f Report No. 14850.35-AV1 DEC. 1986 i
i l
BASELINE VIBRATION SURVEY EMERGENCY DIESEL GENERATOR
'A' RANCHO SECO NUCLEAR POWER PLANT PREPARED FOR-SACRAMENTO MUNICIPAL UTILITY DISTRICT PREPARED BY EUGENE BERCEL 8901070072 871229 PDR ADOCK 05000312 S
PDR STONE & WEBSTER ENGINEERING CORPORATION BOSTON, MASSACHUSETTS
.s gJh iU__--_----_________
TABLE OF CONTENTS Section Title Page Summary and Conclusions 3
1.0 Objectives 4
h 2.0 Test Equipment 4
2.1 Instrumentation 4
2.2 Calibration 5
2.3 Diesel Generator Data 5
3.0 Measurement and Analysis Procedure 6
4.0 Survey Results 6
5.0 Conclusions and Recommendations 8
\\
APPENDIX 9
TABLE 1 Equipment Frequency Response TABLE 2 Measurement Locations TABLE 3 Survey Results by Location TABLE 4 Survey Results by Velocity TABLE 5 Survey Results by Displacement FIGURE 1
Instrumentation Schematic FIGURES 2-2A Measurement Locations FIGURES 3-72 Vibration Spectra e
_m___
g
SUMMARY
AND CONCLUSIONS A vibration baseline survey was carried out Nov. 13 1986 to i
identify the vibration characteristics of the emergency diesel
' generator
'A' at the Rancho Seco Nuclear Power Station.
The diesel engine involved was an in-line 8-cylinder engine (DSR-48) manufactured by Transamerica DeLaval.
Sixty-eight measurements were taken at thirty-five locations on l
the engine and its auxiliary equipment.
The vibration survey was carried out in accordance with a document issued by the TDI Owners Group and entitled:
" Test Procedure for Engine Baseline-Vibration Survey for DSR-48 Engines".
The field measurements were analyzed in the 0-100 Hz range and are presented here in the form of tables of vibration amplitudes and plots of vibration spectra.
The measured overall vibration amplitudes, with the exception of the t'urbo-charger were well below 1.0 in/see pk.
A vibration level of 1.0 in/sec pk.
is generally considered the upper limit of acceptable vibration for large diesel engines.
Up to 4.92 in/sec pk. was measured on the turbo-charger.
That level is somewhat higher-than the vibration level observed on the turbo-charger of a
similar engine at the River Bend Nuclear Power Station before modifications to the turbine exhaust arrangement.
The average vibration level, calculated from 55 measurements (excluding the turbo-charger locations) was 0.2 in/sec ph.
That level is lower than the corresponding values measured on two similar engines surveyed in other plants.
s l
3 j
4 i
1.0 OBJECTIVES A-vibration baseline survey was carried out to identify the vibration characteristics of Diesel Generator
'A'.
The diesel engine involved' is an in-line 8-cylinder engine (DSR-48) manufactured by Transamerica DeLaval.
To demonstrate acceptability the baseline data will be'. compared against vibration data taken on similar engines at other-sites.
2.0 TEST EQUIPMENT 2.1 INSTRUMENTATION The following instrumentation was used in the vibration surveys reported here.
Transducers Reference velocity probe Mark Products SN 203 Horizontal velocity probe Mark Products SN 303
-Vertical velocity probe Mark Products SN 206 Reference Accelerometer PCB 308B SN 3722 Signal Conditioning / Recording Equipment 7-channel preamplifier Trig-Tek 205B SN 103-4-channel tape recorder Teac R-71 SN 160362 Accelerometer power supply PCB 480D09 SN 365 Data Analysis Equipment 4-channel tape recorder Teac R-71 SN 160362 2-channel spectrum analyzer Nicolet 660B SN 5620079006-System control computer HP 9826 SN 2205A04469 The instrumentation was interconnected to form the system illustrated schematically in Figure 1.
The frequency response characteristics of the individual components and those of the system are tabulated in Table 1.
4
~
2.2 CALIBRATION The velocity probes and the reference accelerometer were l
calibrated against a
precision accelerometer in the Acoustics and Vibration Laboratory of Stone Webster Engineering Corporation.
A shaker table,
' swept-sine' excitation and transfer function techniques were used.
The calibration is traceable to NBS.
The calibration of the velocity probes was verified in the field both before and after each baseline survey in the following manner.
The probes were mounted on a fixture back to back with an accelerometer (one velocity probe at a time).
The fixture was then attached to the engine under operating conditions. Using transfer function measurements on the two vibration signals the calibration of each velocity transducer and the associated signal conditioning equipment was verified in t.erms of the known output of the reference accelerometer.
The correct functioning of the reference accelerometer was verified in the field by employing a
' free-fall' technique that provided a momentary 1.0 g input to the system.
The overall accuracy of the subsequently performed vibration measurements is estimated to be +/- 10 per cent.
2.3 DIESEL GENERATOR DATA Engine Model DSR-48 Serial Number 81015-3057 Bore 17" Stroke 21" Engine Speed 450 rpm Firing Order 1,4,7,3,8,5,2,6 Generator Rated Output 3500 kW, 3-phase 4375 kVA 607.2 Amps.
Service Factor 1.0 5
3.0 MEASUREMENT AND ANALYSIS PROCEDURE The survey was carried out in accordance with a document issued by the TDI Owners Group and entitled:
" Test Procedure for Engine Baseline Vibration Survey for DSR-48 Engines". Vibration measurements were made at 35 points on the engine with the engine operated at 3500 kW, 500 kVAR synchronous load. The measurement locations are identified in Figures 2
and 2A.
A brief description of each measurement location is given in Table 2.
At each location measurements were made in as many of the axial (A), horizontal (H) and vertical (V) directions as permitted by local geometry.
The measurement axes were mutually perpendicular and the axial direction was paral 3 e1 to the axis of the crankshaft.
All measurements were taken using two velocity transducers.
One reference transducer was mounted on the generator outboard bearing (location No. 1), and kept there for the duration of the test.
Its function was to verify that the operating conditions remained the same throughout the test.
The second velocity probe served as a roving transducer at the measurement locations.
The output from both transducers was recorded on magnetic tape in analog form for later analysis.
The magnetic recordings were subsequently processed in the laboratory with a dual channel Fast Fourier Transform (FFT) analyzer to obtain velocity and displacement amplitudes in terms of in/see pk.
and mils p p respectively.
Plots of vibration amplitudes vs.
frequency were prepared in the frequency range of 0-100 Hz and the spectral amplitudes corresponding to 18 engine half orders were printed out.
The processed data presented in the Appendix were stored in digital form for future reference.
4.0 SURVEY RHSULTS The vibration spectra plotted in terms of both velocity and displacement are presented in Figures 3
through 70.
The frequency range covered is 0-100 Hz.
The amplitudes are plotted to a linear scale.
The vibration amplitudes of 18 engine half orders and the overall vibration levels have also been printed in Figures 3 through 70.
Tables 3
through 5 summarize the overall vibration levels observed at the various measurement locations on the engine.
Table 3
is organized according to measurement location while the entries in Tables 4 and 5 are sorted in desconding order of velocity and displacement amplitudes respectively.
The highest vibration level was measured on the turbo-charger at location 11.
The measured 4.92 in/sec pk. vibration is excessive and represents a rocking motion of the scroll case.
The motion 6
L
.is identical and comparable or slightly la on 1r 'similar engine ~
problem until the turbine exhaust athat experienced rger in amplitude than.
rrangement was modified.a-tu The overall
-locations are vibration
- levels, i
spectral peaks generally well.belowexcluding the turbo charger (Figures 3 1.0 in/sec. pk.
and the orders and half orders.
through 70). occur at the engine generall A vibration level of 1.0 in/see yk However,y considered acceptable for large diesel it. must be
.is accepted or in any pointed out that it is not engines.
'way official criterion and a comparisa univers similar engines in a better~ measure average overall (0-100 Hz) vibration level on with of measurements acceptability.
