- 05000206/LER-1987-003-02, :on 870310,reactor Trip Occurred Due to Loss of Generator Field.Caused by Electrical Short Due to Brush Dropped Into Main Exciter Commutator Assembly.Temporary Improvements to Available Lighting Made + (ML13331A212)
- 05000206/LER-1987-004, :on 870313,east Main Feedwater Pump Removed from Svc While Loose Deflector Ring Repositioned & Set Screw Tightened,Constituting Entry Into Tech Spec 3.0.3.Request to Operate One Train for 72 H Submitted + (ML13331A213)
- 05000206/LER-1987-005-02, On 870324,Nuclear Instrumentation Sys Power Channel 1207 Declared Inoperable Due to Low Output Resulting in Entry Into Limiting Condition for Operation 3.0.3.Caused by Inadequate Procedure.Procedure Revised + (ML13331A214)
- ML13331A215 + (ML13331A215)
- 05000206/LER-1986-015-02, :on 860219,diesel Generator 2 Inadvertently Started When Inner Compartment Door of 4-kV Bus Breaker Cubicle Opened.Caused by Personnel Error.Personnel Counseled + (ML13331A217)
- 05000206/LER-1986-016-02, :on 860515,diesel Generator 1 Automatically Started During Realignment of Generator from Locked to Standby Position.Cause Not Stated.Circuit Restored. Operability Testing Satisfactorily Completed + (ML13331A218)
- 05000206/LER-1986-017-01, :on 861113,actuation of Reactor Protection Sys Occurred While in Shutdown Mode.Caused by Personnel Error. Personnel Counseled + (ML13331A219)
- 05000206/LER-1987-006-01, :on 870513,during Insp of Environ Qualified Butt Spliced Connections Per IE Info Notice 86-104,one Level Switch Found Missing Raychem Heat Shrink Sleeving.Caused by Requirement Being Deleted During Drawing Rev + (ML13331A220)
- ML13331A221 + (ML13331A221)
- 05000206/LER-1987-008-01, :on 870602,while in Mode 5,meggering of CRD Mechanism Coil Circuits Revealed Low Insulation Resistance in 22 Circuits.Cause of Damage Occurred During Penetration Installations.Cable Tray Covers to Be Provided + (ML13331A222)
- 05000206/LER-1987-009-01, :on 870610,during Performance of Procedural Steps in Preparation of Engine Air Roll,Diesel Generator 1 Inadvertently Started.Caused by Operator Failure to Identify Control push-button.Operator Counseled + (ML13331A223)
- 05000206/LER-1987-010-01, :on 870620,containment Isolation Sys Actuated Due to Momentary Loss of Power to Three Train 4 Detector Channels.Caused by Loose Connection at Common Power Supply to Transmitters.Nest Receptacle Repaired + (ML13331A224)
- 05000206/LER-1986-007, :on 870729,main Feedwater Regulating Valves Closed Resulting in Decrease in Steam Generator Water Levels to 5%.On 870730,steam Flow Signals Failed Low & Unit Shutdown Per Tech Specs.Event Under Review + (ML13331A225)
- 05000206/LER-1987-007-02, :on 870713,discovered Boric Acid Storage Tank Level Instrumentation Monthly Functional Test Performed Delinquently.Caused by Failure of Planner to Include Test in Tracking Sys.Planner Counseled + (ML13331A226)
- 05000206/LER-1987-012-02, :on 870825,containment Air Luck Hatch Did Not Fully Close Due to Hatch Drive Failure,Resulting in Brief Breach of Containment Integrity.Caused by Broken Master Link.Broken Master Link Replaced + (ML13331A228)
- ML13331A229 + (ML13331A229)
- 05000206/LER-1987-013-01, :on 870902,redundant Pump G-002B Not Tested Prior to Disabling of auto-start Capability of Pump G-002A During Calibr of Hydrazine Storage Tank Level Transmitter. Caused by Personnel Error.Personnel Counseled + (ML13331A230)
- ML13331A231 + (ML13331A231)
- ML13331A232 + (ML13331A232)
- 05000206/LER-1987-015-02, :on 871007,determined That Engineered Safety Sys Design Failed to Meet Single Criteria.Caused by Newly Identified time-dependent Single Failure Susceptibilty. Special Operator Training Provided + (ML13331A233)
