ML23135A193

From kanterella
Jump to navigation Jump to search
EQSD-II, Rev 34, Equipment Qualification Summary Document
ML23135A193
Person / Time
Site: Wolf Creek 
Issue date: 09/01/2022
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML23135A163 List: ... further results
References
WO 23-0006
Download: ML23135A193 (119)


Text

Revision 34 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT EQSD-II COVER SHEET Page 1 of 6 EQSD-II EQ PROGRAM MASTER LIST (Table 1)

Plus Mild Environment SR Electrical Equipment List (Table 2)

Revision History Revision Description 34 See Revision Summary Prepared by:

Yasir Alobaidi Date:

09/01/2022 Qualification Required: ES9280907 Verified by:

Brian Masters Date:

09/01/2022 Qualification Required: ES9280907 Approved by:

John E. Ashley Date:

09/27/2022 Document Service Release by:

Date:

DC7 09/28/2022

Revision 34 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT EQSD-II COVER SHEET Page 2 of 6 EQSD-II R34 Revision

Description:

EQSD-II Change Notices Addressed:

EQSD Change Sequence Number Date Status None

Revision 34 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT EQSD-II COVER SHEET Page 3 of 6 Other Noted Revisions for R34:

Items Affected Reason for Change Changes Made BBZS8010A BBZS8010B BBZS8010C PQE-HE-7-P01, Rev.1 determined the qualified life of listed Crosby switches as being 72.97 years. Based on the last replacement date shown in this PQE Qualification Summary section no further replacement.

Based on last time Crosby switches components been replaced as shown in the PQE Qualification Summary section they will never need to be replaced even with a plant 80 years operation life.

Note:

The Crosby switches components are also removed from EQSD-III as a result on revision 15, since there is no longer a need for any EQ maintenance contingency.

Each of the components identified have been updated to in Table 1, in the MC column field to change the designator from Y to N.

Revision 34 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT EQSD-II COVER SHEET Page 4 of 6 EQSD-II Cover Sheet Instructions 1.0 PURPOSE The EQUIPMENT QUALIFICATION (EQ) MASTER LIST is Table 1 only. Table 1 is used to maintain a listing of components at WCGS that require EQ program documents to maintain qualification of the equipment. This list also identifies if there are any maintenance contingencies required to maintain the identified equipment qualification. It is noted that the Engineering Information System (EIS) and MPAC maintenance databases can be used to identify components that are in the EQ program.

Table 1:

This is the EQ program Master List. It identifies the safety related electrical components that are located in a harsh environment and are required to have an EQ program document. This table lists the equipment that is required to function during an accident and is identified as Category A or B in the LOCA/ HELB/ MSLB fields.

Table 2:

List of safety related electrical components that are either located in a mild environment or not required to function during a design bases accident (DBA). These components, while still needing to be qualified, are not required to have an EQ program file/ document. The equipment is identified as Category C or D in the LOCA/ HELB/ MSLB fields. In some cases, Category C is listed for what was ultimately determined to be a Category D mild environment. This Category C is maintained to retain the knowledge for breach door and/or future EQ related analysis.

Mechanical equipment that was originally in the EQ program and had MEQ type files with a HOT, COLD or BOTH shutdown function is also included.

2.0 FIELDS USED:

The underlined fields below are only used in Table 1. This additional information is not necessary for the equipment not required to have an EQ program document. The EQ program documents are either an Equipment Qualification Work Package (EQWP) or the new electronic version Plant Qualification Evaluation (PQE).

Component Number:

The number used to identify the equipment that is to be created, updated and deleted to track the EQ program activities.

Revision 34 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT EQSD-II COVER SHEET Page 5 of 6 MC: (Maintenance Contingency required)

This field provides information on if the identified EQSD-II master list Table 1 equipment requires any EQSD-III identified Table 1 or Table 2 activities. It also identifies any Table 1 equipment that does not require any EQ QL replacement based on the current plant life of 60 years. Components with no maintenance required can be either due to the QL being greater than 60 years or because the equipment has been replaced recently enough that it no longer needs to be replaced during the 60-year plant life (Ref. QH-2020-2135 as one review and/or see MPAC). It is noted that QH-2020-2135 also provides a good reference for any equipment that may need to be replaced if the life of the plant is extended to 80 years. The following codes are used as applicable:

N - Qualified life (QL) is greater than 60 years, plus there is no EQSD-III Table 2 required activity.

N/Y2 - Qualified life (QL) is greater than 60 years, plus there is no EQSD-III Table 2 required activity, but on EQSD-III Table 2 with an EQ gasket or O-ring replacement requirement.

Y1 - Listed on EQSD-III on Table 1 with EQ QL requirement, but no EQSD-III Table 2 required activity.

Y1/2 - Listed on EQSD-III on Table 1 with an EQ QL requirement and on EQSD-III Table 2 with an EQ gasket or O-ring replacement requirement.

Note:

EIS does not allow the use of any codes other than No or Yes without a software change.

Therefore, when using EIS a No includes only the N code in the EQSD-II and Yes includes codes N/Y2, Y1 and Y1/2.

Equipment Qualification

Description:

The EQ description of the component. This may be different than the over all component description.

Installed Elevation:

Additional information on the location of the equipment. This includes the building, level and area (BLA) identifier to help locate the equipment.

EQ Room:

The room environment the equipment is installed in. Environmental conditions (temperature, pressure, humidity, radiation and flooding) are identified in EQSD-I, Attachment A and B.

EQ Spec:

On Table 1 the identified specification what is used to find the applicable EQWP or PQE program document. On Table 2 it is the associated specification that the equipment was bought to.

Model #:

The installed part number.

Manufacturer:

The name of the manufacture for the model number identified.

LOCA:

Describes the mode in which the component is to function when there is a loss of coolant accident.

HELB:

Describes the mode in which the component is to function when there is a high energy line break.

MSLB:

Describes the mode in which the component is to function when there is a main steam line break.

Revision 34 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT EQSD-II COVER SHEET Page 6 of 6 System:

The system the equipment is part of, for more detail on the system go to the system description.

HOT/ COLD:

HOT SHUTDOWN specifies that the component is required for hot shutdown.

COLD SHUTDOWN specifies that the component is required for cold shutdown.

Notes:

Specifies the number of the note at the end of the list that is related to the component.

3.0 EQSD-II, General Notes Section The notes in this section are applicable to both Table 1 and Table 2. It is noted that there are additional notes that are provided at the end of each table. Those notes are typically specific notes to the equipment for those tables.

General Notes Applicable to All of EQSD-II Tables 1 and 2:

A. The Hot and Cold Shutdown designations are based on a normal shutdown assuming a loss of offsite power and a safe shutdown earthquake. Components located in a harsh environment which are required for safe shutdown because of a LOCA, MSLB, or HELB are identified as Category A or B, except for mechanical equipment with a shutdown function listed as Category C or D listed in Table 2.

B. The normal and accident environment temperature, pressure, radiation, humidity and spray information can be found in EQSD-I Attachments A and B under the room number the equipment is located in.

C. A suffix (i.e. -E01 or -E02) has been added to some component numbers to allow additional EQ information related to the component to be listed in the table. This additional information may include subcomponents qualified to a different Equipment Qualification Work Package (EQWP) or, in some cases, identifies an approved alternative component (for example, a Barton and a Rosemount gauge approved for the identified component application).

EQSD-II Rev. 32 EQSD-II Table 1:

EQ Harsh Environment Equipment List 1 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes 3XBM13 N

AUX RELAY IN PANEL RP209 (BMHV0001) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM14 N

AUX RELAY IN PANEL RP209 (BMHV0002) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM15 N

AUX RELAY IN PANEL RP209 (BMHV0003) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM16 N

AUX RELAY IN PANEL RP209 (BMHV0004) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM17 N

AUX RELAY IN PANEL RP209 (BMHV0065) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM18 N

AUX RELAY IN PANEL RP209 (BMHV0066) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM19 N

AUX RELAY IN PANEL RP209 (BMHV0067) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM20 N

AUX RELAY IN PANEL RP209 (BMHV0068) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM42 N

AUX RELAY IN PANEL RP209 (BMHV0065/ 66/ 67/ 68) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM43 N

AUX RELAY IN PANEL RP209 (BMHV0065/ 66/ 67/ 68) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM44 N

AUX RELAY IN PANEL RP209 (BMHV0065/ 66/ 67/ 68) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XBM45 N

AUX RELAY IN PANEL RP209 (BMHV0065/ 66/ 67/ 68) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

BM BOTH 16 30 3XEG20 N

AUX RELAY IN PANEL RP330 (EGTV0029) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

EG BOTH 17 30 3XEJ01 N

EJHV0014 OPEN AND SEAL IN AUX RELAY IN RP209 (EJHV0014) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

EJ BOTH 16 30 3XEN03 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

EN BOTH 18 30 3XGE05 N

AUX RELAY PANEL RP332 (GEHZ0101, 102, 103, 104) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GE BOTH 18 30 3XGE07 N

AUX RELAY PANEL RP332 (GEHZ0101, 102, 103, 104) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GE BOTH 18 30 3XGE09 N

AUX RELAY PANEL RP332 (GEHZ0101, 102, 103, 104) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GE BOTH 18 30 3XGE11 N

AUX RELAY PANEL RP332 (GEHZ0101, 102, 103, 104) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GE BOTH 18 30 3XGE13 N

AUX RELAY PANEL RP332 (GEHZ0101, 102, 103, 104) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GE BOTH 18 30 3XGE15 N

AUX RELAY PANEL RP332 (GEHZ0101, 102, 103, 104) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GE BOTH 18 30 3XGK16 N

AUX RELAY PANEL RP330 (SGK04A )

134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GK BOTH 17 30 3XGK17 N

AUX RELAY PANEL RP330 (SGK05A )

134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GK BOTH 17 30 3XGN03 N

AUX RELAY IN PANEL RP330 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GN BOTH 17 30

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 2 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes 3XGN05 N

AUX RELAY IN PANEL RP330 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GN BOTH 17 30 3XGN07 N

AUX RELAY IN PANEL RP330 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GN BOTH 17 30 3XGN09 N

AUX RELAY IN PANEL RP330 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GN BOTH 17 30 3XGS01 N

AUX RELAY IN PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS03 N

AUX RELAY IN PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS05 N

AUX RELAY IN PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS07 N

AUX RELAY IN PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS09 N

AUX RELAY IN PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS11 N

AUX RELAY IN PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS13 N

AUX RELAY IN PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS15 N

AUX RELAY PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS17 N

AUX RELAY IN PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS19 N

AUX RELAY IN PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS21 N

AUX RELAY IN PANEL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 16 30 3XGS25 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS27 N

AUX RELAY PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS29 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS31 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS33 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS35 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS37 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS39 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS41 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS43 N

AUX RELAY PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 2 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 3 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes 3XGS45 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS47 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XGS49 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GS BOTH 18 30 3XSJ01 N

120 VAC AUX RELAY IN RP209 FOR SJHV006, 13, 19 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 16 30 3XSJ03 N

120 VAC AUX RELAY IN RP209 FOR SJHV0006 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 16 30 3XSJ05 N

120 VAC AUX RELAY IN RP209 FOR SJHV0006 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 16 30 3XSJ07 N

120 VAC AUX RELAY IN RP209 FOR SJHV0013 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 16 30 3XSJ09 N

120 VAC AUX RELAY IN PANEL RP209 FOR SJHV0013 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 16 30 3XSJ11 N

120 VAC AUX RELAY IN RP209 FOR SJHV0019 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 16 30 3XSJ13 N

120 VAC AUX RELAY IN RP209 FOR SJHV0019 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 16 30 3XSJ25 N

AUX RELAY IN PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 18 30 3XSJ27 N

AUX RELAY IN PNL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 18 30 3XSJ29 N

AUX RELAY IN PNL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 18 30 3XSJ31 N

120 VAC AUX RELAY IN PANEL RP332 FOR SJHV0128, 130 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 18 30 3XSJ33 N

120 VAC AUX RELAY IN PANEL RP332 FOR SJHV0128 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 18 30 3XSJ35 N

120 VAC AUX RELAY IN PANEL RP332 FOR SJHV0128 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

SJ BOTH 18 30 62TDDAL1 N

AUX RELAY IN PANEL RP330 134 AUX BLDG/

ELEV 2000-0 1320 E-093 237NE Ref. E-11012 Struthers-Dunn A

B D

AL BOTH 18 30 62TDEEN1 N

AUX RELAY IN RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 236NE See E-11012 Struthers-Dunn A

B D

EN BOTH 18 30 62TDEGN11 N

AUX RELAY IN PANEL RP330 134 AUX BLDG/

ELEV 2000-0 1320 E-093 236NE See E-11012 Struthers-Dunn A

B D

EG BOTH 17 30 62TDEGN13 N

AUX RELAY IN PANEL RP330 134 AUX BLDG/

ELEV 2000-0 1320 E-093 236NE See E-11012 Struthers-Dunn A

B D

EG BOTH 17 30 62TDENB01 N

NB01 DEGRADED VOLTAGE TRIP RELAY (NB0112) IN RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 236NE See E-11012 Struthers-Dunn A

B D

EN BOTH 18 30 62TDENB02 N

NB01 DEGRADED VOLTAGE TRIP RELAY (NB0109) IN RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 236NE See E-11012 Struthers-Dunn A

B D

EN BOTH 18 30 62TDENB05 N

NB01 DEGRADED VOLTAGE ANNUNCIATOR RELAY (NB0112)

IN RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 236NE See E-11012 Struthers-Dunn A

B D

EN BOTH 18 30 3 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 4 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes 62TDENB06 N

NB01 DEGRADED VOLTAGE ANNUNCIATOR RELAY (NB0109)

IN RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 236NE See E-11012 Struthers-Dunn A

B D

EN BOTH 18 30 94XAB05 N

AUX RELAY IN PNL RP209 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

AB BOTH 16 30 95XGE01 Y1 AUX RELAY PANEL RP330 (GEHZ0103) 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GE BOTH 17 30 95XGE03 N

AUX RELAY PANEL RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

GE BOTH 18 30 95XKA004 N

AUX RELAY IN RP332 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Ref. E-11012 Struthers-Dunn A

B D

KA BOTH 18 30 ABHV0005-E01 N

VALVE TERMINAL BOX 145 AUX BLDG/

ELEV 2026-0 1412 E-093 NQB. 616822 Buchanan (Amerace) C D

A AB BOTH ABHV0006-E01 N

VALVE TERMINAL BOX 145 AUX BLDG/

ELEV 2026-0 1412 E-093 NQB. 616822 Buchanan (Amerace) C D

A AB BOTH ABHV0011-MV1 Y1 LOOP 4 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-1 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0011-MV2 Y1 LOOP 4 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-2 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0011-MV3 Y1 LOOP 4 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-3 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0011-MV4 Y1 LOOP 4 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-4 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0011-MV5 Y1 LOOP 4 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-5 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0011-MV6 Y1 LOOP 4 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-6 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0014-MV1 Y1 LOOP 1 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-1 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0014-MV2 Y1 LOOP 1 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-2 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0014-MV3 Y1 LOOP 1 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-3 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0014-MV4 Y1 LOOP 1 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-4 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0014-MV5 Y1 LOOP 1 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-5 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 4 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 5 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ABHV0014-MV6 Y1 LOOP 1 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-6 145 AUX BLDG/

ELEV 2026-0 1508 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0017-MV1 Y1 LOOP 2 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-1 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0017-MV2 Y1 LOOP 2 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-2 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0017-MV3 Y1 LOOP 2 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-3 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0017-MV4 Y1 LOOP 2 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-4 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0017-MV5 Y1 LOOP 2 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-5 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0017-MV6 Y1 LOOP 2 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-6 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0020-MV1 Y1 LOOP 3 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-1 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0020-MV2 Y1 LOOP 3 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-2 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0020-MV3 Y1 LOOP 3 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-3 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0020-MV4 Y1 LOOP 3 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-4 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0020-MV5 Y1 LOOP 3 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-5 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0020-MV6 Y1 LOOP 3 MAIN STEAM ISO VALVE CONTROL SOLENOID VALVE MV-6 145 AUX BLDG/

ELEV 2026-0 1509 M-630 MV-1 CCI A

D A

AB BOTH 31 ABHV0048-E01 N

VALVE TERMINAL BOX 145 AUX BLDG/

ELEV 2026-0 1412 E-093 NQB. 616822 Buchanan (Amerace) C D

A AB BOTH ABHV0049-E01 N

VALVE TERMINAL BOX 145 AUX BLDG/

ELEV 2026-0 1412 E-093 NQB. 616822 Buchanan (Amerace) C D

A AB BOTH ABHY0012A N

ABHV0012 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1508 M-237 NP8320A187E ASCO A

D C

AB BOTH 31 ABHY0012A-E01 N

VALVE TERMINAL BOX (ABZS0012A) 145 AUX BLDG/

ELEV 2026-0 1508 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH 31 ABHY0012B N

ABHV0012 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1508 M-237 NP8320A187E ASCO A

D C

AB BOTH 31 5 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 6 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ABHY0012B-E01 N

VALVE TERMINAL BOX (ABZS0012B) 145 AUX BLDG/

ELEV 2026-0 1508 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH 31 ABHY0015A N

ABHV0015 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1508 M-237 NP8320A187E ASCO A

D C

AB BOTH 31 ABHY0015A-E01 N

VALVE TERMINAL BOX (ABZS0015A) 145 AUX BLDG/

ELEV 2026-0 1508 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH 31 ABHY0015B N

ABHV0015 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1508 M-237 NP8320A187E ASCO A

D C

AB BOTH 31 ABHY0015B-E01 N

VALVE TERMINAL BOX (ABZS0015B) 145 AUX BLDG/

ELEV 2026-0 1508 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH 31 ABHY0018A N

ABHV0018 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1509 M-237 NP8320A187E ASCO A

D C

AB BOTH 31 ABHY0018A-E01 N

VALVE TERMINAL BOX (ABZS0018A) 145 AUX BLDG/

ELEV 2026-0 1509 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH 31 ABHY0018B N

ABHV0018 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1509 M-237 NP8320A187E ASCO A

D C

AB BOTH 31 ABHY0018B-E01 N

VALVE TERMINAL BOX (ABZS0018B) 145 AUX BLDG/

ELEV 2026-0 1509 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH 31 ABHY0021A N

ABHV0021 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1509 M-237 NP8320A187E ASCO A

D C

AB BOTH 31 ABHY0021A-E01 N

VALVE TERMINAL BOX (ABZS0021A) 145 AUX BLDG/

ELEV 2026-0 1509 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH 31 ABHY0021B N

ABHV0021 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1509 M-237 NP8320A187E ASCO A

D C

AB BOTH 31 ABHY0021B-E01 N

VALVE TERMINAL BOX (ABZS0021B) 145 AUX BLDG/

ELEV 2026-0 1509 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH 31 ABLY0007A N

ABLV0007 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1412 M-237 NP8320A189E ASCO A

D C

AB BOTH ABLY0007A-E01 N

VALVE TERMINAL BOX (ABLY0008B) 145 AUX BLDG/

ELEV 2026-0 1412 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH ABLY0007B N

ABLV0007 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1412 M-237 NP8320A189E ASCO A

D C

AB BOTH ABLY0007B-E01 N

VALVE TERMINAL BOX (ABLY0008A) 145 AUX BLDG/

ELEV 2026-0 1412 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH ABLY0008A N

ABLV0008 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1412 M-237 NP8320A189E ASCO A

D C

AB BOTH ABLY0008B N

ABLV0008 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1412 M-237 NP8320A189E ASCO A

D C

AB BOTH ABLY0009A N

ABLV0009 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1411 M-237 NP8320A189E ASCO A

D C

AB BOTH ABLY0009A-E01 N

VALVE TERMINAL BOX (ABLY0010B) 145 AUX BLDG/

ELEV 2026-0 1411 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH ABLY0009B N

ABLV0009 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1411 M-237 NP8320A189E ASCO A

D C

AB BOTH ABLY0009B-E01 N

VALVE TERMINAL BOX (ABLY0010A) 145 AUX BLDG/

ELEV 2026-0 1411 E-093 NQB. 616822 Buchanan (Amerace) A D

A AB BOTH ABLY0010A N

ABLV0010 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1411 M-237 NP8320A189E ASCO A

D C

AB BOTH 6 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 7 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ABLY0010B N

ABLV0010 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1411 M-237 NP8320A189E ASCO A

D C

AB BOTH ABPT0514 Y1/2 MAIN STEAM PRESSURE LOOP 1 145 AUX BLDG/

ELEV 2026-0 1411 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPT0515 Y1/2 MAIN STEAM PRESSURE LOOP 1 145 AUX BLDG/

ELEV 2026-0 1411 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPT0516 Y1/2 MAIN STEAM PRESSURE LOOP 1 145 AUX BLDG/

ELEV 2026-0 1411 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPT0524 Y1/2 MAIN STEAM PRESSURE LOOP 2 145 AUX BLDG/

ELEV 2026-0 1412 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPT0525 Y1/2 MAIN STEAM PRESSURE LOOP 2 145 AUX BLDG/

ELEV 2026-0 1412 ESE-1A 763A ITT Barton A

D B

AB BOTH 41 42 ABPT0526 Y1/2 MAIN STEAM PRESSURE LOOP 2 145 AUX BLDG/

ELEV 2026-0 1412 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPT0534 Y1/2 MAIN STEAM PRESSURE LOOP 3 145 AUX BLDG/

ELEV 2026-0 1412 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPT0535 Y1/2 MAIN STEAM PRESSURE LOOP 3 145 AUX BLDG/

ELEV 2026-0 1412 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPT0536 Y1/2 MAIN STEAM PRESSURE LOOP 3 145 AUX BLDG/

ELEV 2026-0 1412 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPT0544 Y1/2 MAIN STEAM PRESSURE LOOP 4 145 AUX BLDG/

ELEV 2026-0 1411 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPT0545 Y1/2 MAIN STEAM PRESSURE LOOP 4 145 AUX BLDG/

ELEV 2026-0 1411 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPT0546 Y1/2 MAIN STEAM PRESSURE LOOP 4 145 AUX BLDG/

ELEV 2026-0 1411 ESE-1A 763 ITT Barton A

D B

AB BOTH 41 ABPV0001-E01 N

VALVE TERMINAL BOX 145 AUX BLDG/

ELEV 2026-0 1508 E-093-P03 NQB. 616822 Buchanan (Amerace) B D

A AB BOTH 31 ABPV0002-E01 N

VALVE TERMINAL BOX 145 AUX BLDG/

ELEV 2026-0 1509 E-093-P03 NQB. 616822 Buchanan (Amerace) B D

A AB BOTH 31 ABPV0003-E01 N

VALVE TERMINAL BOX 145 AUX BLDG/

ELEV 2026-0 1509 E-093-P03 NQB. 616822 Buchanan (Amerace) B D

A AB BOTH 31 ABPY0001 Y1 ABPV0001 I/P converter/ transducer 145 AUX BLDG/

ELEV 2026-0 1508 J-601B 8005N Masoneilan B

D A

AB BOTH 31 ABPY0002 Y1 ABPV0002 I/P converter/ transducer 145 AUX BLDG/

ELEV 2026-0 1509 J-601B 8005N Masoneilan B

D A

AB BOTH 31 ABPY0003 Y1 ABPV0003 I/P converter/ transducer 145 AUX BLDG/

ELEV 2026-0 1509 J-601B 8005N Masoneilan B

D A

AB BOTH 31 ABPY0004 Y1 ABPV0004 I/P converter/ transducer 145 AUX BLDG/

ELEV 2026-0 1508 J-601B 8005N Masoneilan B

D A

AB BOTH 31 ABZS0001 Y1/2 ABPV0001 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1508 NAMCO EA180-11302 EA180-12302 NAMCO B

D A

AB BOTH 31 ABZS0002 Y1/2 ABPV0002 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1509 NAMCO EA180-11302 EA180-12302 NAMCO B

D A

AB BOTH 31 ABZS0003 Y1/2 ABPV0003 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1509 NAMCO EA180-11302 EA180-12302 NAMCO B

D A

AB BOTH 31 ABZS0004 Y1/2 ABPV0004 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1508 NAMCO EA180-11302 EA180-12302 NAMCO B

D A

AB BOTH 31 7 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 8 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ABZS0007A Y1/2 ABLV0007 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1412 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

AB BOTH ABZS0007B Y1/2 ABLV0007 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1412 NAMCO EA180-11302 NAMCO A

D C

AB BOTH ABZS0008A Y1/2 ABLV0008 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1412 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

AB BOTH ABZS0008B Y1/2 ABLV0008 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1412 NAMCO EA180-11302 NAMCO A

D C

AB BOTH ABZS0009A Y1/2 ABLV0009 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1411 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

AB BOTH ABZS0009B Y1/2 ABLV0009 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1411 NAMCO EA180-11302 NAMCO A

D C

AB BOTH ABZS0010A Y1/2 ABLV0010 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1411 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

AB BOTH ABZS0010B Y1/2 ABLV0010 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1411 NAMCO EA180-11302 NAMCO A

D C

AB BOTH ABZS0012A Y1/2 ABHV0012 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1508 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

AB BOTH 31 ABZS0012B Y1/2 ABHV0012 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1508 NAMCO EA180-11302 NAMCO A

D C

AB BOTH 31 ABZS0015A Y1/2 ABHV0015 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1508 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

AB BOTH 31 ABZS0015B Y1/2 ABHV0015 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1508 NAMCO EA180-11302 NAMCO A

D C

AB BOTH 31 ABZS0018A Y1/2 ABHV0018 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1509 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

AB BOTH 31 ABZS0018B Y1/2 ABHV0018 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1509 NAMCO EA180-11302 NAMCO A

D C

AB BOTH 31 ABZS0021A Y1/2 ABHV0021 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1509 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

AB BOTH 31 ABZS0021B Y1/2 ABHV0021 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1509 NAMCO EA180-11302 NAMCO A

D C

AB BOTH 31 AEFV0039-MV1 Y1 LOOP 1 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-1 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH AEFV0039-MV2 Y1 LOOP 1 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-2 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH AEFV0039-MV3 Y1 LOOP 1 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-3 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH AEFV0039-MV4 Y1 LOOP 1 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-4 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH AEFV0039-MV5 Y1 LOOP 1 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-5 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH 8 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 9 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes AEFV0039-MV6 Y1 LOOP 1 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-6 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH AEFV0040-MV1 Y1 LOOP 2 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-1 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0040-MV2 Y1 LOOP 2 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-2 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0040-MV3 Y1 LOOP 2 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-3 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0040-MV4 Y1 LOOP 2 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-4 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0040-MV5 Y1 LOOP 2 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-5 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0040-MV6 Y1 LOOP 2 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-6 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0041-MV1 Y1 LOOP 3 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-1 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0041-MV2 Y1 LOOP 3 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-2 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0041-MV3 Y1 LOOP 3 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-3 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0041-MV4 Y1 LOOP 3 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-4 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0041-MV5 Y1 LOOP 3 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-5 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0041-MV6 Y1 LOOP 3 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-6 145 AUX BLDG/

ELEV 2026-0 1412 M-630 MV-1 CCI A

D A

AE BOTH AEFV0042-MV1 Y1 LOOP 4 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-1 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH AEFV0042-MV2 Y1 LOOP 4 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-2 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH AEFV0042-MV3 Y1 LOOP 4 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-3 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH 9 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 10 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes AEFV0042-MV4 Y1 LOOP 4 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-4 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH AEFV0042-MV5 Y1 LOOP 4 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-5 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH AEFV0042-MV6 Y1 LOOP 4 MAIN FEEDWATER ISO VALVE CONTROL SOLENOID VALVE MV-6 145 AUX BLDG/

ELEV 2026-0 1411 M-630 MV-1 CCI A

D A

AE BOTH AELT0501 N/Y2 SG LEVEL WIDE RANGE LOOP 1 231 RX BLDG/

ELEV 1998-6 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH AELT0502 N/Y2 SG LEVEL WIDE RANGE LOOP 2 232 RX BLDG/

ELEV 1998-6 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH AELT0503 N/Y2 SG LEVEL WIDE RANGE LOOP 3 232 RX BLDG/

ELEV 1998-6 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH AELT0504 N/Y2 SG LEVEL WIDE RANGE LOOP 4 231 RX BLDG/

ELEV 1998-6 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH AELT0517 N/Y2 SG LEVEL NARROW RANGE LOOP 1 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH AELT0518 N/Y2 SG LEVEL NARROW RANGE LOOP 1 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

AELT0519 N/Y2 SG LEVEL NARROW RANGE LOOP 1 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

AELT0527 N/Y2 SG LEVEL NARROW RANGE LOOP 2 242 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH AELT0528 N/Y2 SG LEVEL NARROW RANGE LOOP 2 242 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

AELT0529 N/Y2 SG LEVEL NARROW RANGE LOOP 2 242 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

AELT0537 N/Y2 SG LEVEL NARROW RANGE LOOP 3 242 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

AELT0538 N/Y2 SG LEVEL NARROW RANGE LOOP 3 242 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

AELT0539 N/Y2 SG LEVEL NARROW RANGE LOOP 3 242 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

AELT0547 N/Y2 SG LEVEL NARROW RANGE LOOP 4 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

AELT0548 N/Y2 SG LEVEL NARROW RANGE LOOP 4 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

AELT0549 N/Y2 SG LEVEL NARROW RANGE LOOP 4 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH AELT0551 N/Y2 SG LEVEL NARROW RANGE LOOP 1 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

AELT0552 N/Y2 SG LEVEL NARROW RANGE LOOP 2 242 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH AELT0553 N/Y2 SG LEVEL NARROW RANGE LOOP 3 242 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH AELT0554 N/Y2 SG LEVEL NARROW RANGE LOOP 4 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

AE BOTH 9

10 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 11 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BB004A N/Y2 TC REFERENCE JUNCTION BOX 251 RX BLDG/

ELEV 2047-6 2000 ESE-44A WX-34794 Westinghouse A

D A

BB BB004A-E01 N

TC REFERENCE JUNCTION BOX SPLICES - RTD - (121JJ079) 231 RX BLDG/

ELEV 1998-6 2000 ESE-43G 4-Wire Cu Wire/Brass at the reference junction box Westinghouse A

D A

BB 43 BB004A-E02 N/Y2 TC REFERENCE JUNCTION BOX SPLICES - THERMOCOUPLE 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB BB004B N/Y2 TC REFERENCE JUNCTION BOX 251 RX BLDG/

ELEV 2047-6 2000 ESE-44A WX-34794 Westinghouse A

D A

BB BB004B-E01 N

TC REFERENCE JUNCTION BOX SPLICES - RTD - (121JJ079) 231 RX BLDG/

ELEV 1998-6 2000 ESE-43G 4-Wire Cu Wire/Brass at the reference junction box Westinghouse A

D A

BB 43 BB004B-E02 N/Y2 TC REFERENCE JUNCTION BOX SPLICES - THERMOCOUPLE 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB BBFT0017 N/Y2 RCP 1A THRM BARR CLG FLOW 241 RX BLDG/

ELEV 2026-0 2000 J-301 1153DD4RA Rosemount Nuclear B

D B

BB BOTH BBFT0018 N/Y2 RCP 1B THRM BARR CLG FLOW 232 RX BLDG/

ELEV 1998-6 2000 J-301 1153DD4RA Rosemount Nuclear B

D B

BB BOTH BBFT0019 N/Y2 RCP 1C THRM BARR CLG FLOW 242 RX BLDG/

ELEV 2026-0 2000 J-301 1153DD4RA Rosemount Nuclear B

D B

BB BOTH BBFT0020 N/Y2 RCP 1D THRM BARR CLG FLOW 241 RX BLDG/

ELEV 2026-0 2000 J-301 1153DD4RA Rosemount Nuclear B

D B

BB BOTH BBHV0013 N

RCP THERMAL BARRIER COOLER ISOLATION VALVE 2026' CTMT BLDG 2000 LIMITORQU E

SB-00 LIMITORQUE B

D B

BB BOTH BBHV0014 N

RCP THERMAL BARRIER COOLER ISOLATION VALVE 2000' CTMT BLDG.

2000 LIMITORQU E

SB-00 LIMITORQUE B

D B

BB BOTH BBHV0015 N

RCP THERMAL BARRIER COOLER ISOLATION VALVE 2026' CTMT BLDG 2000 LIMITORQU E

SB-00 LIMITORQUE B

D B

BB BOTH BBHV0016 N

RCP THERMAL BARRIER COOLER ISOLATION VALVE 232 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SB-00 LIMITORQUE B

D B

BB BOTH BBHV8000A N

PRESSURIZER PORV ISOLATION VALVE 261 RX BLDG/

ELEV 2068-8 2601 LIMITORQU E

SB-00 LIMITORQUE A

D A

BB BOTH BBHV8000B N

PRESSURIZER PORV ISOLATION VALVE 261 RX BLDG/

ELEV 2068-8 2601 LIMITORQU E

SB-00 LIMITORQUE A

D A

BB BOTH BBHV8001A N/Y2 REACTOR VESSEL HEAD VENT VALVE 252 RX BLDG/

ELEV 2047-6 2000 HE-10A 79AB-001BB Target Rock Corp.