The i
on the
'A' engine is"0.2 in/see yk 20 per.
calculated from~the 54 A
cent lower than the corresponding. values measThis is'abouk other DSR-48 engines.
ured on two In general the
{
components only measured frequencies corresponding to 1
at the,
\\
orders and half orders.
the 4.0'th Most of.the vibration is concent engine order of the frequency ne (30.0 Hz).
content is normal for four cycle enginesThat vibration correspo.nding to the turbo charger is rotational The-shown in the
. expected to rotational spectr be well above 100 _Hz and is not speed of the of measurem. speed was.al Plots.
It is not known.what ents at two turbo charger locations (11HIn F
'that one prominent peak at 105 He 6300 rpm ). '
-0.177 and ~0.105 in/see pk..respec(tiv l c ra.
and 33V) show peak at Tme amplitudes are j
charger locations.105 Hz in the vibration spectra obtaiThere is no c e y.
ned at other turbo-7 a
5.0 CONCLUSION
S AND RECOMMENDATIONS A
careful' review of the data indicates that the measurements are accurate and consistent.
In general the measured vibration spectra contain significant components only at the-expected frequencies corresponding to the engine orders and half orders.
The distribution of the frequency content appears to be normal.
The vibration level on the turbo-charger was over 4.9 in/see pk. and must be considered excessive.
Similar vibration levels were observed on other DSR-48 engines before corrective modifications.
The average overall vibration level on engine
'A' was 0.2 in/see pk.
which is about 20 per cent lower than the corresponding vibration level measured on two other DSR-48 engines previously surveyed.
c i
APPENDIX 1
9
TABLE 1
RANCHO SECO NUCLEAR POWER STATION BASELINE VIBRATION SURVEY, DG
'A' NOV. 13, 1986
SUMMARY
OF FREQUENCY RESPONSE CHARACTERISTICS Flat Equipment Model Serial No.
Frequency Response, Hz Accelerometer PCB 308B 3772 1-5000 Cal. due 1/24/87 Velocity Probes Mark Products 203,206,303 8-2000 Cal. due 12/13/86 Preamplifier Trig-Tek 205B 103 0-100,000 Cal. due 7/23/87 Tape Recorder Teac R-71 160362 0-1250 Cal. due 4/16/87 FFT Analyser Nicolet 660B 5620079006 1-20,000 Cal. due 10/8/86 Overall System Response Acceleration 1-1250 Velocity 1-1250
TABLE 2 RANCBO SECO NUCLEAR POWER STATION BASELINE VIBRATION SURVEY, DG
'A' NOV. 13, 1986 MEASUREMENT DESCRIPTION OF MEASUREMENT LOCATIONS LOCATION 1
Generator Outboard Bearing 2A Skid, between Cylinders No. 7 and 8
2B Skid, between Cylinders No.'4 and 5
2C Skid, between Cylinders No. 1 and 2
3A Base of Engine, between Cylinders No. 7 and 8
3B Base of Engine, between Cylinders No. 4'and 5
3C Base of Engine, between Cylinders No..1 and 2-4A Casing, Crankshaft Level, between Cyl. No. 7 and 8 4B Casing, Crankshaft Level, between Cyl. No. 4 and 5 4C
. Casing, Crankshaft Level, between Cyl. NO. 1 and 2.
I SA Top of Casing, between Cylinders No. 7 and 8
SB Top of Casing, between Cylinders No. 4 and 5
SC Top of Casing, between Cylinders No. 1 and 2
'6A Cylinder Bead, between Cylinders No. 7 and 8
6B Cylinder Head, between Cylinders No. 4 and 5
6C Cylinder Head, between Cylinders No; 1 and 2
11 Turbocharger Compressor Casing, 12 o' clock Position 14 Turbocharger Compressor Casing, 9 o' clock Position 16 Engine Casing, Crankshaft Level, Near Flywheel 19 Turbocharger End of Lube Oil Cooler 20 Generator End of Lube Oil Cooler 21 Top of Lube Oil Filter 22 Top of Lube Oil Filter 23 Turbocharger Support 24
- 1 Cylinder, Bead Bolt on Intake Side 25
- 2 Cylinder, Head Bolt on Intake Side 26
- 3 Cylinder, Head Bolt on Intake Side 27
- 4 Cylinder, Head Bolt on Intake Side 28
- 5 Cylinder, Head Bolt on Intake Side 29
- 6 Cylinder, Head Bolt on Intake Side 30
- 7 Cylinder, Bead Bolt on Intake Side 31
- 8 Cylinder, Head Bolt on Intake Side 32 Top of Jacket Water Standpipe l
33 Top of Turbine of Turbocharger-34 Centerline of Turbine of Turbocharger L_____ ________ _ __ _ ___
.)
TABLE 3 RANCHO SECO NUCLEAR POWER STATION BASELINE VIBRATION SURVEY, DG
'A' NOV. 13, 1986 OVERALL VIBRATION LEVELS 7-100 Hz BY LOCATION L
Measurement Velocity Displacement i
Locations in/sec pk.
mils pp 1A 0.300 2.18 1B 0.146 1.18 1V 0.180 1.54 2A B 0.025 0.24 2A V 0.022 0.20 2B H 0.027 0.41 2B V 0.023 0.40 2C H 0.026 0.28 2C V 0.022 0.22 3A H 0.051 0.49 3A V 0.040 0.39 3B H 0.052 1.31 3B V 0.042 0.98 3C H 0.042 0.51 3C V 0.031 0.36 4A B 0.211 2.48 4A V 0.089 0.92 4B H 0.169 3.90 4B V 0.081 1.89 4C H 0.143 2.18 SA H 0.427 4.60 SA V 0.127 1.35 SB H 0.393 4.09 SB V 0.127 2.82 SC H 0.301 3.69 SC V 0.100 1.33 6A B 0.657 6.94 6B H 0.576 5.68 6C H 0.419 5.17 11 A 2.120 25.5 11 H 4.920 63.7 11 V 1.410 22.6 14 A 1.620 17.4 14 H 2.620 31.6 14 V 1.500 18.8 16 A 0.054 0.70 16 H 0.140 2.28 16 V 0.114 1.92 19 A 0.414 2.15 19 H 0.168 0.92 19 V 0.387 2.28 20 A 0.410 2.14 20 H 0.158 1.28
TABLE 3 (cont'd)
RANCHO SECO NUCLEAR POWER STATION BASELINE VIBRATION SURVEY, DG
'A' NOV. 13, 1986 OVERALL VIBRATION LEVELS 7-100 Hz BY LOCATION Measurement Velocity Displacement Locations in/sec pk mils pp 20 V 0.652 3.61 21 A 0.137 3.54 21 H 0.055 0.95 21 V 0'.027 0.41 22 A 0.156 3.29 22 H 0.060 0.80 22 V 0.049 0.30 23 A 0.714 7.83 23 H 1.130 13.40 23 V 0.113 0.73 24 V 0.277 5.26 25 V 0.252 4.47 26 V 0.234 4.41 27 V 0.240 4.58 28 V 0.246 5,19 29 V 0.230 4.24 30 V 0.236 4.54 31 V 0.238 4.47 32 A 0.657 6.44 32 H 0.594 7.08 33 A 1.450 15.40 33 8 2.890 32.70 33 V 1.150 12.80 34 A 1.110 11.80 34 H 2.390 27.30 I
t
TABLE 4 RANCHO SECO NUCLEAR POWER STATION BASELINE VIBRATION SURVEY, DG
'A' NOV. 13, 1986 OVERALL VIBRATION LEVELS 7-100 Hz BY VELOCITY AMPLITUDES Measurement Velocity Displacement Locations in/sec pk mils pp 11 H 4.920 63.70 33 H 2.890 32.70 14 H 2.620 31.60 34 8 2.390 27.30 11 A 2.120 25.50 14 A 1.620 17.40 14 V 1.500 18.80 33 A 1.450 15.40 11 V 1.410 22.60 33 V 1.150 12.80 23 H 1.130 13.40 34 A 1.110 11.80 23 A 0.714 7.83 6A H 0.657 6.94 32 A 0.657 6.44 20 V 0.652 3.61 32 H 0.594 7.08 6B B 0.576 5.68 SA H 0.427 4.60 6C H 0.419 5.17 19 A 0.414 2.15 20 A 0.410 2.14 SB B 0.393 4.09 19 V 0.387 2.28 SC H 0.301 3.69 1A 0.300 2.18 24 V 0.277 5.26 25 V 0.252 4.47 28 V 0.246 5.19 27 Y 0.240 4.58 31 V 0.238 4.47 30 V 0.236 4.54 26 V 0.234 4.41 29 V 0.230 4.24 4A B 0.211 2.48 l
1V 0.180
'1.54 l
4B B 0.169 3.90 19 H 0.168 0.92 20 H 0.158 1.28 22 A 0.150 3.29 1H 0.146 1.18 4C H 0.143 2.18 16 H 0.140 2.28 1
I I
TABLE 4 (cont'd)
RANCHO SECO NUCLEAR POWER STATION L
BASELINE VIBRATION SURVEY, DG
'A' NOV. 13, 1986 OVERALL VIBRATION LEVELS 7-100 Hz BY VELOCITY AMPLITUDES Measurement Velocity Displacement
~
Locations in/sec pk mils pp 21 A 0.137 3.54 5A 'i 0.127 1.35 SB V 0.127 2.82 16 V 0.114 1.92 23 V 0.113 0.73 SC V 0.100 1.33 4A V 0.089 0.92 4B V 0.081 1.89 l
22 H 0.060 0.80 l
21 H 4.055 0.95 l
16 A s.054 0.70 I
3B H 0.052 1.31 I
3A H 0.051 0.49 l
22 V 0.049 0.30 l
3B V 0.042 0.98 3C H 0.042 0.51 3A V 0.040 0.39 3C V 0.030 0.36 21 V 0.027 0.41 2B H 0.027 0.41 2C H 0.026 0.28 2A B 0.025 0.24 2B V 0.023 0.40 2A V 0.022 0.20 2C V 0.022 0.22
TABLE 5 RANCHO SECO NUCLEAR POWER STATION BASELINE VIBRATION SURVEY, DG
'A' NOV. 13, 1986 OVERALL VIBRATION LEVELS 7-100 Hz BY DISPLACEMENT AMPLITUDES Measurement Velocity Displacement Locations in/sec pk mils pp 3
