LER-1983-005-03, /03L-0:on 830211,during Full Power Test PT-15.1C, Turbine Driven Auxiliary Feed Pump Ran Intermittently.Caused by Corrosion Piston of Pump Governor Regulator.Piston Cleaned + (ML20069A625)
- ML20069A626 + (ML20069A626)
- ML20069A629 + (ML20069A629)
- ML20069A630 + (ML20069A630)
- ML20069A631 + (ML20069A631)
- ML20069A632 + (ML20069A632)
- 05000281/LER-1983-006-03, /03L-0:on 830214,during Full Power,Trip Valve TV-DA-200B Failed to Close When Containment Sump Pump Stopped.Caused by Defective solenoid-operated Valve.Valve Replaced + (ML20069A636)
- ML20069A640 + (ML20069A640)
- ML20069A648 + (ML20069A648)
- 05000387/LER-1983-022, Forwards LER 83-022/03L-0 + (ML20069A650)
- ML20069A653 + (ML20069A653)
- ML20069A659 + (ML20069A659)
- 05000387/LER-1983-022-03, /03L-0:on 830203,reagent Gas Bottle (Oxygen) for Hydrogen Analyzer Found Exhausted During Startup Test Program.Caused by Periodic Gas Bottle Pressure Check Omission & Inadequate Storeroom Min Inventory + (ML20069A661)
- ML20069A664 + (ML20069A664)
- ML20069A666 + (ML20069A666)
- ML20069A673 + (ML20069A673)
- 05000271/LER-1994-007, :on 940420,SBGTS Initiation & Reactor Building Ventilation Isolation Occurred Concurrent W/Pcis Group III Isolation.Caused by Dirty/Oxidized Contacts on Switch. Corrective Action:Cleaning Switch Contacts + (ML20069A675)
- 05000387/LER-1983-025, Forwards LER 83-025/03L-0 + (ML20069A677)
- ML20069A678 + (ML20069A678)
- 05000277/LER-1983-003-03, /03L-0:on 830206,coolant Leak Discovered in Cooling Sys of Diesel Driven Fire Pump.Caused by Leaking Water Pump Shaft Seal.Replacement Pump Placed in Svc on 830209 + (ML20069A681)
- 05000387/LER-1983-025-03, /03L-0:on 830204,reactor Recirculation Pump a Tripped off-line During Startup Test Program.Caused by Deficiency in Silicon Controlled Rectifier,Resulting in High Field Circuit Current.Voltage Regulator Board Replaced + (ML20069A683)
- ML20069A686 + (ML20069A686)
- ML20069A688 + (ML20069A688)
- 05000219/LER-1983-005, Forwards LER 83-005/03L-0.Detailed Event Analysis Encl + (ML20069A692)
- 05000280/LER-1983-010-03, /03L-0:on 830207,activity Samples of RCS Indicated Dose Equivalent I-131 Level Greater than Tech Spec Following Reactor Trip.Caused by Fuel Element Defect in Reactor Core. Accelerated Sampling Frequency Implemented + (ML20069A697)
- 05000382/LER-1994-007, :on 940426,automatic Reactor Trip Occurred Due to Low Pressurizer Pressure Core Protection Calculator Auxiliary Trip.Corrective Action:Replacing Faulty Relay & Removing Reactor Power System from Service + (ML20069A698)
- ML20069A700 + (ML20069A700)
- ML20069A702 + (ML20069A702)
- 05000219/LER-1983-005-03, /03L-0:on 830126,while Performing Containment Spray Sys Automatic Actuation Test,High Drywell Pressure Switches IP15A,B & C Tripped at Value Greater than Tech Spec Limit.Cause Not Determined.Pressure Switches Readjusted + (ML20069A703)
- ML20069A706 + (ML20069A706)
- 05000280/LER-1983-011-03, /03L-0:on 830211,instrument Air Check Valve to PORV Found Installed Backwards.Caused by Installation Error During Implementation of Design Change 79-53.Valve Removed & Reinstalled in Correct Orientation + (ML20069A707)
- 05000219/LER-1983-002, Forwards LER 83-002/03L-0.Detailed Event Analysis Encl + (ML20069A716)
- ML20069A719 + (ML20069A719)
- ML20069A724 + (ML20069A724)
- ML20069A733 + (ML20069A733)
- 05000219/LER-1983-002-03, /03L-0:on 830123,startup Banks Removed from Svc Due to Dilution Plant Main Breaker Cable Termination Failure.Cause Under Investigation.Dilution Pump Power Feed Terminations Replaced + (ML20069A735)
- ML20069A737 + (ML20069A737)
- ML20069A740 + (ML20069A740)
- ML20069A743 + (ML20069A743)
- ML20069A745 + (ML20069A745)