A D

A BB COLD 20 BBHV8001A-E01 N

REACTOR VESSEL HEAD VENT VALVE CONNECTOR 252 RX BLDG/

ELEV 2047-6 2000 J-603A-P04 N11085 Conax A

D A

BB COLD 20 BBHV8001A-E02 N

VALVE TERMINAL BOX 252 RX BLDG/

ELEV 2047-6 2000 E-028 1600 NUC Marathon Special Products A

D A

BB 20 BBHV8001B N/Y2 REACTOR VESSEL HEAD VENT VALVE 252 RX BLDG/

ELEV 2047-6 2000 HE-10A 79AB-001BB Target Rock Corp.

A D

A BB COLD 20 BBHV8001B-E01 N

REACTOR VESSEL HEAD VENT VALVE CONNECTOR 252 RX BLDG/

ELEV 2047-6 2000 J-603A-P04 N11085 Conax A

D A

BB COLD 20 BBHV8001B-E02 N

VALVE TERMINAL BOX 252 RX BLDG/

ELEV 2047-6 2000 E-028 1600 NUC Marathon Special Products A

D A

BB 20 11 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 12 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBHV8002A N/Y2 REACTOR VESSEL HEAD VENT VALVE 252 RX BLDG/

ELEV 2047-6 2000 HE-10A 79AB-001BB Target Rock Corp.

A D

A BB COLD 20 BBHV8002A-E01 N

REACTOR VESSEL HEAD VENT VALVE CONNECTOR 252 RX BLDG/

ELEV 2047-6 2000 J-603A-P04 N11085 Conax A

D A

BB COLD 20 BBHV8002A-E02 N

VALVE TERMINAL BOX 252 RX BLDG/

ELEV 2047-6 2000 E-028 1600 NUC Marathon Special Products A

D A

BB 20 BBHV8002B N/Y2 REACTOR VESSEL HEAD VENT VALVE 252 RX BLDG/

ELEV 2047-6 2000 HE-10A 79AB-001BB Target Rock Corp.

A D

A BB COLD 20 BBHV8002B-E01 N

REACTOR VESSEL HEAD VENT VALVE CONNECTOR 252 RX BLDG/

ELEV 2047-6 2000 J-603A-P04 N11085 Conax A

D A

BB COLD 20 BBHV8002B-E02 N

VALVE TERMINAL BOX 252 RX BLDG/

ELEV 2047-6 2000 E-028 1600 NUC Marathon Special Products A

D A

BB 20 BBHV8010A-E01 N

VALVE TERMINAL BOX 261 RX BLDG/

ELEV 2068-8 2000 E-028 1600 NUC Marathon Special Products A

D A

BB BOTH BBHV8010B-E01 N

VALVE TERMINAL BOX 261 RX BLDG/

ELEV 2068-8 2000 E-028 1600 NUC Marathon Special Products A

D A

BB BOTH BBHV8010C-E01 N

VALVE TERMINAL BOX 261 RX BLDG/

ELEV 2068-8 2000 E-028 1600 NUC Marathon Special Products A

D A

BB BOTH BBHV8026-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D A

BB BBHV8027-E01 N

VALVE TERMINAL BOX 133 AUX BLDG/

ELEV 2000-0 1322 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D D

BB BBHV8351A N

RCP SEAL INJECTION CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SMB-00 LIMITORQUE A

D D

BB BOTH BBHV8351B N

RCP SEAL INJECTION CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SMB-00 LIMITORQUE A

D D

BB BOTH BBHV8351C N

RCP SEAL INJECTION CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SMB-00 LIMITORQUE A

D D

BB BOTH BBHV8351D N

RCP SEAL INJECTION CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SMB-00 LIMITORQUE A

D D

BB BOTH BBHY8026 N

CONTAINMENT ISOL VALVE NITROGEN SUPPLY TO PRT 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO A

D A

BB BBHY8026-E01 N

CONT ISOL VLV NITROGEN SUPPLY TO PRT CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

BB BBHY8027 N

CONTAINMENT ISOL VALVE NITROGEN SUPPLY TO PRT 133 AUX BLDG/

ELEV 2000-0 1322 M-237 NPK831654E ASCO A

D D

BB BBLIS1311 Y1 RVLIS HYDRAULIC ISOLATOR 134 AUX BLDG/

ELEV 2000-0 1323 ESE-49A 581-4 ITT Barton A

D D

BB 26 BBLIS1312 Y1 RVLIS HYDRAULIC ISOLATOR 134 AUX BLDG/

ELEV 2000-0 1323 ESE-49A 581-4 ITT Barton A

D D

BB 26 BBLIS1321 Y1 RVLIS HYDRAULIC ISOLATOR 133 AUX BLDG/

ELEV 2000-0 1322 ESE-49A 581-4 ITT Barton A

D D

BB 26 BBLIS1322 Y1 RVLIS HYDRAULIC ISOLATOR 133 AUX BLDG/

ELEV 2000-0 1322 ESE-49A 581-4 ITT Barton A

D D

BB 26 12 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 13 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBLT0459 N/Y2 PRESSURIZER LEVEL TRANSMITTER 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

BB BOTH BBLT0460 N/Y2 PRESSURIZER LEVEL TRANSMITTER 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

BB BOTH BBLT0461 N/Y2 PRESSURIZER LEVEL TRANSMITTER 241 RX BLDG/

ELEV 2026-0 2201 ESE-3A 764 ITT Barton A

D A

BB BOTH BBLT1311 N

REACTOR VESSEL LEVEL TRANSMITTER NARROW RANGE 134 AUX BLDG/

ELEV 2000-0 1320 ESE-4A 752 ITT Barton A

C D

BB 26 BBLT1312 N

REACTOR VESSEL LEVEL TRANSMITTER WIDE RANGE 134 AUX BLDG/

ELEV 2000-0 1320 ESE-4A 752 ITT Barton A

C D

BB 26 BBLT1321 N

REACTOR VESSEL LEVEL TRANSMITTER NARROW RANGE 121 AUX BLDG/

ELEV 1988-0 1202 ESE-4A 752 ITT Barton A

C D

BB 26 BBLT1322 N

REACTOR VESSEL LEVEL TRANSMITTER WIDE RANGE 123 AUX BLDG/

ELEV 1988-0 1202 ESE-4A 752 ITT Barton A

C D

BB 26 BBPCV0455A N/Y2 PRESSURIZER POWER OPERATED RELIEF VALVE 261 RX BLDG/

ELEV 2068-8 2601 HE-9 3750014 Westinghouse/

Garrett A

D A

BB BOTH BBPCV0455A-E01 N

PRESSURIZER POWER OPERATED RELIEF VLV CONNECTOR 241 RX BLDG/

ELEV 2026-0 2601 J-603A-P04 N11007 Conax A

D A

BB BOTH BBPCV0455A-E02 N

VALVE TERMINAL BOX 261 RX BLDG/

ELEV 2068-8 2601 E-028 1600-NUC Marathon Special Products A

D A

BB BOTH BBPCV0456A N/Y2 PRESSURIZER POWER OPERATED RELIEF VALVE 261 RX BLDG/

ELEV 2068-8 2601 HE-9 3750014 Westinghouse/

Garrett A

D A

BB BOTH BBPCV0456A-E01 N

PRESSURIZER POWER OPERATED RELIEF VLV CONNECTOR 261 RX BLDG/

ELEV 2068-8 2601 J-603A-P04 N11007 Conax A

D A

BB BOTH BBPCV0456A-E02 N

VALVE TERMINAL BOX 261 RX BLDG/

ELEV 2068-8 2601 E-028 1600-NUC Marathon Special Products A

D A

BB BOTH BBPT0403 N/Y2 REACTOR COOLANT SYSTEM PRESSURE WIDE RANGE 123 AUX BLDG/

ELEV 1988-0 1202 ESE-1A 763 ITT Barton A

A D

BB BOTH 41 BBPT0405 N/Y2 REACTOR COOLANT SYSTEM PRESSURE WIDE RANGE 134 AUX BLDG/

ELEV 2000-0 1320 ESE-1B 76PHSS Veritrak A

A D

BB BOTH 30 BBPT0406 N/Y2 REACTOR COOLANT SYSTEM PRESSURE WIDE RANGE 123 AUX BLDG/

ELEV 1988-0 1202 ESE-1A 763 ITT Barton A

A D

BB BOTH 41 BBPT0455 Y1/2 PRESSURIZER PRESSURE TRANSMITTER 241 RX BLDG/

ELEV 2026-0 2201 J-301 1154SH9RA Rosemount Nuclear A

D A

BB BOTH BBPT0456 Y1/2 PRESSURIZER PRESSURE TRANSMITTER 241 RX BLDG/

ELEV 2026-0 2201 J-301 1154SH9RA Rosemount Nuclear A

D A

BB BOTH BBPT0457 Y1/2 PRESSURIZER PRESSURE TRANSMITTER 251 RX BLDG/

ELEV 2047-6 2201 J-301 1154SH9RA Rosemount Nuclear A

D A

BB BOTH BBPT0458 Y1/2 PRESSURIZER PRESSURE TRANSMITTER 251 RX BLDG/

ELEV 2047-6 2201 J-301 1154SH9RA Rosemount Nuclear A

D A

BB BOTH BBPV8702A N

RHR PUMP SUCTION ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-2 LIMITORQUE C

D A

BB BOTH BBPV8702B N

RHR PUMP SUCTION ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-2 LIMITORQUE C

D A

BB BOTH BBT/C0001 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 13 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 14 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBT/C0001-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0002 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0002-E01 N/Y2 THERMOCOUPLE CONNECTOR/

CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0003 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0003-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0004 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0004-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0005 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0005-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0006 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0006-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0007 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0007-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0008 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0008-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0009 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 241 RX BLDG/

ELEV 2026-0 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 14 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 15 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBT/C0009-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0010 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0010-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0012 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0012-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0013 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0013-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0014 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0014-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0015 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0015-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0017 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0017-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0018 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0018-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0019 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 15 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 16 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBT/C0019-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0020 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0020-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0021 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0021-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0022 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0022-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0023 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0023-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0024 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0024-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0025 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0025-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0026 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0026-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0027 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 16 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 17 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBT/C0027-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0028 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0028-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0029 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0029-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0030 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0030-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0031 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0031-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0032 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0032-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0033 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0033-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0034 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0034-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0036 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 17 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 18 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBT/C0036-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0037 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0037-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0038 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0038-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0039 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0039-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0040 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0040-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0041 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0041-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0042 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0042-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0043 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0043-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0044 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 18 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 19 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBT/C0044-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0045 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0045-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0046 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0046-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0047 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0047-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0048 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0048-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0049 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0049-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBT/C0050 N

RV CORE SUBCOOLING MONITOR INCORE THERMOCOUPLES 231 RX BLDG/

ELEV 1998-6 2000 ESE-43A Type K Westinghouse/ CKB Inc.

A D

A BB 26 BBT/C0050-E01 N/Y2 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES 231 RX BLDG/

ELEV 1998-6 2000 J-565 Mineral insulated cable assemblies Combustion Engineering A

D A

BB 26 BBTE0410A1 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0410A2 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0410A3 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0410B N/Y2 RCS COLD LEG RTD TEMP ELE (INSTALLED SPARE) 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0411A1 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 1 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH 19 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 20 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBTE0411A2 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 1 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0411A3 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 1 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0411B N/Y2 RCS COLD LEG RTD TEMP ELEMENT LOOP 1 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0413A N

RCS HOT LEG TEMPERATURE ELEMENT (WR) LOOP 1 231 RX BLDG/

ELEV 1998-6 2201 ESE-6 21205 RDF Corp.

A D

A BB BOTH BBTE0413A-E01 N

RCS HOT LEG RTD CONNECTOR (WR) LOOP 1 231 RX BLDG/

ELEV 1998-6 2201 J-603A-P04 N11007 Conax A

D A

BB BOTH BBTE0413B N

RCS COLD LEG TEMP ELEMENT (WR) LOOP 1 231 RX BLDG/

ELEV 1998-6 2201 ESE-6 21205 RDF Corp.

A D

A BB BOTH BBTE0413B-E01 N

RCS COLD LEG RTD CONNECTOR (WR) LOOP 1 231 RX BLDG/

ELEV 1998-6 2201 J-603A-P04 N11007 Conax A

D A

BB BOTH BBTE0420A1 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0420A2 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0420A3 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0420B N/Y2 RCS COLD LEG RTD TEMP ELE (INSTALLED SPARE) 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0421A1 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 2 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0421A2 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 2 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0421A3 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 2 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0421B N/Y2 RCS COLD LEG RTD TEMP ELEMENT LOOP 2 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0423A N

RCS HOT LEG TEMP ELEMENT (WR) LOOP 2 232 RX BLDG/

ELEV 1998-6 2201 ESE-6 21205 RDF Corp.

A D

A BB BOTH BBTE0423A-E01 N

RCS HOT LEG RTD CONNECTOR (WR) LOOP 2 232 RX BLDG/

ELEV 1998-6 2201 J-603A-P04 N11007 Conax A

D A

BB BOTH BBTE0423B N

RCS COLD LEG TEMP ELEMENT (WR) LOOP 2 232 RX BLDG/

ELEV 1998-6 2201 ESE-6 21205 RDF Corp.

A D

A BB BOTH BBTE0423B-E01 N

RCS COLD LEG RTD CONNECTOR (WR) LOOP 2 232 RX BLDG/

ELEV 1998-6 2201 J-603A-P04 N11007 Conax A

D A

BB BOTH BBTE0430A1 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 3 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0430A2 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0430A3 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0430B N/Y2 RCS COLD LEG RTD TEMP ELE (INSTALLED SPARE) 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0431A1 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB 20 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 21 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBTE0431A2 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 3 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0431A3 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 3 232 RX BLDG/

ELEV 1998-6 2201 ESE-6 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0431B N/Y2 RCS COLD LEG RTD TEMP ELEMENT LOOP 3 232 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0433A N

RCS HOT LEG TEMPERATURE ELEMENT (WR) LOOP 3 232 RX BLDG/

ELEV 1998-6 2201 ESE-6 21205 RDF Corp.

A D

A BB BOTH BBTE0433A-E01 N

RCS HOT LEG RTD CONNECTOR (WR) LOOP 3 232 RX BLDG/

ELEV 1998-6 2201 J-603A-P04 N11007 Conax A

D A

BB BOTH BBTE0433B N

RCS COLD LEG TEMPERATURE ELEMENT (WR) LOOP 3 232 RX BLDG/

ELEV 1998-6 2201 ESE-6 21205 RDF Corp.

A D

A BB BOTH BBTE0433B-E01 N

RCS COLD LEG RTD CONNECTOR (WR) LOOP 3 232 RX BLDG/

ELEV 1998-6 2201 J-603A-P04 N11007 Conax A

D A

BB BOTH BBTE0440A1 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0440A2 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0440A3 N/Y2 RCS HOT LEG RTD TEMP ELE (INSTALLED SPARE) 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0440B N/Y2 RCS COLD LEG RTD TEMP ELE (INSTALLED SPARE) 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BBTE0441A1 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 4 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0441A2 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 4 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0441A3 N/Y2 RCS HOT LEG RTD TEMP ELEMENT LOOP 4 231 RX BLDG/

ELEV 1998-6 2201 ESE-6 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0441B N/Y2 RCS COLD LEG RTD TEMP ELEMENT LOOP 4 231 RX BLDG/

ELEV 1998-6 2201 J-564 N9004E-2A-SP Weed Instrument Co., Inc.

C D

A BB BOTH BBTE0443A N

RCS HOT LEG TEMPERATURE ELEMENT (WR) LOOP 4 231 RX BLDG/

ELEV 1998-6 2201 J-564 21205 RDF Corp.

A D

A BB BOTH BBTE0443A-E01 N

RCS HOT LEG RTD CONNECTOR (WR) LOOP 4 231 RX BLDG/

ELEV 1998-6 2201 J-603A-P04 N11007 Conax A

D A

BB BOTH BBTE0443B N

RCS COLD LEG TEMPERATURE ELEMENT (WR) LOOP 4 231 RX BLDG/

ELEV 1998-6 2201 ESE-6 21205 RDF Corp.

A D

A BB BOTH BBTE0443B-E01 N

RCS COLD LEG RTD CONNECTOR (WR) LOOP 4 231 RX BLDG/

ELEV 1998-6 2201 J-603A-P04 N11007 Conax A

D A

BB BOTH BBTE1313 N

RVLIS HEAD IMPULSE LINE TEMP ELEMENT 242 RX BLDG/

ELEV 2026-0 2000 ESE-42A S8809 MINCO/

Westinghouse A

D A

BB 26 BBTE1314 N

RVLIS HEAD IMPULSE LINE TEMP ELEMENT 242 RX BLDG/

ELEV 2026-0 2000 ESE-42A S8809 MINCO/

Westinghouse A

D A

BB 26 BBTE1317 N

RVLIS SEAL IMPULSE LINE TEMP ELEMENT 241 RX BLDG/

ELEV 2026-0 2000 ESE-42A S8810 MINCO/

Westinghouse A

D A

BB 26 BBTE1318 N

RVLIS SEAL IMPULSE LINE TEMP ELEMENT 241 RX BLDG/

ELEV 2026-0 2000 ESE-42A S8810 MINCO/

Westinghouse A

D A

BB 26 BBTE1323 N

RVLIS HEAD IMPULSE LINE TEMP ELEMENT 241 RX BLDG/

ELEV 2026-0 2000 ESE-42A S8809 MINCO/

Westinghouse A

D A

BB 26 21 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 22 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BBTE1324 N

RVLIS HEAD IMPULSE LINE TEMP ELEMENT 241 RX BLDG/

ELEV 2026-0 2000 ESE-42A S8809 MINCO/

Westinghouse A

D A

BB 26 BBTE1327 N

RVLIS SEAL IMPULSE LINE TEMP ELEMENT 242 RX BLDG/

ELEV 2026-0 2000 ESE-42A S8810 MINCO/

Westinghouse A

D A

BB 26 BBTE1328 N

RVLIS SEAL IMPULSE LINE TEMP ELEMENT 242 RX BLDG/

ELEV 2026-0 2000 ESE-42A S8810 MINCO/

Westinghouse A

D A

BB 26 BBTE1329 N

RVLIS HEAD IMPULSE LINE TEMP ELEMENT 241 RX BLDG/

ELEV 2026-0 2000 ESE-42A S8809 MINCO/

Westinghouse A

D A

BB 26 BBZS0455A N

PRESSURIZER PORV LIMIT SWITCH 261 RX BLDG/

ELEV 2068-8 2601 HE-9 3760060 Westinghouse/

Garrett A

D A

BB BOTH 22 BBZS0455A-E01 N

PRESSURIZER PORV LIMIT SWITCH CONNECTOR 261 RX BLDG/

ELEV 2068-8 2601 J-603A-P04 N11007 Conax A

D A

BB BOTH 22 BBZS0456A N

PRESSURIZER PORV LIMIT SWITCH 261 RX BLDG/

ELEV 2068-8 2601 HE-9 3760060 Westinghouse/

Garrett A

D A

BB BOTH 22 BBZS0456A-E01 N

PRESSURIZER PORV LIMIT SWITCH CONNECTOR 261 RX BLDG/

ELEV 2068-8 2601 J-603A-P04 N11007 Conax A

D A

BB BOTH 22 BBZS8010A N

PRESSURIZER SAFETY RELIEF VALVE LIMIT SWITCH 261 RX BLDG/

ELEV 2068-8 2602 HE-7 65322 Westinghouse/

Garrett A

D A

BB BOTH 22 BBZS8010A-E01 N

PRESSURIZER SAFETY RELIEF VALVE LS CONNECTOR 261 RX BLDG/

ELEV 2068-8 2602 J-603A-P04 N11007 Conax A

D A

BB BOTH 22 BBZS8010B N

PRESSURIZER SAFETY RELIEF VALVE LIMIT SWITCH 261 RX BLDG/

ELEV 2068-8 2602 HE-7 65322 Westinghouse/

Garrett A

D A

BB BOTH 22 BBZS8010B-E01 N

PRESSURIZER SAFETY RELIEF VALVE LS CONNECTOR 261 RX BLDG/

ELEV 2068-8 2602 J-603A-P04 N11007 Conax A

D A

BB BOTH 22 BBZS8010C N

PRESSURIZER SAFETY RELIEF VALVE LIMIT SWITCH 261 RX BLDG/

ELEV 2068-8 2602 HE-7 65322 Westinghouse/

Garrett A

D A

BB BOTH 22 BBZS8010C-E01 N

PRESSURIZER SAFETY RELIEF VALVE LS CONNECTOR 261 RX BLDG/

ELEV 2068-8 2602 J-603A-P04 N11007 Conax A

D A

BB BOTH 22 BBZS8026 N/Y2 CONTMN ISOL VLV NIT SUPPLY TO PRT LIMIT SWITCH 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-14303 EA180-15303 NAMCO A

D A

BB BBZS8026-E01 N

CONT ISOL VLV NIT SUPPLY TO PRT LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

BB BBZS8027 N/Y2 CONTMN ISOL VLV NIT SUPPLY TO PRT LIMIT SWITCH 231 RX BLDG/

ELEV 1998-6 1322 HE-3/6 EA180-35303 EA180-34303 NAMCO A

D D

BB BBZS8702AA N/Y2 RHR PUMP SUCTION ISOLATION VALVE LIMIT SWITCH 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-12303 EA180-12303 NAMCO C

D A

BB BOTH BBZS8702AA-E01 N

VALVE TERMINAL BOX (BBZS8702AB) 231 RX BLDG/

ELEV 1998-6 2000 E-028 1600-NUC Marathon Special Products A

D A

BB BOTH BBZS8702AA-E02 N

RHR PUMP SUCTION ISOLATION VALVE LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax C

D A

BB BOTH BBZS8702AB N/Y2 RHR PUMP SUCTION ISOLATION VALVE LIMIT SWITCH 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-12303 EA180-12303 NAMCO C

D A

BB BOTH BBZS8702AB-E01 N

RHR PUMP SUCTION ISOLATION VALVE LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax C

D A

BB BOTH BGFT0215A Y1 RCP SEAL INJECTION FLOW TRANSMITTER 123 AUX BLDG/

ELEV 1988-0 1202 J-301 1153HB5RCN0012 Rosemount Nuclear A

C D

BG BOTH BGFT0215B N

RCP SEAL INJECTION FLOW TRANSMITTER 123 AUX BLDG/

ELEV 1988-0 1202 ESE-4A 752 ITT Barton A

C D

BG BOTH 22 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 23 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BGFT0215B-E01 N

RCP SEAL INJECTION FLOW TRANSMITTER 123 AUX BLDG/

ELEV 1988-0 1202 J-301 1153HB5RC Rosemount Nuclear A

C D

BG BOTH BGHV8100 N

SEAL WATER RETURN CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SMB-00 LIMITORQUE A

D D

BG BGHV8105 N

CHARGING LINE CONTAINMENT ISOLATION VALVE 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SB-00 LIMITORQUE A

D D

BG BOTH BGHV8106 N

CHARGING LINE ISOLATION VALVE 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SB-00 LIMITORQUE A

D D

BG BOTH BGHV8110 N

CCP A MINIFLOW ISOLATION VALVE 112 AUX BLDG/

ELEV 1974-0 1114 LIMITORQU E

SMB-00 LIMITORQUE A

D D

BG BOTH 29 BGHV8111 N

CCP B MINIFLOW ISOLATION VALVE 111 AUX BLDG/

ELEV 1974-0 1107 LIMITORQU E

SMB-00 LIMITORQUE A

D D

BG BOTH 28 BGHV8112 N

SEAL WATER RETURN CONTAINMENT ISOL VALVE 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-00 LIMITORQUE A

D A

BG BGHV8152-E01 N

VALVE TERMINAL BOX 133 AUX BLDG/

ELEV 2000-0 1322 E-093 NQB. 616822 Buchanan (Amerace) A D

D BG BGHV8153A N/Y2 EXCESS LETDOWN/RCS ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 HE-10A (XR-5240)

Target Rock Corp.

C D

B BG BOTH 45 BGHV8153A-E01 N

EXCESS LETDOWN/RCS ISOLATION VALVE CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax C

D B

BG BOTH BGHV8153B N/Y2 EXCESS LETDOWN/RCS ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 HE-10A 79AB-001BB Target Rock Corp.

C D

B BG BOTH 45 BGHV8153B-E01 N

EXCESS LETDOWN/RCS ISOLATION VALVE CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax C

D B

BG BOTH BGHV8154A N/Y2 EXCESS LETDOWN/RCS ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 HE-10A 79AB-001BB Target Rock Corp.

B D

B BG BOTH 45 BGHV8154A-E01 N

EXCESS LETDOWN/RCS ISOLATION VALVE CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax B

D B

BG BOTH BGHV8154B N/Y2 EXCESS LETDOWN/RCS ISOLATION VALVE 231 CTMT BLDG/

ELEV 2006 2000 HE-10A 79AB-001BB Target Rock Corp.

B D

B BG BOTH 45 BGHV8154B-E01 N

EXCESS LETDOWN/RCS ISOLATION VALVE CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax B

D B

BG BOTH BGHV8160-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-035B-P02 601-JJ, 602-JJ, 604-JJ Kulka A

D A

BG BGHY8152 Y1 LETDOWN CONTAINMENT ISOLATION VALVE (BGHV8152) 133 AUX BLDG/

ELEV 2000-0 1322 M-237 NPK831654E ASCO (NE)

A D

D BG BGHY8160 Y1 LETDOWN CONTAINMENT ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO (NE)

A D

A BG BGHY8160-E01 N

LETDOWN CONTAINMENT ISOLATION VALVE CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

BG BGLCV0112B N

VCT ISOLATION VALVE FROM CHARGING PUMP SUCTION 132 AUX BLDG/

ELEV 2000-0 1318 LIMITORQU E-P04 SB-00 LIMITORQUE A

C D

BG BOTH BGLCV0112C N

VCT ISOLATION VALVE FROM CHARGING PUMP SUCTION 132 AUX BLDG/

ELEV 2000-0 1318 LIMITORQU E-P04 SB-00 LIMITORQUE A

C D

BG BOTH BGZS8152 N/Y2 LETDOWN CONTAINMENT ISOL VLV LMT SWITCH 133 AUX BLDG/

ELEV 2000-0 1322 NAMCO HE-3/6 EA180-11302 EA180-12303 NAMCO A

D D

BG 23 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 24 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BGZS8160 N/Y2 LETDOWN CONTAINMENT ISOL VLV LIMIT SWITCH 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-11303 EA180-12303 NAMCO A

D A

BG BGZS8160-E01 N

LETDOWN CONTAINMENT ISOL VLV LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

BG BLHV8047-E01 N

VALVE TERMINAL BOX 133 AUX BLDG/

ELEV 2000-0 1322 E-093 NQB. 616822 Buchanan (Amerace) A D

D BL BLHY8047 Y1 CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 M-237 NPK831654E ASCO (NE)

A D

D BL BLZS8047 N/Y2 CONTAINMENT ISOLATION VALVE LIMIT SWITCH 133 AUX BLDG/

ELEV 2000-0 1322 HE-3/6 EA180-14303 EA180-15303 NAMCO A

D D

BL BMHV0001-E01 N

VALVE TERMINAL BOX 145 AUX BLDG/

ELEV 2026-0 1411 E-093 NQB. 616822 Buchanan (Amerace) A D

A BM HOT BMHV0002-E01 N

VALVE TERMINAL BOX (AEFV0044) 145 AUX BLDG/

ELEV 2026-0 1412 E-093 NQB. 616822 Buchanan (Amerace) A D

A BM HOT BMHV0003-E01 N

VALVE TERMINAL BOX 145 AUX BLDG/

ELEV 2026-0 1412 E-093 NQB. 616822 Buchanan (Amerace) A D

A BM HOT BMHV0004-E01 N

VALVE TERMINAL BOX (AEFV0046) 145 AUX BLDG/

ELEV 2026-0 1411 E-093 NQB. 616822 Buchanan (Amerace) A D

A BM HOT BMHY0001A Y1 BMHV0001 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1411 M-237 NP8321A6E ASCO (NE)

A D

C BM HOT BMHY0001B Y1 BMHV0001 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1411 M-237 NP8321A6E ASCO (NE)

A D

C BM HOT BMHY0001B-E01 N

VALVE TERMINAL BOX (AEFV0043, BMZS0001B) 145 AUX BLDG/

ELEV 2026-0 1411 E-093 NQB. 616822 Buchanan (Amerace) A D

A BM BOTH BMHY0002A Y1 BMHV0002 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1412 M-237 NP8321A6E ASCO (NE)

A D

C BM HOT BMHY0002B Y1 BMHV0002 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1412 M-237 NP8321A6E ASCO (NE)

A D

C BM HOT BMHY0002B-E01 N

VALVE TERMINAL BOX (BMZS0002B) 145 AUX BLDG/

ELEV 2026-0 1412 E-093 NQB. 616822 Buchanan (Amerace) A D

A BM HOT BMHY0003A Y1 BMHV0003 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1412 M-237 NP8321A6E ASCO (NE)

A D

C BM HOT BMHY0003B Y1 BMHV0003 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1412 M-237 NP8321A6E ASCO (NE)

A D

C BM HOT BMHY0003B-E01 N

VALVE TERMINAL BOX (AEFV0045, BMZS0003B) 145 AUX BLDG/

ELEV 2026-0 1412 E-093 NQB. 616822 Buchanan (Amerace) A D

A BM BOTH BMHY0004A Y1 BMHV0004 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1411 M-237 NP8321A6E ASCO (NE)

A D

C BM HOT BMHY0004B Y1 BMHV0004 SOLENOID VALVE 145 AUX BLDG/

ELEV 2026-0 1411 M-237 NP8321A6E ASCO (NE)

A D

C BM HOT BMHY0004B-E01 N

VALVE TERMINAL BOX (BMZS0004B) 145 AUX BLDG/

ELEV 2026-0 1411 E-093 NQB. 616822 Buchanan (Amerace) A D

A BM HOT BMZS0001A Y1/2 BMHV0001 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1411 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

BM HOT BMZS0001B Y1/2 BMHV0001 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1411 NAMCO EA180-11302 NAMCO A

D C

BM HOT BMZS0002A Y1/2 BMHV0002 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1412 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

BM HOT 24 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 25 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes BMZS0002B Y1/2 BMHV0002 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1412 NAMCO EA180-11302 NAMCO A

D C

BM HOT BMZS0003A Y1/2 BMHV0003 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1412 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

BM HOT BMZS0003B Y1/2 BMHV0003 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1412 NAMCO EA180-11302 NAMCO A

D C

BM HOT BMZS0004A Y1/2 BMHV0004 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1411 NAMCO EA180-11302 EA180-12302 NAMCO A

D C

BM HOT BMZS0004B Y1/2 BMHV0004 LIMIT SWITCH 145 AUX BLDG/

ELEV 2026-0 1411 NAMCO EA180-11302 NAMCO A

D C

BM HOT BNHCV8800A-E01 N

VALVE TERMINAL BOX 121 AUX BLDG/

ELEV 1988-0 1202 E-093 NQB. 616822 Buchanan (Amerace) A C

D BN BOTH BNHCV8800B-E01 N

VALVE TERMINAL BOX 121 AUX BLDG/

ELEV 1988-0 1202 E-093 NQB. 616822 Buchanan (Amerace) A C

D BN BOTH BNHV0003 N

CONTAINMENT SPRAY PUMP SUCTION ISO VALVE 111 AUX BLDG/

ELEV 1974-0 1110 LIMITORQU E

SMB-00 LIMITORQUE A

D D

BN BNHV0004 N

CONTAINMENT SPRAY PUMP SUCTION ISO VALVE 112 AUX BLDG/

ELEV 1974-0 1112 LIMITORQU E

SMB-00 LIMITORQUE A

D D

BN BNHV8806A N

SAFETY INJECTION PUMP RWST SUCTION VALVE 112 AUX BLDG/

ELEV 1974-0 1113 LIMITORQU E

SB-00 LIMITORQUE A

D D

BN 29 BNHV8806B N

SAFETY INJECTION PUMP RWST SUCTION VALVE 111 AUX BLDG/

ELEV 1974-0 1108 LIMITORQU E

SB-00 LIMITORQUE A

D D

BN 28 BNHV8812A N

RHR PUMP RWST SUCTION VALVE 112 AUX BLDG/

ELEV 1974-0 1111 LIMITORQU E

SB-1 LIMITORQUE A

D D

BN COLD BNHV8812B N

RHR PUMP RWST SUCTION VALVE 111 AUX BLDG/

ELEV 1974-0 1109 LIMITORQU E

SB-1 LIMITORQUE A

D D

BN COLD BNHV8813 N

ISOLATION VALVE FOR SI PUMPS MIN RECIRCULATION 111 AUX BLDG/

ELEV 1974-0 1108 LIMITORQU E

SMB-00 LIMITORQUE A

D D

BN 28 BNHY8800A N

RWST ISOLATION VALVE FOR FUEL POOL CLEANUP PUMPS 121 AUX BLDG/

ELEV 1988-0 1202 M-237 NP831655E ASCO A

C D

BN BOTH BNHY8800B N

RWST ISOLATION VALVE FOR FUEL POOL CLEANUP PUMPS 121 AUX BLDG/

ELEV 1988-0 1202 M-237 NP831655E ASCO A

C D

BN BOTH BNLCV0112D N

CHARGING PUMP RWST SUCTION VALVE 112 AUX BLDG/

ELEV 1974-0 1114 LIMITORQU E

SB-00 LIMITORQUE A

D D

BN BOTH 29 BNLCV0112E N

CHARGING PUMP RWST SUCTION VALVE 111 AUX BLDG/

ELEV 1974-0 1107 LIMITORQU E

SB-00 LIMITORQUE A

D D

BN BOTH 28 BNZS8800A N/Y2 RWST ISOL VLV FOR FUEL POOL CLEANUP PUMPS LMT SW 121 AUX BLDG/

ELEV 1988-0 1202 NAMCO HE-3/6 EA180-12302 EA180-11303 NAMCO A

C D

BN COLD BNZS8800B N/Y2 RWST ISOL VLV FOR FUEL POOL CLEANUP PUMPS LMT SW 121 AUX BLDG/

ELEV 1988-0 1202 NAMCO EA180-11302 EA180-11302 NAMCO A

C D

BN COLD BNZS8812AA N/Y2 RHR PUMP RWST SUCTION VALVE LIMIT SWITCH 112 AUX BLDG/

ELEV 1974-0 1111 HE-3/6 EA180-12303 EA180-12303 (spare)

NAMCO A

D D

BN COLD 39 BNZS8812BA N/Y2 RHR PUMP RWST SUCTION VALVE LIMIT SWITCH 111 AUX BLDG/

ELEV 1974-0 1109 HE-3/6 NAMCO EA180-12303 (spare)

EA180-12302 NAMCO A

D D

BN COLD 39 BNZS8813 N/Y2 ISOL VLV FOR SI PUMPS MIN.

