 Issue dateTitleTopic
ML20086B1739 November 1976AO 50-267/74-20A:on 741116,during Low Power Physics Testing, Conflict Found Between Tech Specs 4.2.11 & 4.4.1 Re Moisture Limits.Caused by Last Minute Change in Tech Specs 4.2.11. Tech Specs Revised
ML20086B1789 November 1976AO 50-267/74-20A:on 741116,during Low Power Physics Testing, Conflict Found Between Tech Specs 4.2.11 & 4.4.1 Re Moisture Limits.Caused by Last Minute Change to Tech Specs 4.2.11. Tech Specs Revised
ML20086B1003 September 1976AO 50-267/74-21C:on 741121,high Pressure in Gas Waste Vacuum Tank Lifted Relief Valve Allowing Release of 700 Scf Uncontaminated Gas.Caused by Operator Error.Valves Will Be Replaced W/Kerotest Valves & Change Notice 91 Issued
ML20086A04428 May 1976Telecopy AO 76-012:on 760527,helium Circulator 1B Tripped Twice.Caused by Buffer Seal Malfunction.Sys Operating Procedure Will Be Revised
ML20086A06920 May 1976AO 76-011:on 760510,helium Circulator 1C Tripped Due to Negative buffer-midbuffer Differential Pressure.Cause Associated W/Test
ML20086A0873 May 1976Telecopy AO 76-010:on 760429 & 30,circulators 1A & 1B Tripped on Loss of Bearing Water.Caused by Operator Error
ML20085M43517 February 1976Telecopy AO 76/005:on 760227,loss of Essential 480-volt Bus 2 Caused Trip of Three Helium Circulators Due to Circulator Bearing Water Problems.Loss of 480-volt Bus Could Cause Temporary Loss of Forced Circulation
ML20085M4736 February 1976Telecopy AOs 76/03 & 76/04:on 760206,generator Set 1-B Load Breaker Would Not Close & Generator Set 1A Trouble Alarm Received,Indicating Partial Disconnection of Engine 1B from Generator.Causes Not Stated
ML20085M56522 December 1975AO 50-267/74/23A:on 741211,engine a of Standby Diesel Generator 1A Declutched During 2 H Surveillance Run & No Alarm Annunciated.Caused by Dirt Under Seat of Solenoid Valve.Plant Change Notice 12 Initiated
ML20085M71822 December 1975AO 50-267/75/15A:on 750709,during Repair of Minor Oil Leak on Gasoline Engine of Emergency Fire Pump,Inlet Manifold Piping Found Cracked.Caused by Component Failure.Manifold Repaired
ML20086B15418 December 1975AO 50-267/74-7A:on 740424,fuel Handling Machine Failed to Engage & Lift Reflector Element 09-06-R-01.Caused by Mfg Error.Reflectors de-burred & Ga Co Will Supply Two Column 1 Metal Clad Reflector Elements
ML20085M56318 November 1975AO 50-267/75/24:on 751108,static Seal on Helium Circulator B Inadvertently Released.Cause Presently Undetermined. Circulator B Brake & Seal Manually Set
ML20085M62121 October 1975AO 50-267/75/18A:on 750816,during Installation Preparation, Helium Circulation Damaged.Caused by Lack of Adherence to Approved Procedure.Personnel Counseled to Adhere to Approved Procedures & Supervision
ML20085M57126 September 1975AO 50-267/75/23:on 750916,essential Electrical Cable Discovered to Have Failed.Caused by Circumstances Associated W/Work in Progress.Damaged Cable Replaced
ML20085M57726 September 1975AO 50-267/75/22:on 750912,during Gas Waste Routine Release, Trouble W/Gas Vacuum Tank Observed by Reactor Operator.Cause of Malfunction Unknown.Failure Could Not Be Reproduced.No Further Action Planned
ML20086B11526 September 1975AO 50-267/74-21B:on 741121,high Pressure in Gas Waste Vacuum Tank Lifted Relief Valve Allowing Release of 700 Scf Uncontaminated Gas.Caused by Operator Error.Inlet Valve Seats Will Be Replaced W/Soft Seats
ML20085M58222 September 1975AO 50-267/75/21:on 750911,control Rod Drive Inserted Into Pcrv Rotated 180 Degrees from Required Orientation During Control Rod Drive Mod.Caused by Design & Procedure Error. Procedures Modified
