RC-16-0086, Special Report 2016-003 Regarding Fire Barrier Not Restored to Operability Status within 7 Days of Inoperability

From kanterella
Jump to navigation Jump to search
Special Report 2016-003 Regarding Fire Barrier Not Restored to Operability Status within 7 Days of Inoperability
ML16162A753
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 06/09/2016
From: Lippard G
South Carolina Electric & Gas Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
RC-16-0086, SPR 2016-003
Download: ML16162A753 (1)


Text

George Lippard Vice President. Nuclear Operations 41(_ SCE&G@ A SCANA COMPANY 803.345.4810 June 9, 2016 Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555

Dear Sir I Madam:

Subject:

VIRGIL C. SUMMER NUCLEAR STATION (VCSNS), UNIT NO. 1 DOCKET NO. 50-395 OPERATING LICENSE NO. NPF-12 SPECIAL REPORT (SPR) 2016-003 South Carolina Electric & Gas Company (SCE&G) is submitting this Special Report pursuant to the requirements of Technical Specifications 6.9.2 and as required by Station Administrative Procedure (SAP)-131A, Fire Protection Program Surveillances and Compensatory Measures, Enclosure 6.1, step. 6.1.11, Action 4. This report addresses a fire barrier not being restored to operability status within seven days after declaration of inoperability.

On May 7, 2016, at 17:00 hours, Penetration Seal Trace TB-81, Tur.bine Building 412.foot elevation, was declared inoperable after not meeting its surveillance acceptance criteria. The surveillance results revealed cracking in the foam material. The failed surveillance was entered into the station's corrective action program. Fire detection equipment is installed on one side of the penetration and was operable. Upon declaring Penetration Seal Trace TB-81 inoperable, VCSNS implemented an hourly roving fire watch patrol.

Action to repair the penetration consisted of filling an internal void with Kaowool and replacing the damaged foam material. Repairs were completed on May, 26, 2016, and relested

. satisfactorily. Penetration Seal Trace TB-81.was returned to operable status on May 26, 2016, at 13:40 hours.

Should you have any questions, please call Bruce Thompson at (803) 931-5042 at your convenience.

Very truly yours, WCM/GL/ts

~£::~

c: K. B. Marsh S. A. Williams S. A. Byrne NRC Resident Inspector J.B. Archie K.M.Sutton N.S.Carns NSRC J. H. Hamilton RTS (CR-16-'02309)

J. *w. Williams File (818.08)

W. M. Cherry PRSF (RC-16-0086).

C. Haney V. C. Summer Nuclear Station* P. 0. Box 88 *J.enkinsville, SC* 29065