11 H.
4.920 63.70 33 H
'2.890 32.70 14 H 2.620 31.60
-34 H 2.390 27.30 11 A 2.120 25.50 11 V 1.140 22.60 14 V 1.500 18.80
.14 A 1.620 17.40 33 A 1.450 15.40 23 H 1.130 13.40 33 V 1.150 12.80 34 A 1.110 11.80 23 A 0.714 7.83 32 H 0.594 7.08 6A H 0.657 6.94 32 A 0.657 6.44 6B H 0.576 5.68 24 V 0.277 5.26 28 V 0.246 5.19 BC H 0.419 5.17 5A H 0.427 4.60 27 V 0.240 4.58 30 V 0.236 4.54 25 V 0.252 4.47 31 V 0.238 4.47 26 V 0.234 4.41 29 V 0.230 4.24 SB B 0.393 4.09 4B H 0.169 3.90 SC H 0.301 3.69
-20 V 0.652' 3.61 1
21 A 0.137 3.54 22 A 0.156 3.29 SB V 0.127-2.82 4A H 0.211 2.48 19 V 0.387 2.28 16 H 0.140 2.28 1A 0.300 2.18 4C H 0.143 2.18 19 A O.414 2.15 20 A 0.410 2.14 16 V 0.114 1.92 4B V 0.081 1.89 L__
TABLE 5 (cont'd)
RANCHO SECO NUCLEAR POWER STATION BASELINE VIBRATION SURVEY, DG
'A' NOV. 13, 1986 OVERALL VIBRATION LEVELS 7-100 Hz BY DISPLACEMENT AMPLITUDES Measurement Velocity Displacement Locations-in/sec pk mils-pp 1V 0.180 1.54 5A V 0.127 1.35 50 V 0.100 1.33 3B H 0.052 1.31 20 H 0.158 1.28 1H 0.146 1.18 3B V 0.042 0.98 21 H 0.055 0.95 19 H 0.168 0.92 4A V 0.089 0.92 22 B 0.060 0.80 23 V 0.113 0.73 16 A 0.054 0.70 3C B 0.042 0.51 3A B 0.051 0.49 2B B 0.027 0.41 21 V 0.027 0.41 2B V 0.023 0.40 3A V-0.040 0.39 3C V 0.030 0.36 22 V 0.049 0.30 2C H 0.026 0.28 2A H 0.025 0.24 2C V 0.022 0.22 2A Y 0.022 0.20 1
1 4
i
1 N
PREAMPLIFIER
]
TRIG-TEK
( 30' 205B N
i I
N
( 60'
_,l COMPUTER N
HP 9826 l
[
I PM TAPE l
VELOCITY PROBE RECORDER l
REFERENCE TEAC R-71 C
1 i
VELOCITY PROBE l
R0vER i
SIGNAL l
MONITOR /
g ANALYZER NICOLET 660B VIBRATION BASELINE SURVEY SCHEMATIC FIGURE 1
l L
I 5
a s
1 I
W D
.I i,
E C
j
$o e
1 a H
E$
,Q g
I
~Wg cy 3 Hy 285 lg e:
x w..c, m
4
_w w
y: _ a n '+e. z,4
~
{@ji 1,-
- @ l @.
~
e -
o i
% /
^
s 9
(
n
- .. ?
O '* >'--
~
t)e n_
r-C' Q-I q)
I e
a c
D I
nE L.O.
a 5
g l
_,J
=
p A
b
\\
e
/
o I \\
5' (R
==
gg ji
,- ummmu
(-
x j
I e
I I
W-M j
i i i
I s __
I i
1 x
w f
,r fle f I (e l II
O a
N e
I y-g u
L________
5 3
5 0
H EEg k
l W"o 3*5 I i
[
p _r4
')
C*"
rj Na
-- Gl V '
C I:
CZ I: CZ 7-g_
1:
00 C_
u I:
' O C ~-
DCa I:
O C
9 I:
3-4> l' 8
I,fx_
.._ C'O
//\\\\
(5) f_. i *
~
/
( )
B e 4 bI es 2.
e
@ s,,
c w}
e y
-g,
~__
v
.______-___-________m
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 198E Measurement Location 1 AXIAL ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p
!.0 7.50 13.6-03 572.-03 1.5 11.25 5.81-03 164.-03 2.0 15.00 8.20-03 175.-03 2.5 18.75 13.0-03 220.-03 3.0 22.50 26.8-03 380.-03 3.5 26.25 17.8-03 215.-03 4.0 30.00 18.7-03 198.-03 4.5 33.75 40.7-03 382.-03 5.0 37.50 190.-03 1.6t+00 5.5 41.25 39.4-03 302.-03 6.0 45.00 52.1-03 367.-03 6.5 48.75 84.6-03 549.-03 7.0 52.50 21.3-03 128.-03 7.5 56.25 53.8-03 302.-03 8.0 60.00 55.0-03 289.-03 8.5 63.75 113.-03 560.-03 9.0 67.50 93.3-03 434.-03 9.5 71.25 65.9-03 290.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 300.-03 2.18+00 1.09+0B V/ER 300.-03 E VLN 546.-06 V/EB 2.50+00 E C
RANCHO SECO D I E S E L, G E N,.
'A'
,1 1 / 1,3 / 0 6 A..
n.. VELOCITY in/sec pk 1 RXIAL SU 2 7.
16 7 RS
((DISPLRCCMENT mtIs p-p
].
B[,,
((
M.
p 1
i
~~
f L^(biLit)
AAkAJU.<
I FIGURE 3
s STONE a
WEBSTER ENGINEERING CORP.
Acoustics Vibrations L. ab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' I
I Date of Survey:
NOV 13, 1986 Measurement Location 1 HDRIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 12.1-03 513.-03 1.5 11.25 1.40-03 39.9-03 2.0 15.00 11.2-03 237.-03 2.5 18.75 3.00-03 51.1-03 3.0 22.50 19.3-03 273.-03 3.5 26.25 15.8-03 191.-03 4.0 30.00 44.0-03 465.-03 4.5 33.75 42.0-03 395.-03 5.0 37.50 50.2-03 424.-03 5.5 41.25 18.5-03 142.-03 6.0 45.00 52.6-03 370.-03 6.5 48.75 39.8-03 258.-03 7.0 52.50 21.1-03 127.-03 7.5 56.25 62.8-03 353.-03 8.0 60.00 31.2-03 164.-03 8.5 63.75 52.1-03 257.-03 9.0 67.50 21.8-03 101.-03 9.5 71.25 16.5-03 72.5-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 146.-03 1.18+00 2.72+00 V/ER 100.-03 E VLN 1.37-03 V/EB B00.-03 E C
RRNCHO sECO D I E 3 E L, G E N,.