- ML13331A234 + (ML13331A234)
- 05000206/LER-1987-005, :on 870324,nuclear Instrumentation Sys Power Range Channel 1207 Declared Inoperable.Channel Placed in Trip Condition.On 870428 & 29,Channel 1207 Automatically Reset from Trip to Inoperable Condition + (ML13331A235)
- 05000206/LER-1987-014-02, :on 870626,determined That Battery Weekly Surveillance Not Performed Prior to Mode Change,Contrary to Tech Spec 4.0.4.Caused by Personnel Error.Individual Involved Reinstructed + (ML13331A236)
- 05000206/LER-1987-016-02, :on 871110,Automatic Switch Co Solenoid Valve Failures Occurred.Caused by Thin Hard Film Between Top of Slug & Housing.Root Cause Evaluation Continuing.Further Testing Performed + (ML13331A237)
- 05000206/LER-1987-003-01, :on 870310,turbine & Reactor Trips Occurred as Result of Trip Signal in Response to Generator Field Loss. Caused by Electrical Short Resulting from Brush Being Dropped in Main Exciter Commutator Assembly + (ML13331A238)
- 05000206/LER-1987-017-02, :on 870910 & 1201,containment Isolation Valves Loop B Header Would Not Fully Close Upon Demand.Cause Undetermined.Administrative Controls Implemented to Prevent Inadvertent Opening of Valves + (ML13331A239)
- 05000206/LER-1986-014, :on 861230,ground Alarm Received in Control Room for Dc Bus 2.Opening Feeder Breaker Constitutes Brief Entry Into Tech Spec 3.0.3.Caused by Moisture in Control Circuitry Junction Box.Ground Cleared + (ML13331A240)
- 05000206/LER-1986-011, :on 860904,main Feedwater Pump Failed.Caused by Loss of Thrust Disk Assembly Preload.New Assembly Instructions Developed to Avoid Loss of Preload.Vibration Amplitude Will Be Monitored + (ML13331A241)
- 05000206/LER-1987-018-01, :on 871216,Tech Spec 3.0.3 Voluntarily Entered During Dc Ground Troubleshooting.Caused by Presence of Water Inside Housing of Solenoid.Ground Eliminated by Drying Electrical Connections + (ML13331A242)
- ML13331A243 + (ML13331A243)
- ML13331A244 + (ML13331A244)
- ML13331A245 + (ML13331A245)
- ML13331A246 + (ML13331A246)
- 05000206/LER-1988-001-02, :on 880225,several Components Requiring Environ Qualification Found Omitted from Equipment Qualification Master List.Caused by Inadequate Methodology During List Generation.Installed Equipment Reviewed + (ML13331A248)
- ML13331A249 + (ML13331A249)
- 05000206/LER-1988-002-02, :on 880317,Tech Spec Continuous Fire Watch for Containment Interrupted When Equipment Hatch Closed.Caused by Removing Contiguous Area from Combination Post When Hatch Closed.Instructions to Be More Explicit + (ML13331A250)
- ML13331A251 + (ML13331A251)
- ML13331A252 + (ML13331A252)
- ML13331A253 + (ML13331A253)
- 05000206/LER-1988-006-01, :on 880321,discovered That Backup Nitrogen Sys (Bns) Design Criteria Had Not Been Fully Implemented in Design & Installation of Sys.Caused by Surveillance of Bns Not Being Performed.Changes Instituted + (ML13331A254)
- 05000206/LER-1988-005-01, :on 880329,review of Tech Spec 4.15 Surveillance Procedures Revealed Two Valves Not Adequately Addressed in Surveillance Program.Caused by Oversight. Procedures Will Be Revised + (ML13331A255)
- ML13331A256 + (ML13331A256)
- ML13331A257 + (ML13331A257)
- ML13331A258 + (ML13331A258)
- 05000206/LER-1988-007-01, :on 880206 & 07,failed to Retain Sample from Ctr Holdup Tank.Caused by Inadequate Chemistry Cintrols. Amend Requiring Verification of Retained Sample Releases Planned & Average of Jan-Mar Values to Be Used + (ML13331A260)
- 05000206/LER-1987-015, :on 871007,determined That ESF Designs Failed to Meet Single Failure Criteria.Cause Re motor-operated Valve MOV-883 Due to Failure to Review Affect of Revised Single Failure Regulatory Guidance + (ML13331A261)