RECIRC LIMIT SWITCH 111 AUX BLDG/

ELEV 1974-0 1108 NAMCO HE-3/6 EA180-21302 EA180-21303 NAMCO A

D D

BN 28 25 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 26 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes DPBG05A N

CENTRIFUGAL CHARGING PUMP A MOTOR 112 AUX BLDG/

ELEV 1974-0 1114 AE-2 FRAME-5808-P39 500 HP Westinghouse A

D D

BG BOTH 29 DPBG05A-E01 N

CENTRIFUGAL CHARGING PUMP A MOTOR TERMINATE KIT 112 AUX BLDG/

ELEV 1974-0 1114 E-029-P02 DS-7445/ P/N 3.99.16-3x250MCM-HVNS Kerite/ EGS (option) A C

D BG BOTH 29 DPBG05B N

CENTRIFUGAL CHARGING PUMP B MOTOR 111 AUX BLDG/

ELEV 1974-0 1107 AE-2 FRAME-5808-P39 500 HP Westinghouse A

D D

BG BOTH 28 DPBG05B-E01 N

CENTRIFUGAL CHARGING PUMP B MOTOR TERMINATE KIT 111 AUX BLDG/

ELEV 1974-0 1107 E-029-P02 P/N 3.99.16-3x250MCM-HVNS EGS A

D D

BG BOTH 28 DPEJ01A N

RHR PUMP A MOTOR 112 AUX BLDG/

ELEV 1974-0 1111 AE-2 FRAME-5808-P39 500 HP Westinghouse A

D D

EJ COLD DPEJ01A-E01 N

RHR PUMP A MOTOR TERMINATION KIT 112 AUX BLDG/

ELEV 1974-0 1111 E-029-P02 P/N 3.99.16-3x250MCM-HVNS EGS A

D D

EJ COLD DPEJ01B N

RHR PUMP B MOTOR 111 AUX BLDG/

ELEV 1974-0 1109 AE-2 FRAME-5808-P39 500 HP Westinghouse A

D D

EJ COLD DPEJ01B-E01 N

RHR PUMP B MOTOR TERMINATION KIT 111 AUX BLDG/

ELEV 1974-0 1109 E-029-P02 P/N 3.99.16-3x250MCM-HVNS EGS A

D D

EJ COLD DPEM01A N

SI PUMP A MOTOR 112 AUX BLDG/

ELEV 1974-0 1113 AE-2 LIFELINE D, FRAME 5808H Westinghouse A

D D

EM 29 DPEM01A-E01 N

SI PUMP A MOTOR TERMINATION KIT 112 AUX BLDG/

ELEV 1974-0 1113 E-029-P02 P/N 3.99.16-3x250MCM-HVNS EGS A

D D

EM 29 DPEM01B N

SI PUMP B MOTOR 111 AUX BLDG/

ELEV 1974-0 1108 AE-2 LIFELINE D, FRAME 5808H Westinghouse A

D D

EM 28 DPEM01B-E01 N

SI PUMP B MOTOR TERMINATION KIT 111 AUX BLDG/

ELEV 1974-0 1108 E-029-P02 P/N 3.99.16-3x250MCM-HVNS EGS A

D D

EM 28 DPEN01A N

CONTAINMENT SPRAY PUMP A MOTOR 112 AUX BLDG/

ELEV 1974-0 1112 M-088/AE P01 Motor info on drawing M-088-00051 Westinghouse A

D D

EN DPEN01A-E01 N

CONTAINMENT SPRAY PUMP A MOTOR TERMINATION KIT 112 AUX BLDG/

ELEV 1974-0 1112 E-029-P02 DS-7445/ P/N 3.99.16-3x250MCM-HVNS Kerite/ EGS (option) A D

D EN DPEN01B N

CONTAINMENT SPRAY PUMP B MOTOR 112 AUX BLDG/

ELEV 1974-0 1110 M-088/AE P01 Motor info on drawing M-088-00051 Westinghouse A

D D

EN DPEN01B-E01 N

CONTAINMENT SPRAY PUMP B MOTOR TERMINATION KIT 112 AUX BLDG/

ELEV 1974-0 1110 E-029-P02 DS-7445/ P/N 3.99.16-3x250MCM-HVNS Kerite/ EGS (option) A D

D EN DSGL09A N

SI PUMP ROOM COOLER MOTOR 112 AUX BLDG/

ELEV 1974-0 1113 M-612 Lifeline T: Frame 256T Westinghouse/

Carrier A

D D

GL 29 DSGL09B N

SI PUMP ROOM COOLER MOTOR 111 AUX BLDG/

ELEV 1974-0 1108 M-612 Lifeline T: Frame 256T Westinghouse/

Carrier A

D D

GL 28 DSGL10A N

RHR PUMP ROOM COOLER MOTOR 112 AUX BLDG/

ELEV 1974-0 1111 M-612 Lifeline T: Frame 256T Westinghouse/

Carrier A

D D

GL COLD DSGL10B N

RHR PUMP ROOM COOLER MOTOR 111 AUX BLDG/

ELEV 1974-0 1109 M-612 Lifeline T: Frame 256T Westinghouse/

Carrier A

D D

GL COLD DSGL12A N

CENT. CHARGING PUMP ROOM COOLER MOTOR 112 AUX BLDG/

ELEV 1974-0 1114 M-612 Lifeline T: Frame 256T Westinghouse/

Carrier A

D D

GL BOTH 29 DSGL12B N

CENT. CHARGING PUMP ROOM COOLER MOTOR 112 AUX BLDG/

ELEV 1974-0 1107 M-612 Lifeline T: Frame 256T Westinghouse/

Carrier A

D D

GL BOTH 28 26 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 27 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes DSGL13A N

CTMT. SPRAY PUMP ROOM COOLER MOTOR 112 AUX BLDG/

ELEV 1974-0 1112 M-612 Lifeline T: Frame 256T Westinghouse/

Carrier A

D D

GL DSGL13B N

CTMT. SPRAY PUMP ROOM COOLER MOTOR 111 AUX BLDG/

ELEV 1974-0 1110 M-612 Lifeline T: Frame 256T Westinghouse/

Carrier A

D D

GL DSGL15A N

PENETRATION ROOM COOLER MOTOR 144 AUX BLDG/

ELEV 2026-0 1410 M-612 Lifeline T: Frame 258T Westinghouse/

Carrier A

D D

GL BOTH DSGL15B N

PENETRATION ROOM COOLER MOTOR 143 AUX BLDG/

ELEV 2026-0 1409 M-612 Lifeline T: Frame 258T Westinghouse/

Carrier A

D D

GL BOTH DSGN01A N

CONTAINMENT COOLER FAN MOTOR 262 RX BLDG/

ELEV 2068-8 2000 M-620 600287-43 MOTOR, 150/75 HP NOMINAL, 460 VAC, 3 PHASE, 60 HZ,

RELIANCE, 5005UCZ FRAME American Air Filter (Joy/Reliance)

A D

A GN BOTH DSGN01B N

CONTAINMENT COOLER FAN MOTOR 262 RX BLDG/

ELEV 2068-8 2000 M-620 600287-43 MOTOR, 150/75 HP NOMINAL, 460 VAC, 3 PHASE, 60 HZ,

RELIANCE, 5005UCZ FRAME American Air Filter (Joy/Reliance)

A D

A GN BOTH DSGN01C N

CONTAINMENT COOLER FAN MOTOR 261 RX BLDG/

ELEV 2068-8 2000 M-620 600287-43 MOTOR, 150/75 HP NOMINAL, 460 VAC, 3 PHASE, 60 HZ,

RELIANCE, 5005UCZ FRAME American Air Filter (Joy/Reliance)

A D

A GN BOTH DSGN01D N

CONTAINMENT COOLER FAN MOTOR 261 RX BLDG/

ELEV 2068-8 2000 M-620 600287-43 MOTOR, 150/75 HP NOMINAL, 460 VAC, 3 PHASE, 60 HZ,

RELIANCE, 5005UCZ FRAME American Air Filter (Joy/Reliance)

A D

A GN BOTH EFHV0031 N

CONTAINMENT COOLER ISOLATION VALVE 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SMB-000 LIMITORQUE B

D D

EF BOTH EFHV0032 N

CONTAINMENT COOLER ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SMB-000 LIMITORQUE B

D D

EF BOTH EFHV0033 N

CONTAINMENT COOLER ISOLATON VALVE 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-000 LIMITORQUE B

D B

EF BOTH EFHV0034 N

CONTAINMENT COOLER ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-000 LIMITORQUE B

D B

EF BOTH EFHV0043-E01 N

VALVE TERMINAL BOX 134 AUX BLDG/

ELEV 2000-0 1320 E-093 NQB. 616822 Buchanan (Amerace) A A

D EF BOTH 30 EFHV0044-E01 N

VALVE TERMINAL BOX 134 AUX BLDG/

ELEV 2000-0 1320 E-093 NQB. 616822 Buchanan (Amerace) A A

D EF BOTH 30 EFHV0045 N

CONTAINMENT COOLER ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-000 LIMITORQUE B

B D

EF BOTH EFHV0046 N

CONTAINMENT COOLER ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-000 LIMITORQUE B

B D

EF BOTH 27 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 28 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes EFHV0049 N

CONTAINMENT COOLER ISOLATION VALVE 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SMB-000 LIMITORQUE A

D D

EF BOTH EFHV0050 N

CONTAINMENT COOLER ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SMB-000 LIMITORQUE A

D D

EF BOTH EFHY0043 Y1 EFHV0043 SOLENOID VALVE 134 AUX BLDG/

ELEV 2000-0 1320 M-237 NP8320A187E ASCO (NE)

A A

D EF BOTH 30 EFHY0044 Y1 EFHV0044 SOLENOID VALVE 134 AUX BLDG/

ELEV 2000-0 1320 M-237 NP8320A187E ASCO (NE)

A A

D EF BOTH 30 EFPDT0043 Y1 ESW TO AIR COMPRESOR ISO 134 AUX BLDG/

ELEV 2000-0 1320 J-301 1153DB6R Rosemount Nuclear A

C D

EF BOTH 30 EFPDT0044 Y1 ESW TO AIR COMPRESOR ISO 134 AUX BLDG/

ELEV 2000-0 1320 J-301 1153DB6R Rosemount Nuclear A

C D

EF BOTH 30 EFZS0043 N/Y2 EFHV0043 LIMIT SWITCH 134 AUX BLDG/

ELEV 2000-0 1320 NAMCO EA180-11302 EA180-12302 NAMCO A

A D

EF BOTH 30 EFZS0044 N/Y2 EFHV0044 LIMIT SWITCH 134 AUX BLDG/

ELEV 2000-0 1320 NAMCO EA180-11302 EA180-12302 NAMCO A

A D

EF BOTH 30 EGFT0062 Y1 RCP THERMAL BARRIER (TOTAL)

OUTLET FLOW 134 AUX BLDG/

ELEV 2000-0 1127 J-301 1153DB4R Rosemount Nuclear A

D D

EG BOTH EGFT0128 Y1 CCW HX OUT TO RCP BY-PASS 134 AUX BLDG/

ELEV 2000-0 1320 J-301 1153DB5R Rosemount Nuclear B

C D

EG BOTH 30 EGFT0129 Y1 CCW HX OUT TO RCP BY-PASS 134 AUX BLDG/

ELEV 2000-0 1320 J-301 1153DB5R Rosemount Nuclear B

C D

EG BOTH 30 EGHV0058 N

RC PUMP CCW SUPPLY CONT ISO 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SB-0 LIMITORQUE A

D D

EG BOTH EGHV0059 N

RC PUMP CCW RETURN CONT ISO 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SMB-0 LIMITORQUE A

D D

EG BOTH EGHV0060 N

RC PUMP CCW RETURN CONT ISO 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-0 LIMITORQUE A

D A

EG BOTH EGHV0061 N

CONT ISO VLV CCW RTN FROM RC PMP THER BARR 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SMB-000 LIMITORQUE A

D D

EG BOTH EGHV0062 N

CONT ISO VLV CCW RTN FROM RC PMP THER BARR 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-00 LIMITORQUE A

D A

EG BOTH EGHV0071 N

ISO VALVE CCW SUPPLY TO RC PUMP 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SB-0 LIMITORQUE A

D D

EG BOTH EJFCV0610 N

RHR MINI FLOW ISOLATION VALVE LOOP A 111 AUX BLDG/

ELEV 1974-0 1111 LIMITORQU E

SMB-000 LIMITORQUE A

D D

EJ COLD EJFCV0611 N

RHR MINI FLOW ISOLATION VALVE LOOP B 111 AUX BLDG/

ELEV 1974-0 1109 LIMITORQU E

SMB-000 LIMITORQUE A

D D

EJ COLD EJFIS0611 Y1 RHR PUMP B MIN. FLOW INDICATING SWITCH 131 AUX BLDG/

ELEV 2000-0 1107 ESE-40A 581A-0 ITT Barton A

D D

EJ COLD 28 EJHCV8825-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D A

EJ EJHCV8890A-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D A

EJ COLD EJHCV8890B-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D A

EJ COLD EJHV0014 N

RHR 1A TO NUC SAM SYS 132 AUX BLDG/

ELEV 2000-0 1310 J-603A V52600-6040-7 Valcor Engineering B

D D

EJ 28 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 29 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes EJHV0015 N

RHR 1B TO NUC SAM SYS 131 AUX BLDG/

ELEV 2000-0 1309 J-603A V52600-6040-7 Valcor Engineering B

D D

EJ EJHV8701A N

RHR SHUTDOWN SUCTION LINE ISOLATION VALVE LOOP A 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-2 LIMITORQUE B

D A

EJ BOTH EJHV8701B N

RHR SHUTDOWN SUCTION LINE ISOLATION VALVE LOOP B 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-2 LIMITORQUE B

D A

EJ BOTH EJHV8716A N

RHR INJECTION BALANCE LINE/HL FEED LINE VALVE 132 AUX BLDG/

ELEV 2000-0 1310 LIMITORQU E

SB-1 LIMITORQUE A

D D

EJ COLD EJHV8716B N

RHR INJECTION BALANCE LINE/HL FEED LINE VALVE 131 AUX BLDG/

ELEV 2000-0 1309 LIMITORQU E

SB-1 LIMITORQUE A

D D

EJ COLD EJHV8804A N

RHR TO CHARGING SI PUMP SUCTIONS 132 AUX BLDG/

ELEV 2000-0 1310 LIMITORQU E

SB-00 LIMITORQUE A

D D

EJ COLD EJHV8804B N

RHR TO CHARGING/SI PUMP SUCTIONS 111 AUX BLDG/

ELEV 1974-0 1108 LIMITORQU E

SB-00 LIMITORQUE A

D D

EJ COLD 28 EJHV8809A N

RHR ISOL VALVE TO COLD LEG RCS LOOPS 1 AND 2 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SBD-3 LIMITORQUE A

D D

EJ COLD EJHV8809B N

RHR ISOL VALVE TO COLD LEG RCS LOOPS 3 AND 4 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SBD-3 LIMITORQUE A

D D

EJ COLD EJHV8811A N

CONT RECIRC SUMP ISOLATION VALVE (ENCAPSULATED) 124 AUX BLDG/

ELEV 1988-0 1204 LIMITORQU E

SB-1 LIMITORQUE A

B D

EJ COLD EJHV8811B N

CONT RECIRC SUMP ISOLATION VALVE (ENCAPSULATED) 123 AUX BLDG/

ELEV 1988-0 1203 LIMITORQU E

SB-1 LIMITORQUE A

B D

EJ COLD EJHV8840 N

RHR ISOL VALVE TO HOT LEGS RCS LOOPS 2 AND 3 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SBD-3 LIMITORQUE A

D D

EJ COLD EJHY8825 N

TEST LINE ISOL VLV HOT LEG INJ LINE SOL 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO A

D A

EJ EJHY8825-E01 N

TEST LINE ISO VLV HOT LEG INJ LINE SOL CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EJ EJHY8890A N

TEST LINE ISOLATION VALVE COLD LEG INJ LINE SOL 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO A

D A

EJ COLD EJHY8890A-E01 N

TEST LINE ISO VLV COLD LEG INJ LINE SOL CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EJ COLD EJHY8890B N

TEST LINE ISOLATION VALVE COLD LEG INJ LINE SOL 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO A

D A

EJ COLD EJHY8890B-E01 N

TEST LINE ISO VLV COLD LEG INJ LINE SOL CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EJ COLD EJLT0007 Y1/2 CTMT RECIRC SUMP LEVEL TRANSMITTER REACTOR BLDG 2000' EL 90 DEG WEST OF N/S CENTER LINE 2000 J-301 1154DP4RG Rosemount Nuclear A

D C

EJ 25 EJLT0008 Y1/2 CTMT RECIRC SUMP LEVEL TRANSMITTER REACTOR BLDG 2000' EL 90 DEG WEST OF N/S CENTER LINE 2000 J-301 1154DP4RG Rosemount Nuclear A

D C

EJ 25 EJZS8701BA N/Y2 RHR SHUTDOWN SUCT LINE ISOL VLV LOOP B LMT SW 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-12303 EA180-12303 NAMCO B

D A

EJ BOTH 29 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 30 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes EJZS8701BA-E01 N

VALVE TERMINAL BOX (EJZS8701BB) 231 RX BLDG/

ELEV 1998-6 2000 E-028 1600-NUC Marathon Special Products A

D A

EJ BOTH EJZS8701BA-E02 N

RHR PUMP SUCT LINE ISOL VLV LOOP B LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax B

D A

EJ BOTH EJZS8701BB N/Y2 RHR SHUTDOWN SUCT LINE ISOL VLV LOOP B LMT SW 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-12303 EA180-12303 NAMCO B

D A

EJ BOTH EJZS8701BB-E01 N

RHR PUMP SUCT LINE ISOL VLV LOOP B LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax B

D A

EJ BOTH EJZS8804A N/Y2 RHR TO CHARGING/SI PUMP SUCTIONS LIMIT SWITCH 132 AUX BLDG/

ELEV 2000-0 1310 HE-3/6 NAMCO EA180-12303 EA180-12302 NAMCO A

D D

EJ COLD 39 EJZS8804BA N/Y2 RHR TO CHARGING/SI PUMP SUCTIONS LIMIT SWITCH 111 AUX BLDG/

ELEV 1974-0 1108 HE-3/6 EA180-12303 EA180-12303 (spare)

NAMCO A

D D

EJ COLD 28 39 EJZS8804BB N/Y2 RHR TO CHARGING/SI PUMP SUCTIONS LIMIT SWITCH 111 AUX BLDG/

ELEV 1974-0 1108 HE-3/6 EA180-12303 EA180-12303 (spare)

NAMCO A

D D

EJ COLD 28 39 EJZS8809AA N/Y2 RHR ISOL VLV TO COLD LEG RCS LOOPS 1&2 LIMIT SW 134 AUX BLDG/

ELEV 2000-0 1323 HE-3/6 EA180-12303 EA180-12303 NAMCO A

D D

EJ COLD EJZS8809BA N/Y2 RHR ISOL VLV TO COLD LEG RCS LOOPS 3&4 LIMIT SW 133 AUX BLDG/

ELEV 2000-0 1322 HE-3/6 NAMCO EA180-12303 EA180-12302 NAMCO A

D D

EJ COLD EJZS8811A N/Y2 CONT RECIRC SUMP ISOLATION VALVE LIMIT SWITCH 124 AUX BLDG/

ELEV 1988-0 1204 HE-3/6 NAMCO EA180-12303 (spare)

EA180-12302 NAMCO A

B D

EJ COLD 39 EJZS8811A-E01 N

CONT RECIRC SUMP ISOLATION VALVE LS CONNECTOR 124 AUX BLDG/

ELEV 1988-0 1204 J-603A-P04 N11007 Conax A

B D

EJ COLD EJZS8811B N/Y2 CONT RECIRC SUMP ISOLATION VALVE LIMIT SWITCH 123 AUX BLDG/

ELEV 1988-0 1203 NAMCO HE-3/6 EA180-12303(spare)

EA180-12302 NAMCO A

B D

EJ COLD 39 EJZS8811B-E01 N

CONT RECIRC SUMP ISOLATION VALVE LS CONNECTOR 123 AUX BLDG/

ELEV 1988-0 1203 J-603A-P04 N11007 Conax A

B D

EJ COLD EJZS8825 N/Y2 TEST LINE ISO VLV HOT LEG INJ LINE LIMIT SW 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-11303 EA180-12303 NAMCO A

D A

EJ EJZS8825-E01 N

TEST LINE ISO VLV HOT LEG INJ LINE LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EJ EJZS8840A N/Y2 RHR ISOL VLV TO HOT LEGS RCS LOOPS 2&3 LIMIT SW 133 AUX BLDG/

ELEV 2000-0 1322 HE-3/6 NAMCO EA180-12303 EA180-12302 NAMCO A

D D

EJ COLD EJZS8890A N/Y2 TEST LINE ISOL VLV COLD LEG INJ LINE LIMIT SW 231 RX BLDG/

ELEV 1998-6 2000 NAMCO EA180-11303 EA180-12303 NAMCO A

D A

EJ COLD EJZS8890A-E01 N

TEST LINE ISO VLV COLD LEG INJ LINE LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EJ COLD EJZS8890B N/Y2 TEST LINE ISOL VLV COLD LEG INJ LINE LIMIT SW 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-11303 EA180-12303 NAMCO A

D A

EJ COLD EJZS8890B-E01 N

TEST LINE ISO VLV COLD LEG INJ LINE LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 EA180-12303 N11007 Conax A

D A

EJ COLD EMHV8801A N

BIT DISCHARGE VALVE TO RCS 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SBD-00 LIMITORQUE A

D D

EM BOTH EMHV8801B N

BIT DISCHARGE VALVE TO RCS 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SBD-00 LIMITORQUE A

D D

EM BOTH 30 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 31 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes EMHV8802A N

SI PUMP A DISCHARGE VALVE TO HOT LEGS 2 & 3 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SBD-00 LIMITORQUE A

D D

EM EMHV8802B N

SI PUMP B DISCHARGE VALVE TO HOT LEGS 1 & 4 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SBD-00 LIMITORQUE A

D D

EM EMHV8803A N

CHARGING PUMP DISCHARGE VALVE TO BIT 111 AUX BLDG/

ELEV 1974-0 1126 LIMITORQU E

SBD-00 LIMITORQUE A

D D

EM BOTH EMHV8803B N

CHARGING PUMP DISCHARGE VALVE TO BIT 111 AUX BLDG/

ELEV 1974-0 1126 LIMITORQU E

SBD-00 LIMITORQUE A

D D

EM BOTH EMHV8807A N

RHR TO CVCS AND SI PUMPS ISOL VALVE 112 AUX BLDG/

ELEV 1974-0 1113 LIMITORQU E

SB-00 LIMITORQUE A

D D

EM COLD 29 EMHV8807B N

RHR TO CVCS AND SI PUMPS ISOL VALVE 111 AUX BLDG/

ELEV 1974-0 1108 LIMITORQU E

SB-00 LIMITORQUE A

D D

EM COLD 28 EMHV8814A N

ISOLATION VALVE MINIFLOW LINE OF SI PUMP A 112 AUX BLDG/

ELEV 1974-0 1113 LIMITORQU E

SMB-00 LIMITORQUE A

D D

EM 29 EMHV8814B N

ISOLATION VALVE MINIFLOW LINE OF SI PUMP B 112 AUX BLDG/

ELEV 1974-0 1113 LIMITORQU E

SMB-00 LIMITORQUE A

D D

EM 29 EMHV8821A N

SI PUMP A DISCHARGE VALVE TO RCS COLD LEGS 112 AUX BLDG/

ELEV 1974-0 1113 LIMITORQU E

SB-00 LIMITORQUE A

D D

EM 29 EMHV8821B N

SI PUMP B DISCHARGE VALVE TO RCS COLD LEGS 111 AUX BLDG/

ELEV 1974-0 1108 LIMITORQU E

SB-00 LIMITORQUE A

D D

EM 28 EMHV8823-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D C

EM EMHV8824-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D C

EM EMHV8835 N

SI PUMPS A & B DISCHARGE VALVE TO RCS COLD LEGS 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SBD-00 LIMITORQUE A

D D

EM EMHV8843-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D A

EM BOTH EMHV8871-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D A

EM EMHV8881-E01 N

VALVE TERMINAL BOX 232 RX BLDG/

ELEV 1998-6 2000 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D C

EM EMHV8888-E01 N

VALVE TERMINAL BOX 133 AUX BLDG/

ELEV 2000-0 1322 E-093 NQB. 616822 Buchanan (Amerace) A D

D EM EMHV8923A N

RWST SUCTION VALVE TO SI PUMP A 112 AUX BLDG/

ELEV 1974-0 1113 LIMITORQU E

SB-00 LIMITORQUE A

D D

EM 29 EMHV8923B N

RWST SUCTION VALVE TO SI PUMP B 111 AUX BLDG/

ELEV 1974-0 1108 LIMITORQU E

SB-00 LIMITORQUE A

D D

EM 28 EMHV8964-E01 N

VALVE TERMINAL BOX 134 AUX BLDG/

ELEV 2000-0 1323 E-093 NQB. 616822 Buchanan (Amerace) A D

D EM EMHY8823 N

TESTLINE/CONTAINMENT ISOL VALVE SI COLD LEGS 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO A

D C

EM EMHY8823-E01 N

TEST LINE CONT ISOL VLV SI COLD LEGS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D C

EM EMHY8824 N

TESTLINE/ CONTAINMENT ISOL VLV RCS HOT LEGS 1 & 4 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO A

D C

EM EMHY8824-E01 N

TEST LINE CONT ISOL VLV RCS HOT LEGS 1 & 4 CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D C

EM 31 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 32 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes EMHY8843 N

BIT TEST LINE AND CONTAINMENT ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO A

D A

EM BOTH EMHY8843-E01 N

BIT TEST LINE AND CONT ISOL VALVE CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EM BOTH EMHY8871 N

SI TESTLINE/CONTAINMENT ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO A

D A

EM EMHY8871-E01 N

SI TEST LINE CONT ISOL VALVE CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EM EMHY8881 N

TESTLINE/CONTAINMENT ISOL VLV RCS HOT LEGS 2 & 3 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO A

D C

EM EMHY8881-E01 N

TEST LINE CONT ISOL VLV RCS HOT LEGS 2 & 3 CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D C

EM EMHY8888 N

ACC FILL LINE CONTAINMENT ISO VALVE 133 AUX BLDG/

ELEV 2000-0 1322 M-237 NP831655E ASCO A

D D

EM EMHY8964 N

SI TESTLINE/CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1323 M-237 NPK831654E ASCO A

D D

EM EMZS8802AA N/Y2 SI PUMP A DISCH VLV TO HOT LEGS 2&3 LIMIT SWITCH 134 AUX BLDG/

ELEV 2000-0 1323 HE-3/6 EA180-12303 EA180-12303 NAMCO A

D D

EM EMZS8802BA N/Y2 SI PUMP B DISCH VLV TO HOT LEGS 1&4 LIMIT SWITCH 133 AUX BLDG/

ELEV 2000-0 1322 HE-3/6 EA180-12303 EA180-12303 NAMCO A

D D

EM EMZS8814A N/Y2 ISOL VLV MINIFLOW LINE OF SI PUMP A LIMIT SWITCH 112 AUX BLDG/

ELEV 1974-0 1113 HE-3/6 EA180-21303 EA180-21303 (spare)

NAMCO A

D D

EM 29 39 EMZS8814B N/Y2 ISOL VLV MINIFLOW LINE OF SI PUMP B LIMIT SWITCH 112 AUX BLDG/

ELEV 1974-0 1113 NAMCO HE-3/6 EA180-21302 EA180-21303 (spare)

NAMCO A

D D

EM 29 39 EMZS8823 N/Y2 TEST/LINE/CONTAINMENT ISOL VLV SI COLD LEGS LMT SW 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-11303 EA180-12303 NAMCO A

D C

EM EMZS8823-E01 N

TEST LINE CONT ISO VLV SI COLD LEGS LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D C

EM EMZS8824 N/Y2 TESTLINE/CONT ISOL VLV RCS HOT LEGS 1&4 LIMIT SW 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-11303 EA180-12303 NAMCO A

D C

EM EMZS8824-E01 N

TEST LINE CONT ISO VLV HOT LEGS 1 & 4 LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D C

EM EMZS8835A N/Y2 SI PMPS A&B DISCH VLV TO RCS COLD LEGS LIMIT SW 133 AUX BLDG/

ELEV 2000-0 1322 HE-3/6 NAMCO EA180-12303 EA180-12302 NAMCO A

D D

EM EMZS8843 Y1/2 BIT TESTLINE AND CONTAINMENT ISOL VLV LIMIT SW 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-11303 EA180-12303 NAMCO A

D A

EM BOTH EMZS8843-E01 N

BIT TEST LINE CONT ISOL VLV LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EM BOTH EMZS8871 N/Y2 SI TESTLINE/CONTAINMENT ISOL VALVE LIMIT SWITCH 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-11303 EA180-12303 NAMCO A

D A

EM EMZS8871-E01 N

SI TEST LINE CONT ISOL VLV LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EM EMZS8881 N/Y2 TESTLINE/CONT ISOL VLV RCS HOT LEGS 2&3 LIMIT SW 232 RX BLDG/

ELEV 1998-6 2000 HE-3/6 NAMCO EA180-11303 EA180-12303 NAMCO A

D C

EM 32 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 33 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes EMZS8881-E01 N

TEST LINE CONT ISO VLV HOT LEGS 2 & 3 LS CONNECTOR 232 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D C

EM EMZS8888 N/Y2 ACC FILL LINE CONTAINMENT ISOL VLV LIMIT SWITCH 133 AUX BLDG/

ELEV 2000-0 1322 HE-3/6 NAMCO EA180-11303 EA180-12302 NAMCO A

D D

EM EMZS8964 N/Y2 SI TESTLINE/CONTAINMENT ISOL VALVE LIMIT SWITCH 133 AUX BLDG/

ELEV 2000-0 1323 NAMCO EA180-11302 EA180-12302 NAMCO A

D D

EM ENHV0001 N

CONTAINMENT ISOLATION (ENCAPSULATED) 124 AUX BLDG/

ELEV 1988-0 1204 LIMITORQU E

SMB-00 LIMITORQUE A

C D

EN ENHV0006 N

CONTAINMENT ISOLATION 134 AUX BLDG/

ELEV 2000-0 1323 LIMITORQU E

SMB-00 LIMITORQUE A

D D

EN ENHV0007 N

CONTAINMENT ISOLATION (ENCAPSULATED) 123 AUX BLDG/

ELEV 1988-0 1203 LIMITORQU E

SMB-00 LIMITORQUE A

C D

EN ENHV0012 N

CONTAINMENT ISOLATION 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SMB-00 LIMITORQUE A

D D

EN ENHV0015 N

SPRAY ADD TANK TO SPRAY ADD EDUCTOR 132 AUX BLDG/

ELEV 2000-0 1315 LIMITORQU E

SMB-00 LIMITORQUE A

D D

EN 30 ENHV0016 N

SPRAY ADD TANK TO SPRAY ADD EDUCTOR 132 AUX BLDG/

ELEV 2000-0 1315 LIMITORQU E

SMB-00 LIMITORQUE A

D D

EN 30 ENLT0015 Y1 CTMT SPRAY ADD TK LEVEL 132 AUX BLDG/

ELEV 2000-0 1315 J-301 1153DB3RA Rosemount Nuclear A

D D

EN 30 ENLT0016 Y1 CTMT SPRAY ADD TK LEVEL 132 AUX BLDG/

ELEV 2000-0 1315 J-301 1153DB3RA Rosemount Nuclear A

D D

EN 30 ENLT0017 Y1 SPRAY ADD TANK LEVEL 132 AUX BLDG/

ELEV 2000-0 1315 J-301 1153DB5R Rosemount Nuclear A

D D

EN 30 ENLT0019 Y1 SPRAY ADD TANK LEVEL 132 AUX BLDG/

ELEV 2000-0 1315 J-301 1153DB5R Rosemount Nuclear A

D D

EN 30 EPHV8808A N

ACCUMULATOR TANK A ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SBD-3 LIMITORQUE C

D A

EP COLD EPHV8808D N

ACCUMULATOR TANK D ISOLATION VALVE 232 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SBD-3 LIMITORQUE C

D A

EP COLD EPHV8880-E01 N

VALVE TERMINAL BOX 133 AUX BLDG/

ELEV 2000-0 1322 E-093 NQB. 616822 Buchanan (Amerace) A D

D EP EPHV8950A N/Y2 ACCUMULATOR TANK A VENT VALVE 241 RX BLDG/

ELEV 2026-0 2000 HE-10A 79AB-004-3 Target Rock Corp.

