- ML19318A920 + (ML19318A920)
- 05000245/LER-1980-007, Forwards LER 80-007/03L-0 + (ML19318A922)
- ML19318A925 + (ML19318A925)
- ML19318A926 + (ML19318A926)
- 05000245/LER-1980-007-03, /03L-0:on 800516,discovered That Semiannual Functional Test of Cable Vault Smoke Detection Sys Had Been Overlooked.Caused by Test Not Being Listed on Unit Surveillance Schedule.Verification of Schedules Performed + (ML19318A928)
- ML19318A929 + (ML19318A929)
- 05000327/LER-1980-045, Supplemental LER 80-045/01T-1:on 800509,gate Between Spent Fuel Pool & Cask Loading Area Found Not to Be Designed or Constructed to Category 1 Requirements.Caused by Overlooking Loading Effects in Seismic Analysis + (ML19318A930)
- ML19318A931 + (ML19318A931)
- ML19318A932 + (ML19318A932)
- ML19318A933 + (ML19318A933)
- ML19318A934 + (ML19318A934)
- ML19318A935 + (ML19318A935)
- 05000327/LER-1980-061, Forwards LER 80-061/03L-0 + (ML19318A936)
- ML19318A937 + (ML19318A937)
- ML19318A938 + (ML19318A938)
- 05000327/LER-1980-072, Forwards LER 80-072/03L-0 + (ML19318A939)
- ML19318A940 + (ML19318A940)
- ML19318A941 + (ML19318A941)
- ML19318A942 + (ML19318A942)
- ML19318A943 + (ML19318A943)
- 05000302/LER-1980-024, Forwards LER 80-024/04L-0 + (ML19318A944)
- ML19318A945 + (ML19318A945)
- 05000327/LER-1980-061-03, /03L-0:on 800521,auxiliary Bldg,Vent Radiation monitor,0-RM-90-10B,declared Inoperable Due to Spurious High Rad Spikes.Caused by Defective 24-volt Power Supply. Power Supply Replaced & Monitor Returned to Svc + (ML19318A946)
- ML19318A947 + (ML19318A947)
- 05000327/LER-1980-072-03, /03L-0:on 800522,essential Raw Cooling Water Effluent Monitors O-RE-90-134/141 Declared Inoperable.Caused by Spurious High Rad Spikes & High Rad Alarm.Changeout of Relay & Further Investigations Planned + (ML19318A948)
- ML19318A949 + (ML19318A949)
- 05000327/LER-1980-070, Forwards LER 80-070/03L-0 + (ML19318A950)
- ML19318A951 + (ML19318A951)
- 05000302/LER-1980-024-04, /04L-0:on 800523,discovered That I-131 Charcoal Cartridge for Wk Ending 800401 Was Inadvertently Discarded. Caused by Personnel Error.Responsible Personnel Were Instructed on Proper Procedures + (ML19318A952)
- ML19318A953 + (ML19318A953)
- ML19318A954 + (ML19318A954)
- 05000366/LER-1980-054, Forwards LER 80-054/03L-0 + (ML19318A955)
- ML19318A956 + (ML19318A956)
- 05000327/LER-1980-070-03, /03L-0:on 800517,during Cooldown from Mode 3, Refueling Water Storage Tank Water Level Fell Below Required Limit.Caused by Failure to Initiate Early Makeup.Makeup Immediately Initiated + (ML19318A957)
- ML19318A958 + (ML19318A958)
- 05000366/LER-1980-054-03, /03L-0:on 800524,while Performing Calibr of Both Primary Containment Purge Vacuum Breaker Pressure Switches, 2T48-N211 Found Inoperable.Caused by Personnel Error.Stuck Switch Removed & Repaired.Switch Wiring Corrected + (ML19318A959)
- ML19318A960 + (ML19318A960)
- ML19318A961 + (ML19318A961)
- 05000366/LER-1980-088, Forwards LER 80-088/03L-0 + (ML19318A962)
- ML19318A963 + (ML19318A963)
- ML19318A964 + (ML19318A964)
- ML19318A966 + (ML19318A966)
- ML19318A967 + (ML19318A967)
- ML19318A968 + (ML19318A968)
- 05000366/LER-1980-084, Forwards LER 80-084/03L-0 + (ML19318A970)
- ML19318A971 + (ML19318A971)
- 05000366/LER-1980-088-03, /03L-0:on 800529,while Performing HNP-2-3154, Reactor Pressure Vessel Level Instrument (LPCI) Ft&C, Switch 2 on 2B21-NO31A Failed.Caused by Switch Being Out of Adjustment Due to Loose Screw.Switch Readjusted + (ML19318A972)
- ML19318A973 + (ML19318A973)
- 05000366/LER-1980-084-03, /03L-0:on 800521,unit Scrammed While Operating at Steady State.Reactor Core Isolation Cooling Tripped on High Water Level.Sys Maunally Restarted,But Tripped on Mechanical Overspeed Trip + (ML19318A974)
- ML19318A975 + (ML19318A975)
- ML19318A976 + (ML19318A976)