'R'
,11/1,3/86 R__
in/sec pk VELOCITY M-1 HORIZ.
SU l
l le T l
J t
-J J
as
{
_ DISPLACEMENT mtis pp B
M N
)
N i
b
.d. I _ Ji 1 ! k lLi n a.en a.es a/2 s sz tes t
I Fr I C3 LJ FR E-e'4
STONE a
WEBSTER ENGINEERING CORP.
Acoustics a
Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 1 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
uils p p I.0 7.50 17.9-03 763.-03 1.5 11.25 5.07-03 144.-03 2.0 15.00 8.73-03 185.-03 2.5 18.75 12.4-03 210. 30 22.50 22.0-03 312.~03 3.5 26,25 12.3-03 148.-03 4.0 30.00 21.3-03 225 -03 4.5 33.75 25.0-03 235.-03 5.0 37.50 134.-03 1.f4+00 5.5 41,25 25.3-03 194.-03 6.0 45.00 25.2-03 177.-03 6.5 48.75 58.3-03 378.-03 7.0 52.50 13.4-03 80.6-03 7.5 56.25 24.1-03 135.-03 8.0 60.00 21.2-03 111.-03 8.5 63.75 55.0-03 271.-03 9.0 67.50 44.1-03 205.-03 9.5 71.25 22.3-03 98.0-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 180.-03 1.54+00 2.72+00 V/ER 200.-03 E VLN 1.37-03 V/EB 2.00+00 E C
RRNCHO,5ECO D I E S E L, G E N,.
- R'
,1 1 / 1,3 / 9 6 R
1 VELOCITY t n /s er e pk M
t VERT.
1 SU 16 ---
pg
$$ DISPLACEMENT miis pp M__
J J.
3 4 A LA_i a A__ x.1_.l. s <b.,..
FIGURE 5
STONE WEBSTER ENGINEERING CORP.
Acoustics V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' E
5 Date of Survey:
NOV 13, 1986 Measurement Location 2A HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p
!.0 7.50 1.50-03 63.2-03 1.5 11.25 1.81-03 51.4-03 2.0 15.00 1.24-03 26.4-03 2.5 18.75 2.47-03 41.8-03 3.0 22.50 2.28-03 32.1-03 3.5 26.25 6.95-03 83.8-03 4.0 30.00 13.7-03 145.-03 4.5 33.75 2.59-03 24.4-03 5.0 37.50 4.11-03 34.8-03 5.5 41.25 15.4-03 118.-03 6.0 45.00 1.75-03 12.3-03 6.5 48.75 4.49-03 29.2-03 7.0 52.50 2.23-03 13.3-03 7.5 56.25 5.46-03 30.7-03 8.0 60.00 t.47-03 7.77-03 8.5 63.75 5.72-03 28.5-03 9.0 67.50 1.03-03 4.81-03 9.5 71.25 1.26-03 5.61-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 25.1-03 240.-03 5.45+00 V/ER 25.0-03 E VLN 2.73-03 V/EB 250.-03 E C
RANCHO SECO D I E s E L, G E N,.
"R"
,1 1 / 1,3 / 0 5 A..
M -
VELOCITY t n / s sr c pk d.
2R HORIZ.
SU..
f 16 --
RS
[_ DISPLACEMENT mtis p-p T.
M.-
l
.+
1 l
bk)_A1A$
LlI 4 L A.3 _..
[
t i
FIGURE 6
l STONE a
WEBSTER ENGINEERING CORP.
Acousties a
V1brations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR *A' Date of Survey:
NOV 13. 1986 Measurement Location 2A VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 936.-06 39.7-03 1.5 11.25 1.63-03 46.3-03 2.0 15.00 878.-06 18.7-03 2.5 18.75 1.60-03 27.1-03 3.0 22.50 1.11-03 15.7-03 3.5 26.25 5.04-03 60.9-03 4.0 30.00 9.80 03 104.-03 4.5 33.75 1.91-03 17.9-03 5.0 37.50 10.4-03 88.0-03 5.5 41.25 13.0-03 99.6-03 6.0 45.00 1.65-03 11.6-03 6.5 48.75 758.-06 4.88-03 7.0 52.50 1.66-03 9.93-03 7.5 56.25 4.70-03 26.4-03 8.0 60.00 1.15-03 6.08-03 8.5 63.75 4.76-03 23.5-03 9.0 67.50 2.28-03 10.6-03 9.5 71.25 1.44-03 6.32-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 22.1-03 202.-03 10.9+00 V/ER 20.0-03 E VLN 5.45-03 V/EB 200.-03 E C
RRNCHO SECO DIESEL, GEN.
"R"
,1 1 / 1,3 / 9 5 A..
VELOCITY in/sec pk M-
'R VERT.
l SU.
16 --
Mk.
J pg
(( DISPLACEMENT mtis p-p g __
M..
T l
T l
~-
h LLLdL.Abo A L..,m 2.OA 2.OA A 16 HZ LOO t__ _
e FIGURE 7
STONE WEBSTER ENGINEERING CORP.
Acoustics V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' s
Date of Survey:
NOV 13, 1986 Measurement Location 2B HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p I.0 7.50 10.2-03 436.-03 1.5 11.25 125.-06 3.68-03 2.0 15.00 2.46-03 52.1-03 2.5 18.75 1.28-03 21.7-03 3.0 22.50 2.53-03 35.8-03 3.5 26,25 7.93-03 96.0-03 4.0 30.00 13.6-03 143.-03 4.5 33.75 791.-06 7.45-03 5.0 37.50 3.94-03 33.3-03 5.5 41.25 17.6-03 135.-03 6.0 45.00 2.31-03 16.3-03 6.5 48,75 2.69-03 17.4-03 7.0 52.50 1.31-03 7.87-03 7.5 56.25 2.39-03 13.4-03 8.0 60.00 3.39-03 17.8-03 8.5 63.75 2.40-03 11.8-03 9.0 67.50 1.34-03 6.24-03 9.5 71.25 371.-06 1.60-03 Overall Vibration Level 25.0 Hz to 1000.0 H2 26.6-03 409.-03 10.9+00 V/ER 25.0-03 E VLN 5.46-03 V/EB 500.-03 E C
RRNCHO SECO DIESEL, GEN,.
"R"
,1 1 / 1,3 / B 6 VELOCITY in/see pk 2B HORI2..
SU S f
r
~
Ad d O -
h~
Rs
$ DISPLACEMENT mtis p-p
~
s::
M 7
a. A,.A I a
.x._
2.OR 2.OA A/16 HZ 100 i
f Fr I C3 LJ FR EE E3
STONE a
WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 2B VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 10.5-03 446.-03 1.5 11.25 111.-06 3.17-03 2.0 15.00 2.64-03 56.1-03 2.5 18.75 1.10-03 18.6-03 3.0 22.50 3.15-03 44.6-03 3.5 26.25 7.32-03 88.5-03 4.0 30.00 9.12-03 96.5-03 4.5 33.75 496.-06 4.62-03 5.0 37.50 5.53-03 46.8-03 5.5 41.25 14.4-03 111.-03 6.0 45.00 1.38-03 9.71-03 6.5 48.75 5.31-03 34.4-03 7.0 52.50 1.24-03 7.41-03 7.5 56.25 2.06-03
!!.6-03 8.0 60.00 1.03-03 5.41-03 8.5 63.75 2.08-03 10.3-03 9.0 67.50 2.42-03 11.3-03 9.5 71.25 2.76-03 12.1-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 23.0-03 396.-03 10.9+00 V/ER 25.0-03 E VLN 5.46-03 V/EB 500.-03 E C
RRNCHO SECO D I E S E L, G E N,.
"R"
,11/1,3/06 A..
. VELOCITY ir,/see pk g.
.l.
2B VERT.
su::
16 --
gg
[ DISPLACEMENT mtis p-p
~
M._
I LAA8 d a..
m t
a FIGURE 9
______________ - __ a
STONE WEBSTER ENGINEERING CORP.