B D

A EP COLD 44 EPHV8950A-E01 N

ACCUMULATOR TANK A VENT VALVE CONNECTOR 241 RX BLDG/

ELEV 2026-0 2000 J-603A-P04 N11007 Conax B

D A

EP COLD EPHV8950B N/Y2 ACCUMULATOR TANK B VENT VALVE 242 RX BLDG/

ELEV 2026-0 2000 HE-10A 79AB-004-3 Target Rock Corp.

B D

A EP COLD 44 EPHV8950B-E01 N

ACCUMULATOR TANK B VENT VALVE CONNECTOR 242 RX BLDG/

ELEV 2026-0 2000 J-603A-P04 N11007 Conax B

D A

EP COLD EPHV8950C N/Y2 ACCUMULATOR TANK B VENT VALVE 242 RX BLDG/

ELEV 2026-0 2000 HE-10A 79AB-004-3 Target Rock Corp.

B D

A EP COLD 44 EPHV8950C-E01 N

ACCUMULATOR TANK B VENT VALVE CONNECTOR 242 RX BLDG/

ELEV 2026-0 2000 J-603A-P04 N11007 Conax B

D A

EP COLD EPHV8950D N/Y2 ACCUMULATOR TANK C VENT VALVE 242 RX BLDG/

ELEV 2026-0 2000 HE-10A 79AB-004-3 Target Rock Corp.

B D

A EP COLD 44 EPHV8950D-E01 N

ACCUMULATOR TANK C VENT VALVE CONNECTOR 242 RX BLDG/

ELEV 2026-0 2000 J-603A-P04 N11007 Conax B

D A

EP COLD 33 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 34 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes EPHV8950E N/Y2 ACCUMULATOR TANK C VENT VALVE 242 RX BLDG/

ELEV 2026-0 2000 HE-10A 79AB-004-3 Target Rock Corp.

B D

A EP COLD 44 EPHV8950E-E01 N

ACCUMULATOR TANK C VENT VALVE CONNECTOR 242 RX BLDG/

ELEV 2026-0 2000 J-603A-P04 N11007 Conax B

D A

EP COLD EPHV8950F N/Y2 ACCUMULATOR TANK D VENT VALVE 241 RX BLDG/

ELEV 2026-0 2000 HE-10A 79AB-004-3 Target Rock Corp.

B D

A EP COLD 44 EPHV8950F-E01 N

ACCUMULATOR TANK D VENT VALVE CONNECTOR 241 RX BLDG/

ELEV 2026-0 2000 J-603A-P04 N11007 Conax B

D A

EP COLD EPHY8880 N

N2 SUPPLY CONT ISOL VALVE 231 RX BLDG/

ELEV 1998-6 1322 M-237 NP831655E ASCO A

D D

EP EPZS8808AB N/Y2 ACCUMULATOR TANK A ISOLATION VALVE LIMIT SWITCH 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-12303 EA180-12303 NAMCO A

D A

EP COLD EPZS8808AB-E01 N

ACCUMULATOR TANK A ISOL VLV LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EP COLD EPZS8808AB-E02 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-028 1600 NUC Marathon Special Products A

D A

EP COLD EPZS8808DB N/Y2 ACCUMULATOR TANK D ISOLATION VALVE LIMIT SWITCH 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-12303 EA180-12303 NAMCO A

D A

EP COLD EPZS8808DB-E01 N

ACCUMULATOR TANK D ISOL VLV LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

EP COLD EPZS8808DB-E02 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-028 1600 NUC Marathon Special Products A

D A

EP COLD EPZS8880 N/Y2 N2 SUPPLY CONT ISOL VALVE LIMIT SWITCH 231 CTMT BLDG/

ELEV 1998-6 1322 HE-3/6 EA180-11303 EA180-12303 NAMCO A

D D

EP GEHZ0101 Y1 AUX BLDG ISO DAMPER ACTUATOR - GED0047 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GE 34 GEHZ0102 Y1 AUX BLDG ISO DAMPER ACTUATOR - GED0046 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GE 34 GFHZ0011 Y1 AUX BLDG ISO DAMPER ACTUATOR - GFD0033 - ELEC 1122 GENERAL FLOOR AREA (NO. 3) 1122 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A C

D GF 27 GFHZ0012 Y1 AUX BLDG ISO DAMPER ACTUATOR - GFD0034 - ELEC 1122 GENERAL FLOOR AREA (NO. 3) 1122 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A C

D GF 27 GFHZ0013 Y1 AUX BLDG ISO DAMPER ACTUATOR - GFD0035 - ELEC 1122 GENERAL FLOOR AREA (NO. 3) 1122 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A C

D GF 27 GFHZ0014 Y1 AUX BLDG ISO DAMPER ACTUATOR - GFD0036 - ELEC 1122 GENERAL FLOOR AREA (NO. 3) 1122 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A C

D GF 27 34 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 35 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes GFHZ0020 Y1 AUX BLDG ISO DAMPER ACTUATOR - GFD0029 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GF 34 GFHZ0021 Y1 AUX BLDG ISO DAMPER ACTUATOR - GFD0028 - ELEC 1504 CTMT PRG EXH & MECH EQUIP RM B 1506 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GF 34 GFHZ0030A Y1 AUX BLDG ISO DAMPER ACTUATOR - GFD0066 - ELEC 144 AUX BLDG/

ELEV 2026-0 1410 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GF GFHZ0030B Y1 AUX BLDG ISO DAMPER ACTUATOR - GFD0062 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1127 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GF 31 GFHZ0031A Y1 AUX BLDG ISO DAMPER ACTUATOR - GFD0065 - ELEC 144 AUX BLDG/

ELEV 2026-0 1410 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GF GFHZ0031B Y1 AUX BLDG ISO DAMPER ACTUATOR - GFD0063 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1127 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GF 31 GKHY0184E Y1 GKHZ0184E SOLENOID VALVE 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-237 WPHCX8320A182E ASCO (NE)

A D

D GK 34 GKHZ0150 Y1 CTRL BLDG ISO DAMPER ACTUATOR - GKD0129 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GK 34 GKHZ0151 Y1 CTRL BLDG ISO DAMPER ACTUATOR - GKD0128 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GK 34 GKHZ0184E N

CTRL BLDG ISO DAMPER ACTUATOR - GKD0314 - PNEU 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-627A PAS-111 American Warming and Ventilating (Raymond Control Systems)

A D

D GK 34 GLHZ0013 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0046 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL 34 GLHZ0014 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0047 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL 34 35 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 36 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes GLHZ0062 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0058 - ELEC 1507 PERSONNEL HATCH AREA 1507 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL 34 GLHZ0069 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0030 - ELEC 1314 AUX BLDG/

CORRIDOR NO.

3 OUTSIDE HMS DOOR 1314 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL 30 GLHZ0070 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0031 - ELEC 1314 AUX BLDG/

CORRIDOR NO.

3 OUTSIDE HMS DOOR 1314 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL 30 GLHZ0071 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0032 - ELEC 1314 AUX BLDG/

CORRIDOR NO.

3 OUTSIDE HMS DOOR 1314 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL 30 GLHZ0072 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0033 - ELEC 1314 AUX BLDG/

CORRIDOR NO.

3 OUTSIDE HMS DOOR 1314 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL 30 GLHZ0085 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0132 - ELEC 1308 AUX BLDG/

DEMIN ALLEY 1307 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL GLHZ0086 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0134 - ELEC 1308 AUX BLDG/

DEMIN ALLEY 1307 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL GLHZ0087 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0133 - ELEC 1308 AUX BLDG/

DEMIN ALLEY 1308 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL GLHZ0088 Y1 AUX BLDG ISO DAMPER ACTUATOR - GLD0135 - ELEC 1308 AUX BLDG/

DEMIN ALLEY 1308 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GL GNPT0934 Y1 CONTAINMENT PRESSURE SENSOR 143 AUX BLDG/

ELEV 2026-0 1409 J-301-P02 1153DB6PAN0073 Rosemount Nuclear A

D D

GN GNPT0935 N

CONTAINMENT PRESSURE TRANSMITTER 144 AUX BLDG/

ELEV 2026-0 1410 ESE-4A 752 ITT Barton A

D D

GN GNPT0936 N

CONTAINMENT PRESSURE TRANSMITTER 143 AUX BLDG/

ELEV 2026-0 1409 ESE-4A 752 ITT Barton A

D D

GN GNPT0937 N

CONTAINMENT PRESSURE TRANSMITTER 144 AUX BLDG/

ELEV 2026-0 1410 ESE-4A 752 ITT Barton A

D D

GN 36 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 37 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes GNPT0938 N

CONTAINMENT PRESSURE TRANSMITTER WIDE RANGE 144 AUX BLDG/

ELEV 2026-0 1410 ESE-4A 752 ITT Barton A

D D

GN HOT 25 GNPT0939 N

CONTAINMENT PRESSURE TRANSMITTER WIDE RANGE 143 AUX BLDG/

ELEV 2026-0 1409 ESE-4A 752 ITT Barton A

D D

GN HOT 25 GNTE0060 N/Y2 CTMT COOLER A TEMP 262 RX BLDG/

ELEV 2068-8 2000 J-558B 611-1B-C-4-C-2-A2-0 Weed Instrument Co., Inc.

A D

A GN BOTH GNTE0061 N/Y2 CTMT COOLER B TEMP 261 RX BLDG/

ELEV 2068-8 2000 J-558B 611-1B-C-4-C-2-A2-0 Weed Instrument Co., Inc.

A D

A GN BOTH GNTE0062 N/Y2 CTMT COOLER C TEMP 261 RX BLDG/

ELEV 2068-8 2000 J-558B 611-1B-C-4-C-2-A2-0 Weed Instrument Co., Inc.

A D

A GN BOTH GNTE0063 N/Y2 CTMT COOLER D TEMP 262 RX BLDG/

ELEV 2068-8 2000 J-558B 611-1B-C-4-C-2-A2-0 Weed Instrument Co., Inc.

A D

A GN BOTH GSHV0003 N

HYDROGEN ANALYZER CTMT SAMPLE 2047 AUX BLDG EAST OF RE-31 ABOUT 6' OFF OF THE FLOOR 1507 J-603A V52600-5940-2 Valcor Engineering A

D D

GS 34 GSHV0004 N

HYDROGEN ANALYZER CTMT SAMPLE 251 RX BLDG/

ELEV 2047-6 2000 J-603A V52600-5940-2A Valcor Engineering A

D A

GS GSHV0005 N

HYDROGEN ANALYZER CTMT SAMPLE 251 RX BLDG/

ELEV 2047-6 2000 J-603A V52600-5940-2A Valcor Engineering A

D A

GS GSHV0008 N

HYDROGEN ANAL SAMPLE RETURN TO CTMT 133 AUX BLDG/

ELEV 2000-0 1322 J-603A V52660-5940-2 Valcor Engineering A

D D

GS GSHV0009 N

HYDROGEN ANAL SAMPLE RETURN TO CTMT 242 RX BLDG/

ELEV 2026-0 2000 J-603A V52600-5940-2A Valcor Engineering A

D A

GS GSHV0012 N

HYDROGEN ANALYZER CTMT SAMPLE 2047 AUX BLDG NE OF RE-32 ABOUT 6' OFF OF THE FLOOR 1506 J-603A V52660-5940-2 Valcor Engineering A

D D

GS 34 GSHV0013 N

HYDROGEN ANALYZER CTMT SAMPLE 252 RX BLDG/

ELEV 2047-6 2000 J-603A V52600-5940-2A Valcor Engineering A

D A

GS GSHV0014 N

HYDROGEN ANALYZER CTMT SAMPLE 251 RX BLDG/

ELEV 2047-6 2000 J-603A V52600-5940-2A Valcor Engineering A

D A

GS GSHV0017 N

HYDROGEN ANAL SAMPLE RETURN TO CTMT 134 AUX BLDG/

ELEV 2000-0 1323 J-603A V52660-5940-2 Valcor Engineering A

D D

GS GSHV0018 N

HYDROGEN ANAL SAMP RETURN TO CTMT 242 RX BLDG/

ELEV 2026-0 2000 J-603A V52660-5940-2A Valcor Engineering A

D A

GS GSHV0020 N

CTMT ISO ON AUX BUILDING ESF FILTERS INLET 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-000 LIMITORQUE A

A D

GS GSHV0021 N

CONTAINMENT ISOLATION 133 AUX BLDG/

ELEV 2000-0 1322 LIMITORQU E

SMB-000 LIMITORQUE A

D D

GS GSHV0030 N

PASS ISOLATION 2047 AUX BLDG NE OF RE-32 ABOUT 6' OFF OF THE FLOOR 1506 J-603A V52660-5940-2 Valcor Engineering A

D D

GS 21 34 GSHV0031 N

CTMT ATM MONITOR ISOL VALVE 251 RX BLDG/

ELEV 2047-6 2000 J-603A V52600-5940-2A Valcor Engineering A

D A

GS GSHV0032 N

CTMT ATM MONITOR ISOL VALVE 154 AUX BLDG/

ELEV 2047-6 1506 J-603A V52660-5940-2 Valcor Engineering A

D D

GS 34 37 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 38 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes GSHV0033 N

CTMT ATM MONITOR ISOL VALVE 133 AUX BLDG/

ELEV 2000-0 1323 J-603A V52600-5940-2 Valcor Engineering A

D D

GS GSHV0034 N

CTMT ATM MONITOR ISOL VALVE 231 RX BLDG/

ELEV 1998-6 2000 J-603A V52600-5940-2A Valcor Engineering A

D A

GS GSHV0035 N

PASS ISOLATION 251 RX BLDG/

ELEV 2047-6 1507 J-603A V52600-5940-2 Valcor Engineering A

D D

GS 21 34 GSHV0036 N

CTMT ATM MONITOR ISOL VALVE 252 RX BLDG/

ELEV 2047-6 2000 J-603A V52600-5940-2A Valcor Engineering A

D A

GS GSHV0037 N

2047 AUX BLDG EAST OF RE-31 ABOUT 6' OFF OF THE FLOOR.

153 AUX BLDG/

ELEV 2047-6 1507 J-603A V52600-5940-2 Valcor Engineering A

D D

GS 34 GSHV0038 N

CTMT ATM MONITOR ISOL VALVE 133 AUX BLDG/

ELEV 2000-0 1322 J-603A V52600-5940-2 Valcor Engineering A

D D

GS GSHV0039 N

CTMT ATM MONITOR ISOL VALVE 231 RX BLDG/

ELEV 1998-6 2000 J-603A V52600-5940-2A Valcor Engineering A

D A

GS GTHY0004 N

GTHZ0004 SOLENOID VALVE 154 AUX BLDG/

ELEV 2047-6 1506 M-237 NP8320A185V ASCO A

D D

GT 34 GTHY0005 N

GTHZ0005 SOLENOID VALVE 252 RX BLDG/

ELEV 2047-6 2000 M-237 NP8320A185V ASCO (NDE)

A D

A GT GTHY0006 N

GTHZ0006 SOLENOID VALVE 154 AUX BLDG/

ELEV 2047-6 1506 M-237 NP8320A185V ASCO A

D D

GT 34 GTHY0007 N

GTHZ0007 SOLENOID VALVE 252 RX BLDG/

ELEV 2047-6 2000 M-237 NP8320A185V ASCO (NDE)

A D

A GT GTHY0008 N

GTHZ0008 SOLENOID VALVE 252 RX BLDG/

ELEV 2047-6 2000 M-237 NP8320A185V ASCO (NDE)

A D

A GT GTHY0009 N

GTHZ0009 SOLENOID VALVE 153 AUX BLDG/

ELEV 2047-6 1507 M-237 NP8320A185V ASCO A

D D

GT 34 GTHY0011 N

GTHZ0011 SOLENOID VALVE 252 RX BLDG/

ELEV 2047-6 2000 M-237 NP8320A185V ASCO (NDE)

A D

A GT GTHY0012 N

GTHZ0012 SOLENOID VALVE 153 AUX BLDG/

ELEV 2047-6 1507 M-237 NP8320A185V ASCO A

D D

GT 34 GTHZ0004 N

CONTAINMENT ISOLATION control valve conduit seal resin and terminal box conduit EPDM O-Ring 154 AUX BLDG/

ELEV 2047-6 1506 M-237-P03 Scotchcast Brand 9 (XR-5240) & EPDM 3M A

D D

GT 34 GTHZ0005 N

Fisher Butterfly control valve conduit seal resin and terminal box conduit EPDM O-Ring 251 RX BLDG/

ELEV 2047-6 2000 M-237-P03 Scotchcast Brand 9 (XR-5240) & EPDM 3M A

D A

GT 7

GTHZ0006 N

Fisher Butterfly control valve conduit seal resin and terminal box conduit EPDM O-Ring 154 AUX BLDG/

ELEV 2047-6 1506 M-237-P03 Scotchcast Brand 9 (XR-5240) & EPDM 3M A

D D

GT 34 GTHZ0007 N

Fisher Butterfly control valve conduit seal resin and terminal box conduit EPDM O-Ring 251 RX BLDG/

ELEV 2047-6 2000 M-237-P03 Scotchcast Brand 9 (XR-5240) & EPDM 3M A

D A

GT 7

GTHZ0008 N

Fisher Butterfly control valve conduit seal resin and terminal box conduit EPDM O-Ring 251 RX BLDG/

ELEV 2047-6 2000 M-237-P03 Scotchcast Brand 9 (XR-5240) & EPDM 3M A

D A

GT 7

GTHZ0009 N

Fisher Butterfly control valve conduit seal resin and terminal box conduit EPDM O-Ring 153 AUX BLDG/

ELEV 2047-6 1507 M-237-P03 Scotchcast Brand 9 (XR-5240) & EPDM 3M A

D D

GT 34 38 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 39 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes GTHZ0011 N

Fisher Butterfly control valve conduit seal resin and terminal box conduit EPDM O-Ring 251 RX BLDG/

ELEV 2047-6 2000 M-237-P03 Scotchcast Brand 9 (XR-5240) & EPDM 3M A

D A

GT 7

GTHZ0012 N

Fisher Butterfly control valve conduit seal resin and terminal box conduit EPDM O-Ring 153 AUX BLDG/

ELEV 2047-6 1507 M-237-P03 Scotchcast Brand 9 (XR-5240) & EPDM 3M A

D D

GT 34 GTHZ0026 Y1 AUX BLDG ISO DAMPER ACTUATOR - GTD0009 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GT 34 GTHZ0027 Y1 AUX BLDG ISO DAMPER ACTUATOR - GTD0010 - ELEC 1506 CTMT PRG SPLY AIR HDLG UNIT RM A 1506 M-627A MAR-25 American Warming and Ventilating (Raymond Control Systems)

A D

D GT 34 GTRE0059 N

CTMT HIGH RANGE AREA RADN MON 261 RX BLDG/

ELEV 2068-8 2000 J-361A RD-23 General Atomic Co.

A D

A GT 25 GTRE0060 N

CTMT HIGH RANGE AREA RADN MON 252 RX BLDG/

ELEV 2047-6 2000 J-361A RD-23 General Atomic Co.

A D

A GT 25 GTZS0004 N/Y2 GTHZ0004 LIMIT SWITCH 154 AUX BLDG/

ELEV 2047-6 1506 NAMCO EA180-32302 EA180-31302 NAMCO A

D D

GT 34 GTZS0005 Y1/2 GTHZ0005 LIMIT SWITCH 252 RX BLDG/

ELEV 2047-6 2000 NAMCO EA180-32302 EA180-31302 NAMCO A

D A

GT 7

GTZS0006 N/Y2 GTHZ0006 LIMIT SWITCH 154 AUX BLDG/

ELEV 2047-6 1506 NAMCO EA180-32302 EA180-31302 NAMCO A

D D

GT 34 GTZS0007 Y1/2 GTHZ0007 LIMIT SWITCH 252 RX BLDG/

ELEV 2047-6 2000 NAMCO EA180-32302 EA180-31302 NAMCO A

D A

GT 7

GTZS0008 Y1/2 GTHZ0008 LIMIT SWITCH 252 RX BLDG/

ELEV 2047-6 2000 NAMCO EA180-32302 EA180-31302 NAMCO A

D A

GT 7

GTZS0009 N/Y2 GTHZ0009 LIMIT SWITCH 153 AUX BLDG/

ELEV 2047-6 1507 NAMCO EA180-32302 EA180-31302 NAMCO A

D D

GT 34 GTZS0011 Y1/2 GTHZ0011 LIMIT SWITCH 252 RX BLDG/

ELEV 2047-6 2000 NAMCO EA180-32302 EA180-31302 NAMCO A

D A

GT 7

GTZS0012 N/Y2 GTHZ0012 LIMIT SWITCH 153 AUX BLDG/

ELEV 2047-6 1507 NAMCO EA180-32302 EA180-31302 NAMCO A

D D

GT 34 HBHV7126-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-028 1600 NUC Marathon Special Products A

D A

HB HBHV7136-E01 N

VALVE TERMINAL BOX 133 AUX BLDG/

ELEV 2000-0 1322 E-093 NQB. 616822 Buchanan (Amerace) A D

D HB HBHV7150-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 1322 E-093 NQB. 616822 Buchanan (Amerace) A D

D HB HBHV7176-E01 N

VALVE TERMINAL BOX 231 RX BLDG/

ELEV 1998-6 2000 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

D A

HB HBHY7126 N

CONTAINMENT ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 M-237 NPK831654E ASCO A

D A

HB HBHY7126-E01 N

CONTAINMENT ISOLATION VALVE CONNECTOR ROOM 2000 2000 J-603A-P04 N11007 Conax A

D A

HB HBHY7136 N

CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 M-237 NPK831654E ASCO A

D D

HB 39 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 40 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes HBHY7150 N

CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 M-237 NPK831654E ASCO A

D D

HB HBHY7176 N

CONTAINMENT ISOLATION VALVE ROOM 2000 2000 M-237 NPK831654E ASCO A

D A

HB HBHY7176-E01 N

CONTAINMENT ISOLATION VALVE CONNECTOR ROOM 2000 2000 J-603A-P04 N11007 Conax A

D A

HB HBZS7126-E01 N

CONTAINMENT ISOLATION VALVE LS CONNECTOR 231 RX BLDG/

ELEV 1998-6 2000 J-603A-P04 N11007 Conax A

D A

HB HBZS7176-E01 N

CONTAINMENT ISOLATION VALVE LS CONNECTOR 231 RX BLDG 2000 J-603A-P04 N11007 Conax A

D A

HB HBZS7126 N/Y2 CONTAINMENT ISOLATION VALVE LIMIT SWITCH 231 RX BLDG/

ELEV 1998-6 2000 HE-3/6 EA180-14303 EA180-15303 NAMCO A

D A

HB HBZS7136 N/Y2 CONTAINMENT ISOLATION VALVE LIMIT SWITCH 133 AUX BLDG/

ELEV 2000-0 1322 HE-3/6 EA180-14303 EA180-15303 NAMCO A

D D

HB HBZS7150 N/Y2 CONTAINMENT ISOLATION VALVE LIMIT SWITCH 133 AUX BLDG/

ELEV 2000-0 1322 NAMCO EA180-34302 EA180-35302 NAMCO A

D D

HB HBZS7176 N/Y2 CONTAINMENT ISOLATION VALVE LIMIT SWITCH 231 RX BLDG 2000 HE-3/6 EA180-14303 EA180-15303 NAMCO A

D A

HB KAFV0029-E01 N

VALVE TERMINAL BOX 132 AUX BLDG/

ELEV 2000-0 1322 E-093-P03 NQB. 616822 Buchanan (Amerace) A D

D KA KAFY0029 Y1 KAFV0029 SOLENOID VALVE 133 AUX BLDG/

ELEV 2000-0 1322 E-093 NP8320A187E ASCO (NE)

A D

D KA KAHV0030 N

HYDROGEN MAKEUP AIR SUPPLY VALVE 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-000 LIMITORQUE A

D C

KA KAZS0029 N/Y2 KAFV0029 LIMIT SWITCH 133 AUX BLDG/

ELEV 2000-0 1322 NAMCO EA180-11302 EA180-12302 NAMCO A

D D

KA KCHV0253 N

CONTAINMENT ISOLATON VALVE 1322 PIPE PENETRATION ROOM B 1322 LIMITORQU E

SMB-000 LIMITORQUE A

D D

KC LFFV0095 N

CONTAINMENT ISOLATON VALVE 231 RX BLDG/

ELEV 1998-6 2000 LIMITORQU E

SMB-00 LIMITORQUE A

D A

LF LFFY0096A N

LFFV0096 SOLENOID VALVE 133 AUX BLDG/

ELEV 2000-0 1322 M-237 NP8321A6E ASCO A

D D

LF LFFY0096A-E01 N

VALVE TERMINAL BOX (LFZS0096B) 133 AUX BLDG/

ELEV 2000-0 1322 E-093-P03 NQB. 616822 Buchanan (Amerace) A D

D LF LFHV0105 N

ISOLATION VALVE 111 AUX BLDG/

ELEV 1974-0 1101 LIMITORQU E

SMB-000 LIMITORQUE A

C D

LF 27 LFHV0106 N

ISOLATION VALVE 111 AUX BLDG/

ELEV 1974-0 1101 LIMITORQU E

SMB-000 LIMITORQUE A

C D

LF 27 LFLE0009A N

CTMT NORMAL SUMP 232 RX BLDG/

ELEV 1998-6 2000 J-481 XM-54852 TransAmerica Delaval Inc. GEMS Sensors Division A

D C

LF 25 LFLE0009B N

CTMT NORMAL SUMP 232 RX BLDG/

ELEV 1998-6 2000 J-481 XM-54853 TransAmerica Delaval Inc. GEMS Sensors Division A

D C

LF 25 LFLE0010A N

CTMT NORMAL SUMP 231 RX BLDG/

ELEV 1998-6 2000 J-481 XM-54852 TransAmerica Delaval Inc. GEMS Sensors Division A

D C

LF 25 40 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 41 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes LFLE0010B N

CTMT NORMAL SUMP 231 RX BLDG/

ELEV 1998-6 2000 J-481 XM-54853 TransAmerica Delaval Inc. GEMS Sensors Division A

D C

LF 25 LFLE0101A N

RHR PMP ROOM LEAKAGE LEVEL 111 AUX BLDG/

ELEV 1974-0 1109 J-481 XM-54854 TransAmerica Delaval Inc. GEMS Sensors Division A

D D

LF COLD LFLE0101B N

RHR PMP ROOM LEAKAGE LEVEL 111 AUX BLDG/

ELEV 1974-0 1109 J-481 XM-54853 TransAmerica Delaval Inc. GEMS Sensors Division A

D D

LF COLD LFLE0102A N

RHR PMP ROOM LEAKAGE LEVEL 112 AUX BLDG/

ELEV 1974-0 1111 J-481 XM-54854 TransAmerica Delaval Inc. GEMS Sensors Division A

D D

LF COLD LFLE0102B N

RHR PMP ROOM LEAKAGE LEVEL 112 AUX BLDG/

ELEV 1974-0 1111 J-481 XM-54853 TransAmerica Delaval Inc. GEMS Sensors Division A

D D

LF COLD LFLE0103A N

AUX BLDG SUMP LEVEL 114 AUX BLDG/

ELEV 1974-0 1121 J-481 XM-54854 TransAmerica Delaval Inc. GEMS Sensors Division A

A D

LF 27 LFLE0103B N

AUX BLDG SUMP LEVEL 114 AUX BLDG/

ELEV 1974-0 1121 J-481 XM-54853 TransAmerica Delaval Inc. GEMS Sensors Division A

A D

LF 27 LFLE0104A N

AUX BLDG SUMP LEVEL 114 AUX BLDG/

ELEV 1974-0 1121 J-481 XM-54854 TransAmerica Delaval Inc. GEMS Sensors Division A

A D

LF 27 LFLE0104B N

AUX BLDG SUMP LEVEL 114 AUX BLDG/

ELEV 1974-0 1121 J-481 XM-54853 TransAmerica Delaval Inc. GEMS Sensors Division A

A D

LF 27 LFZS0096A N/Y2 LFFV0096 LIMIT SWITCH 133 AUX BLDG/

ELEV 2000-0 1322 NAMCO EA180-11302 NAMCO A

D D

LF LFZS0096B N/Y2 LFFV0096 LIMIT SWITCH 133 AUX BLDG/

ELEV 2000-0 1322 NAMCO EA180-11302 EA180-12302 NAMCO A

D D

LF RP209 N

AUX RELAY RACK 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Cegelec Automation Inc. (Comsip Customline Corp)/

Struthers-Dunn A

B D

RP BOTH 30 RP330 N

REVERSE ISOL RELAY RACK 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Cegelec Automation Inc. (Comsip Customline Corp)/

Struthers-Dunn A

B D

RP BOTH 30 RP332 N

AUX. RELAY RACK 134 AUX BLDG/

ELEV 2000-0 1320 E-093 219NE Cegelec Automation Inc. (Comsip Customline Corp)/

Struthers-Dunn A

B D

RP BOTH 30 SENE0060 N

EX-CORE NEUTRON FLUX DETECTOR ROOM 2000 2000 J-364 200262-101 Gamma Metric A

D A

SE SENE0061 N

EX-CORE NEUTRON FLUX DETECTOR ROOM 2000 2000 J-364 200262-101 Gamma Metric A

D A

SE SGS02A N

H2 ANALYZER 154 AUX BLDG/

ELEV 2047-6 1506 J-359 K-IV Comsip-Delphi Inc.

A D

D GS 34 41 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 42 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes SGS02B N

H2 ANALYZER 153 AUX BLDG/

ELEV 2047-6 1507 J-359 K-IV Comsip-Delphi Inc.