ML20085M6185 September 1975AO 50-267/75/19:on 750825,engine a of Standby Generator a Automatically Shut Down & Declutched During Cooldown Portion of Weekly Surveillance Test.Caused by Difference in Fuel Rack Setting.Setting Changed
ML20085M6235 September 1975AO 50-267/75/18:on 750816,during Installation Preparation, Helium Circulator Damaged.Caused by Lack of Adherence to Approved Procedure.Personnel Counseled to Adhere to Approved Procedures & Supervision
ML20085M6125 September 1975AO 50-267/75/20:on 750826,12 Cord Sets Connecting Process Controllers at I-05 & I-06 Control Board to Cable Rack in Auxiliary Electric Equipment Room Switched.Caused by Malicious Mischief
ML20085M67815 August 1975AO 50-267/75/17:on 750808,instrument Air Compressor 1C Observed Running Continuously in Unloaded Condition.Caused by Component Failure.Failed Unloader Actuator Replaced W/New Unloader Actuator & Tested
ML20085M70221 July 1975AO 50-267/75/16:on 750610,when Engine B of Standby Generator a Dissassembled,Broken Rings,Scored Cylinders & Cracked Pistons Found.Caused by Water Engine.Engines Inspected.Pistons,Liners & Rings Replaced
ML20085M72518 July 1975AO 50-267/75/15:on 750709,during Repair of Minor Oil Leak on Gasoline Engine of Emergency Fire Pump Inlet Manifold, Piping Found Cracked.Caused by Component Failure.New Manifold Ordered & Defective Casting Replaced
ML20085M74011 June 1975AO 50-267/75/14:on 750530,engine B of a Diesel Generator Oversped to 1,900 Rpm While Electrical Overspeed Trip Being Set.Caused by Procedure Error.Test Procedure Changed
ML20085L63327 May 1975AO 75-267/75/13:on 750519,I-B Engine of I-A Standby Diesel Generator Failed to Start.Caused by Failure to Transmit Info That Engine Was Out of Svc to Adjust Overspeed Switches
ML20085L64812 May 1975AO 50-267/75/10:on 750501,exam Revealed Pin on Declutching Mechanism of Engine D of Standby Diesel Generator D Sheared Off.Caused by Inadequate Lubrication.Pin Replaced & Lubrication Frequency Increased
ML20085L63012 May 1975AO 50-267/75/9:on 750404,valve HV-2188-8 Did Not Open When Circulator Seal Release Permissive Circuit Directed Valve to Open.Cause Not Stated.Air Solenoids Inspected & Cleaned
ML20085L7877 May 1975AO 50-267/74-25:on 741018,diesel Engine B of Standby Generator a Tripped from High Water Jacket Temp on Routine Test.Caused by Improper Filling of Water Jackets.Personnel Counseled
ML20085L6417 May 1975AO 50-267/75/11:on 750424,preliminary Calculations Indicated That Helium Bottles Supplying Reserve Shutdown Sys Did Not Have Adequate Restraint for Dbe.Cause Not Stated.New Bottle Racks Designed & InstalledDesign basis earthquake
ML20085L78816 April 1975AO 50-267/74/24A:on 741222,static Seal on Helium Circulator a Released During Removal of Temporary Jumpers.Caused by Jumper Contact W/Station Ground
ML20085L7678 April 1975AO 50-267/75/3A:on 750123,dew Point Moisture Monitor Failed to Initiate Reactor Scram When Moisture Content Exceeded Trip Setpoint.Caused by Design & Procedure Inadequacies.New Procedure Developed
ML20085L6497 April 1975AO 50-267/75/9:on 750329,leak in Mechanical Seal of Helium Circulator B Discovered.Caused by Foreign Matl on Sealing Surfaces.No Corrective Actions Planned
ML20085L6832 April 1975AO 50-267/75/6A:on 750202,gas Waste Vacuum Tank Rupture Disc Ruptured,Releasing Small Quantity of Gas.Caused by Improper Closure of Air Operated Drain Valve Due to Foreign Matl on Valve Seat.Seat Repaired