Acoustics V 16 r a t l o ri s Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERAIOR
'A' 5
3 Date of Survey:
NOV 13, 1986 Measurement Location 2C HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 3.78-03 162.-03 1.5 11.25 1.97-03 55.7-03 2.0 15.00 1.80-03 38.2-03 2.5 18.75 2.57-03 43.7-03 3.0 22.50 636.-06 9.00-03 3.5 26.25 9.73-03 118.-03 4.0 30.00 11.5-03 122.-03 4.5 33.75 2.06-03 19.4-03 5.0 37.50 3.10-03 26.3-03 5.5 41.25 16.2-03 124.-03 6.0 45.00 3.05-03 21.4-03 6.5 48.75 5.86-03 38.i-03 7.0 52.50 f.59-03 9.68-03 7.5 56.25 4.58-03 25.8-03 8.0 60.00 4.45-03 23.4-03 8.5 63.75 1.08-03 5.39-03 9.0 67.50 2.16-03 10.1-03 9.5 71.25 3.58-03 15.8-03 j
Overall Vibration Level 25.0 Hz to 1000.0 Hz 26.1-03 276.-03 5.45+00 V/ER 25.0-03 E
.VLN 2.73-03 V/EB 200.-03 E C
RRNCHO SECO D I E S E L, G E N,.
- R*
,11/1,3/06 g
~
VELOCITY in/see pk j
Mf
'C HORIZ.
+
E-U j
.J g
Rs _ _LutJLhu
)
A 2
[.~ DISPLACEMENT m11s p-p e::
M..
j j
l I
l
_rj L1 A__I8 4.1A # _A.. A 1
8 FIGURE 1O
STONE a
WEBSTER ENGINEERING CORP.
Acoustics Ulbrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' B
B Date of Survey:
NOV 13, 1986 Measurement Location 2C VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT l
Hz in/sec pk.
mils p p l
1.0 7.50 1.63-03 69.2-03 1.5 11.25 1.65-03 46.9-03 2.0 15.00 527.-06 11.3-03 2.5 18.75 2.42-03 41.0-03 3.0 22.50 667.-06 9.51-03 3.5 26,25 9.60-03 116.-03 4.0 30.00 11.0-03 I17.-03 4. 5.
33.75 3.77-03 35.4-03 5.0 37.50 2.02-03 17.0-03 5.5 41.25 11.6-03 89.4-03 6.0 45.00 2.59-03 18.1-03 6.5 48.75 5.39-03 35.0-03 7.0 52.50 640.-06 3.88-03 7.5 56.25 2.76-03 15.5-03 8.0 60.00 2.93-03 15.4-03 8.5 63.75 1.65-03 8.13-03 9.0 67.50 2.54-03 if.8-03 9.5 71.25 4.11-03 18.1-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 22.1-03 222.-03 10.9+00 V/ER 20.0-03 C VLN 5.46-03 V/CB 200.-03 C C
RANCHO SECO DIE 5EL, GEN,.
'R'
,1 1 / 1,3 / 0 6 f
A g
VELOCITY 6n/sec pk
'C VERT.
SU j
26 T pg DISPLACEMENT mtis p-p 3
M.
j I
I LA
_ A 1. 2 AAm a, i
_1
~
2.OA 2.OA A/16 HZ 100 t
g FIGURE 11 i
i
STONE WEBSTER ENGINEERING CORP.
Acoust1es a
V16 rations Lab.
VIBRATION BASEl'NE SURVEY, RANCHO SECO DIESEL GENERATOR
'A'
.w Date of Survey:
NOV 13, 1986 Measurement Location 3A HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/seC pk.
mils p p I.0 7.50 6.05-03 257.-03 1.5 11.25 2.22-03 62.3-03 2.0 15.00 4.19-03 88.8-03 2.5 18.75 3.32-03 56.2-03 3.0 22.50 9.60-03 136.-03 3.5 26.25 5.78-03 70.1-03 4.0 30.00 24.6-03 260.-03 4.5 33.75 8.50-03 79.9-03 5.0 37.50 17.5-03 148.-03 5.5 41.25 26.7-03 205.-03 6.0 45.00 5.74-03 40.3-03 6.5 48.75 15.3-03 99.0-03 7.0 52.50 4.94-03 29.7-03 7.5 56.25 12.9-03 72.2-03 8.0 60.00 4.27-03 22.3-03 8.5 63.75 10.9-03 53.8-03 9.0 67.50 1.09-03 5.06-03 9.5 71.25 3.18-03 13.9-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 50.7-03 491.-03 i
l 5.45+00 V/ER 40.0-03 E VLN l
2.73-03 V/EB 400.-03 E C
RRNCHO SECO D I E S E L, G E N,,
'R'
,1 1 / 1,3 / 0 5
[$ VELOCITY enesse pk 2
3R HCRIZ. 1 j
is --
4 J
pg
$$ DISPLACEMENT mtis p-p MU f.
I i uhu utu a &..
I FIGURE 12
STONE a
WEBSTER ENGINEERING CORP.
Acoustics V1 bra.tions Lab.
VIBRATION BASELINE SURVEY.
RANCHO SECO DIESEL GENERATOR 'A' i
i Date of Survey:
NOV 13, 1986 Measurement Location 3A VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 2.13-03 91.1-03 1.5 11.25 3.75-03 106.-03 2.0 15.00 2.14-03 45.8-03 2.5 18.75 3.38-03 57.4-03 3.0 22.50 7.54-03 107.-03 3.5 26.25 6.79-03 82.3-03 4.0 30.00 19.7-03 209.-03 4.5 33.75 5.66-03 53.2-03 5.0 37.50 20.2-03 172.-03 5.5 41.25 20.1-03 155.-03 6.0 45.00 1.62-03 11.5-03 6.5 48.75 7.10-03 46.1-03 7.0 52.50 3.67-03 22.1-03 7.5 56.25 9.03-03 50.7-03 8.0 60.00 4.88-03 25.7-03 8.5 63.75 4.88-03 24.1-03 9.0 67.50 1.41-03 6.57-03 9.5 71.25-823.-06 3.68-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 40.3-03 390.-03 5.45+00 V/ER 30.0-03 E VLN 2.73-03 V/EB 300.-03 E C
RRNCHO SECO D I E S C L, G E N,.
"R"
,1 1 / 1,3 / 0 6 g,_
g__ VELOCITY in/sme pk 3R VERT.
SU$~
16 --
J pg
[~_ DISPLACEMENT mils p-p B',"
- ~
l M..
A L_A
, a
_,i,_a I
___ u t 4 i
I FIGURE 13 l
_____-____--__u
STONE a
WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' Drite of Survey:
NOV 13.1986 Measurement Location 38 HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 38.6-03 1,63 00 1.5 11.25 908.-06 25.9-03 2.0 15.00 6.46-03 137.-03 2.5 18.75 1.89-03 32.0-03 3.0 22.50 2.94-03 41.6-03 3.5 26.25 11.7-03 141.-03 4.0 30.00 20.3-03 216.-03 4.5 33.75 3.31-03 31.1-03 5.0 37.50 9.64-03 81.6-03 5.5 41,25 28.8-03 221.-03 6.0 45.00 3.90-03 27.5-03 6.5 48.75 9.19-03 59.6-03 7.0 52.50 3.74-03 22.5-03 7.5 56.25 6.22-03 35.0-03 8.0 60.00 5.70-03 29.8-03 8.5 63.75 4.52-03 22.3-03 9.0 67,50 6.07-03 28.2-03 9.5 71.25 2.04-03 8.91-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 52.2-03 1.31+00 j
5.45+00 V/ER 50.0-03 E VLN 2.73-03 V/EB 2.00+00 E C
RANCHO SECO DIE 5EL, GEN,.
'R'
,1 1 / 1,3 / 0 6 A..
M-VELOCITY in/sec pk 3D HCRIZ...
J SU..
l 16 --
l 9
RS W
-Ad
(( DISPLACEMENT mtis p-p
((
s::
M..
{
l fl 1 i s
.xaa.
m 2.OR 2.OA A/16 HZ 100 I
1 FIGURE 14
___m-___
._a___
J STONE a
WEBSTER ENGINEERING CORP.
Acoustics a
Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' Date of Survey:
NOV 13, 1986 Measurement Location 3B VERT.