A D

D GS 34 SJHV0003 N

HOT LEG LOOP 1 SAMPLE VALVE 231 RX BLDG/

ELEV 1998-6 2000 J-603A V52600-5688-9 Valcor Engineering A

D A

SJ 21 SJHV0004 N

HOT LEG LOOP 3 SAMPLE VALVE 231 RX BLDG/

ELEV 1998-6 2000 J-603A V526-5688-9 Valcor Engineering A

D A

SJ 21 SJHV0005 N

PASS CONTAINMENT ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 J-603A V526-5688-9 Valcor Engineering A

D A

SJ 21 SJHV0006 N

PASS CONTAINMENT ISOLATION VALVE 134 AUX BLDG/

ELEV 2000-0 1323 J-603A V526-5688-6 Valcor Engineering A

D D

SJ 21 SJHV0012 N

PRESSURIZER VAPOR SPACE SAMPLE ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 J-603A V52600-6042-1A Valcor Engineering A

D A

SJ 21 SJHV0013 N

PRESSURIZER VAPOR SPACE SAMPLE ISOLATION VALVE 134 AUX BLDG/

ELEV 2000-0 1323 J-603A V52600-6042-1 Valcor Engineering A

D D

SJ 21 SJHV0018 N

ACCUMULATOR SAMPLES CTMT ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 J-603A V52600-6040-7A Valcor Engineering A

D A

SJ 21 SJHV0019 N

ACCUMULATOR SAMPLES CTMT ISOLATION VALVE 134 AUX BLDG/

ELEV 2000-0 1323 J-603A V52600-6040-7 Valcor Engineering A

D D

SJ 21 SJHV0127 N

PASS CONTAINMENT ISOLATION VALVE 134 AUX BLDG/

ELEV 2000-0 1323 J-603A V526-5688-6 Valcor Engineering A

D D

SJ 21 SJHV0128 N

PASS CONTAINMENT ISOLATION VALVE 231 RX BLDG/

ELEV 1998-6 2000 J-603A V526-5688-9 Valcor Engineering A

D A

SJ 21 SJHV0129 N

PASS CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 J-603A V526-5688-6 Valcor Engineering A

D D

SJ 21 SJHV0130 N

PASS CONTAINMENT ISOLATION VALVE 133 AUX BLDG/

ELEV 2000-0 1322 J-603A V526-5688-6 Valcor Engineering A

D D

SJ 21 ZNE-1-EQ N

ELECTRICAL PENETRATION MODULES ROOM 1410 1410 E-035B Low Voltage Power/Control/

Instrumentation 7040-1000- (Kapton)

Conax A

D D

XX BOTH 37, 38 ZNE263(Spare)

N ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE264 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE265 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE267 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE268 N

ELECTRICAL PENETRATION ASSY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZNE269 N

ELECTRICAL PENETRATION ASSY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZNE271 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE272 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE274 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

42 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 43 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ZNE275 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE276 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE277 N

ELECTRICAL PENETRATION ASSY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZNE278 N

ELECTRICAL PENETRATION ASSY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZNE279 N

ELECTRICAL PENETRATION ASSY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZNE280 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE281 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE282 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZNE283 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE284 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE285 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE287 N

ELECTRICAL PENETRATION ASSY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZNE288 N

ELECTRICAL PENETRATION ASSY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZNE289 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE290 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE291 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE292 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZNE293 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNE294 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZNE295 N

ELECTRICAL PENETRATION ASSY 144 AUX BLDG/

ELEV 2026-0 1410 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZNE296 N

ELECTRICAL PENETRATION ASSY (ENCAPSULATION) 124 AUX BLDG/

ELEV 1988-0 1204 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A B

D XX BOTH 38 ZNE297 N

ELECTRICAL PENETRATION ASSY (ENCAPSULATION) 123 AUX BLDG/

ELEV 1988-0 1203 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A B

D XX BOTH 38 ZNE298 N

ELECTRICAL PENETRATION ASSY (ENCAPSULATION) 124 AUX BLDG/

ELEV 1988-0 1204 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A C

D XX BOTH 38 43 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 44 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ZNI-1-EQ N

ELECTRICAL PENETRATION MODULES ROOM 2000 2000 E-035B Low Voltage Power/Control/

Instrumentation 7040-1000- (Kapton)

Conax A

A D

XX BOTH 37, 38 ZNI263(Spare)

N ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI264 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI265 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI267 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI268 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZNI269 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZNI271 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI272 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI274 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZNI275 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI276 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI277 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZNI278 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZNI279 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZNI280 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI281 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 44 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 45 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ZNI282 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZNI283 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI284 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI285 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI287 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZNI288 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZNI289 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI290 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI291 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI292 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZNI293 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZNI294 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZNI295 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZNI296 N

VALVE TERMINAL BOX 124 AUX BLDG/

ELEV 1988-0 1204 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

B D

XX COLD ZNI297 N

VALVE TERMINAL BOX 123 AUX BLDG/

ELEV 1988-0 1203 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

B D

XX COLD ZNI298 N

VALVE TERMINAL BOX 124 AUX BLDG/

ELEV 1988-0 1204 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

C D

XX ZSE-1-EQ N

ELECTRICAL PENETRATION MODULES ROOM 1409 1409 E-035B Low Voltage Power/Control/

Instrumentation 7040-1000- (Kapton)

Conax A

D D

XX BOTH 37, 38 ZSE206(Spare)

N ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 45 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 46 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ZSE207 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSE208 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSE210 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSE215 N

ELECTRICAL PENETRATION ASSY (ENCAPSULATION) 124 AUX BLDG/

ELEV 1988-0 1204 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A B

D XX BOTH 38 ZSE216 N

ELECTRICAL PENETRATION ASSY (ENCAPSULATION) 123 AUX BLDG/

ELEV 1988-0 1203 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A B

D XX BOTH 38 ZSE217 N

ELECTRICAL PENETRATION ASSY (ENCAPSULATION) 123 AUX BLDG/

ELEV 1988-0 1203 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A C

D XX BOTH 38 ZSE218 N

ELECTRICAL PENETRATION ASSY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZSE219 N

ELECTRICAL PENETRATION ASSY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZSE222 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSE223 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSE224 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSE225 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSE226 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSE233 N

ELECTRICAL PENETRATION ASSY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZSE234 N

ELECTRICAL PENETRATION ASSY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZSE240 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSE243 N

ELECTRICAL PENETRATION ASSY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZSE249 N

ELECTRICAL PENETRATION ASSY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZSE250 N

ELECTRICAL PENETRATION ASSY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZSE251(Spare)

N ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSE252 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSE253 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSE254 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSE255 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

46 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 47 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ZSE258 N

ELECTRICAL PENETRATION ASSY 143 AUX BLDG/

ELEV 2026-0 1409 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

D XX BOTH 38 ZSI-1-EQ N

ELECTRICAL PENETRATION MODULES ROOM 2000 2000 E-035B Low Voltage Power/Control/

Instrumentation 7040-1000- (Kapton)

Conax A

A D

XX BOTH 37, 38 ZSI206(Spare)

N ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSI207 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSI208 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSI210 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSI215 N

VALVE TERMINAL BOX 124 AUX BLDG/

ELEV 1988-0 1204 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

B D

XX COLD ZSI216 N

VALVE TERMINAL BOX 123 AUX BLDG/

ELEV 1988-0 1203 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

B D

XX COLD ZSI217 N

VALVE TERMINAL BOX 123 AUX BLDG/

ELEV 1988-0 1203 E-035B 601-JJ, 602-JJ, 604-JJ Kulka A

C D

XX ZSI218 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZSI219 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZSI222 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSI223 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSI224 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSI225 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSI226 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSI233 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZSI234 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 47 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 48 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ZSI240 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSI243 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZSI249 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZSI250 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZSI251(Spare)

N ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH ZSI252 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSI253 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSI254 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSI255 N

ELECTRICAL PENETRATION ASSY PRESSURE BOUNDARY 241 RX BLDG/ELEV 2026-0 / AREA 1 2000 E-035 50027200 Amphenol (Bunker-Ramo)

B D

B XX BOTH 4

ZSI258 N

ELECTRICAL PENETRATION ASSY 241 RX BLDG/

ELEV 2026-0 2000 E-035 Low Voltage 50027200 Amphenol (Bunker-Ramo)

A D

A XX BOTH 38 ZTB-1-EQ N

TERMINAL BOXES (commodity item) 8 E-028-P01 1600 NUC Marathon Special Products A

A A

XX 8

ZTB-2-EQ N

TERMINAL BOXES (commodity item) 2 E-093-P03 NQB. 616822 Buchanan (Amerace) A A

A XX 2

ZTB-3-EQ N

TERMINAL BOXES (commodity item) 8 E-035B-P02 601-JJ, 602-JJ, 604-JJ Kulka A

A A

XX 8

ZTB-4-EQ N

Terminal Lugs or Terminal Connectors 2 - Used throughout the plant 2

E-093-P04 RAT-Series, RBT-Series & RDT Series Thomas & Betts A

A A

XX BOTH ZTB-5-EQ N

TERMINAL BOXES (commodity item) 8 LIMITORQU E-P05 (see P03 for Marathon 300s)

Marathon 1600; Buchanan 0222 and 0524; General Electric EB-5 and EB-25; Curtis Type "L Marathon Buchanan General Electric Curtis A

A A

XX 8

ZZB-1-EQ N

5 KV POWER CABLES 5 - Used throughout the plant - outside containment 5

E-029-P01 HTK/HTNs Type Kerite Company A

D D

XX BOTH 48 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 49 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ZZC-1-EQ N

600 VOLT COPPER CONTROL CABLE 2 - Used throughout the plant 2

E-057-P01 Chemically cross-linked polyethylene insulated Firewall III/

Insulation Formulation KXL760, KXL-760-5, KXL-7600, KXL-780 Rockbestos Company/ Firewall III A

A A

XX BOTH ZZC-2-EQ N

600 VOLT COPPER CONTROL CABLE 2 - Used throughout the plant 2

E-057A FR-EP Anaconda-Ericsson Inc.

A A

A XX BOTH ZZC-3-EQ N

600 VOLT COPPER CONTROL CABLE 2 - Used throughout the plant 2

E-057B XLPE Brand-Rex Company/XLPE A

A A

XX BOTH ZZC-4-EQ N

600 VOLT FIRE-RESISTIVE CONTROL AND POWER CABLE 1402 CORRIDOR NO. 1/141 AUX BLDG AND 1501 CTRL RM A/C &

FILTRN UNITS RM B 2

E-057C Appendix R Meggitt Safety Systems, Inc.

D D

A XX BOTH ZZE-1-EQ N/Y2 1/2, 3/4, 1-1/2 Inch Quick Disconnect Electrical Connector 2 - Used throughout the plant 2

E-103-P02 880701-1, 880702-1B, 9139601-1, 913601-1B, 913602-1, 913602-1B EGS Corporation A

A A

XX BOTH ZZF-1-EQ N

GTE Sylvania Fuse Block, Gould Fuse A6Y, General Electric Busbar Standoff 2 - Used throughout the plant 2

E-093-P05 PFS-3322 Fuse A6Y 796A526P4 GTE Sylvania, Gould

& GE A

A A

XX BOTH ZZG-1-EQ N

600 VOLT POWER CABLE 2 - Used throughout the plant 2

E-058 Durasheath 'EP' Anaconda-Ericsson Inc./Durasheath 'EP' A

A A

XX BOTH ZZJ-1-EQ N

600 VOLT SHIELDED INSTRUMENTATION CABLE 2 - Used throughout the plant 2

E-062A E-057-P02 Irradiation cross-linked polyethylene insulated Firewall III/Insulation Formation KXL 760G (Originally EQWP-E-062A)

Rockbestos Company/ Firewall III A

A A

XX BOTH ZZJ-2-EQ N

600 VOLT SHIELDED INSTRUMENTATION CABLE 2 - Used throughout the plant 2

E-062 EPR-CSPE Boston Insulated Wire and Cable Company A

A A

XX BOTH ZZQ-1-EQ N

NUCLEAR JACKET REPAIR TAPE MATERIAL 2 - Used throughout the plant 2

E-01013 P02 NJRT (old part #,

original material)

Raychem A

A A

XX BOTH ZZR-1-EQ N

CABLE BREAKOUT KIT MATERIAL 2 - Used throughout the plant 2

E-01013 P05 NCBK, NCBX, NESK (old part #, original material)

Raychem A

A A

XX BOTH 49 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 50 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes ZZS-1-EQ N

600 VOLT SHIELDED INSTRUMENTATION CABLE 2 - Used throughout the plant 2

E-062 EPR-CSPE Boston Insulated Wire and Cable Company A

A A

XX BOTH ZZT-1-EQ N

THERMOCOUPLE EXTENSION CABLE 2 - Used throughout the plant 2

E-061 EPDM Eaton Corp. (Samuel Moore Operations)

A A

A XX BOTH ZZU-1-EQ N

5 KV CABLE SPLICE MATERIAL 5 - Used throughout the plant - outside containment 5

E-029 EQWP-E-029 Check sheet #2 S-5NS-NUC-DISC and IT/OT-5NS-NUC Kerite Company A

D D

XX BOTH ZZV-1-EQ N

CABLE END SEAL, BREAKOUT, STUB CONNECTION, TRANSITION SPLICE KITS MATERIAL AND JACKET REPAIR MATERIAL 2 - Used throughout the plant 2

E-01013 P08 NCBK,NESK, NJRT, NMCK, NPKC, NPKP, NPKS, NPKV, NPKX (new part #s & materials)

Raychem A

A A

XX BOTH ZZV-2-EQ N

THREAD SEALANT 2 - Used throughout the plant 2

E-103-P03 M-771-00454 (Test Report)

P-1 EGS Corporation A

A A

XX BOTH ZZW-1-EQ N

NUCLEAR MOTOR CONNECTION KITS MATERIAL 2 - Used throughout the plant 2

E-01013 P04 N-MCK (old part #,

original material)

Raychem A

A A

XX BOTH ZZX-1-EQ N

COAXIAL & TRIAXIAL CABLE 2 - Used throughout the plant 2

E-060 RG-11A/U, RG-58 C/U, RG-59 B/U (FR-XLPE)

Brand-Rex Company A

A A

XX BOTH ZZY-1-EQ N

CABLE TERMINATION HEAT SHRINK FLD SPLICING MATERIAL SYSTEM 2 - Used throughout the plant 2

E-01013 P01 WCSF-N (old part #,

original material)

Raychem A

A A

XX BOTH ZZY-2-EQ N

HEAT SHRINK FLD. SPLICING SYSTEM MATERIAL 2 - Used throughout the plant 2

E-01013 P09 WCSF-N (new part #

& material)

Raychem A

A A

XX BOTH ZZY-3-EQ N

SHIM STOCK MATERIAL 2 - Used throughout the plant 2

E-01013 P07 WCSF-N-050 (old part #, original material)

Raychem A

A A

XX BOTH ZZZ-1-EQ N

STUB CONNECTION KIT MATERIAL 2 - Used throughout the plant 2

E-01013 P02 NPKV (old part #,

original material)

Raychem A

A A

XX BOTH ZZZ-2-EQ N

IN-LINE BOLTED CONNNECTION MATERIAL 2 - Used throughout the plant 2

E-01013 P06 WCSF-N (old part #,

original material)

Raychem A

A A

XX BOTH ZZZ-3-EQ N

TRANSITION SPLICE KIT MATERIAL 2 - Used throughout the plant 2

E-01013 P03 NPKS, NPKC, NPKP, NPKX (old part #, original material)

Raychem A

A A

XX BOTH GENERAL Electrical Equipment Categories for LOCA/MSLB/HELB fields 50 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 51 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes Cat. A Item is required to function post accident Cat. B Item is not required to function post accident; however, item must not adversely fail post accident Cat. C Item's status post accident has no effect on plant safety Cat. D Item is in mild environment post accident 51 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 52 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes Notes:

2 3

4 5

7 8

9 11 12 16 17 18 19 20 21 22 24 25 26 27 28 29 30 31 32 Used inside containment.

Description Used throughout the plant.

The spent fuel pool cooling system will be operated during these conditions to maintain fuel pool temperatures.

This note identifies that Non-IE Conax modules used in this penetration and addressed in PQE-E-035B-P01 have a safety related function of maintaining the pressure boundary of containment. PQE-E-035B-P01 documents that Conax modules used in ZSE/ZSI222E (I), ZSE/ZSI252E (I), ZNE/ZNI253C (I), ZSE/ZSI254E (I),

ZSE/ZSI255E (I), ZSE/ZSI255D (I), ZNE/ZNI292F (I) and ZNE/ZNI294C (I) ZSE/ZSI222F (LVP), ZNE/ZNI224C (LVP), ZNE/ZNI274A (LVP), ZNE/ZNI274G (LVP) and ZNE/ZNI282C (LVP) are acceptable for use in the environments identified.

Used throughout the plant - outside containment.

This equipment was added in response to NUREG-0737 Category II.E.1.2 Used throughout the plant with exception of instrumentation circuits inside containment and auxilary building rooms 1411, 1412, 1508, and 1509 Alternate EGS connector approved for installation per CP 12467 as necessary.

Determined by XX-81 analysis to be mild environment equipment post accident (also reference EQWP-J-605A R3) states that a location-specific dose calculation and analysis was performed on the butterfly valves located in Room 1314, and concluded that the subject valves can be recategorized as mild environment equipment. The parameters constitute a mild environment.

Determined by XX-53 analysis to be mild environment equipment post accident. EQWP-E-018 R5 states that a specific-location dose calculation and analysis was performed on the MCC's located in Room 1409 and 1410, and concluded that subject MCCs can be recategorized as a mild environment equipment.

Qualified as a sub-component of Panel RP209 Qualified as a sub-component of Panel RP330 Qualified as a sub-component of Panel RP332 Spared in Place This equipment was added in response to NUREG-0737 Category II.B.1 This equipment was added in response to NUREG-0737 Category II.B.3 This equipment was added in response to NUREG-0737 Category II.D.3 This equipment was added in response to NUREG-0737 Category II.F.1 This equipment was added in response to NUREG-0737 Category II.F.2 Rooms 1101, 1102, 1120, 1121, 1122 and 1130 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1107 and 1108 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1113 and 1114 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1301, 1314, 1315 and 1320 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1508 and 1509 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1206 and 1207 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

52 of 53

EQSD-II Rev. 34 Table 1: EQ Harsh Environment Equipment List 53 of 53 Component Number MC Code Equipment Qualification Description Installed Elevation EQ Room EQ Spec Model #

Manufacturer LO CA HE LB MS LB System HOT/

COLD SHUT DOWN Notes 33 34 35 36 37 38 39 40 41 42 43 44 45 50 Rooms 6301 and 6302 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1401, 1402 and 1408 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1502, 1503, 1505 and 1507 plus Rooms 1504, 1506 and 1513 (due to transfer grill GLD0175 on M-1H1431) are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 3401, 3406 and 3412 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

PQE-ESE-43G-P01 CP 13788 CP 14701 Located in yard.

Reference E-035B-00050, Table 3.1, Page 11. The power and control modules are ZSE/ZSI233E, ZSE/ZSI233F, ZSE/ZSI234F, ZNE/ZNI278F and ZNE/ZNI278G. The instrumentation modules are ZSE/ZSI233D, ZSE/ZSI233G, ZSE/ZSI234E, ZSE/ZSI243C, ZSE/ZSI249C, ZSE/ZSI249D, ZSE/ZSI250A, ZSE/ZSI250B, ZSE/ZSI250D, ZSE/ZSI250F, ZSE/ZSI250G, ZSE/ZSI258F, ZNE/ZNI277F, ZNE/ZNI278C, ZNE/ZNI278D, ZNE/ZNI278E, ZNE/ZNI279E, ZNE/ZNI287C, ZNE/ZNI287D, ZNE/ZNI287E, ZNE/ZNI288B, ZNE/ZNI288D, ZNE/ZNI288F, ZNE/ZNI295F and ZNE/ZNI295G.

GDI-30F (Long-glass, fiber filled, diallyl-phthalate) terminal blocks that are Series 601-JJ, 602-JJ, 604-JJ, 605-JJ, 812-JJ type are qualified under PQE-E-035B-P02 for each of these applications. Instrumentation applications do not use the Kulka terminal blocks inside the containment, PQE-E-11013-P01/ P06/P07/ P08/ P09 splices are used in these applications.

These assets contain two limit switches. However one of the limit switches is an installed spare and doesnt have power running to it. Therefore, doesnt perform any safety function and doesnt need qualified by the EQ program.

Not used DRE 20217 approves changing the identified model 763 to 763A.

SWO 18-446734-002 changed model number to 763A.

53 of 53

EQSD-II Rev. 32 EQSD-II Table 2:

EQ Mild Environment Equipment List 1 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes 27XQB01 AUX RELAY IN PANEL RP330 1320 E-093 C C C QB BOTH 17 30 27XQB02 AUX RELAY IN PANEL RP330 1320 E-093 C C C QB BOTH 17 30 3XAP02 AUX RELAY IN PANEL RP330 (APV0015) 1320 E-093 C C C AP BOTH 17 30 3XGS23 AUX RELAY IN PANEL RP209 1320 E-093 C C C GS BOTH 16 30 45XJE01 125 VDC AUX RELAY IN PANEL RP330 FOR FIRE SIGNAL ISO 1320 E-093 C C C JE BOTH 17 30 63XFC15 AUX RELAY IN PANEL RP330 1320 E-093 C C C FC BOTH 17 30 63XFC17 AUX RELAY IN PANEL RP330 1320 E-093 C C C FC BOTH 17 30 74XBG03 AUX RELAY PANEL RP209 1320 E-093 C C C BG BOTH 16 30 74XEJ05 AUX RELAY IN PANEL RP332 FOR EJHCV0606 COMPUTER POINT 1320 E-093 C C C EJ BOTH 18 30 95XGK07 AUX RELAY PANEL RP330 1320 E-093 C C C GK BOTH 17 30 AB007 AUX. RELAY RACK 3413 E-093 D D D AB BOTH ABFHC0002 ABPV0002 LOCAL CONTROLLER 1509 J-601B C D C AB BOTH 31 ABFHC0003 ABPV0003 LOCAL CONTROLLER 1509 J-601 C D C AB BOTH 31 ABHY0005 ABHV0005 SOLENOID VALVE 1412 J-601A C D C AB BOTH ABHY0006 ABHV0006 SOLENOID VALVE 1412 J-601A C D C AB BOTH ABHY0048A ABHV0048 SOLENOID VALVE 1412 J-601A C D C AB BOTH ABHY0049A ABHV0049 SOLENOID VALVE 1412 J-601 C D C AB BOTH ABLT0007 MAIN STM LINE DRN VLV LP 3 LV 1331 J-301 D C D AB BOTH ABLT0008 MAIN STM LINE DRN VLV LP 2 LV 1331 J-301 D C D AB BOTH ABLT0009 MAIN STM LINE DRN VLV LP 1 LV 1326 J-301 D D D AB BOTH ABLT0010 MAIN STM LINE DRN VLV LP 4 LV 1325 J-301 D D D AB BOTH ABPI0514A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0515A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0516A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0516X STEAMLINE PRESSURE 1413 ESE-14 D D D AB BOTH ABPI0524A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0524B STEAMLINE PRESSURE 1413 ESE-14 D D D AB BOTH ABPI0525A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0526A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0534A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0535A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0535X STEAMLINE PRESSURE 1413 ESE-14 D D D AB BOTH ABPI0536A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0544A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0544B STEAMLINE PRESSURE 1413 ESE-14 D D D AB BOTH ABPI0545A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0546A STEAMLINE PRESSURE 3501 ESE-1 D D D AB BOTH ABPIC0001A STM GEN A ATM STEAM DUMP 3501 J-110 D D D AB BOTH ABPIC0001B STM GEN A ATM STEAM DUMP 1413 J-110 D D D AB BOTH ABPIC0002A STM GEN B ATM STEAM DUMP 3501 J-110 D D D AB BOTH ABPIC0002B STM GEN B ATM STEAM DUMP 1413 J-110 D D D AB BOTH ABPIC0003A STM GEN C ATM STEAM DUMP 3501 J-110 D D D AB BOTH ABPIC0003B STM GEN C ATM STEAM DUMP 1413 J-110 D D D AB BOTH ABPIC0004A STM GEN D ATM STEAM DUMP 3501 J-110 D D D AB BOTH ABPIC0004B STM GEN D ATM STEAM DUMP 1413 J-110 D D D AB BOTH ABPT0001 STM GEN A STEAMLINE PRESSURE 1304 J-301 D D D AB BOTH

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 2 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes ABPT0002 STM GEN B STEAMLINE PRESSURE 1305 J-301 D D D AB BOTH ABPT0003 STM GEN C STEAMLINE PRESSURE 1305 J-301 D D D AB BOTH ABPT0004 STM GEN D STEAMLINE PRESSURE 1304 J-301 D D D AB BOTH ABPV0001 STM GEN A ATM RELIEF VLV 1508 J-601 C D C AB BOTH 31 ABPV0002 STM GEN B ATM RELIEF VLV 1509 J-601 C D C AB BOTH 31 ABPV0003 STM GEN C ATM RELIEF VLV 1509 J-601 C D C AB BOTH 31 ABPV0004 STM GEN D ATM RELIEF VLV 1508 J-601 C D C AB BOTH 31 ABPY0001 ABPV0001 I/P CONVERTER 1508 J-601B C D C AB BOTH 31 ABPY0002 ABPV0002 I/P CONVERTER 1509 J-601B C D C AB BOTH 31 ABPY0003 ABPV0003 I/P CONVERTER 1509 J-601B C D C AB BOTH 31 ABPY0004 ABPV0004 I/P CONVERTER 1508 J-601B C D C AB BOTH 31 ABZC0001 ABPV0001 POSITIONER - STM GEN A ATM VENT VALVE 1508 J-601B C D C AB BOTH ABZC0002 ABPV0002 POSITIONER - STM GEN B ATM VENT VALVE 1509 J-601B C D C AB BOTH ABZC0003 ABPV0003 POSITIONER - STM GEN C ATM VENT VALVE 1509 J-601B C D C AB BOTH ABZC0004 ABPV0004 POSITIONER - STM GEN D ATM VENT VALVE 1508 J-601B C D C AB BOTH ABZE0011AC LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 CLOSED POSITION DETECTION ELEMENT A 1508 M-630 C D C AB ABZE0011AO LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 OPEN POSITION DETECTION ELEMENT A 1508 M-630 C D C AB ABZE0011BC LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 CLOSED POSITION DETECTION ELEMENT B 1508 M-630 C D C AB ABZE0011BO LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 OPEN POSITION DETECTION ELEMENT B 1508 M-630 C D C AB ABZE0014AC LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 CLOSED POSITION DETECTION ELEMENT A 1508 M-630 C D C AB ABZE0014AO LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 OPEN POSITION DETECTION ELEMENT A 1508 M-630 C D C AB ABZE0014BC LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 CLOSED POSITION DETECTION ELEMENT B 1508 M-630 C D C AB ABZE0014BO LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 OPEN POSITION DETECTION ELEMENT B 1508 M-630 C D C AB ABZE0017AC LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 CLOSED POSITION DETECTION ELEMENT A 1509 M-630 C D C AB ABZE0017AO LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 OPEN POSITION DETECTION ELEMENT A 1509 M-630 C D C AB ABZE0017BC LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 CLOSED POSITION DETECTION ELEMENT B 1509 M-630 C D C AB ABZE0017BO LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 OPEN POSITION DETECTION ELEMENT B 1509 M-630 C D C AB ABZE0020AC LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 CLOSED POSITION DETECTION ELEMENT A 1509 M-630 C D C AB ABZE0020AO LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 OPEN POSITION DETECTION ELEMENT A 1509 M-630 C D C AB ABZE0020BC LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 CLOSED POSITION DETECTION ELEMENT B 1509 M-630 C D C AB 2 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 3 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes ABZE0020BO LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 OPEN POSITION DETECTION ELEMENT B 1509 M-630 C D C AB ABZS0005 ABHV0005 LIMIT SWITCH 1412 NAMCO C D C AB BOTH ABZS0006 ABHV0006 LIMIT SWITCH 1412 NAMCO C D C AB BOTH ABZS0048 ABHV0048 LIMIT SWITCH 1412 NAMCO C D C AB BOTH ABZS0049 ABHV0049 LIMIT SWITCH 1412 NAMCO C D C AB BOTH ABZT0011A LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 POSITION TRANSMITTER A 1508 M-630 C D C AB ABZT0011B LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 POSITION TRANSMITTER B 1508 M-630 C D C AB ABZT0014A LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 POSITION TRANSMITTER A 1508 M-630 C D C AB ABZT0014B LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 POSITION TRANSMITTER B 1508 M-630 C D C AB ABZT0017A LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 POSITION TRANSMITTER A 1509 M-630 C D C AB ABZT0017B LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 POSITION TRANSMITTER B 1509 M-630 C D C AB ABZT0020A LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 POSITION TRANSMITTER A 1509 M-630 C D C AB ABZT0020B LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 POSITION TRANSMITTER B 1509 M-630 C D C AB ACPSL0231 MN STM CTRL VLV 2 PRESS SW 4401 J-110 D D D AC ACPSL0232 MN STM CTRL VLV 3 PRESS SW 4401 J-110 D D D AC ACPSL0233 MN STM CTRL VLV 1 PRESS SW 4401 J-110 D D D AC ACPT0231 MN STM CTRL VLV 3 4401 J-301 D D D AC ACPT0232 MN STM CTRL VLV 2 4401 J-301 D D D AC ACPT0233 MN STM CTRL VLV 1 4401 J-301 D D D AC ACPT0505 TURBINE IMPULSE PRESSURE 4401 M-771 D D D AC ACPT0506 TURBINE IMPULSE PRESSURE 4401 M-771 D D D AC ACZS0043C TURB TRP STOP VLV LMT SWITCH 4401 J-601A D D D AC ACZS0044C TURB TRP STOP VLV LMT SWITCH 4401 J-601A D D D AC ACZS0045C TURB TRP STOP VLV LMT SWITCH 4401 J-601A D D D AC ACZS0046C TURB TRP STOP VLV LMT SWITCH 4401 J-601 D D D AC AEFY0043 AEFV0043 SOLENOID VALVE 1411 J-601A C D C AE BOTH AEFY0044 AEFV0044 SOLENOID VALVE 1412 J-601A C D C AE BOTH AEFY0045 AEFV0045 SOLENOID VALVE 1412 J-601A C D C AE BOTH AEFY0046 AEFV0046 SOLENOID VALVE 1411 J-60 C D C AE BOTH AEFY0510AA FEEDWATER CONTROL VALVE LOOP 1 4401 HE-5 D D D AE AEFY0510BB FEEDWATER CONTROL VALVE LOOP 1 4401 HE-5 D D D AE AEFY0520AA FEEDWATER CONTROL VALVE LOOP 2 4401 HE-5 D D D AE AEFY0520BB FEEDWATER CONTROL VALVE LOOP 2 4401 HE-5 D D D AE AEFY0530AA FEEDWATER CONTROL VALVE LOOP 3 4401 HE-5 D D D AE AEFY0530BB FEEDWATER CONTROL VALVE LOOP 3 4401 HE-5 D D D AE AEFY0540AA FEEDWATER CONTROL VALVE LOOP 4 4401 HE-5 D D D AE 3 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 4 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes AEFY0540BB FEEDWATER CONTROL VALVE LOOP 4 4401 HE-5 D D D AE AEFY0550A FEEDWATER CONTROL BYPASS VALVE LOOP 1 4401 HE-5 D D D AE AEFY0550B FEEDWATER CONTROL BYPASS VALVE LOOP 1 4401 HE-5 D D D AE AEFY0560A FEEDWATER CONTROL BYPASS VALVE LOOP 2 4401 HE-5 D D D AE AEFY0560B FEEDWATER CONTROL BYPASS VALVE LOOP 2 4401 HE-5 D D D AE AEFY0570A FEEDWATER CONTROL BYPASS VALVE LOOP 3 4401 HE-5 D D D AE AEFY0570B FEEDWATER CONTROL BYPASS VALVE LOOP 3 4401 HE-5 D D D AE AEFY0580A FEEDWATER CONTROL BYPASS VALVE LOOP 4 4401 HE-5 D D D AE AEFY0580B FEEDWATER CONTROL BYPASS VALVE LOOP 4 4401 HE-5 >

