Amendment 29 to Updated Final Safety Analysis Report, Chapter 8, Table 8.5, Standby AC Power Supply
ML21286A414
Person / Time
Site: Browns Ferry  Tennessee Valley Authority icon.png
Issue date: 10/04/2021
From:
Tennessee Valley Authority
To:
Office of Nuclear Reactor Regulation
Shared Package
ML21286A574 List: ... further results
References
Download: ML21286A414 (10)


Text

BFN-21

Table 8.5-2

(Deleted by Amendment 7)

BFN-21

Table 8.5-2a

(Deleted by Amendment 7)

BFN-21

Table 8.5-3

(Deleted by Amendment 7)

BFN-21

Table 8.5-4

(Deleted by Amendment 7)

BFN-21

Table 8.5-5

CSCS LOAD STARTING-NORMAL POWER

TIME (from accident signal) Shdn Bd A Shdn Bd C Shdn Bd B Shdn Bd D Seconds Start Start Start Start

0 RHR, CS Required 480V Required 480V Required 480 Required 480V Loads Loads Loads Loads

7 RHR, CS

14 RHR, CS

21 RHR, CS

28 RHRSW (FOR EECW) RHRSW (FOR EECW) RHRSW (FOR EECW) RHRS (FOR EECW)

BFN-21

TABLE 8.5-6

DIESEL GENERATOR RATINGS

Rating (See Notes) Description Time

1. Engine - Maximum steady-state active 0 - 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> Short-Time power output 2860/2800kW (running kW)
2. Engine - Maximum steady-state active > 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> Continuous power output 2600/2550kW (running kW)
3. Engine - Maximum instantaneous active 0 - 3 minutes Instantaneous power output (Cold) (running kW + starting kW) 2850kW
4. Engine - Maximum instantaneous active > 3 minutes Instantaneous power output (Hot) (running kW + starting kW) 3048kW
5. Generator - Maximum steady-state 0 - 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> Short-Time apparent power output 3575KVA (running KVA)
6. Generator - Maximum steady-state > 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> Continuous apparent power output 3250KVA (running KVA)

Notes:

DG Ratings 1 and 2: Engine short-time and continuous maximum steady state active power output (running kW) is denoted in the table as Non-derated Rating/Derated Rating.

  • Non-derated rating for intake air temperatures less or equal than 90 °F.
  • Derated Rating for either intake air temperatures greater than 90 °F or a combination of intake air temperatures greater than 90°F and engine cooling heater outlet temperature greater than 190°F.

DG Ratings 3 and 4: Engine instantaneous cold and hot maximum instantaneous active power (running kW plus starting kW) is denoted in the table as Non-derated Rating.

  • Due to BFNs elevation is less than 800 feet above sea level with maximum intake air temperatures of less than 115°F, the maximum instantaneous active power output does not require derating for temperature.