--____=__ - ___ - _ ____ _

f ESO 205 PULLMAN J0WER-PR000 CTS L ;r A T, T I

f

/,.i.

SECTION NO.

1 PREPARED BY:R R W Linld.. c.s %FRROVE0 Bt:" R:'U.7 fhk' OATE:

9-23-71 3

~

'~

DIABLO CANYON E

O PAGE PROJECT PROCEDURE I

,J08#

7177 NO.

1 of 3 f

't L

P. G. AND E. CODE CLASSES em CODE CLASS "A",=831.7 CLASS 1, DESIGN CLASS 1 Requires full Q.A. procedures. Modified Data Reports, Third Party Inspection, Code Plates without the "NA" stamp.

100% R.T. to ES-0206 Girth Butt Welds 100% M.T. to ES-0208 for C.S.

100% P.T. to ES-0210 for S.S.

100% M.T. to ES-0208 for C.S.

Fillet, socket, seal or Attachments welds, Support legs, anchors and 100% P.T. to ES-0210 for 5.5.

Guides 100% R.T. to ES-0206 Welded Branch Connections 100% M.T. to ES-0208 for C.S.

]k Over 5" pipe size 100% P.T. to ES-0210 for 5.5.

100% M.T. to ES-0208 for C.S.

- Welded Branch Connections 4" pipe size and under 100% P.T. to ES-0210 for S.S.

All stainless steel butt welds in the S-5 or S-6 specification, which weld to Westinghouse equipment or valves, shall have the root pass liquid pene-trant examined in accordance with ESO-210.

Hydrostatic test to P.G. & E. specifications.

CODE CLASS "B",=831.7 CLASS 11, DESIGN CLASS 1 Requires full O A. procedures.

"NPP-1" A.S.M.E. Data Reports Third Party Inspection code plates with the "NA" stamp.

100% R.T. to ES-0206 Girth Butt Welds 100% M.T. to ES-0208 for C.S.

Fillet, Socket, seal or Attachment welds, 100% P.T. to ES-0210 for S.S.

Support legs, achors and Guides 100i,R.T. to ES-0206 for C.S.

Welded Branch Connections Over 4" pipe size 100% M.T. to ES-0208 for C.S.

O Weleee erench Connect 4ons 4" Pipe size and under 100% P.T. to ES-0210 for S.S.

SF 1.06 8708190292 870814 PDR FOIA DEVINEB4-743 PDR

OwiFRUDbCTS;

[ ?@2 ESD 205 S

l.

!:. I i?

Ic

_'. '. i. (..

L.c.

,.U &

SECTION NO.-

PREPARED BY:

R. G. F i7i k ' -

1 APPROVED.QY;,.l.,G. Fink DATE:

9-23-71 1

TO BE(u thql ytf rIjg1 4

DIABLO CANYON i

PAGE PROJECT PROCEDURE ONLY W4WaJ 4177 30.

2 of 3 4

All stainless steel butt welds in the S-5 or S-6 specification which weld to Westinghouse equipment or valves, shall have the root pass liquid l

penetrant examined in accordance with ESD-210.

l Hydrostatic test to P.G. & E. specifications.

CODE CLASS "C" -B31.7 CLASS 111. DESIGN CLASS 1 Requires full 0.A. procedures.

Girth Butt Welds 100% R.T. in accordance with ESll-206 for butt welds with steam service above 925 F. greater than 1-5/8" nominal wall and for water service all pressures and temperatures greater than 1-1/8" nominal q

wall.

NJ If no radiography is performed,100% M.T. to ESD-208 for C.S. or 100% P T. to ESD-210 for S.S. shall be performed.

Fillet, socket and seal welds 100% M.T. to ESD-20E for C.S.

and all welded branch connections 100% P.T. to ESD-210 for S.S.

All stainless steel butt welds in the S-5 or 5-6 specification, which weld to Westinghouse equipment or valves, shall have the root pass liquid penetrant v

examined dn accordance with ESD-210.

Hydrostatic test to P.G. & E. specifications.

No nondestructive testing shall be required on line attachments.

CODE CL ASS "G",=B31.1, DESIGN CL ASS 1 N.F.P. A. #13 Q.A. procedure per ESD-265.

100% Radiography in accordance with ESD-207 for butt welds with steam service above 925*F. greater than 1-5.8" nominal wall and for greater service all pressures and temperatures greater than 1-1/8" nominal wall.

100% liquid Penetrant Test in accordance with ESD-211 for butt welds of austenitic

(

materials with steam service above 925*F. and for fillet and socket welds in stean 1

service above 2500 p.s.i. or 925'F.