D D D AE AELI0501 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0501A STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0502 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0502A STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0503 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0503A STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0504 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0504A STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0517 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0517X STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0518 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0519 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0527 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0527X STEAM GENERATOR WATER LEVEL (INSTALLED SPARE) 1413 ESE-14 D D D AE AELI0528 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0528X STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0529 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0537 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0537X STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0538 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0539 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0547 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0548 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0548X STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0549 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AEZE0039AC LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 CLOSED POSITION DETECTION ELEMENT A 1411 M-628 C D C AE AEZE0039AO LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 OPEN POSITION DETECTION ELEMENT A 1411 M-628 C D C AE AEZE0039BC LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 CLOSED POSITION DETECTION ELEMENT B 1411 M-628 C D C AE AEZE0039BO LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 OPEN POSITION DETECTION ELEMENT B 1411 M-628 C D C AE AEZE0040AC LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 CLOSED POSITION DETECTION ELEMENT A 1411 M-628 C D C AE AEZE0040AO LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 OPEN POSITION DETECTION ELEMENT A 1411 M-628 C D C AE 4 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 5 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes AEZE0040BC LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 CLOSED POSITION DETECTION ELEMENT B 1411 M-628 C D C AE AEZE0040BO LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 OPEN POSITION DETECTION ELEMENT B 1411 M-628 C D C AE AEZE0041AC LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV0041 CLOSED POSITION DETECTION ELEMENT A 1412 M-628 C D C AE AEZE0041AO LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV00341 OPEN POSITION DETECTION ELEMENT A 1412 M-628 C D C AE AEZE0041BC LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV0041 CLOSED POSITION DETECTION ELEMENT B 1412 M-628 C D C AE AEZE0041BO LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV0041 OPEN POSITION DETECTION ELEMENT B 1412 M-628 C D C AE AEZE0042AC LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 CLOSED POSITION DETECTION ELEMENT A 1412 M-628 C D C AE AEZE0042AO LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 OPEN POSITION DETECTION ELEMENT A 1412 M-628 C D C AE AEZE0042BC LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 CLOSED POSITION DETECTION ELEMENT B 1412 M-628 C D C AE AEZE0042BO LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 OPEN POSITION DETECTION ELEMENT B 1412 M-628 C D C AE AEZS0043 AEFV0043 LIMIT SWITCH 1411 NAMCO C D C AE BOTH AEZS0044 AEFV0044 LIMIT SWITCH 1412 NAMCO C D C AE BOTH AEZS0045 AEFV0045 LIMIT SWITCH 1412 NAMCO C D C AE BOTH AEZS0046 AEFV0046 LIMIT SWITCH 1411 NAMCO C D C AE BOTH AEZT0039A LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 POSITION TRANSMITTER A 1411 M-628 C D C AE AEZT0039B LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 POSITION TRANSMITTER B 1411 M-628 C D C AE AEZT0040A LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 POSITION TRANSMITTER A 1411 M-628 C D C AE AEZT0040B LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 POSITION TRANSMITTER B 1411 M-628 C D C AE AEZT0041A LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV0041 POSITION TRANSMITTER A 1412 M-628 C D C AE AEZT0041B LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV0041 POSITION TRANSMITTER B 1412 M-628 C D C AE AEZT0042A LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 POSITION TRANSMITTER A 1412 M-628 C D C AE AEZT0042B LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 POSITION TRANSMITTER B 1412 M-628 C D C AE ALFI0001A AUX FDWTR PMP TO STEAM GEN D 3501 J-110 D D D AL HOT 24 ALFI0001B AUX FDWTR PMP TO STEAM GEN D 1413 J-110 D D D AL HOT 24 ALFI0002A AUX FDWTR PMP TO STEAM GEN A 3501 J-110 D D D AL HOT 24 ALFI0002B AUX FDWTR PMP TO STEAM GEN A 1413 J-110 D D D AL HOT 24 ALFI0003A AUX FDWTR PMP TO STEAM GEN B 3501 J-110 D D D AL HOT 24 5 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 6 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes ALFI0003B AUX FDWTR PMP TO STEAM GEN B 1413 J-110 D D D AL HOT 24 ALFI0004A AUX FDWTR PMP TO STEAM GEN C 3501 J-110 D D D AL HOT 24 ALFI0004B AUX FDWTR PMP TO STEAM GEN C 1413 J-110 D D D AL HOT 24 ALFT0001 AUX FDWTR PMP TO STEAM GEN D 1304 J-301 C D D AL HOT 24 ALFT0002 AUX FDWTR PMP TO STEAM GEN A 1304 J-301 C D D AL HOT 24 ALFT0003 AUX FDWTR PMP TO STEAM GEN B 1305 J-301 D D D AL HOT 24 ALFT0004 AUX FDWTR PMP TO STEAM GEN C 1305 J-301 D D D AL HOT 24 ALFT0007 AUX FDW FLO TO SG A 1304 J-301 C D D AL HOT 24 ALFT0009 AUX FDW FLO TO SG B 1305 J-301 D D D AL HOT 24 ALFT0011 AUX FDW FLO TO SG C 1305 J-301 D D D AL HOT 24 ALHK0005A MOT AUX FW PMP B DISCH TO STM GEN D 3501 J-110 D D D AL HOT ALHK0005B MOT AUX FW PMP B DISCH TO STM GEN D 1413 J-110 D D D AL HOT ALHK0006A TURB AFP DISCH TO STEAM GEN D 3501 J-110 D D D AL HOT ALHK0006B TURB AFP DISCH TO STEAM GEN D 1413 J-110 D D D AL HOT ALHK0007A MOT AUX FW PMP B DISCH TO STM GEN A 3501 J-110 D D D AL HOT ALHK0007B MOT AUX FW PMP B DISCH TO STM GEN A 1413 J-110 D D D AL HOT ALHK0008A TURB AFP DISCH TO STEAM GEN A 3501 J-110 D D D AL HOT ALHK0008B TURB AFP DISCH TO STEAM GEN A 1413 J-110 D D D AL HOT ALHK0009A MOT AUX FW PMP A DISCH TO STM GEN B 3501 J-110 D D D AL HOT ALHK0009B MOT AUX FW PMP A DISCH TO STM GEN B 1413 J-110 D D D AL HOT ALHK0010A TURB AFP DISCH TO STEAM GEN B 3501 J-110 D D D AL HOT ALHK0010B TURB AFP DISCH TO STEAM GEN B 1413 J-110 D D D AL HOT ALHK0011A MOT AUX FW PMP A DISCH TO STM GEN C 3501 J-110 D D D AL HOT ALHK0011B MOT AUX FW PMP A DISCH TO STM GEN C 1413 J-110 D D D AL HOT ALHK0012A TURB AFP DISCH TO STEAM GEN C 3501 J-110 D D D AL HOT ALHK0012B TURB AFP DISCH TO STEAM GEN C 1413 J-110 D D D AL HOT ALHV0005 MOT AUX FDWTR PMP B DISCH ISO 1324 J-601 D D D AL HOT ALHV0006-E01 VALVE TERMINAL BOX 1327 E-028 D D D AL HOT ALHV0007 MOT AUX FDWTR PMP B DISCH ISO 1324 J-601 D D D AL HOT ALHV0008-E01 VALVE TERMINAL BOX 1327 E-028 D D D AL HOT ALHV0009 MOT AUX FDWTR PMP A DISCH ISO 1328 J-601 D D D AL HOT ALHV0010-E01 VALVE TERMINAL BOX 1330 E-028 D D D AL HOT ALHV0011 MOT AUX FDWTR PMP A DISCH ISO 1328 J-601 D D D AL HOT ALHV0012-E01 VALVE TERMINAL BOX 1330 E-028 D D D AL HOT ALHV0030 ESW TO AUX. FEED PUMP B 1206 M-236A C D D AL HOT 32 ALHV0031 ESW TO AUX. FEED PUMP A 1206 M-236A C D D AL HOT 32 ALHV0032 TURBINE AF PUMP SUCTION FROM ESW A 1207 M-236A C D D AL HOT 32 ALHV0033 TURBINE AF PUMP SUCTION FROM ESW B 1207 M-236A C D D AL HOT 32 ALHV0034 CST TO AUXILIARY FEED PUMP B 1206 LIMITORQUE C D D AL HOT 32 ALHV0035 CST TO AUXILIARY FEED PUMP A 1206 LIMITORQUE C D D AL HOT 32 ALHV0036 TURBINE AF PUMP SUCTION FROM CST 1207 LIMITORQUE C D D AL HOT 32 ALHY0006 ALHV0006 I/P CONVERTER 1327 J-601A D D D AL HOT ALHY0008 ALHV0008 I/P CONVERTER 1327 J-601A D D D AL HOT ALHY0010 ALHV0010 I/P CONVERTER 1330 J-601A D D D AL HOT ALHY0012 ALHV0012 I/P CONVERTER 1330 J-601 D D D AL HOT ALPI0024A MOT AUX FDWTR PMP B SUCT PRESS 3501 J-110 D D D AL HOT 6 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 7 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes ALPI0024B MOT AUX FDWTR PMP B SUCT PRESS 1413 J-110 D D D AL HOT ALPI0025A MOT AUX FDW PMP A SUCT PRESS 3501 J-110 D D D AL HOT ALPI0025B MOT AUX FDW PMP A SUCT PRESS 1413 J-110 D D D AL HOT ALPI0026A TURB AUX FDWTR PMP SUCT PRESS 3501 J-110 D D D AL HOT ALPI0026B TURB AUX FDWTR PMP SUCT PRESS 1413 J-110 D D D AL HOT ALPI0037 AFW SPLY PRESS FROM COND STR TK 3501 J-110 D D D AL HOT ALPI0038 AFW SPLY PRESS FROM COND STR TK 3501 J-110 D D D AL HOT ALPI0039 AFW SPLY PRESS FROM COND STR TK 3501 J-110 D D D AL HOT ALPT0024 MOT AUX FEEDWATER PMP B SUCT PRESS 1325 J-301 D D D AL HOT ALPT0025 CST TO MOT AUX FDW PMP A SUCT PRESS 1326 J-301 D D D AL HOT ALPT0026 TURB AUX FEEDWATER PMP SUCT PRESS 1331 J-301 D C D AL HOT ALPT0037 ESFAS LOW SUCTION PRESS 1207 J-301 C D D AL HOT 32 ALPT0038 ESFAS LOW SUCTION PRESS 1207 J-301 C D D AL HOT 32 ALPT0039 ESFAS LOW SUCTION PRESS 1207 J-301 C D D AL HOT 32 ALZS0006 ALHV0006 LIMIT SWITCH 1327 J-601A D D D AL HOT ALZS0008 ALHV0008 LIMIT SWITCH 1327 J-601A D D D AL HOT ALZS0010 ALHV0010 LIMIT SWITCH 1330 J-601A D D D AL HOT ALZS0012 ALHV0012 LIMIT SWITCH 1330 J-601A D D D AL HOT BB007 D.C. CONTACTOR FOR PORV 1403 E-018A D D D BB BOTH BB008 D.C. CONTACTOR FOR PORV 1408 E-018 D D D BB BOTH 33 BBFT0414 RCS FLOW TRANSMITTER LOOP 1 2201 ESE-4 C D C BB BOTH BBFT0415 RCS FLOW TRANSMITTER LOOP 1 2201 ESE-4 C D C BB BOTH BBFT0416 RCS FLOW TRANSMITTER LOOP 1 2201 ESE-4 C D C BB BOTH BBFT0424 RCS FLOW TRANSMITTER LOOP 2 2201 ESE-4 C D C BB BOTH BBFT0425 RCS FLOW TRANSMITTER LOOP 2 2201 ESE-4 C D C BB BOTH BBFT0426 RCS FLOW TRANSMITTER LOOP 2 2201 ESE-4 C D C BB BOTH BBFT0434 RCS FLOW TRANSMITTER LOOP 3 2201 ESE-4 C D C BB BOTH BBFT0435 RCS FLOW TRANSMITTER LOOP 3 2201 ESE-4 C D C BB BOTH BBFT0436 RCS FLOW TRANSMITTER LOOP 3 2201 ESE-4 C D C BB BOTH BBFT0444 RCS FLOW TRANSMITTER LOOP 4 2201 ESE-4 C D C BB BOTH BBFT0445 RCS FLOW TRANSMITTER LOOP 4 2201 ESE-4 C D C BB BOTH BBFT0446 RCS FLOW TRANSMITTER LOOP 4 2201 ESE-4 C D C BB BOTH BBHV8037A PRT EMERGENCY DRAIN LINE 2000 LIMITORQUE C D C BB BOTH BBHV8037B PRT EMERGENCY DRAIN LINE 2000 LIMITORQUE C D C BB BOTH BBHV8157A EXCESS LETDOWN PATH TO PRT ISOLATION 2000 M-231E C D C BB BOTH BBHV8157B EXCESS LETDOWN PATH TO PRT ISOLATION 2000 M-231E C D C BB BOTH BBLI0459A PRESSURIZER LEVEL 3501 ESE-14 D D D BB BOTH BBLI0459B PRESSURIZER LEVEL 1413 ESE-14 D D D BB BOTH BBLI0460A PRESSURIZER LEVEL 3501 ESE-14 D D D BB BOTH BBLI0460B PRESSURIZER LEVEL 1413 ESE-14 D D D BB BOTH BBLI0461 PRESSURIZER LEVEL 3501 ESE-14 D D D BB BOTH BBLI1311 REACTOR VESSEL LEVEL INDICATORS 3501 ESE-14 D D D BB 26 BBLI1312 REACTOR VESSEL LEVEL INDICATORS 3501 ESE-14 D D D BB 26 BBLI1321 REACTOR VESSEL LEVEL INDICATORS 3501 ESE-14 D D D BB 26 BBLI1322 REACTOR VESSEL LEVEL INDICATORS 3501 ESE-14 D D D BB 26 BBPI0403 REACTOR COOLANT PRESSURE INDICATOR 3501 ESE-14 D D D BB BOTH 7 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 8 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes BBPI0403X REACTOR COOLANT PRESSURE INDICATOR (ASP-SPARE) 1413 ESE-14 D D D BB BBPI0405 REACTOR COOLANT PRESSURE INDICATOR 3501 ESE-14 D D D BB BOTH BBPI0405X REACTOR COOLANT PRESSURE INDICATOR 1413 ESE-14 D D D BB BOTH BBPI0406 REACTOR COOLANT PRESSURE INDICATOR 3501 ESE-14 D D D BB BOTH BBPI0406X REACTOR COOLANT PRESSURE INDICATOR 1413 ESE-14 D D D BB BOTH BBT/C0011-E01 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES Spare 2000 J-565 C C C BB 26 BBT/C0016-E01 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES Spare 2000 J-565 C C C BB 26 BBT/C0035-E01 THERMOCOUPLE CONNECTOR/CABLE ASSEMBLIES Spare 2000 J-565 C C C BB 26 BBTI0413A TH WIDE RANGE LOOP 1 HOT LEG TEMP 3501 ESE-14 D D D BB BOTH BBTI0413B TH WIDE RANGE LOOP 1 COLD LEG TEMP 3501 ESE-14 D D D BB BOTH BBTI0423A TH WIDE RANGE LOOP 2 HOT LEG TEMP 3501 ESE-14 D D D BB BOTH BBTI0423B TH WIDE RANGE LOOP 2 COLD LEG TEMP 3501 ESE-14 D D D BB BOTH BBTI0423X TH WIDE RANGE LOOP 2 COLD LEG TEMP 1413 ESE-14 D D D BB BOTH BBTI0443A TH WIDE RANGE LOOP 4 HOT LEG TEMP 1413 ESE-14 D D D BB BOTH BBTI1390A SUBCOOLING TEMP IND 3501 ESE-14 D D D BB 26 BBTI1390B SUBCOOLING TEMP IND 3501 ESE-14 D D D BB 26 BBTR1390A SUBCOOLING RECORDER 3605 ESE-46B D D D BB BBTR1390B SUBCOOLING RECORDER 3605 ESE-46B D D D BB BBUU1390A SUBCOOLING REMOTE DISPLAY 3605 ESE-46A D D D BB BBUU1390B SUBCOOLING REMOTE DISPLAY 3605 ESE-46A D D D BB BGFI0138A EXCESS LETDOWN FLOW TO PRT 3501 ESE-14 D D D BG BOTH BGFI0138B EXCESS LETDOWN FLOW TO PRT 3501 ESE-14 D D D BG BOTH BGFI0215A SEAL INJECTION FLOW 3501 ESE-14 D D D BG BOTH BGFI0215B SEAL INJECTION FLOW 3501 ESE-14 D D D BG BOTH BGFT0138A EXCESS LETDOWN PATH TO PRT FLOW TRANSMITTER 2000 ESE-3 C D C BG BOTH BGFT0138B EXCESS LETDOWN PATH TO PRT FLOW TRANSMITTER 2000 ESE-3 C D C BG BOTH BGHV8104 EMERGENCY BORATION PATH ISOLATION VALVE 1113 LIMITORQUE C D D BG BOTH 29 BGHV8357A CCP A ALTERNATE DISCHARGE TO RCP SEALS 1114 M-231E C D D BG BOTH 29 BGHV8357B CCP B ALTERNATE DISCHARGE TO RCP SEALS 1107 M-231E C D D BG BOTH 28 BGLI0102 BORIC ACID TANK #1 LEVEL 3501 ESE-14 D D D BG BOTH BGLI0104 BORIC ACID TANK 1 LEVEL 3501 ESE-14 D D D BG BOTH BGLI0105 BORIC ACID TANK #2 LEVEL 3501 ESE-14 D D D BG BOTH BGLI0106 BORIC ACID TANK 2 LEVEL 3501 ESE-14 D D D BG BOTH BGLI0112 VOLUME CONTROL TANK LEVEL 3501 ESE-14 D D D BG BOTH BGLI0185 VOLUME CONTROL TANK LEVEL 3501 ESE-14 D D D BG BOTH BGLT0102 BORIC ACID TANK A LEVEL TRANSMITTER 1117 ESE-4 C D D BG BOTH BGLT0104 BORIC ACID TANK A LEVEL TRANSMITTER 1117 ESE-4 C D D BG BOTH BGLT0105 BORIC ACID TANK B LEVEL TRANSMITTER 1116 ESE-4 C D D BG BOTH BGLT0106 BORIC ACID TANK B LEVEL TRANSMITTER 1116 ESE-4 C D D BG BOTH BGLT0112 VCT LEVEL TRANSMITTER 1318 ESE-4 C C D BG BOTH BGLT0185 VCT LEVEL TRANSMITTER 1316 ESE-4A C C D BG BOTH BGTE0032 DPBG05A INBOARD BEARING TEMPERATURE 1114 M-721 C D D BG 29 BGTE0033 DPBG05A OUTBOARD BEARING TEMPERATURE 1114 M-721 C D D BG 29 BGTE0034 DPBG05B INBOARD BEARING TEMPERATURE 1107 M-721 C D D BG 28 BGTE0035 DPBG05B OUTBOARD BEARING TEMPERATURE 1107 M-721 C D D BG 28 8 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 9 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes BGTE0137A EXCESS LETDOWN PATH TO PRT TEMPERATURE ELEMENT 2000 ESE-42A C D C BG BOTH BGTE0137B EXCESS LETDOWN PATH TO PRT TEMPERATURE ELEMENT 2000 ESE-42A C D C BG BOTH BGTI0137A EXCESS LETDOWN TO PRT TEMP 3501 ESE-14 D D D BG BOTH BGTI0137B EXCESS LETDOWN FLOW TO PRT TEMP 3501 ESE-14 D D D BG BOTH BNHS8812B ISOLATION SWITCH FOR BNHV8812B 3302 E-028B D D D BN COLD BNLI0930 RWST LEVEL 3501 ESE-14 D D D BN BNLI0931 RWST LEVEL 3501 ESE-14 D D D BN BNLI0932 RWST LEVEL 3501 ESE-14 D D D BN BNLI0933 RWST LEVEL 3501 ESE-14 D D D BN BNLT0930 RWST LEVEL TRANSMITTER 9102 ESE-4 D D D BN BNLT0931 RWST LEVEL TRANSMITTER 9102 ESE-4 D D D BN BNLT0932 RWST LEVEL TRANSMITTER 9102 ESE-4 D D D BN BNLT0933 RWST LEVEL TRANSMITTER 9102 ESE-4 D D D BN BNTE0002 RWST TEMP 9102 J-558B D D D BN BNTE0005 RWST TEMP 9102 J-558B D D D BN BNTI0002 RWST TEMP 3501 J-110 D D D BN BNTI0005 RWST TEMP 3501 J-110 D D D BN BNTT0002 RWST TEMP 3605 J-110 D D D BN BNTT0005 RWST TEMP 3605 J-110 D D D BN BNZS0011 RWST OUTLET HEADER VALVE POSITION 9102 M-221 D D D BN BNZS8717 POSITION SWITCH ON RHR RETURN VALVE 1310 HE-6 C D D BN DCGD01A ESW PUMP ROOM SUPPLY FAN MOTOR K105 M-619.2 D D D GD BOTH DCGD01B ESW PUMP ROOM SUPPLY FAN MOTOR K104 M-619.2 D D D GD BOTH DCGG02A EMERGENCY EXH. FAN MOTOR 6304 M-619.2 D D D GG DCGG02B EMERGENCY EXH. FAN MOTOR 6303 M-619.2 D D D GG DCGK03A CONTROL ROOM FILTER FAN MOTOR 1512 M-619.2 D D D GK DCGK03B CONTROL ROOM FILTER FAN MOTOR 1501 M-619.2 D D D GK DCGK04A CONTROL ROOM PRESSURE FAN MOTOR 3416 M-619.2 D D D GK DCGK04B CONTROL ROOM PRESSURE FAN MOTOR 3415 M-619.2 D D D GK DCGM01A DIESEL GEN. VENT. SUPPLY FAN MOTOR 5203 M-619.2 D D D GM BOTH DCGM01B DIESEL GEN. VENT. SUPPLY FAN MOTOR 5201 M-619.2 D D D GM BOTH DCGN03A HYDROGEN MIXING FAN MOTOR 2000 M-619.3 C D C GN HOT DCGN03B HYDROGEN MIXING FAN MOTOR 2000 M-619.3 C D C GN HOT DCGN03C HYDROGEN MIXING FAN MOTOR 2000 M-619.3 C D C GN HOT DCGN03D HYDROGEN MIXING FAN MOTOR 2000 M-619.3 C D C GN HOT DPAL01A AUX FEEDWATER PUMP A MOTOR 1326 E-012.2 D D D AL HOT DPAL01B AUX FEEDWATER PUMP B MOTOR 1325 E-012.2 D D D AL HOT DPBG02A BORIC ACID TRANSFER PUMP A MOTOR 1117 AE-3 C D D BG BOTH DPBG02B BORIC ACID TRANSFER PUMP B MOTOR 1116 AE-3 C D D BG BOTH DPEC01A SPENT FUEL POOL COOLING PUMP A MOTOR 6105 M-084 D D D EC 3

DPEC01B SPENT FUEL POOL COOLING PUMP B MOTOR 6104 M-084 D D D EC 3

DPEF01A ESW PUMP A MOTOR K105 E-012.2 D D D EF BOTH DPEF01B ESW PUMP B MOTOR K104 E-012.2 D D D EF BOTH DPEG01A CCW PUMP A MOTOR TRAIN A 1406 E-012.2 D D D EG BOTH DPEG01B CCW PUMP B MOTOR TRAIN B 1401 E-012.2 D D D EG BOTH 33 9 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 10 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes DPEG01C CCW PUMP C MOTOR TRAIN A 1406 E-012.2 D D D EG BOTH DPEG01D CCW PUMP D MOTOR TRAIN B 1401 E-012.2 D D D EG BOTH 33 DPJE01A EMERGENCY FUEL OIL TRANSFER PUMP A MOTOR (50)

M-087 D D D JE BOTH DPJE01B EMERGENCY FUEL OIL TRANSFER PUMP B MOTOR (50)

M-087 D D D JE BOTH DPKJ01A JACKET WATER KEEP WARM PUMP A MOTOR 5203 M-018 D D D KJ BOTH DPKJ01B JACKET WATER KEEP WARM PUMP B MOTOR 5201 M-018 D D D KJ BOTH DPKJ02A ROCKER PRELUBE PUMP A MOTOR 5203 M-018 D D D KJ BOTH DPKJ02B ROCKER PRELUBE PUMP B MOTOR 5201 M-018 D D D KJ BOTH DPKJ03A AUXILIARY LUBE OIL KEEP WARM PUMP A MOTOR 5203 M-018 D D D KJ BOTH DPKJ03B AUXILIARY LUBE OIL KEEP WARM PUMP B MOTOR 5201 M-018 D D D KJ BOTH DSGF02A AUX FEED PUMP ROOM COOLER MOTOR 1326 M-612 D D D GF BOTH DSGF02B AUX FEED PUMP ROOM COOLER MOTOR 1325 M-612 D D D GF BOTH DSGG04A SFP PUMP ROOM COOLER MOTOR 6105 M-612 D D D GG 3

DSGG04B SFP PUMP ROOM COOLER MOTOR 6104 M-612 D D D GG 3

DSGL11A CCW PUMP ROOM COOLER MOTOR 1406 M-612 D D D GL BOTH DSGL11B CCW PUMP ROOM COOLER MOTOR 1401 M-612 D D D GL BOTH 33 ECHV0011 F.P.C.H. EX. CCW ISOLATION VALVE LOOP A 6105 M-236 D D D EC BOTH ECHV0012 F.P.C.H. EX. CCW ISOLATION VALVE LOOP B 6104 M-236 D D D EC BOTH ECLSL0057 FUEL POOL LEVEL SWITCH 6106 J-481 D D D EC BOTH ECLSL0058 FUEL POOL LEVEL SWITCH 6106 J-481 D D D EC BOTH EF155 ESW CONTROL PNL K104 J-201 D D D EF BOTH EF156 ESW CONTROL PNL K105 J-201 D D D EF BOTH EFFI0053 ESW A FLO TO POWER BLOCK 3501 J-110 D D D EF EFFI0054 ESW B FLO TO POWER BLOCK 3501 J-110 D D D EF EFFT0039 WARMING LINE FLOW TRANSMITTER K105 J-301 D D D EF EFFT0042 WARMING LINE FLOW TRANSMITTER K104 J-301 D D D EF EFFT0053 ESW A FLO TO POWER BLOCK 3101 J-301 D D D EF EFFT0054 ESW B FLO TO POWER BLOCK 3101 J-301 D D D EF EFHS0003 LOCAL CONTROL STATION K105 E-028 D D D EF EFHS0004 LOCAL CONTROL STATION K104 E-028 D D D EF EFHS0026A ISOLATION SWITCH FOR EFHV0026 3302 E-028B D D D EF BOTH EFHS0038A ISOLATION SWITCH FOR EFHV0038 3302 E-028B D D D EF BOTH EFHV0023 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0024 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0025 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0026 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0037 ULTIMATE HEAT SINK ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0038 ULTIMATE HEAT SINK ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0039 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0040 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0041 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0042 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0051 CCW ISOLATION VALVE 1406 M-236 D D D EF BOTH EFHV0052 CCW ISOLATION VALVE 1401 M-236 D D D EF BOTH 33 EFHV0059 CCW ISOLATION VALVE 1406 M-236 D D D EF BOTH 10 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 11 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes EFHV0060 CCW ISOLATION VALVE 1401 M-236 D D D EF BOTH 33 EFHV0091 TRAVELING WATER SCREEN A SPRAY VALVE K105 LIMITORQUE D D D EF BOTH EFHV0092 TRAVELING WATER SCREEN B SPRAY VALVE K104 LIMITORQUE D D D EF BOTH EFHV0097 ESW PUMP A VENT VALVE K105 LIMITORQUE D D D EF BOTH EFHV0098 ESW PUMP B VENT VALVE K104 LIMITORQUE D D D EF BOTH EFPDI0019 ESW 2A SELF-CLN STR DIFF PRES K105 J-110 D D D EF BOTH EFPDI0020 ESW 2B SELF-CLN STR DIFF PRES K104 J-110 D D D EF BOTH EFPDS0019A ESW 2A SELF-CLN STR. DP SWITCH K105 J-301 D D D EF BOTH EFPDS0020A ESW 2B SELF-CLN STR. DP SWITCH K104 J-301 D D D EF BOTH EFPDT0019 ESW 2A SELF-CLN STR DIFF PRES K105 J-301 D D D EF BOTH EFPDT0020 ESW 2B SELF-CLN STR DIFF PRES K104 J-301 D D D EF BOTH EFPDV0019 STRAINER A TRASH VALVE K105 LIMITORQUE D D D EF BOTH EFPDV0020 STRAINER B TRASH VALVE K104 LIMITORQUE D D D EF BOTH EFPI0001 ESW PUMP 1A DISCH PRESS 3501 J-110 D D D EF BOTH EFPI0002 ESW PMP 1B DISCH PRESS 3501 J-110 D D D EF BOTH EFPT0001 ESW PMP 1A DISCH PRESS K105 J-301 D D D EF BOTH EFPT0002 ESW PMP 1B DISCH PRESS K104 J-301 D D D EF BOTH EFTE0061 ESW A TEMP TO POWER BLOCK 3101 J-558B D D D EF EFTE0062 ESW B TEMP TO POWER BLOCK 3101 J-558B D D D EF EFTI0061 ESW A TEMP TO POWER BLOCK 3501 J-110 D D D EF EFTI0062 ESW B TEMP TO POWER BLOCK 3501 J-110 D D D EF EGFI0128 CCW HX OUT TO RCP BY-PASS 3501 J-110 D D D EG BOTH EGFI0129 CCW HX OUT TO RCP BY-PASS 3501 J-110 D D D EG BOTH EGFT0107 CCW HX`S FLOW OUT TO RWB NONESSENTIAL COMP 1314 J-301 C D D EG BOTH 30 EGFT0108 CCW HX`S FLOW OUT TO RWB NONESSENTIAL COMP 1314 J-301 C D D EG BOTH 30 EGHS0070A LOCAL CONTROL STATION 1408 E-028B D D D EG COLD 33 EGHV0011 EMERGENCY MAKEUP WATER TRAIN A FROM ESW 1406 M-231B D D D EG BOTH EGHV0012 EMERGENCY MAKEUP WATER TRAIN B FROM ESW 1401 M-231B D D D EG BOTH 33 EGHV0013 EMERGENCY MAKEUP WATER TRAIN A FROM ESW 1406 M-231B D D D EG BOTH EGHV0014 EMERGENCY MAKEUP WATER TRAIN B FROM ESW 1401 M-231 D D D EG BOTH 33 EGHV0015 CCW COMMON HEADER RETURN ISO TRAIN A 1402 M-261 D D D EG COLD 33 EGHV0016 CCW COMMON HEADER RETURN ISO TRAIN B 1402 M-261 D D D EG COLD 33 EGHV0053 TRAIN A CCW TO COMMON HEADER 1402 M-261 D D D EG COLD 33 EGHV0054 TRAIN B CCW TO COMMON HEADER 1401 M-261 D D D EG COLD 33 EGHV0069A CCW SUPPLY WASTE HEADER ISO 1314 CORR.

J-605A D D D EG COLD 11 EGHV0069A-E01 VALVE TERMINAL BOX 1314 CORR.

E-028 D D D EG COLD EGHV0069B CCW RETURN WASTE HEADER ISO 1314 CORR.

J-605A D D D EG COLD 11 EGHV0069B-E01 VALVE TERMINAL BOX 1314 CORR.

E-028 D D D EG COLD EGHV0070A CCW SUPPLY WASTE HEADER ISO 1314 CORR.

J-605A D D D EG COLD 11 EGHV0070A-E01 VALVE TERMINAL BOX 1314 CORR.

E-028 D D D EG COLD EGHV0070B CCW RETURN WASTE HEADER ISO 1314 CORR.

J-605A D D D EG COLD 11 EGHV0070B-E01 VALVE TERMINAL BOX 1314 E-028 D D D EG COLD 30 EGHV0101 RHR A INLET CCW ISOLATION VALVE 1408 M-236 D D D EG COLD 33 EGHV0102 RHR B INLET CCW ISOLATION VALVE 1402 M-236 D D D EG COLD 33 EGHV0126 EGHV0071 BYPASS VALVE 1323 LIMITORQUE C D D EG BOTH EGHV0127 EGHV0058 BYPASS VALVE 1323 LIMITORQUE C D D EG BOTH 11 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 12 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes EGHV0130 EGHV0060 BYPASS VALVE 2000 LIMITORQUE C D C EG BOTH EGHV0131 EGHV0059 BYPASS VALVE 1323 LIMITORQUE C D D EG BOTH EGHV0132 EGHV0062 BYPASS VALVE 2000 LIMITORQUE C D C EG BOTH EGHV0133 EGHV0061 BYPASS VALVE 1323 LIMITORQUE C D D EG BOTH EGHY0069A EGHV0069A SOLENOID VALVE 1314 CORR.

J-605A D D D EG COLD EGHY0069B EGHV0069B SOLENOID VALVE 1314 CORR.

J-605A D D D EG COLD EGHY0070A EGHV0070A SOLENOID VALVE 1314 CORR.

J-605A D D D EG COLD EGHY0070B EGHV0070B SOLENOID VALVE 1314 J-605A D D D EG COLD 30 EGLI0001 CCW SURGE TK A LEVEL 3501 J-110 D D D EG BOTH EGLI0002 CCW SURGE TK B LEVEL 3501 J-110 D D D EG BOTH EGLT0001 CCW SURGE TK A LEVEL 1503 J-301 D D D EG BOTH 34 EGLT0002 CCW SURGE TK B LEVEL 1502 J-301 D D D EG BOTH 34 EGPT0077 CCW PMPS A&C DISCH PRESS 1406 J-301 D D D EG BOTH EGPT0078 CCW PMPS B&D DISCH PRESS 1401 J-301 D D D EG BOTH 33 EGTE0031 CCW HX A OUTLET TEMP 1406 J-558B D D D EG BOTH EGTE0032 CCW HX B OUTLET TEMP 1401 J-558B D D D EG BOTH 33 EGTI0031 CCW HX A OUTLET TEMP 3605 J-110 D D D EG BOTH EGTI0032 CCW HX B OUTLET TEMP 3605 J-110 D D D EG BOTH EGTT0031 CCW HX A OUTLET TEMP 3605 J-110 D D D EG BOTH EGTT0032 CCW HX B OUTLET TEMP 3605 J-110 D D D EG BOTH EGTV0029 CCW HX A BYPASS ISO 1406 J-605A D D D EG BOTH EGTV0029-E01 VALVE TERMINAL BOX 1406 E-028 D D D EG BOTH EGTV0030 CCW HX B BYPASS ISO 1401 J-605A D D D EG BOTH 33 EGTV0030-E01 VALVE TERMINAL BOX 1401 E-028 D D D EG BOTH 33 EGTY0029A EGTV0029 SOLENOID VALVE 1406 J-605A D D D EG BOTH EGTY0030A EGTV0030 SOLENOID VALVE 1401 J-605A D D D EG BOTH 33 EGZS0029 EGTV0029 LIMIT SWITCH 1406 J-605A D D D EG BOTH EGZS0030 EGTV0030 LIMIT SWITCH 1401 J-605A D D D EG BOTH 33 EGZS0069A EGHV0069A LIMIT SWITCH 1314 CORR.

J-605A D D D EG COLD EGZS0069B EGHV0069B LIMIT SWITCH 1314 CORR.

J-605A D D D EG COLD EGZS0070A EGHV0070A LIMIT SWITCH 1314 CORR.