1 ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT l
Hz in/sec pk.
mils p p 1.0 7.50 27.6-03 1.17 00 1.5 11.25 501.-06 14.2-03 2.0 15.00 7.93-03 168.-03 l
2.5 18.75 460.-06 7.76-03 3.0 22.50 9.13-03 129.-03 3.5 26.25 10.2-03 I23.-03 4.0 30.00 19.0-03 201.-03 4.5 33.75 908.-06 8.48-03 5.0 37.50 7.00-03 59.2-03 5.5 41.25 21.6-03 166.-03 6.0 45.00 2.25-03 15.8-03 6.5 48.75 9.72-03 63.0-03 7.0 52.50 4.18-03 25.1-03 7.5 56.25 3.14-03 17.6-03 8.0 60.00 715.-06 3.76-03 8.5 63.75 4.01-03 20.0-03 9.0 67.50 2.01-03 9.29-03 9.5 71.25 3.06-03 13.4-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 41.9-03 975.-03 5.45+00 V/ER 40.0-03 E VLN 2.73-03 V/EB 1.50+0B E C
RANCHO,5ECO DIE 5EL, GEN,.
'R'
,11/1,3/05
[ VELOCITY tn/sec pk
."[
3B VCRT.
su::
J 16 --
l b
L A.'
g, a
.=
2 DISPLACEMENT mtis p-p MA h
I
[:
~C_]
k__. A A b
+I
~~
i i
i 2 OR 2.OA A/18 HZ 100 t
f FIGURE 15
STONE a
WEBSTER ENGINEERING CORP.
Acoustics a
V1brations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' Date of Survey:
NOV 13, 1986 Measurement Location 3C HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 10.7-03 454.-03 1;5 11.25 428.-06 12.0-03 2.0 15.00 1.97-03 41.8-03 l
2.5 18.75 1.46-03 25.0-03 3.0 22.50 3.t8-03 44.9-03 3.5 26.25 18.4-03 223.-03 4.0 30.00 15.9-03 168.-03 4.5 33.75 4.58-03 43.1-03 5.0 37.50 10.1-03 85.8-03 5.5 41.25 20.8-03 160.-03 6.0 45.00 5.78-03 40.8-03 6.5 48.75 12.3-03 80.0-03 7.0 52.50 3.50-03 21.1-03 7.5 56.25 9.69-03 54.7-03 8.0 60.00 8.53-03 45.0-03 8.5 63.75 2.64-03 13.1-03 9.0 67.50 2.75-03 13.0-03 9.5 71.25 6.04-03 26.7-03 Overall Vibration Level 25.0 Hz to 1000,0 Hz 42.0-03 510.-03 2.72+00 V/ER 30.0-03 E VLN 1.37-03 V/EB 500.-03 C C
RANCHO SECO DIE 5EL, GEN,.
'A'
,1 1 / 1,3 / B 5 A..
g..
VELOCITY tn/sec pk 3C HORIZ...
su::
i 16 --
y pg L.
J b
(( DISPLACEMENT m11s p-p 5
e::
M..
I l_.t.A1.AJl d)Lda a
...m.
2.OA 2.GR A/16 HZ 1GG I
I FIGURE 16
STONE WEBSTER ENGINEERING CORP.
Acoustics V i b r a t i o ri s Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL.2NERATOR 'A' i
i Date of Survey:
NOV 13, 1986 Measurement Location 3C VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1 '. 0 7.50 5.25-03 222.-03 1.5 11.25 3.64-03 103.-03 2.0 15.00 1.45-03 30.7-03 2.5 18.75 6.02-03 102.-03 3.0 22.50 1.98-03 28.0-03 3.5 26.25 13.9-03 169.-03 4.0 30.00 15.4-03 163.-03 4.5 33.75 5.28-03 49.6-03 5.0 37.50 4.58-03 38.7-03 5.5 41.25 13.1-03 (01.-03 6.0 45.00 3.97-03 28.0-03 6.5 48.75 7.43-03 48.5-03 7.0 52.50 1.52-03 9.17-03 7.5 56.25 5.31-03 29.8-03 8.0 60.00 4.21-03 22.1-03 8.5 63.75 7.18-03 15.6-03 9.0 67.50 2.40'-03 11.2-03 9.5 71.25 4.72-03 20.9-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 30.5-03 362.-03 5.45+00 V/ER 25.0-03 E VLN 2.73-03 V/EB 250.-03 E C
RANCHO SECO DIE 5EL, GEN,.
'R'
,1 1 / 1,3 0 5 A..
g..
VELOCITY t n / s e c: pk 3C VERT.
SU$$
16 --
iL pg
$$ DISPLACEMENT mels p-p
][
B$$
M..
d1; MLAJ blA_I.A3oA.mi
-~
_t.
2.OA 2.OA A/16 HZ 100 f
I FIGURE 17
i STONE a
WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' g
5 Date of Survey:
NOV 13, 1986 Measurement Location 4A HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p i
1.0 7.50 11.7-03 499.-03 l
1.5 11.25 37.3-03 1.06+00 2.0 15.00 43.3-03 918.-03 2.5 18.75 32.5-03 551.-03 3.0 22.50 60.4-03 853.-03 3.5 26.25 22.7-03 275.-03 4.0 30.00 107.-03 1.14+00 4.5 33.75 40.8-03 384.-03 5.0 37.50 87.1-03 737.-03 5.5 41.25 87.3-03 672.-03 6.0 45.00 20.5-03 145.-03 6.5 48.75 60.6-33 393.-03 7.0 52.50 5.13-03 31.2-03 7.5 56.25 35.8-03 201.-03 8.0 60.00 19.6-03 l02.-03 8.5 63.75 15.9-03 78.8-03 9.0 67.50 3.86-03 18.1-03 9.5 71.25 7.95-03 35.0-03 Overall Vibration Level i
25.0 Hz to 1000.0 Hz 211.-03 2.48+00 1.09+DO V/ER 200.-03 E VLN 546.-05 V/EB 2.00+00 E C
RRNCHO SECO D I E S E L, G E N,.
- R'
,1 1 / 1,3 / 0 5 A._
g__ VELOCITY
$n/mme pk 4R HORIZ, __
SU_$
g6__
l U
1 jdI AJ C __ ~ - d Rs
$$ DISPLACEMENT mtIs p-p
[~
g--
M.
J
[_
j l
i t
j
~:
A A bl
.A._,a
~
FIGURE 18
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 4A VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p I.0 7.50 3.54-03 150 -03 1.5 11.25 8.85-03 250.-03 2.0 15.00 8.32-03 177.-03 2.5 18.75 11.3-03 192.-03 3.0 22.50 22.3-03 315.-03 3.5 26.25 17.8-03 215.-03 4.0 30.00 48.3-03 511.-03 4.5 33.75 12.1-03 113.-03 5.0 37.50 4!.3-03 350 -03
[
5.5 41.25 40.3-03 310.-03
{
6.0 45.00 4.97-03 35.0-03 6.5 48.75 16.3-03 105.-03 7.0 52.50 5.19-03 31.2-03 7.5 56.25 14.9-03 83.4-03 8.0 60.00 8.01-03 42.2-03 8.5 63.75 6.84-03 33.3-03 9.0 67.50 1.18-03 5.36-03 9.5 71.25 491.-06 2.22-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 88.9-03 918.-03 2.72+00 V/ER 80.0-03 E VLN 1.37-03 V/EB 800.-03 E C
RRNCHO SECO D I E S E L, G E N,.
'R'
,1 1 / 1,3 / 8 5 A..
VELOCITY in/sec pk M-4A VERT.
SU_-
l t
16 --
I J
pg
[ DISPLACEMENT mtis p-p
((
e::
M__
I l
1
\\
hNlb LU, lam _,
._c-2.OA 2.OR A/1S HZ 100 3
J FIGURE 19
STONE a
WEBSTER ENGINEERING CORP.
