ML21356A577

From kanterella
Jump to navigation Jump to search

Slar Breakout Questions - Fire Protection Scoping and Screening
ML21356A577
Person / Time
Site: Saint Lucie  
Issue date: 12/22/2021
From:
Office of Nuclear Reactor Regulation
To:
Rodriguez-Luccioni H
References
L-2021-SLR-0002
Download: ML21356A577 (3)


Text

1 St. Lucie Units 1 and 2 SLRA Breakout Questions SLRA Section Scoping and Screening:

2.1.3.4.1 Fire Protection (10 CFR 50.48) 2.1.4.2.1 Nonsafety-Related SSCs with Potential to Prevent Satisfactory Accomplishment of Safety Functions 2.3.3.5 Fire Protection/Service Water 2.4 Scoping and Screening Results: Structures (only fire barrier portion) 2.4.17 Fire Rated Assemblies Technical Reviewer Thinh Dinh/Naeem Iqbal 12/20/2021 Technical Branch Chief Jay Robinson (for Jennifer Whitman) 12/20/2021 Breakout Session Applicant Staff NRC staff Question Number SLRA Section SLRA Page Background / Issue (As applicable/needed)

Discussion Question / Request Outcome of Discussion 1

2.3.3.5 2.3-37 The descripton for the Fire Protection /

Service Water does not include the following:

seismic support for fire water system including tanks, standpipes, piping, etc.:

floor drains for removal of fire water structural steel fire proofing Fixed emergency lighting Verify whether the fire protection components listed are within the scope of SLRA in accordance with 10 CFR 54.4(a) and whether they are subject to an aging management review (AMR) in accordance with 10 CFR 54.21(a)(1). If any of the listed components are not within the scope of SLRA and are not

2 subject to an AMR, the staff requests that the applicant provide justification for the exclusion.

2 2.3.3.5 2.3-38 Oil collection dikes and curbs are credited fire protection features. The SLRA, however, only specifies the RCP oil collection system.

Clarify whether other oil collection dikes and curbs such as for the diesel oil and day tanks, pumps, etc. are within the scope of the SLRA in accordance with 10 CFR 54.4(a) and whether they are subject to an aging management review (AMR) in accordance with 10 CFR 54.21(a)(1). If they are not within the scope of SLRA and are not subject to an AMR, the staff requests that the applicant provide justification for the exclusion.

3 2.4.17 2.4-34 Only conduit fire wraps are included in the description of the fire rated assemblies section.

Clarify whether other fire wraps or electrical raceway fire barrier system (ERFBS) credited for cable tray, ducts, electrical panels or junction boxes, etc., if any, are within the scope of the SLRA in accordance with 10 CFR 54.4(a) and whether they are subject to an aging management review (AMR) in accordance with 10 CFR 54.21(a)(1). If they are not within the scope of SLRA and are not subject to an AMR, the staff requests that the

3 applicant provide justification for the exclusion.