ML20086E16521 March 1975AO 50-267/74/6A:on 750202,gas Waste Vacuum Tank Rupture Disc Ruptured,Releasing Small Quantity of Gas.Caused by Failure of Air Operated Drain Valve to Close Properly.Valve Repaired & Reinstalled
ML20085L70714 March 1975AO 50-267/75-4-A:on 750125,tritium Leaked from Secondary Closure of Refueling Region 1.Caused by Normal Presence of Tritium in Pressurizing Gas
ML20085L6517 March 1975AO 50-267/75/8:on 750224,diesel Engine B of Standby Generator a Failed to Function Properly During Weekly Test. Caused by Defective Temp Thermocouple.New Thermocouple Installed & Preventive Maint Program Instigated
ML20085L6584 March 1975AO 50-267/75/7:on 750121-23,reactivity Anamoly Occurred Due to Release of Hopper of Reserve Shutdown Mall Into Core. Cause Not Stated.Valve Seats ModifiedBoric Acid
ML20086B06826 February 1975AO 50-267/74-22A:on 741129,high Pressure in Gas Waste Vacuum Tank Blew Rupture Disc & Lifted Relief Valve Allowing Release of 750 Scf Uncontaminated Gas.Caused by Design Inadequacy.Pressure Indicator Installed
ML20085L68518 February 1975AO 50-267/75/6:on 750202,gas Waste Vacuum Tank Rupture Disc Ruptured,Releasing Small Quantity of Gas.Caused by Improper Closure of Air Operated Drain Valve.Valve Will Be Disassembled for Insp
ML20085L70117 February 1975AO 50-267/75/5:on 750127,gas Vacuum Tank Rupture Disc Ruptured,Releasing Small Quantity of Gas.Caused by Inadequate Procedures.Procedure Rewritten
ML20085L71214 February 1975AO 50-267/75/4:on 750125,tritium Leaked from Secondary Closure of Refueling Region 1.Cause Will Be Determined When Vessel Pressure Dropped to Atmospheric or Below
ML20085L77212 February 1975AO 50-267/75/3:on 750123,dew Point Moisture Monitors Failed to Initiate Reactor Scram When Moisture Content Exceeded Trip Setpoint.Caused by Failure of Sample of Primary Coolant to Reach Monitor.Tech Specs Revised
ML20086B12312 February 1975AO 50-267/74-21A:on 741121,high Pressure in Gas Waste Vacuum Tank Lifted Relief Valve Allowing Release of 700 Scf Uncontaminated Gas.Caused by Procedural Error.Inlet Valve Seats Will Be Replaced & Interim Procedure Modified
ML20085L7407 February 1975AO 50-267/75/1:on 750118,230-kV Breaker Tripped Due to High Winds,Causing Standby Diesel Generator a to Receive Start Signal.Generator B Did Not Receive Start Signal.Caused by Sensitive Relay Setting.Relay RecalibrHigh winds
ML20085L72731 January 1975AO 50-267/75/2:on 750113,reactor Bldg Exhaust Charcoal Filters Failed to Meet Tech Spec Leak Rate Requirements. Caused by Use of oil-based Paint & Organic Solvents.Filters Changed Out
ML20085L65025 January 1975AO 50-267/75/24A:on 741222,static Seal on C-2101 (Helium Circulator C) Released During Removal of Temporary Jumpers. Caused by Blown Fuse & Seal Release Valve Leak.All Circulator Brake & Seal Vent Valves Checked
ML20085L73424 January 1975Telecopy Ao:Charcoal in Reactor Bldg Exhaust Filters Failed to Meet Tech Spec Requirements
ML20085L79014 January 1975AO 50-267/74/24:on 741222,static Seal on C-2101 (Helium Circulator C) Released During Removal of Temporary Jumpers.Caused by Jumper Across Logic Circulator a Coming in Contact W/Station Ground
ML20086B05023 December 1974AO 50-267/74-23:on 741211,engine a of Standby Diesel Generator 1-A Declutched & No Alarms Annunciated.Caused by Cylinder Air Pressure Decay Due to Dirt Under Solenoid Valve Seat.Change Notice 11 Re in-line Filters Approved
ML20086B06419 December 1974Telecopy AO 50-267/74-23:on 741211,diesel Engine a of Standby Generator 1-A Declutched