J-605A D D D EG COLD EGZS0070B EGHV0070B LIMIT SWITCH 1314 J-605A D D D EG COLD 30 EJFIS0610 RHR PUMP A MIN. FLOW INDICATING SWITCH 1301 WEST ESE-40A D D D EJ COLD EJLI0007 CTMT RECIRC SUMP A LEV 3501 J-110 D D D EJ 25 EJLI0008 CTMT RECIRC SUMP B LEV 3501 J-110 D D D EJ 25 EJLR0006 CTMT RECIRC SUMP LEV 3501 J-110 D D D EJ 25 EMFI0917A CHARGING PUMP DISCHARGE FLOW 3501 ESE-14 D D D EM BOTH EMFI0917B CHARGING PUMP DISCHARGE FLOW 3501 ESE-14 D D D EM BOTH EMFS0917C CHARGING PUMP DISCHARGE MINI FLOW SWITCH 1126 ESE-40A C D D EM BOTH EMFS0917D CHARGING PUMP DISCHARGE MINI FLOW SWITCH 1126 ESE-40A C D D EM BOTH EMFT0917A CHARGING PUMP TO BIT FLOW TRANSMITTER 1126 ESE-4 C D D EM BOTH EMFT0917B CHARGING PUMP TO BIT FLOW TRANSMITTER 1126 ESE-4 C D D EM BOTH EMHS8843 LOCAL CONTROL STATION 1409 E-028 C D D EM BOTH EMHV8924 RHR TO CVCS AND SI PUMPS ISOL VALVE 1108 LIMITORQUE C C C EM 28 12 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 13 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes EMTE0011 DPEM01A INBOARD BEARING TEMPERATURE 1113 M-721 C D D EM 29 EMTE0012 DPEM01A OUTBOARD BEARING TEMPERATURE 1113 M-721 C D D EM 29 EMTE0014 DPEM01B INBOARD BEARING TEMPERATURE 1108 M-721 C D D EM 28 EMTE0015 DPEM01B OUTBOARD BEARING TEMPERATURE 1108 M-721 C D D EM 28 ENLI0017 SPRAY ADD TANK LEVEL 3501 J-110 D D D EN ENLI0019 SPRAY ADD TANK LEVEL 3501 J-110 D D D EN ENZS0097 SPRAY ADDITIVE TANK DISC VALVE POSITION 1315 M-221 C D D EN 30 EPHV8808B ACCUMULATOR TANK B ISOLATION VALVE 2000 LIMITORQUE C D C EP COLD EPHV8808C ACCUMULATOR TANK C ISOLATION VALVE 2000 LIMITORQUE C D C EP COLD EPZS8808BB ACCUMULATOR TANK B ISOLATION VALVE LIMIT SWITCH 2000 HE-3 C D C EP COLD EPZS8808BB-E01 ACCUMULATOR TANK B ISOL VLV LS CONNECTOR 2000 HE-8 C D C EP COLD EPZS8808BB-E02 VALVE TERMINAL BOX 2000 E-028 C D C EP COLD EPZS8808CB ACCUMULATOR TANK C ISOLATION VALVE LIMIT SWITCH 2000 HE-3 C D C EP COLD EPZS8808CB-E01 ACCUMULATOR TANK C ISOL VLV LS CONNECTOR 2000 HE-8 C D C EP COLD EPZS8808CB-E02 VALVE TERMINAL BOX 2000 E-028 C D C EP COLD FC219 AFP TURBINE GAUGE AND CONTROL PANEL 1331 M-021 D C D FC BOTH FCFV0310-E01 VALVE TERMINAL BOX 1207 E-028 C D D FC 32 FCFV0313 TURBINE SPEED-GOVERNING VALVE 1331 M-021 D C D FC BOTH FCFY0310 FCFV0310 SOLENOID VALVE 1207 J-601 C D D FC 32 FCHIK0313A AUX FP TURB SPEED CTRL 3501 J-110 D D D FC BOTH FCHIK0313B AUX FDWTR PMP SPEED GOVERNOR 1413 J-110 D D D FC BOTH FCHV0312 TURBINE MANUAL TRIP AND THROTTLE VALVE 1331 M-021 D C D FC BOTH FCZS0310 FCFV0310 LIMIT SWITCH 1207 J-601 C D D FC 32 FEF01A TRAVELING WATER SCREEN A K105 M-020 D D D EF BOTH FEF01B TRAVELING WATER SCREEN B K104 M-020 D D D EF BOTH FEF02A SELF-CLEANING STRAINER A K105 M-154 D D D EF BOTH FEF02B SELF-CLEANING STRAINER B K104 M-154 D D D EF BOTH FGG02A FILTER-ABSORBER UNIT 6304 M-621 D D D GG FGG02B FILTER-ABSORBER UNIT 6303 M-621 D D D GG FGK01A FILTER ADSORBER UNIT 1512 M-621 D D D GK FGK01B FILTER ADSORBER UNIT 1501 M-621 D D D GK FGK02A CR PRESS FILTER ADSORBER UNIT 3416 M-621 D D D GK FGK02B CR PRESS FILTER ADSORBER UNIT 3415 M-621 D D D GK GDHIS0001B LOCAL CONTROL STATION K105 E-028 D D D GD GDHIS0011B LOCAL CONTROL STATION K104 E-028 D D D GD GDHS0011 LOCAL CONTROL STATION 3302 E-028 D D D GD GDHS0011A LOCAL CONTROL STATION 3302 E-028B D D D GD GDTE0001 ESW PMP RM TEMP 1A DAMPER K105 J-558B D D D GD BOTH GDTE0011 ESW PMP RM TEMP 1B DAMPER K104 J-558B D D D GD BOTH GDTT0001 ESW PMP RM TEMP 1A DAMPER 3605 J-110 D D D GD BOTH GDTT0011 ESW PMP RM TEMP 1B DAMPER 3605 J-110 D D D GD BOTH GDTZ0001A FLOW CONTROL DAMPER ACTUATOR - GDD0002 - ELC/HYD K105 M-627A D D D GD BOTH GDTZ0001B FLOW CONTROL DAMPER ACTUATOR - GDD0004 - ELC/HYD K105 M-627A D D D GD BOTH GDTZ0001C FLOW CONTROL DAMPER ACTUATOR - GDD0012 - ELC/HYD K105 M-627A D D D GD BOTH GDTZ0011A FLOW CONTROL DAMPER ACTUATOR - GDD0009 - ELC/HYD K104 M-627A D D D GD BOTH GDTZ0011B FLOW CONTROL DAMPER ACTUATOR - GDD0011 - ELC/HYD K104 M-627A D D D GD BOTH 13 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 14 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes GDTZ0011C FLOW CONTROL DAMPER ACTUATOR - GDD0013 - ELC/HYD K104 M-627A D D D GD BOTH GEHZ0103 AUX BLDG ISO DAMPER ACTUATOR - GED0045 - ELEC 1504 M-627A D D D GE 34 GEHZ0104 AUX BLDG ISO DAMPER ACTUATOR - GED0044 - ELEC 1504 M-627A D D D GE 34 GFHIS0015 LOCAL CONTROL STATION 1326 E-028 D D D GF GFHIS0016 LOCAL CONTROL STATION 1325 E-028 D D D GF GFHZ0022 AUX BLDG ISO DAMPER ACTUATOR - GFD0024 - ELEC 1504 M-627A D D D GF 34 GFHZ0023 AUX BLDG ISO DAMPER ACTUATOR - GFD0025 - ELEC 1504 M-627A D D D GF 34 GFHZ0032A AUX BLDG ISO DAMPER ACTUATOR - GFD0068 - ELEC 1305 M-627A D D D GF GFHZ0032B AUX BLDG ISO DAMPER ACTUATOR - GFD0060 - ELEC 1328 M-627A D D D GF GFHZ0033A AUX BLDG ISO DAMPER ACTUATOR - GFD0069 - ELEC 1305 M-627A D D D GF GFHZ0033B AUX BLDG ISO DAMPER ACTUATOR - GFD0061 - ELEC 1328 M-627A D D D GF GGHIS0015B LOCAL CONTROL STATION 6304 E-028 D D D GG GGHIS0021B LOCAL CONTROL STATION 6303 E-028 D D D GG GGHIS0036B LOCAL CONTROL STATION 6203 E-028 D D D GG GGHIS0037B LOCAL CONTROL STATION 6203 E-028 D D D GG GGHS0050 LOCAL CONTROL STATION 6301 E-028 D D D GG 36 GGHS0051 LOCAL CONTROL STATION 6301 E-028 D D D GG 36 GGHZ0040 FUEL BLDG ISO DAMPER ACTUATOR - GGD0025 - ELEC 6304 M-627A D D D GG GGHZ0041 AUX BLDG ISO DAMPER ACTUATOR - GGD0026 - ELEC 6304 M-627A D D D GG GGHZ0042 AUX BLDG ISO DAMPER ACTUATOR - GGD0032 - ELEC 6304 M-627A D D D GG GGHZ0043 FUEL BLDG ISO DAMPER ACTUATOR - GGD0018 - ELEC 6303 M-627A D D D GG GGHZ0044 AUX BLDG ISO DAMPER ACTUATOR - GGD0019 - ELEC 6303 M-627A D D D GG GGHZ0056 FUEL BLDG ISO DAMPER ACTUATOR - GGD0042 - ELEC 6304 M-627A D D D GG GGHZ0057 FUEL BLDG ISO DAMPER ACTUATOR - GGD0043 - ELEC 6303 M-627A D D D GG GGPDT0019 EMERGENCY FILTER ADSORBER UNIT A HEPA 6304 M-621 D D D GG GGRE0027 FUEL BLDG EXHAUST RAD MONIT 6301 J-361 D D D GG 36 GGRE0028 FUEL BLDG EXHAUST RAD MONIT 6301 J-361 D D D GG 36 GGRT0027 GGRE0027 TRANSMITTER 6304 J-361 D D D GG GGRT0028 GGRE0028 TRANSMITTER 6304 J-361 D D D GG GGRV0027A SFP RAD MONIT INTAKE 6301 J-603A D D D GG 36 GGRV0027B SFP RAD MONIT RETURN 6301 J-603A D D D GG 36 GGRV0027C SPENT FUEL POOL RAD CNTRL VLV 6301 J-603A D D D GG 36 GGRV0027D SPENT FUEL POOL RAD CNTRL VLV 6301 J-603A D D D GG 36 GGRV0028A SFP RAD MONIT INTAKE 6301 J-603A D D D GG 36 GGRV0028B SFP RAD MONIT RETURN 6301 J-603A D D D GG 36 GGRV0028C SPENT FUEL POOL RAD CONT VLV 6301 J-603A D D D GG 36 GGRV0028D SPENT FUEL POOL RAD CONT VLV 6304 J-603A D D D GG GGRZ0036 FUEL BLDG ISO DAMPER ACTUATOR - GGD0003 - ELEC 6203 M-627A D D D GG GGRZ0037 FUEL BLDG ISO DAMPER ACTUATOR - GGD0004 - ELEC 6203 M-627A D D D GG GGTE0016 FGG02A TEMPERATURE 6304 M-621 D D D GG GGTE0022 FGG02B TEMPERATURE 6303 M-621 D D D GG GGTT0016 GGTE0016 TRANSMITTER 6304 M-621 D D D GG GGTT0022 GGTE0022 TRANSMITTER 6303 M-621 D D D GG GK195A SGK05A CONTROL PANEL 3416 M-622.1A D D D GK BOTH GK195B SGK05A POWER PANEL 3416 M-622.1A D D D GK BOTH GK195C SGK05A POWER AND CONTROL PANEL 3416 M-622.1A D D D GK BOTH 14 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 15 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes GK196A SGK05B CONTROL PANEL 3415 M-622.1A D D D GK BOTH GK196B SGK05B POWER PANEL 3415 M-622.1A D D D GK BOTH GK196C SGK05B POWER AND CONTROL PANEL 3415 M-622.1A D D D GK BOTH GK198A SGK04A CONTROL PANEL 1512 M-622.1A D D D GK BOTH GK198B SGK04A POWER PANEL 1512 M-622.1A D D D GK BOTH GK198C SGK04A POWER AND CONTROL PANEL 1512 M-622.1A D D D GK BOTH GK199A SGK04B CONTROL PANEL 1501 M-622.1A D D D GK BOTH GK199B SGK04B POWER PANEL 1501 M-622.1A D D D GK BOTH GK199C SGK04B POWER AND CONTROL PANEL 1501 M-622.1A D D D GK BOTH GKAE0002 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 1513 J-375A D D D GK 34 GKAE0003 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 1513 J-375A D D D GK 34 GKAI0002 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 3501 J-110 D D D GK GKAI0003 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 3501 J-110 D D D GK GKAT0002 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 1513 J-375A D D D GK 34 GKAT0003 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 1513 J-375A D D D GK 34 GKHS0040 LOCAL CONTROL STATION 1501 E-028 D D D GK GKHS0103 LOCAL CONTROL STATION 1501 E-028 D D D GK GKHY0013A GKHZ0013A SOLENOID VALVE 1501 M-627A D D D GK GKHY0013B GKHZ0013B SOLENOID VALVE 1512 M-627A D D D GK GKHY0013C GKHZ0013C SOLENOID VALVE 1512 M-627A D D D GK GKHY0013D GKHZ0013D SOLENOID VALVE 1513 M-627A D D D GK 34 GKHY0013E GKHZ0013E SOLENOID VALVE 1512 M-627A D D D GK GKHY0013F GKHZ0013F SOLENOID VALVE 1512 M-627A D D D GK GKHY0013G GKHZ0013G SOLENOID VALVE 1512 M-627A D D D GK GKHY0013H GKHZ0013H SOLENOID VALVE 1512 M-627A D D D GK GKHY0055A GKHZ0055A SOLENOID VALVE 3801 M-627A D D D GK GKHY0055B GKHZ0055B SOLENOID VALVE 3801 M-627A D D D GK GKHY0057A GKHZ0057A SOLENOID VALVE 3609 M-627A D D D GK GKHY0057B GKHZ0057B SOLENOID VALVE 3609 M-627A D D D GK GKHY0059A GKHZ0059A SOLENOID VALVE 3501 M-627A D D D GK GKHY0059B GKHZ0059B SOLENOID VALVE 3501 M-627A D D D GK GKHY0098A GKHZ0098A SOLENOID VALVE 3411 M-627A D D D GK GKHY0098B GKHZ0098B SOLENOID VALVE 3412 M-627A D D D GK 35 GKHY0122A GKHZ0122A SOLENOID VALVE 3302 M-627A D D D GK GKHY0122B GKHZ0122B SOLENOID VALVE 3302 M-627A D D D GK GKHY0123A GKHZ0123A SOLENOID VALVE 3211 M-627A D D D GK GKHY0123B GKHZ0123B SOLENOID VALVE 3218 M-627A D D D GK GKHY0123C GKHZ0123C SOLENOID VALVE 3218 M-627A D D D GK GKHY0184A GKHZ0184A SOLENOID VALVE 1501 M-627A D D D GK GKHY0184B GKHZ0184B SOLENOID VALVE 1512 M-627A D D D GK GKHY0184C GKHZ0184C SOLENOID VALVE 1513 M-627A D D D GK 34 GKHY0184D GKHZ0184D SOLENOID VALVE 1513 M-627A D D D GK 34 GKHZ0013A CTRL BLDG ISO DAMPER ACTUATOR - GKD0002 - PNEU 1501 M-627A D D D GK GKHZ0013B CTRL BLDG ISO DAMPER ACTUATOR - GKD0018 - PNEU 1512 M-627A D D D GK GKHZ0013C CTRL BLDG ISO DAMPER ACTUATOR - GKD0025 - PNEU 1512 M-627A D D D GK GKHZ0013D CTRL BLDG ISO DAMPER ACTUATOR - GKD0279 - PNEU 1513 M-627A D D D GK 34 15 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 16 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes GKHZ0013E CTRL BLDG ISO DAMPER ACTUATOR - GKD0283 - PNEU 1512 M-627A D D D GK GKHZ0013F CTRL BLDG ISO DAMPER ACTUATOR - GKD0309 - PNEU 1512 M-627A D D D GK GKHZ0013G CTRL BLDG ISO DAMPER ACTUATOR - GKD0311 - PNEU 1512 M-627A D D D GK GKHZ0013H CTRL BLDG ISO DAMPER ACTUATOR - GKD0313 - PNEU 1512 M-627A D D D GK GKHZ0019A CR FILT SYS ISO DAMPER ACTUATOR - GKD0082 - ELEC 1512 M-627A D D D GK GKHZ0019B CR FILT SYS ISO DAMPER ACTUATOR - GKD0083 - ELEC 1512 M-627A D D D GK GKHZ0019C A/C SYS ISO DAMPER ACTUATOR - GKD0286 - ELEC 1512 M-627A D D D GK GKHZ0019D A/C SYS ISO DAMPER ACTUATOR - GKD0285 - ELEC 1512 M-627A D D D GK GKHZ0029A A/C SYS ISO DAMPER ACTUATOR - GKD0080 - ELEC 1512 M-627A D D D GK BOTH GKHZ0029B A/C SYS ISO DAMPER ACTUATOR - GKD0081 - ELEC 1512 M-627A D D D GK BOTH GKHZ0030A CR FILT SYS ISO DAMPER ACTUATOR - GKD0086 - ELEC 1501 M-627A D D D GK GKHZ0030B CR FILT SYS ISO DAMPER ACTUATOR - GKD0087 - ELEC 1501 M-627A D D D GK GKHZ0030C A/C SYS ISO DAMPER ACTUATOR - GKD0319 - ELEC 1501 M-627A D D D GK GKHZ0030D A/C SYS ISO DAMPER ACTUATOR - GKD0318 - ELEC 1501 M-627A D D D GK GKHZ0040A A/C UNIT ISO DAMPER ACTUATOR - GKD0084 - ELEC 1501 M-627A D D D GK BOTH GKHZ0040B CTRL ROOM ISO DAMPER ACTUATOR - GKD0085 - ELEC 1501 M-627A D D D GK BOTH GKHZ0055A CSR ISO DAMPER ACTUATOR - GKD0004 - PNEU 3801 M-627A D D D GK GKHZ0055B CSR ISO DAMPER ACTUATOR - GKD0016 - PNEU 3801 M-627A D D D GK GKHZ0057A CTRL BLDG ISO DAMPER ACTUATOR - GKD0005 - PNEU 3609 M-627A D D D GK GKHZ0057B CTRL BLDG ISO DAMPER ACTUATOR - GKD0015 - PNEU 3609 M-627A D D D GK GKHZ0059A CSR ISO DAMPER ACTUATOR - GKD0006 - PNEU 3501 M-627A D D D GK GKHZ0059B CSR ISO DAMPER ACTUATOR - GKD0014 - PNEU 3501 M-627A D D D GK GKHZ0075A PRESS SYS ISO DAMPER ACTUATOR - GKD0105 - ELEC 3416 M-627A D D D GK GKHZ0075B PRESS SYS ISO DAMPER ACTUATOR - GKD0317 - ELEC 3416 M-627A D D D GK GKHZ0075C CTRL BLDG ISO DAMPER ACTUATOR - GKD0323 - ELEC 3301 M-627A D D D GK GKHZ0083A PRESS SYS ISO DAMPER ACTUATOR - GKD0088 - ELEC 3415 M-627A D D D GK GKHZ0083B PRESS SYS ISO DAMPER ACTUATOR - GKD0292 - ELEC 3415 M-627A D D D GK GKHZ0083C CTRL BLDG ISO DAMPER ACTUATOR - GKD0320 - ELEC 3302 M-627A D D D GK GKHZ0098A SWGR ROOM ISO DAMPER ACTUATOR - GKD0007 - PNEU 3411 M-627A D D D GK GKHZ0098B BATTERY RM ISO DAMPER ACTUATOR - GKD0013 - PNEU 3412 M-627A D D D GK 35 GKHZ0122A ESF SWGR RM ISO DAMPER ACTUATOR - GKD0008 - PNEU 3302 M-627A D D D GK GKHZ0122B ESF SWGR RM ISO DAMPER ACTUATOR - GKD0012 - PNEU 3302 M-627A D D D GK GKHZ0123A ACCESS CTRL ISO DAMPER ACTUATOR - GKD0009 - PNEU 3211 M-627A D D D GK GKHZ0123B ACCESS CTRL ISO DAMPER ACTUATOR - GKD0219 - PNEU 3218 M-627A D D D GK GKHZ0123C ACCESS CTRL ISO DAMPER ACTUATOR - GKD0220 - PNEU 3218 M-627A D D D GK GKHZ0152 CTRL BLDG ISO DAMPER ACTUATOR - GKD0130 - ELEC 1513 M-627A D D D GK 34 GKHZ0153 CTRL BLDG ISO DAMPER ACTUATOR - GKD0131 - ELEC 1513 M-627A D D D GK 34 GKHZ0154 ACCESS CTRL ISO DAMPER ACTUATOR - GKD0132 - ELEC 1504 M-627A D D D GK 34 GKHZ0155 ACCESS CTRL ISO DAMPER ACTUATOR - GKD0133 - ELEC 1504 M-627A D D D GK 34 GKHZ0160 CR PRESS SYS ISO DAMPER ACTUATOR - GKD0179 - ELC 1512 M-627A D D D GK GKHZ0161 CR PRESS SYS ISO DAMPER ACTUATOR - GKD0181 - ELC 1512 M-627A D D D GK GKHZ0172A CTRL BLDG ISO DAMPER ACTUATOR - GKD0198 - ELEC 3101 M-627A D D D GK GKHZ0172B CTRL BLDG ISO DAMPER ACTUATOR - GKD0203 - ELEC 3101 M-627A D D D GK GKHZ0173A CTRL BLDG ISO DAMPER ACTUATOR - GKD0199 - ELEC 3101 M-627A D D D GK GKHZ0173B CTRL BLDG ISO DAMPER ACTUATOR - GKD0202 - ELEC 3101 M-627A D D D GK GKHZ0174A CTRL BLDG ISO DAMPER ACTUATOR - GKD0212 - ELEC 3224 M-627A D D D GK 16 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 17 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes GKHZ0174B CTRL BLDG ISO DAMPER ACTUATOR - GKD0209 - ELEC 3222 M-627A D D D GK GKHZ0175A CTRL BLDG ISO DAMPER ACTUATOR - GKD0213 - ELEC 3224 M-627A D D D GK GKHZ0175B CTRL BLDG ISO DAMPER ACTUATOR - GKD0208 - ELEC 3222 M-627A D D D GK GKHZ0184A CTRL BLDG ISO DAMPER ACTUATOR - GKD0300 - PNEU 1501 M-627A D D D GK GKHZ0184B CTRL BLDG ISO DAMPER ACTUATOR - GKD0301 - PNEU 1512 M-627A D D D GK GKHZ0184C CTRL BLDG ISO DAMPER ACTUATOR - GKD0310 - PNEU 1513 M-627A D D D GK 34 GKHZ0184D CTRL BLDG ISO DAMPER ACTUATOR - GKD0312 - PNEU 1513 M-627A D D D GK 34 GKME0076 MOISTURE SENSOR ELEMENT (DISABLED) 3416 M-621 D D D GK GKME0084 MOISTURE SENSOR ELEMENT (DISABLED) 3415 M-621 D D D GK GKMT0076 FGK02A MOISTURE TRANS. (DISABLED) 3416 M-621 D D D GK GKMT0076A FGK02A MOISTURE TRANS. (DISABLED) 3416 M-621 D D D GK GKMT0084 FGK02B MOISTURE TRANS. (DISABLED) 3415 M-621 D D D GK GKMT0084A FGK02B MOISTURE TRANS. (DISABLED) 3415 M-621 D D D GK GKRE0004 CTRL BLDG SUP AIR RAD MONIT 1513 J-361 D D D GK 34 GKRE0005 CTRL BLDG SUP AIR RAD MONIT 1513 J-361 D D D GK 34 GKRT0004 GKRE0004 TRANSMITTER 1513 J-361 D D D GK 34 GKRT0005 GKRE0005 TRANSMITTER 1513 J-361 D D D GK 34 GLHIS0002 LOCAL CONTROL STATION 1406 E-028 D D D GL GLHIS0023 LOCAL CONTROL STATION 1401 E-028 D D D GL 33 GLHZ0032-1 AUX BLDG ISO DAMPER ACTUATOR - GLD0052 - ELEC 1504 M-627A D D D GL 34 GLHZ0032-2 AUX BLDG ISO DAMPER ACTUATOR - GLD0052 - ELEC 1504 M-627A D D D GL 34 GLHZ0033-1 AUX BLDG ISO DAMPER ACTUATOR - GLD0053 - ELEC 1504 M-627A D D D GL 34 GLHZ0033-2 AUX BLDG ISO DAMPER ACTUATOR - GLD0053 - ELEC 1504 M-627A D D D GL 34 GLHZ0073 AUX BLDG ISO DAMPER ACTUATOR - GLD0036 - ELEC 1102 M-627A D C D GL 27 GLHZ0074 AUX BLDG ISO DAMPER ACTUATOR - GLD0037 - ELEC 1102 M-627A D C D GL 27 GLHZ0075 AUX BLDG ISO DAMPER ACTUATOR - GLD0038 - ELEC 1102 M-627A D C D GL 27 GLHZ0076 AUX BLDG ISO DAMPER ACTUATOR - GLD0039 - ELEC 1102 M-627A D C D GL 27 GLHZ0080 AUX BLDG ISO DAMPER ACTUATOR - GLD0157 - ELEC 1406 M-627A D D D GL BOTH GLHZ0081 AUX BLDG ISO DAMPER ACTUATOR - GLD0156 - ELEC 1406 M-627A D D D GL BOTH GMHS0011B LOCAL CONTROL STATION 5201 E-028 D D D GM GMHS0019B LOCAL CONTROL STATION 5201 E-028 D D D GM GMHY0009 GMHZ0009 SOLENOID VALVE 5203 M-627A D D D GM GMHY0019 GMHZ0019 SOLENOID VALVE 5201 M-627A D D D GM GMHZ0009 D.G. ROOM ISO DAMPER ACTUATOR - GMD0005 - PNEU 5203 M-627A D D D GM GMHZ0019 D.G. ROOM ISO DAMPER ACTUATOR - GMD0010 - PNEU 5201 M-627A D D D GM GMTE0001 DIESEL GEN VENT SUPPLY FAN 1A 5203 J-558B D D D GM GMTE0011 DIESEL GEN VENT SUPPLY FAN 1B 5201 J-558B D D D GM GMTT0001 DIESEL GEN VENT SUPPLY FAN 1A 3605 J-110 D D D GM GMTT0011 DIESEL GEN VENT SUPPLY FAN 1B 3605 J-110 D D D GM GMTZ0001A FLOW CTRL DAMPER ACTUATOR - GMD0002 - ELEC/HYD 5203 M-627A D D D GM GMTZ0001B FLOW CTRL DAMPER ACTUATOR - GMD0003 - ELEC/HYD 5203 M-627A D D D GM GMTZ0011A FLOW CTRL DAMPER ACTUATOR - GMD0007 - ELEC/HYD 5201 M-627A D D D GM GMTZ0011B FLOW CTRL DAMPER ACTUATOR - GMD0008 - ELEC/HYD 5201 M-627A D D D GM GNPI0934 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN GNPI0935 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN GNPI0936 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN 17 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 18 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes GNPI0937 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN GNPI0938 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN HOT 25 GNPI0939 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN HOT 25 GNTI0060 CTMT ATMOS TEMP 3501 J-110 D D D GN BOTH GNTI0061 CTMT ATMOS TEMP 3501 J-110 D D D GN BOTH GNTI0062 CTMT ATMOS TEMP 3501 J-110 D D D GN BOTH GNTI0063 CTMT ATMOS TEMP 3501 J-110 D D D GN BOTH GNTR0063 CTMT ATMOS TEMP 3501 J-110 D D D GN BOTH GNTT0060 CTMT COOLER A TEMP 3605 J-110 D D D GN BOTH GNTT0061 CTMT COOLER B TEMP 3605 J-110 D D D GN BOTH GNTT0062 CTMT COOLER C TEMP 3605 J-110 D D D GN BOTH GNTT0063 CTMT COOLER D TEMP 3605 J-110 D D D GN BOTH GS001A RECOMBINER POWER PANEL 3301 M-637 D D D GS GS001B RECOMBINER POWER PANEL 3302 M-637 D D D GS GS065A H2 ANALYZER CONTROL PANEL 3605 J-359 D D D GS GS065AA RECOMBINER CONTROL PANEL 3605 M-637 D D D GS GS065B H2 ANALYZER CONTROL PANEL 3605 J-359 D D D GS GS065BA RECOMBINER CONTROL PANEL 3605 M-637 D D D GS GSAI0010 HYDROGEN ANALYZER 2B 3501 J-110 D D D GS GSAI0019 HYDROGEN ANALYZER 2A 3501 J-110 D D D GS GSAR0010 HYDROGEN ANALYZER 3501 J-110 D D D GS GSAT0010 HYDROGEN ANALYZER 2B ANALYSIS TRANSMITTER 3605 J-359 D D D GS GSAT0019 HYDROGEN ANALYZER 2A ANALYSIS TRANSMITTER 3605 J-359 D D D GS GTHZ0028 AUX BLDG ISO DAMPER ACTUATOR - GTD0011 - ELEC 1504 M-627A D D D GT 34 GTHZ0029 AUX BLDG ISO DAMPER ACTUATOR - GTD0012 - ELEC 1504 M-627A D D D GT 34 GTRE0022 CTMT PURGE EXHAUST RAD MONIT 1507 J-361 C D D GT 34 GTRE0031 CTMT ATMOSPHERE RAD MONIT 1507 J-361 C D D GT 34 GTRE0032 CTMT ATMOSPHERE RAD MONIT 1506 J-361 C D D GT 34 GTRE0033 CTMT PURGE EXH RAD MONIT 1507 J-361 C D D GT 34 GTRIC0059 CTMT HRRM CONTROL/DISPLAY MODULE 3501 J-361A D D D GT GTRIC0060 CTMT HRRM CONTROL/DISPLAY MODULE 3501 J-361A D D D GT GTRR0060 CTMT HIGH RANGE AREA RADN RECORDER 3501 J-110 D D D GT 25 GTRT0022 GTRE0022 TRANSMITTER 1507 J-361 C D D GT 34 GTRT0031 GTRE0031 TRANSMITTER 1507 J-361 C D D GT 34 GTRT0032 GTRE0032 TRANSMITTER 1506 J-361 C D D GT 34 GTRT0033 GTRE0033 TRANSMITTER 1507 J-361 C D D GT 34 GTRT0059 CTMT HIGH RANGE AREA RADN MON 1512 J-361A D D D GT 25 GTRT0060 CTMT HIGH RANGE AREA RADN MON 1501 J-361A D D D GT 25 GTRV0022A CTMT PURGE EXHAUST 1507 J-603A C D D GT 34 GTRV0022B CTMT PURGE EXHAUST 1504 J-603A D D D GT 34 GTRV0033A CTMT PURGE EXHAUST 1507 J-603A C D D GT 34 GTRV0033B CTMT PURGE EXHAUST 1504 J-603A D D D GT 34 JELI0012A EMER FUEL OIL DAY TK A LEV 3501 J-110 D D D JE BOTH JELI0012B EMER FUEL OIL DAY TK A LEV 5203 J-110 D D D JE BOTH JELI0032A EMER FUEL OIL DAY TK B LEV 3501 J-110 D D D JE BOTH JELI0032B EMER FUEL OIL DAY TK B LEV 5201 J-110 D D D JE BOTH 18 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 19 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes JELT0001 EMER FUEL OIL DAY TK A LEV 5203 J-301 D D D JE BOTH JELT0012 EMER FUEL OIL DAY TK A LEV 5203 J-301 D D D JE BOTH JELT0021 EMER FUEL OIL DAY TK B LEV 5201 J-301 D D D JE BOTH JELT0032 EMER FUEL OIL DAY TK B LEV 5201 J-301 D D D JE BOTH KFC02 AUX FEED PUMP TURBINE 1331 M-021 D D C FC BOTH KJ121 DIESEL GAUGE AND CONTROL PANEL 5203 M-018 D D D KJ BOTH KJ122 DIESEL GAUGE AND CONTROL PANEL 5201 M-018 D D D KJ BOTH KJHS0110 CONTROL ROOM FIRE ISO SWITCH 5201 M-018 D D D KJ KJLI0031 L.O. LEVEL CONTROL TANK INDICATOR 5203 M-018 D D D KJ BOTH KJLI0038 L.O. AUX. TANK LEVEL INDICATOR 5203 M-018 D D D KJ BOTH KJLI0131 L.O. LEVEL CONTROL TANK INDICATOR 5201 M-018 D D D KJ BOTH KJLI0138 L.O. AUX. TANK LEVEL INDICATOR 5201 M-018 D D D KJ BOTH KJPS0062 JACKET WATER BACKUP TO ELECT SPEED SWITCH 5203 M-018 D D D KJ BOTH KJPS0162 JACKET WATER BACKUP TO ELECT SPEED SWITCH 5201 M-018 D D D KJ BOTH KJPSH0023A HIGH CRANKCASE PRESSURE 5203 M-018 D D D KJ BOTH KJPSH0023B HIGH CRANKCASE PRESSURE 5203 M-018 D D D KJ BOTH KJPSH0023C HIGH CRANKCASE PRESSURE 5203 M-018 D D D KJ BOTH KJPSH0023D HIGH CRANKCASE PRESSURE 5203 M-018 D D D KJ BOTH KJPSH0123A HIGH CRANKCASE PRESS 5201 M-018 D D D KJ BOTH KJPSH0123B HIGH CRANKCASE PRESS 5201 M-018 D D D KJ BOTH KJPSH0123C HIGH CRANKCASE PRESS 5201 M-018 D D D KJ BOTH KJPSH0123D HIGH CRANKCASE PRESS 5201 M-018 D D D KJ BOTH KJPSHL0002A AIR COMPR. A START/STOP PRESS. SWITCH 5203 M-018 D D D KJ BOTH KJPSHL0002B AIR COMPR. B START/STOP PRESS. SWITCH 5203 M-018 D D D KJ BOTH KJPSHL0102A AIR COMPR. A START/STOP PRESS. SWITCH 5201 M-018 D D D KJ BOTH KJPSHL0102B AIR COMPR. B START/STOP PRESS. SWITCH 5201 M-018 D D D KJ BOTH KJPSL0026A LOW LUBE OIL PRESS 5203 M-018 D D D KJ BOTH KJPSL0026B LOW LUBE OIL PRESS 5203 M-018 D D D KJ BOTH KJPSL0026C LOW LUBE OIL PRESS 5203 M-018 D D D KJ BOTH KJPSL0026D LOW LUBE OIL PRESS 5203 M-018 D D D KJ BOTH KJPSL0126A LOW LUBE OIL PRESS 5201 M-018 D D D KJ BOTH KJPSL0126B LOW LUBE OIL PRESS 5201 M-018 D D D KJ BOTH KJPSL0126C LOW LUBE OIL PRESS 5201 M-018 D D D KJ BOTH KJPSL0126D LOW LUBE OIL PRESS 5201 M-018 D D D KJ BOTH KJPV0001A AIR START SOL VLV 1 5203 M-018 D D D KJ BOTH KJPV0001B AIR START SOL VLV 2 5203 M-018 D D D KJ BOTH KJPV0008 SHUTDOWN AIR SOL VLV 5203 M-018 D D D KJ BOTH KJPV0101A AIR START SOL VLV 1 5201 M-018 D D D KJ BOTH KJPV0101B AIR START SOL VLV 2 5201 M-018 D D D KJ BOTH KJPV0108 SHUTDOWN AIR SOL VLV 5201 M-018 D D D KJ BOTH KJTCV0034 LUBE OIL COOLER TEMP CTRL VLV 5203 M-018 D D D KJ BOTH KJTCV0056 INTERCOOLER HEAT EXCHANGER TEMP CTRL VLV 5203 M-018 D D D KJ BOTH KJTCV0060 JACKET WATER HEAT EXCHANGER TEMP CTRL VLV 5203 M-018 D D D KJ BOTH KJTCV0134 LUBE OIL COOLER TEMP CTRL VLV 5201 M-018 D D D KJ BOTH KJTCV0156 INTERCOOLER HEAT EXCHANGER TEMP CTRL VLV 5201 M-018 D D D KJ BOTH KJTCV0160 JACKET WATER HEAT EXCHANGER TEMP CTRL VLV 5201 M-018 D D D KJ BOTH 19 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 20 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes KJTSH0059A HIGH JACKET WATER TEMP 5203 M-018 D D D KJ BOTH KJTSH0059B HIGH JACKET WATER TEMP 5203 M-018 D D D KJ BOTH KJTSH0059C HIGH JACKET WATER TEMP 5203 M-018 D D D KJ BOTH KJTSH0059D HIGH JACKET WATER TEMP 5203 M-018 D D D KJ BOTH KJTSH0159A HIGH JACKET WATER TEMP 5201 M-018 D D D KJ BOTH KJTSH0159B HIGH JACKET WATER TEMP 5201 M-018 D D D KJ BOTH KJTSH0159C HIGH JACKET WATER TEMP 5201 M-018 D D D KJ BOTH KJTSH0159D HIGH JACKET WATER TEMP 5201 M-018 D D D KJ BOTH LELE0105 DIESEL GEN BLDG SUMP 5203 J-481 D D D LE BOTH LELE0106 DIESEL GEN BLDG SUMP 5201 J-481 D D D LE BOTH LELI0105 DIESEL GEN BLDG SUMP 3501 J-200 D D D LE BOTH LELI0106 DIESEL GEN BLDG SUMP 3501 J-200 D D D LE BOTH LELIT0105 DIESEL GEN BLDG SUMP 3605 J-481 D D D LE BOTH LELIT0106 DIESEL GEN BLDG SUMP 3605 J-481 D D D LE BOTH LFLE0124 CONTROL BLDG FL EQUIP DRAIN 3101 J-481 D D D LF LFLE0125 CONTROL BLDG FL EQUIP DRAIN 3101 J-481 D D D LF LFLI0009 CTMT NORMAL SUMP B LEVEL 3501 J-110 D D D LF 25 LFLI0010 CTMT NORMAL SUMP A LEVEL 3501 J-110 D D D LF 25 LFLI0101 RHR PMP ROOM SUMP LEVEL 3501 J-110 D D D LF COLD LFLI0102 RHR PMP ROOM SUMP LEVEL 3501 J-110 D D D LF COLD LFLI0103 AUX BLDG SUMP LEVEL 3501 J-110 D D D LF LFLI0104 AUX BLDG SUMP LEVEL 3501 J-110 D D D LF LFLI0124 CONTROL BLDG FL EQUIP DRAIN 3501 J-200 D D D LF LFLI0125 CONTROL BLDG FL EQUIP DRAIN 3501 J-200 D D D LF LFLIT0009 CTMT NORMAL SUMP 3605 J-481 D D D LF 25 LFLIT0010 CTMT NORMAL SUMP 3605 J-481 D D D LF 25 LFLIT0101 RHR PMP ROOM LEAKAGE LEVEL 3605 J-481 D D D LF COLD LFLIT0102 RHR PMP ROOM LEAKAGE LEVEL 3605 J-481 D D D LF COLD LFLIT0103 AUX BLDG LEAKAGE LEVEL 3605 J-481 D D D LF LFLIT0104 AUX BLDG LEAKAGE LEVEL 3605 J-481 D D D LF LFLIT0124 CONTROL BLDG FL EQUIP DRAIN 3605 J-481 D D D LF LFLIT0125 CONTROL BLDG FL EQUIP DRAIN 3605 J-481 D D D LF NB001 4.16 KV SWITCHGEAR 3301 E-009 D D D NB BOTH NB002 4.16 KV SWITCHGEAR 3302 E-009 D D D NB BOTH NBEI0001 4 KV BUS NB01 VOLTS 3501 J-200 D D D NB NBEI0002 4 KV BUS NB02 VOLTS 3501 J-200 D D D NB NBEI0003 4 KV BUS NB01 SYNCHROSCOPE 3501 J-200 D D D NB NBEI0004 4 KV BUS NB02 SYNCHROSCOPE 3501 J-200 D D D NB NE001 DIESEL GENERATOR 5203 M-018 D D D NE BOTH NE002 DIESEL GENERATOR 5201 M-018 D D D NE BOTH NE106 CONTROL & RELAY PANEL 5201 M-018 D D D NE BOTH NE107 CONTROL & RELAY PANEL 5203 M-018 D D D NE BOTH NF039A LOAD SHED/SEQ PANEL 3605 E-092 D D D NF BOTH NF039B LOAD SHED/SEQ PANEL 3605 E-092 D D D NF BOTH NF039C LOAD SHED/SEQ PANEL 3605 E-092 D D D NF BOTH NG001 LOAD CENTER 3301 E-017 D D D NG BOTH 20 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 21 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes NG001A MCC 3301 E-018 D D D NG BOTH NG001B MCC 1410 E-018 D D D NG BOTH 12 NG001T MCC 1410 E-018 D D D NG BOTH 12 NG002 LOAD CENTER 3302 E-017 D D D NG BOTH NG002A MCC 3302 E-017 D D D NG BOTH NG002B MCC 1409 E-018 D D D NG BOTH 12 NG002T MCC 1409 E-018 D D D NG BOTH 12 NG003 LOAD CENTER 3301 E-017 D D D NG BOTH NG003C MCC 1512 E-018 D D D NG BOTH NG003D MCC 5203 E-018 D D D NG BOTH NG003T MCC 1410 E-018 D D D NG BOTH 12 NG004 LOAD CENTER 3302 E-017 D D D NG BOTH NG004C MCC 1501 E-018 D D D NG BOTH NG004D MCC 5201 E-018 D D D NG BOTH NG004T MCC 1409 E-018 D D D NG BOTH 12 NG005E MCC K105 E-018 D D D NG BOTH NG006E MCC K104 E-018 D D D NG BOTH NK001 125 VDC SWITCHBOARD 3408 E-020 D D D NK BOTH NK002 125 VDC SWITCHBOARD 3410 E-020 D D D NK BOTH NK003 125 VDC SWITCHBOARD 3414 E-020 D D D NK BOTH NK004 125 VDC SWITCHBOARD 3404 E-020 D D D NK BOTH NK011 BATTERY 3407 E-050A D D D NK BOTH NK012 BATTERY 3411 E-050A D D D NK BOTH NK013 BATTERY 3413 E-050A D D D NK BOTH NK014 BATTERY 3405 E-050A D D D NK BOTH NK021 CHARGER 3408 E-051 D D D NK BOTH NK022 CHARGER 3410 E-051 D D D NK BOTH NK023 CHARGER 3414 E-051 D D D NK BOTH NK024 CHARGER 3404 E-051 D D D NK BOTH NK025 SPARE CHARGER 3301 E-051 D D D NK NK026 SPARE CHARGER 3302 E-051A D D D NK NK041 125 VDC SWITCHBOARD 3408 E-020 D D D NK BOTH NK042 125 VDC SWITCHBOARD 3410 E-020 D D D NK BOTH NK043 125 VDC SWITCHBOARD 3414 E-020 D D D NK BOTH NK044 125 VDC SWITCHBOARD 3404 E-020 D D D NK BOTH NK051 125 VDC SWITCHBOARD 3408 E-020 D D D NK BOTH NK051A LIGHTING PANEL 3408 E-020 D D D NK BOTH NK054 125 VDC SWITCHBOARD 3404 E-020 D D D NK BOTH NK071 TRANSFER SWITCH 3408 E-051B D D D NK BOTH NK072 TRANSFER SWITCH 3410 E-051B D D D NK BOTH NK073 TRANSFER SWITCH 3414 E-051B D D D NK BOTH NK074 TRANSFER SWITCH 3404 E-051B D D D NK BOTH NK075 SPARE CHARGER TRANSFER SWITCH 3301 E-051B D D D NK NK076 SPARE CHARGER TRANSFER SWITCH 3302 E-051B D D D NK NK077 SPARE CHARGER TRANSFER SWITCH 3301 E-051B D D D NK NK078 SPARE CHARGER TRANSFER SWITCH 3302 E-051B D D D NK 21 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 22 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes NK079 MANUAL TRANSFER SWITCH 3301 M-766A D D D NK NK080 MANUAL TRANSFER SWITCH 3302 M-766A D D D NK NKEI0001 NK01 125 VDC BUS VOLTS 3501 J-200 D D D NK NKEI0002 NK02 125 VDC BUS VOLTS 3501 J-200 D D D NK NKEI0003 NK03 125 VDC BUS VOLTS 3501 J-200 D D D NK NKEI0004 NK04 125 VDC BUS VOLTS 3501 J-200 D D D NK NKII0001 NK21 BAT CHARGER AMPS 3501 J-200 D D D NK NKII0002 NK11 BAT AMPS 3501 J-200 D D D NK NKII0003 NK22 BAT CHARGER AMPS 3501 J-200 D D D NK NKII0004 NK12 BAT AMPS 3501 J-200 D D D NK NKII0005 NK23 BAT CHARGER AMPS 3501 J-200 D D D NK NKII0006 NK13 BAT AMPS 3501 J-200 D D D NK NKII0007 NK24 BAT CHARGER AMPS 3501 J-200 D D D NK NKII0008 NK14 BAT AMPS 3501 J-200 D D D NK NN001 VITAL AC INST DIST PANEL 3408 E-053 D D D NN BOTH NN002 VITAL AC INST DIST PANEL 3410 E-053 D D D NN BOTH NN003 VITAL AC INST DIST PANEL 3414 E-053 D D D NN BOTH NN004 VITAL AC INST DIST PANEL 3404 E-053 D D D NN BOTH NN011 INVERTER 3408 ESE-18 D D D NN BOTH NN012 INVERTER 3410 ESE-18 D D D NN BOTH NN013 INVERTER 3414 ESE-18 D D D NN BOTH NN014 INVERTER 3404 ESE-1 D D D NN BOTH NN015 UPS/ INVERTER 3301 M-766A D D D NN NN016 UPS/ INVERTER 3302 M-766A D D D NN PA003 PT CUB. FOR RCP MOTOR DPBB01A 1410 E-009 C D D PA BOTH PA004 PT CUB. FOR RCP MOTOR DPBB01B 1410 E-009 C D D PA BOTH PA005 PT CUB. FOR RCP MOTOR DPBB01C 1409 E-009 C D D PA BOTH PA006 PT CUB. FOR RCP MOTOR DPBB01D 1409 E-009 C D D PA BOTH RL001 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL002 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL003 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL004 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL005 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL006 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL011 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL012 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL013 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL014 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL015 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL016 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL017 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL018 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL019 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL020 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL021 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL022 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH 22 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 23 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes RL023 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL024 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL025 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL026 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL027 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL028 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RP053AA BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053AB BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053AC BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053BA BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053BB BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053BC BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053DA BOP INSTR RACK TERMN 3605 J-110 D D D RP BOTH RP053DB BOP INSTR RACK TERMN 3605 J-110 D D D RP BOTH RP068 MISC BOP CONT PNL 3605 J-201 D D D RP RP080 RVLIS MICROPROCESSOR 3605 ESE-51 D D D RP 26 RP081A SUBCOOLING MONITORING PANEL 3605 ESE-46A D D D RP 26 RP081A-E01 SUBCOOLING MONITOR PANEL 3605 ESE-46B D D D RP 26 RP081B SUBCOOLING MONITORING PANEL 3605 ESE-46A D D D RP 26 RP081B-E01 SUBCOOLING MONITOR PANEL 3605 ESE-46B D D D RP 26 RP118A AUX SHUTDOWN PNL 1413 J-201 D D D RP BOTH RP118B AUX SHUTDOWN PNL 1413 J-201 D D D RP BOTH RP139 AUX RELAY RACK 3301 E-093 D D D RP BOTH RP140 AUX RELAY RACK 3302 E-093 D D D RP BOTH RP147A INSTR RACK 3302 J-110 D D D RP RP147B INSTR RACK 3302 J-110 D D D RP RP210 AUX RELAY RACK 1402 E-093 D D D RP BOTH 33 RP266 AUX RELAY RACK 1408 E-093 D D D RP BOTH 33 RP289 125 VDC PANEL 1513 E-028 D D D RP 34 RP290 125 VDC PANEL 1501 E-028 D D D RP RP315 125 VDC PANEL K105 E-028 D D D RP RP316 125 VDC PANEL K104 E-028 D D D RP RP331 REVERSE ISOL RELAY RACK 1408 E-093 D D D RP BOTH 33 RP333 AUX. RELAY RACK 1408 E-093 D D D RP BOTH 33 RP334 LOCKOUT RELAY RACK 3302 E-093 D D D RP BOTH RP335 LOCKOUT RELAY RACK 3302 E-093 D D D RP BOTH SA036A ESFAS CABINET 3605 J-104 D D D SA BOTH SA036B ESFAS CABINET 3605 J-104 D D D SA BOTH SA036C ESFAS CABINET 3605 J-104 D D D SA BOTH SA036D ESFAS CABINET 3605 J-104 D D D SA BOTH SA036E ESFAS CABINET 3605 J-104 D D D SA BOTH SA066A CAB. STATUS LOGIC/TERM.

