ML21286A368
Text
BFN-26 Table 7.3-1 (Deleted by Amendment 9)
BFN-26 TABLE 7.3-2 (Sheet 1)
PRIMARY CONTAINMENT ISOLATION SYSTEM INSTRUMENT SPECIFICATIONS Isolation*
Signal Isolation Function Sensor Trip Setting/
Analytical Limit (AL)
A Reactor vessel low water level differential pressure indicating switch 518 inches above vessel zero (AL)
B Reactor vessel low-low water level differential pressure indicating switch 372.5 inches above vessel zero (AL)
D Main steam line space high temperature temperature switch 205°F (AL) for 12/3-TS-1-17A thru D/
thru D
Main steam line high flow PDIS-1-13A-D, 25A-D, 36A-D, 50A-D differential pressure switch 144% rated flow (AL)
E HPCI diaphragm Rupture Disc high pressure pressure switch 52 psig (AL)
P Main steam line low pressure pressure switch 843 psig F
Primary containment high pressure pressure switch 2.6 psig (AL)
K RCIC turbine steam line space RCIC pump room area high temperature temperature switch 180°F (AL)
K RCIC Turbine steam line space torus area high temperature temperature switch 155°F (AL)
K RCIC turbine steam line high flow differential pressure switch 1114 inch H20 (AL)
K RCIC turbine steam line low pressure pressure switch 40 psig (AL)
L HPCI turbine steam line space HPCI Pump Room Area high temperature temperature switch 200°F (AL)
BFN-26 TABLE 7.3-2 (Sheet 2)
PRIMARY CONTAINMENT ISOLATION SYSTEM INSTRUMENT SPECIFICATIONS Isolation*
Signal Isolation Function Sensor Trip Setting/
Analytical Limit (AL)
L HPCI Turbine Steam Line Space Torus Area High Temperature temperature switch 180°F (AL)
L HPCI turbine steam line high flow differential pressure switch 107 psid (AL)
L HPCI turbine steam line low pressure pressure switch 55 psig (AL)
Z Reactor Building ventilation exhaust high radiation radiation monitor 100 mr/hr J
Reactor Water Cleanup System Main Steam Valve Vault (TE-069-834A-D)
U3 205°F (AL)
J Reactor Water Cleanup System Pipe Trench (TE-069-835A-D)
J Reactor Water Cleanup System Pump Room 2A (TE-069-836A-D)
RTD 148°F*
J Reactor Water Cleanup System Pump Room 2B (TE-069-837A-D)
RTD 148°F*
J Reactor Water Cleanup System Heat Exchanger Room (TE-069-838A-D)
U3 175°F (AL)
J Reactor Water Cleanup System Heat Exchanger Room (TE-069-839A-D)
U3 173°F (AL)
G RCIC diaphragm rupture disc high pressure Pressure switch 50 psig (AL)
- See Table 5.2-2 for Isolation Signal Codes.