Hydrostatic test to P.G. & E. specifications.

SF 1.06

ESD 205 e "~P'/b 1 1 SECTION NO.

PREPARED BY:

R. G. Finkwg A N PPROVED BY:

R. G. Fink U hij

0Mj!

9-23-71 IpB E hS "6MLYTA,Ek N o' DIABLO CANYON P

PROJECT PROCEDURE A JOBf 4 74 NO.

3 of 3 OTlJu h[

0%1 CODE CLASS "E" 83I.1, DESIGN CLASS II No Q.A. required, except for weld rod control procedures.

3-6-83 100% Radiography in accordance with ESD-207 for butt welds with steam service above 925'F, greater than 11/8" nominal wall and for water service all pressures and temperatures greater than 15/8" nominal wall.

100% Liquid Penetrant Test in accordance with ESD-211 for butt welds of austenitic l

materials with steam service above 925'F, and for fillet and socket welds in steam service above 2500 PSI or 925'F.

Hydrostatic Test to P.G. & E. specifications.

CODE CLASS "E SPECIAL" B31.1. DESIGN CLASS II No Q. A. required, except for weld rod control procedures.

p 100% Radiography in accordance with ESD-207 for all butt welded joints,100%

1 L

Magnetic Particle or Liquid Penetrant in accordance with ESD-209 and E50-211 for all welded joints.

Hydrostatic Test to P.G. & E. specifications.

CODE CLASS "SEC.1" ASME SECTION 1 - DESIGN CLASS 1 l

(Main Steam, Feedwater, Steam Dump)

Requires full Q.A. procedures, Third Party Inspection to ASME Section 1. Data reports, and stamping.

100% Radiography in accordance with ESD-207 for all butt welds.

100% Magnetic Particle in accordance with ESD-209 for all pressure retaining welds.

NOTE' Where Magnetic Particle testing is impractical, Liquid Penetrant testing may be substituted.

Hydrostatic Test to P.G. & E. specifications.

CODE CLASS "SEC.1" ASME SECTION 1 - DESIGN CLASS II No 0.A. required, except for weld rod control procedures. Third Party Inspection to ASME Section 1, Data Reports, and stamping are required.

j For N.D.T. requirements, see ASME Section 1 1968, page 71, PW-41.

SF 1.06

.m

%ah, j[v, U

] " ' # 5 % { ] h...., y. %,,e.{ p.[; p g.,{.,.[.' $... @n V,..;. $

- a:a. u. p g$"."u.@ba.

a

.w(g.x, Wa%p.h...

.y a.3

.y

,,g..

,$n ? nyy.rre'. L' w3 agg.W7

' ~

a.~,) +p fr-

?J

,. f

. a.,,,aqAm.u.:es.s:>u&..p, 3 f.,.,.

. 3n.s.j i

i*+

b.

y.,.
g

- - m,3,,na,

.n Sp Mo?

b

..JTLt10FFICE COP. DESPONDENCE Wn.d C DAll!

October 27, 1983

\\1 70 J. Arnold f L'OM S. Zaidi, S. Cornish and H..Karner Suenci

' Clarification of ESD 223 We request the following clarification of ESD 223, rev 8-23-03, be imple. rented 12 mediately.

Read 6.6.2.5 Horizontal and vertical gaps nu.y be increased to h" for fram fabri-cation. These gaps shall be adjusted by shimming to meet drawing requirements after the frams are couplete.

i Change 6.6.2.6 All other shims nust be shown on the as-built drawing, but do not need PG&E authorization.

Shims should be fillet welded on all accesible corners with a mininum weld size in accordance with A.I.S.C.

requirements (weld size should not exceed shim plate thickness for material less than " thick) with 'a mininum length of 1" or four (4) timas the weld size whichever is greater. A mininum of two opposite edges shall be welded.

Note: All changes are underlined.

If you hava any questions, please feel free to contact any one of us.

,.t \\1

'thank you.

Q,?'l.\\

\\

4 F h. -f \\ D, s

.ia=1%'

\\ '..

n,.

E Y, ~, s F

rO'!!hD r

Alt,+ L

<aAc?!,bfn> &

k

. ))@.7 alcu.y,$..

e p

Skip'Cornish Halcld F.P.rncr S p.d 11. A.

Sr. I'ield Engineer Chief Field Engineer QA/CC V.an?.ger Tccht!. cal Advisor

~. 2-[^

IIC/S"/jf S.pprovsd Jiy

. g, Jerry Arnold "N

Posident Mochenicz,1 Encineer c[

k, PG&E

[

h, s

m.%g,,

'3 w