3605 E-094 D D D SA SA066B CAB. STATUS LOGIC/TERM.

3605 E-094 D D D SA SA066C CAB. STATUS LOGIC/TERM.

3605 E-094 D D D SA SA066X STATUS LIGHT DISPLAY PANEL 3501 E-094 D D D SA SA066Y STATUS LIGHT DISPLAY PANEL 3501 E-094 D D D SA 23 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 24 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes SA066Z STATUS LIGHT DISPLAY PANEL 3501 E-094 D D D SA SA075A MN STM & FW ISO ACT PNL 3605 J-105 D D D SA BOTH SA075B MN STM & FW ISO ACT PNL 3605 J-105 D D D SA BOTH SB029A CAB W SS PROT SYS INPUT TRN A 3605 ESE-16 D D D SB BOTH SB029B CAB W SS PROT SYS LOGIC TRN A 3605 ESE-16 D D D SB BOTH SB029C CAB W SS PROT SYS OUT 1 TRN A 3605 ESE-16 D D D SB BOTH SB029D CAB W SS PROT SYS OUT 2 TRN A 3605 ESE-16 D D D SB BOTH SB030A CAB W SAFEGUARDS TEST 1 TRN A 3605 ESE-16 D D D SB BOTH SB030B CAB W SAFEGUARDS TEST 2 TRN A 3605 ESE-16 D D D SB BOTH SB032A CAB W SS PROT SYS INPUT TRN B 3605 ESE-16 D D D SB BOTH SB032B CAB W SS PROT SYS LOGIC TRN B 3605 ESE-16 D D D SB BOTH SB032C CAB W SS PROT SYS OUT 1 TRN B 3605 ESE-16 D D D SB BOTH SB032D CAB W SS PROT SYS OUT 2 TRN B 3605 ESE-16 D D D SB BOTH SB033A CAB W SAFEGUARDS TEST 1 TRN B 3605 ESE-16 D D D SB BOTH SB033B CAB W SAFEGUARDS TEST 1 TRN B 3605 ESE-16 D D D SB BOTH SB037 CAB W PROCESS PROTECTION SET 3 3605 ESE-13 D D D SB BOTH SB038 CAB W PROCESS PROTECTION SET 1 3605 ESE-13 D D D SB BOTH SB041 CAB W PROCESS PROTECTION SET 4 3605 ESE-13 D D D SB BOTH SB042 CAB W PROCESS PROTECTION SET 2 3605 ESE-13 D D D SB BOTH SB078 RVLIS MICROPROCESSOR CABINET 3605 ESE-51 D D D SB 26 SB079 RVLIS MICROPROCESSOR CABINET 3605 ESE-51 D D D SB 26 SB102A CAB W REACTOR TRIP SWGR TRAIN A 1403 ESE-62 D D D SB BOTH SB102A-E01 CAB W REACTOR TRIP SWGR TRAIN A 1403 ESE-20 D D D SB BOTH SB102B CAB W REACTOR TRIP SWGR TRAIN B 1403 ESE-62 D D D SB BOTH SB102B-E01 CAB W REACTOR TRIP SWGR TRAIN B 1403 ESE-20 D D D SB BOTH SB148A CAB W CONTR RM ISOL 3302 ESE-13 D D D SB BOTH SB148B CAB W CONTR RM ISOL 3302 ESE-13 D D D SB BOTH SBUQ0761A SSPS POWER SUPPLY IN SB038 3605 ESE-13 D D D SB BOTH SBUQ0761B SSPS POWER SUPPLY IN SB038 3605 ESE-13 D D D SB BOTH SBUQ0761C SSPS POWER SUPPLY IN SB038 3605 ESE-13 D D D SB BOTH SBUQ0762A SSPS POWER SUPPLY IN SB042 3605 ESE-13 D D D SB BOTH SBUQ0762B SSPS POWER SUPPLY IN SB042 3605 ESE-13 D D D SB BOTH SBUQ0762C SSPS POWER SUPPLY IN SB042 3605 ESE-13 D D D SB BOTH SBUQ0763A SSPS POWER SUPPLY IN SB037 3605 ESE-13 D D D SB BOTH SBUQ0763B SSPS POWER SUPPLY IN SB037 3605 ESE-13 D D D SB BOTH SBUQ0763C SSPS POWER SUPPLY IN SB037 3605 ESE-13 D D D SB BOTH SBUQ0764A SSPS POWER SUPPLY IN SB041 3605 ESE-13 D D D SB BOTH SBUQ0764B SSPS POWER SUPPLY IN SB041 3605 ESE-13 D D D SB BOTH SBUQ0764C SSPS POWER SUPPLY IN SB041 3605 ESE-13 D D D SB BOTH SE001 WELL DET. (NE41) 2000 ESE-8 C D C SE BOTH SE002 WELL DET. (NE31 NE35) 2000 ESE-4 C D C SE SE003 WELL DET. (NE43) 2000 ESE-8 C D C SE BOTH SE005 WELL DET. (NE42) 2000 ESE-8 C D C SE BOTH SE006 WELL DET. (NE32 NE36) 2000 ESE-4 C D C SE SE007 WELL DET. (NE44) 2000 ESE-8 C D C SE BOTH SE031 PREAMP SR CHAN 1 1410 ESE-47B C D D SE 24 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 25 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes SE032 PREAMP SR CHAN 2 1409 ESE-47B C D D SE SE054A W NUC INST. NIS 1 3605 ESE-10 D D D SE BOTH SE054B W NUC INST. NIS 2 3605 ESE-10 D D D SE BOTH SE054C W NUC INST. NIS 3 3605 ESE-10 D D D SE BOTH SE054D W NUC INST. NIS 4 3605 ESE-10 D D D SE BOTH SENI0060A EX-CORE NEUTRON FLUX INDICATOR 3501 J-110 D D D SE SENI0060B EX-CORE NEUTRON FLUX INDICATOR 3501 J-110 D D D SE SENI0061X EX-CORE NEUTRON FLUX INDICATOR 1413 J-110 D D D SE SENI0061Y EX-CORE NEUTRON FLUX INDICATOR 1413 J-110 D D D SE SENIR0061 EX-CORE NEUTRON FLUX RECORDER 3501 J-110 D D D SE SENY0060A NFMS AMPLIFIER 1403 J-364 D D D SE SENY0060B NFMS SIGNAL PROCESSOR 1403 J-364 D D D SE SENY0061A NFMS AMPLIFIER 1501 J-364 D D D SE SENY0061B NFMS SIGNAL PROCESSOR 1501 J-364 D D D SE SGK04A CONTROL ROOM A/C UNIT 1512 M-622.1, M-622.1A D D D GK BOTH SGK04B CONTROL ROOM A/C UNIT 1501 M-622.1, M-622.1A D D D GK BOTH SGK05A CLASS IE ELEC. EQUIP. A/C UNIT 3416 M-622.1, M-622.1A D D D GK BOTH SGK05B CLASS IE ELEC. EQUIP. A/C UNIT 3415 M-622 D D D GK BOTH SGS03A H2 ANALYZER CALIB BOTTLE & CTRL PANEL SKID 1506 J-359 D D D GS 34 SGS03B H2 ANALYZER CALIB BOTTLE & CTRL PANEL SKID 1507 J-359 D D D GS 34 SJ359 CONTROL BOX FOR SJHV0006 1301 WEST J-603A D D D SJ 30 SP067 RAD MONITOR CONT PNL 3605 J-361 D D D SP SP104A RAD MON SYS ISOLATION BOX 1513 J-361 D D D SP 34 SP104B RAD MON SYS ISOLATION BOX 1513 J-361 D D D SP 34 SP105A RAD MON SYS ISOLATION BOX 1513 J-361 D D D SP 34 SP105B RAD MON SYS ISOLATION BOX 1513 J-361 D D D SP 34 25 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 26 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes SP122A RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP 34 SP122B RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP 34 SP127A RAD MON SYS ISOLATION BOX 6301 J-361 D D D SP 36 SP127B RAD MON SYS ISOLATION BOX 6301 J-361 D D D SP 36 SP128A RAD MON SYS ISOLATION BOX 6301 J-361 D D D SP 36 SP128B RAD MON SYS ISOLATION BOX 6301 J-361 D D D SP 36 SP131A RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP 34 SP131B RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP 34 SP132A RAD MON SYS ISOLATION BOX 1506 J-361 C D D SP 34 SP132B RAD MON SYS ISOLATION BOX 1506 J-361 C D D SP 34 SP133A RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP 34 SP133B RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP 34 SP159A RAD MON SYS ISOLATION BOX 1512 J-361 D D D SP SP159B RAD MON SYS ISOLATION BOX 1512 J-361 D D D SP SP160A RAD MON SYS ISOLATION BOX 1501 J-361 D D D SP SP160B RAD MON SYS ISOLATION BOX 1501 J-361 D D D SP SS001 AMSAC PANEL 3605 J-203 D D D SS XNG01 LC TRANSFORMER 3301 E-017 D D D NG BOTH XNG02 LC TRANSFORMER 3302 E-017 D D D NG BOTH XNG03 LC TRANSFORMER 3301 E-017 D D D NG BOTH XNG04 LC TRANSFORMER 3302 E-017 D D D NG BOTH XNG05 ESW MCC TRANSFORMER K105 E-075 D D D NG BOTH XNG06 ESW MCC TRANSFORMER K104 E-075 D D D NG BOTH XNN05 XFMR 3408 E-075 D D D NN BOTH XNN06 XFMR 3408 E-075 D D D NN BOTH ZHS-1-EQ SWITCHES 1410 E-028A D D D XX BOTH ZHS-2-EQ SWITCHES 1409 E-028A D D D XX BOTH ZZP-1-EQ PREFABRICATED CABLE ASSEMBLIES (E-11014) 2 - Used throughout the plant E-095 (Bendix)

C C C XX BOTH Cat. A Item is required to function post accident Cat. B Item is not required to function post accident; however, item must not adversely fail post accident Cat. C Item's status post accident has no effect on plant safety Cat. D Item is in mild environment post accident Notes:

2 3

Used throughout the plant.

The spent fuel pool cooling system will be operated during these conditions to maintain fuel pool temperatures.

26 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 27 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes 4

5 7

8 9

11 12 16 17 18 19 20 21 22 24 25 26 27 28 29 30 31 32 Rooms 1206 and 1207 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

This equipment was added in response to NUREG-0737 Category II.E.1.2 This equipment was added in response to NUREG-0737 Category II.F.1 Used throughout the plant - outside containment.

Used inside containment.

Splices used inside boxes instead of terminal blocks.

This note identifies that Non-IE Conax modules used in this penetration and addressed in PQE-E-035B-P01 have a safety related function of maintaining the pressure boundary of containment. PQE-E-035B-P01 documents that Conax modules used in ZSE/ZSI222E (I), ZSE/ZSI252E (I), ZNE/ZNI253C (I),

ZSE/ZSI254E (I), ZSE/ZSI255E (I), ZSE/ZSI255D (I), ZNE/ZNI292F (I) and ZNE/ZNI294C (I) ZSE/ZSI222F (LVP), ZNE/ZNI224C (LVP), ZNE/ZNI274A (LVP), ZNE/ZNI274G (LVP) and ZNE/ZNI282C (LVP) are acceptable for use in the environments identified.

Rooms 1508 and 1509 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1107 and 1108 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1113 and 1114 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1301, 1314, 1315 and 1320 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Alternate EGS connector approved for installation per CP 12467 as necessary.

Determined by XX-81 analysis to be mild environment equipment post accident (also reference EQWP-J-605A R3) states that a location-specific dose calculation and analysis was performed on the butterfly valves located in Room 1314, and concluded that the subject valves can be recategorized as mild environment equipment. The parameters constitute a mild environment.

Determined by XX-53 analysis to be mild environment equipment post accident. EQWP-E-018 R5 states that a specific-location dose calculation and analysis was performed on the MCC's located in Room 1409 and 1410, and concluded that subject MCCs can be recategorized as a mild environment equipment.

Qualified as a sub-component of Panel RP209 Qualified as a sub-component of Panel RP330 Qualified as a sub-component of Panel RP332 Spared in Place This equipment was added in response to NUREG-0737 Category II.F.2 Rooms 1101, 1102, 1120, 1121, 1122 and 1130 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

This equipment was added in response to NUREG-0737 Category II.B.1 This equipment was added in response to NUREG-0737 Category II.B.3 This equipment was added in response to NUREG-0737 Category II.D.3 27 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 28 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L

O C

A H

E L

B M

S L

B System Hot/Cold Shutdown Notes 33 34 35 36 37 38 39 50 Reference E-035B-00050, Table 3.1, Page 11. The power and control modules are ZSE/ZSI233E, ZSE/ZSI233F, ZSE/ZSI234F, ZNE/ZNI278F and ZNE/ZNI278G. The instrumentation modules are ZSE/ZSI233D, ZSE/ZSI233G, ZSE/ZSI234E, ZSE/ZSI243C, ZSE/ZSI249C, ZSE/ZSI249D, ZSE/ZSI250A, ZSE/ZSI250B, ZSE/ZSI250D, ZSE/ZSI250F, ZSE/ZSI250G, ZSE/ZSI258F, ZNE/ZNI277F, ZNE/ZNI278C, ZNE/ZNI278D, ZNE/ZNI278E, ZNE/ZNI279E, ZNE/ZNI287C, ZNE/ZNI287D, ZNE/ZNI287E, ZNE/ZNI288B, ZNE/ZNI288D, ZNE/ZNI288F, ZNE/ZNI295F and ZNE/ZNI295G.

GDI-30F (Long-glass, fiber filled, diallyl-phthalate) terminal blocks that are Series 601-JJ, 602-JJ, 604-JJ, 605-JJ, 812-JJ type are qualified under PQE-E-035B-P02 for each of these applications. Instrumentation applications do not use the Kulka terminal blocks inside the containment, PQE-E-11013-P01/

P06/P07/ P08/ P09 splices are used in these applications.

These assets contain two limit switches. However one of the limit switches is an installed spare and doesnt have power running to it. Therefore, doesnt perform any safety function and doesnt need qualified by the EQ program.

Located in yard.

Rooms 1401, 1402 and 1408 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1502, 1503, 1505 and 1507 plus Rooms 1504, 1506 and 1513 (due to transfer grill GLD0175 on M-1H1431) are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 3401, 3406 and 3412 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 6301 and 6302 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

28 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 29 of 31 29 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 30 of 31 30 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 31 of 31 31 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 32 of 31 32 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 33 of 31 33 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 34 of 31 34 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 35 of 31 35 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 36 of 31 36 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 37 of 31 37 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 38 of 31 38 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 39 of 31 39 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 40 of 31 40 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 41 of 31 41 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 42 of 31 42 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 43 of 31 43 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 44 of 31 44 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 45 of 31 45 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 46 of 31 46 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 47 of 31 47 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 48 of 31 48 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 49 of 31 49 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 50 of 31 50 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 51 of 31 51 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 52 of 31 52 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 53 of 31 53 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 54 of 31 54 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 55 of 31 55 of 56

EQSD-II Rev. 34 Table 2: EQ Mild Environment Equipment List 56 of 31 56 of 56

GENERAL Electrical Equipment Categories for LOCA/MSLB/HELB fields Cat. A Item is required to function post accident Cat. B Item is not required to function post accident; however, item must not adversely fail post accident Cat. C Item's status post accident has no effect on plant safety Cat. D Item is in mild environment post accident Notes:

2 3

4 5

7 8

9 11 12 16 17 18 19 20 21 22 24 25 26 This equipment was added in response to NUREG-0737 Category II.F.1 This equipment was added in response to NUREG-0737 Category II.F.2 This equipment was added in response to NUREG-0737 Category II.E.1.2 Used throughout the plant with exception of instrumentation circuits inside containment and auxilary building rooms 1411, 1412, 1508, and 1509 Alternate EGS connector approved for installation per CP 12467 as necessary.

Determined by XX-81 analysis to be mild environment equipment post accident (also reference EQWP-J-605A R3) states that a location-specific dose calculation and analysis was performed on the butterfly valves located in Room 1314, and concluded that the subject valves can be recategorized as mild environment equipment. The parameters constitute a mild environment.

Determined by XX-53 analysis to be mild environment equipment post accident. EQWP-E-018 R5 states that a specific-location dose calculation and analysis was performed on the MCC's located in Room 1409 and 1410, and concluded that subject MCCs can be recategorized as a mild environment equipment.

Qualified as a sub-component of Panel RP209 Qualified as a sub-component of Panel RP330 Qualified as a sub-component of Panel RP332 Spared in Place This equipment was added in response to NUREG-0737 Category II.B.1 This equipment was added in response to NUREG-0737 Category II.B.3 This equipment was added in response to NUREG-0737 Category II.D.3 Used inside containment.

Description Used throughout the plant.

The spent fuel pool cooling system will be operated during these conditions to maintain fuel pool temperatures.

This note identifies that Non-IE Conax modules used in this penetration and addressed in PQE-E-035B-P01 have a safety related function of maintaining the pressure boundary of containment. PQE-E-035B-P01 documents that Conax modules used in ZSE/ZSI222E (I), ZSE/ZSI252E (I), ZNE/ZNI253C (I), ZSE/ZSI254E (I), ZSE/ZSI255E (I), ZSE/ZSI255D (I),

ZNE/ZNI292F (I) and ZNE/ZNI294C (I) ZSE/ZSI222F (LVP), ZNE/ZNI224C (LVP), ZNE/ZNI274A (LVP), ZNE/ZNI274G (LVP) and ZNE/ZNI282C (LVP) are acceptable for use in the environments identified.

Used throughout the plant - outside containment.

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 50 PQE-ESE-43G-P01 CP 13788 CP 14701 Located in yard.

Reference E-035B-00050, Table 3.1, Page 11. The power and control modules are ZSE/ZSI233E, ZSE/ZSI233F, ZSE/ZSI234F, ZNE/ZNI278F and ZNE/ZNI278G. The instrumentation modules are ZSE/ZSI233D, ZSE/ZSI233G, ZSE/ZSI234E, ZSE/ZSI243C, ZSE/ZSI249C, ZSE/ZSI249D, ZSE/ZSI250A, ZSE/ZSI250B, ZSE/ZSI250D, ZSE/ZSI250F, ZSE/ZSI250G, ZSE/ZSI258F, ZNE/ZNI277F, ZNE/ZNI278C, ZNE/ZNI278D, ZNE/ZNI278E, ZNE/ZNI279E, ZNE/ZNI287C, ZNE/ZNI287D, ZNE/ZNI287E, ZNE/ZNI288B, ZNE/ZNI288D, ZNE/ZNI288F, ZNE/ZNI295F and ZNE/ZNI295G.

GDI-30F (Long-glass, fiber filled, diallyl-phthalate) terminal blocks that are Series 601-JJ, 602-JJ, 604-JJ, 605-JJ, 812-JJ type are qualified under PQE-E-035B-P02 for each of these applications. Instrumentation applications do not use the Kulka terminal blocks inside the containment, PQE-E-11013-P01/ P06/P07/ P08/ P09 splices are used in these applications.

These assets contain two limit switches. However one of the limit switches is an installed spare and doesnt have power running to it. Therefore, doesnt perform any safety function and doesnt need qualified by the EQ program.

Not used DRE 20217 approves changing the identified model 763 to 763A.

SWO 18-446734-002 changed model number to 763A.

Rooms 6301 and 6302 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1101, 1102, 1120, 1121, 1122 and 1130 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1107 and 1108 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1113 and 1114 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1301, 1314, 1315 and 1320 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1508 and 1509 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1206 and 1207 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1401, 1402 and 1408 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1502, 1503, 1505 and 1507 plus Rooms 1504, 1506 and 1513 (due to transfer grill GLD0175 on M-1H1431) are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 3401, 3406 and 3412 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.