Acoustics a
V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' 5
5 Date of Survey:
NOV 13, 1986 Heasu.rement Location 4B HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 108.-03 4.57 00 1.5 11.25 2.22-03 62.9-03 2.0 15.00 56.0-03 1.19+00 2.5 18.75 8.24-03 140.-03 3.0 22.50 25.7-03 363.-03 3.5 26.25 30.4-03 367.-03 4.0 30.00 91.5-03 969.-03 4.5 33,75 17.5-03 164.-03 5.0 37.50 26.8-03 227.-03 5.5 41.25 69.0-03 529.-03 6.0 45.00 11.3-03 79.4-03 6.5 48.75 23.5-03 153.-03 7.0 52.50 13.9-03 83.6-03 7.5 56.25 16.6-03 93.0-03 8.0 60.00 13.1-03 69.0-03 8.5 63.75 18.7-03 92.4-03 9.0 67.50 28.6-03 133.-03 9.5 71.25 9.11-03 40.0-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 169.-03 3.90+00 2.72+00 V/ER 150.-03 E VLN 1.37-03 V/EB 5.00+00 E C
RANCHO SECO D I E 5 E L, G E N,.
'R'
,1 1/1,3 / B 5 A..
g__
VELOCITY in/sec pk 4D HORIZ...
SU..
l 16 --
l YN Y'
gg
'[ DISPLACEMENT miIs p-p U_
M__
h,. b.. a x b, J..
2.OA 2.OR A/16 HZ 100 f
f FIGURE 20
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A'
=
i Measurement Location 4B VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 53.9-03 2.29 00 1.5 11.25 773.-06 21.9-03 2.0 15.00 II.7-03 248.-03 2.5 18.75 868.-06 14.7-03 3.0 22.50 19.8-03 280.-03 3.5 26.25 14.l-03 170.-03 4.0 30.00 45.4-03 482.-03 4.5 33.75 3.00-03 28.2-03 5.0 37.50 fl.1-03 93.7-03 5.5 41.25 37.2-03 286.-03 6.0 45.00 824.-06 5.63-03 6.5 48.75 16.2-03 105.-03 7.0 52.50 7.70-03 46.3-03 7.5 56.25 813.-06 4.66-03 8.0 60.00 3.42-03 18.0-03 8.5 63.75 7.39-03 36.8-03 9.0 67.50 8.82-03 41.1-03 9.5 71.25 6.21-03 27.4-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 81.1-03 1.89+00 2.72+00 V/ER 80.0-03 E VLN 1.37-03 V/CB 2.50+00 E C
RRNCHO SECO DIE 5EL, GEN,.
'R'
,1 1 / l,3 / 0 6 R._
1 n._ VELOCITY en/sec pk 1
4B VERT.
su::
I 1s --
)
RS
-~J
- DISPLACEMENT mtis p-p s::
n__
I
, A.Arb l
T
I FIGURE 21 1
STONE a
WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 4C HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p-p 1.0 7.50 21.8-03 928.-03 1.5 11.25 40.6-03 1.15+00 2.0 15.00 45.2-03 961.-03 2.5 18.75 34.3-03 582.-03 3.0 22.50 12.9-03 182.-03 3.5 26.25 69.8-03 846.-03 4.0 30.00 64.8-03 688.-03 4.5 33.75 22.0-03 208.-03 5.0 37.50 26.9-03 229.-03 5.5 41.25 27.6-03 212.-03 6.0 45.00 23.6-03 167.-03 6.5 48.75 41.2-03 268.-03 7.0 52.50 8.74-03 52.7-03 7.5 56.25 29.1-03 164.-03 8.0 60.00 14.5-03 76.6-03 8.5 63.75 8.02-03 39.5-03 9.0 67.50 4.85-03 23.1-03 9.5 71.25 9.85-03 43.0-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 143.-03 2.18+00 1.09400 V/ER 100.-03 E VLN 545.-05 V/CB 1.50+00 E C
RRNCHO SECO D I E E E L, G E N,.
"R"
,1 1 / 1,3 / 8 5 A l.
M i VELOCITY en/sec pk 4C HORIZ. --
SU..
16 --
RS L
'.$ DISPLACEMENT m1is p-p
~~
~~
B..
M__
]
j I
IL LAIA1.li......>_
i FIGURE 22
STONE a
WEBSTER ENGINEERING CORP.
I Acoustics a
Vibrations Lab.
~
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' Date of Survey:
NOV 13, 1986 Measurement Location SA HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 9 07-03 384.-03 1.5 11.25 68.0-03 1.92+00 2.0 15.00 19.6-03 417.-03 2.5 18.75 79.5-03 1.35+00 3.0 22.50 15.6-03 220.-03 3.5 26.25 54.5-03 658.-03 4.0 30 00 315.-03 3.33+00 4.5 33.75 29.3-03 274.-03 5.0 37.50 33.7-03 285.-03 5.5 41.25 216.-03 1.66+00 6.0 45.00 12.7-03 88.4-03 6.5 48.75 74.0-03 481.-03 7.0 52.50 20.3-03 122.-03 7.5 56.25 92.8-03 522.-03 8.0 60.00 31.9-03 166.-03 8.5 63.75 27.6-03 136.-03 9.0 67.50 11.0-03 50.7-03 9.5 71.25 24.5-03 108.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 427.-03 4.60+00 595.-03 V/ER 500.-03 E VLN 273.-06 V/EB 5.00+00 C C
RRNCHO SECO D I E S E L, G E N,.
'R'
,1 1 / 1,3 / 0 6 VELOCITY tn/see pk 2
+
5R HORIZ. --
.1.
SU 16 --
l pg Ab h
i
_'_' DISPLACEMENT mtis p-p
[.
B I
N M
T l
~.~
LS Ab A
,.4Jl A.A._._.__
I FIGURE 23
STONE WEBSTER ENGINEERING CORP.
Acoustics V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 5A VERT.
1 ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 8.62-03 364.-03 i
1.5 11.25 15.1-03 427.-03 2.0 15.00 14.6-03 309.-03 2.5 18.75 24.0-03 407.-03 3.0 22.50 27.6-03 390.-03 3.5 26.25 17.2-03 207.-03 4.0 30.00 67.1-03 710.-03 4.5 33,75 20.9-03
.196.-03 5.0 37.50 52.8-03 447.-03 5.5 41.25 67.4-03 518.-03 6.0 45.00 4.87-03 34.1-03 6.5 48.75 19.7-03 128.-03 7.0 52.50 6.49-03 39.3-03 7.5 56.25 19.8-03 111.-03 8.0 60.00 16.8-03 87.9-03 8.5 63.75 5.71-03 28.6-03 9.0 67.50 2.86-03 13.4-03 i
9.5 71.25 2.83-03 12.7-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 127.-03 1.35+00 1.09+00 V/ER 125.-03 C VLN 546.-05 V/CB 1.25+00 C C
RRNCHO,5CCO DIE 5EL, GEN,.
R' 1 1 / 1,3 / 0 6 A..
VELOCITY in/sec pk M-SR VERT.
SU__
j Is --
l d'
RS 2 DISPLACEMENT mtis p-p 0
M..
I
-1_
A a a
- t A
1
- A A
I FIGURE 24 l.
STONE a
WEBSTER ENGINEERING CORP.
Acoustics a
Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 23 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 5.30-03 222.-03 1.5 11.25 3.73-03 106.-03 2.0 15.00 7.71-03 163.-03 2.5 18.75 3.97-03 67.2-03 3.0 22.50 5.08-03 71.8-03 3.5 26.25 14.9-03 180.-03 4.0 30.00 24.8-03 263.-03 4.5 33.75 17.4-03 164.-03 5.0 37.50 7.19-03 60.8-03 5.5 41.25 6.49-03 50.0-03 6.0 45.00 3.79-03 26.7-03 6.5 48.75 5.64-03 36.4-03 7.0 52.50 16.4-03 98.8-03 7.5 56.25 30.6-03 172.-03 8.0 60.00 9.95-03 51.9-03 8.5 63.75 23.5-03 116.-03 9.0 67.50 13.7-03 63.9-03 9.5 71.25 20.9-03 92.3-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 113.-03 733.-03 1.09+00 V/CR 80.0-03 E VLN 545.-05 V/EB 400.-03 C C
RANCHO SECO D I E E E L, G E N,.
'R'
,1 1 / 1,3 / 0 5 A
VELOCITY in/sec pk g
- 3 VERT.
SU__
l 16 --
b
~
. u
'~
DISPLACEMENT mtis p-p
,I M..
l U
M lad 2.OA 2.OA A/16 HZ 100 t
i FIGURE 55
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' I
I Date of Survey:
NOV 13, 1986 Measurement Location 5B HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/see pk.
mils p p 1.0 7.50 32.5-03 f.38 00 1.5 11.25 2.69-03 75.5-03 2.0 15.00 47.6-03 1.01+00 2.5 18.75 9.37-03 158.-03 3.0 22.50 10.4-03 147.-03 3.5 26.25 54.5-03 660.-03 4.0 30.00 317.-03 3.36+00 4.5 33.75 9.20-03 86.6-03 5.0 37.50 49.4-03 418.-03 5.5 41.25 200.-03 1.54+00 6.0 45.00 26.3-03 185.-03 6.5 48.75 12.6-03 81.2-03 7.0 52.50 2.85-03 17.0-03 7.5 56.25 6.52-03 36.4-03 8.0 60.00 23.2-03 122.-03 8.5 63.75 6.71-03 33.4-03 9.0 67.50 17.l-03 79.3-03 9.5 71.25 12.6-03 55.5-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 393.-03 4.09+00 1.09+00 V/ER 500.-03 C'
VLN 546.-06 V/CB 5.00+00 C C
RRNCHO SECO DIE 5EL, GEN,.
- R' 11/l,3/06 R..
_ VELOCITY i n/mac pk g.
5B HORIZ...
SU 2 16 --
~
Ul
^
es 2 DISPLACEMENT mtis p-p 3$.
.2
~
M.-
I-A1 A A
A_
A.
.t a
t.
fm 1.. i_
t f
FIGURE 25 l-
1 STONE WEBSTER ENGINEERING CORP.
Acou.stics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13. 1986 Measurement Location 5B VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT HZ in/sec pk.
mils p p 1.0 7.50 77.8-03 3.30 00 1.5 11.25 1.54-03 43.7-03 2.0 15.00 35.6-03 757.-03 2.5 18.75 2.18-03 37.0-03 3.0 22.50 15.8-03 223.-03 3.5 26.25 19.1-03 231.-03 4.0 30.00 78.2-03 830.-03 4.5 33.75 4.52-03 42.5-03 5.0 37.50 21.5-03 182.-03 5.5 41.25 53.4-03 411.-03 6.0 45.00 6.76-03 47.5-03 6.5 48.75 18.3-03 119.-03 7.0 52.50 8.54-03 51.0-03 7.5 56.25 2.24-03 12.8-03 8.0 60.00 11.6-03 60.7-03 8.5 63.75 9.12-03 45.1-03 9.0 67.50 12.1-03 56.5-03 9.5 71.25 8.57-03 37.7-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 127.-03 2.82+00 2.72+00 V/ER 125 -03 E VLN 1.37-03 V/EB 4.00+0B E C
RRNCHO,5ECO D I E S E L, G E N,.
'R'
,11/l,3/95 A
pk
((
VELOCITY in/sec g
h 3B VERT I
l SU,
)
I 16 7L _J dh._.
. c-ys
[$ DISPLACEMENT mtis p-p
['
s::
M_.
j T
. b. a x b _ J, _., _
2.OA 2.OA A/16 HZ 100 t
I FIGURE 26
. STONE a
WEBSTER ENGINEERING CORP.
Acoustics V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' Date of Survey:
NOV 13, 1986 Measurement Location SC HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 18.3-03 775.-03 1.5 11.25 62.6-03 1.77+00 2.0 15.00 26.9-03 573.-03 2.5 18.75 95.9-03 1.63+00 3.0 22.50 5.82-03 83.2-03 3.5 26.25 108'.-03 1.31+00 4.0 30.00 185.-03 1.96+00 4.5 33.75 36.1-03 340.-03 5.0 37.50 52.8-03 447.-03 5.5 41.25 106.-03 812.-03 6.0 45.00 34.8-03 245.-03 6.5 48.75 75.0-03 488.-03 7.0 52.50 20.3-03 123.-03 7.5 56.25 63.1-03 355.-03 8.0 60.00 37.5-03 198.-03 8.5 63.75 7.29-03 35.6-03 9.0 67.50 17.6-03 81.9-03 9.5 71.25 16.9-03 74.8-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 301.-03 3.69+00 1.09+00 V/ER 300.-03 E VLN 545.-05 V/EB 3.00+00 E C
RANC'HO SECO DI E'5EL, GEN.
'R'
,1 1 / 1,3 / 8 6 A__
M-VELOCITY in/sec pk SC HORIZ. --
su
[.
1g..
l pg DISPLACEMENT mtis p-p B,,
M._
i 6._x 1
_A.*kk 2 i. a o 1 -
a FIGURE 27
F-----
STONE WEBSTER ENGINEERING CORP.
l Acoustics a
Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location SC VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT 1
Hz in/sec pk.
mils p p 1.0 7.50 15.9-03 675 -03 1.5 11.25 16.9-03 476.-03 2.0 15.00
'4.5-03 308.-03 2.5 18.75 36.2-03 614.-03 3.0 22.50 6.19-03 87.7-03 3.5 26.25 41.5-03 501.-03 4.0 30.00 59.9-03 634.-03 4.5 33.75 15.3-03 143.-03 5.0 37.50 9.51-03 80.4-03 5.5 41.25 26.0-03 200.-03 6.0 45.00 9.70-03 68.4-03 6.5 48.75 20.9-03 135.-03 7.0 52.50 5.09-03 30.6-03 7.5 56.25 20.9-03 117.-03 8.0 60.00 10.7-03 56.2-03 8.5 63.75 7.76-03 38.3-03 9.0 67.50 4.04-03 18.8-03 9.5 71.25 12.2-03 53.6-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 100.-03 1.33+00 2.72+00 V/ER 100.-03 E VLN 1.37-03 V/EB 1.00+00 E C
RANCHO SECO D I E*5EL, GEN.
"R' 11/13/05
$$' VELOCITY s n /s si c pl.
_~[
SC VERT.
a.
SU$.
l T
T 16 --
j RS DISPLACEMENT mils p-p a::
_L n__
l L] kJ M kA d A ti
_,i.
_1 t_
2.OA 2.OR A/IS HZ 100 e
a FIGURE 28
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 6A HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 8.59-03 364.-03 1.5 11.25 95.1-03 2.69+00 2.0 15.00 7.94-03 169.-03 2.5 18.75 123.-03 2.08+00 3.0 22.50 6.85-03 98.5-03 3.5 26.25 94.2-03 1.14+00 4.0 30.00 485.-03 5.14+00 4.5 33.75 36.0-03 338.-03 5.0 37.50 49.7-03 420.-03 5.5 41.25 334.-03 2.57+00 6.0 45.00 22.2-03 155.-03 6.5 48.75 108.-03 703.-03 7.0 52.50 32.8-03 197.-03 7.5 56.25 147.-03 824.-03 8.0 60.00 55.5-03 291.-03 8.5 63.75 28.2-03 139.-03 9.0 67.50 19.3-03 89.1-03 9.5 71.25 36.1-03 159.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 657.-03 6.94+00 545.-03 V/ER 800.-03 E VLN 273.-05 V/EB B.00+00 E C
RRNCHO SECO D I E S E L, G E N,.
'R'
,1 1 / 1,3 / 8 5 A
n.
VELOCITY in/see pk SR HORIZ. --
j EU 2
[
16 --
7 as M
__ DISPLACEMENT mits p-p 2
B'"
ml Wm ee i 4 M_. A.. A.
...._ _ m L sjl L_k.
I FIGURE 29
I
\\
STONE WEBSTER ENGINEERING CORP.
Acoustics a
Vibrations Lab.
~
VIBRATION BASELINE SURVEY.
RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location SB HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 3.61-03 154.-03 I
1.5 11.25 2.84-03 82.1-03 1
2.0 15.00 31.6-03 671.-03 I
2.5 18.75 10.7-03 181.-03 j
3.0 22.50 13.7-03 195.-03 3.5 26.25 93.3-03 1.13+00 4.0 30.00 460.-03 4.87+00 4.5 33.75 9.17-03 87.9-03 5.0 37.50 73.7-03 625.-03 5.5 41.25 307.-03 2.36+00 6.0 45.00 44.4-03 313.-03 6.5 48.75 7.86-03 51.0-03 7.0 52.50 5.15-03 31.0-03 7.5 56.25 2.01-03 10.8-03 8.0 60.00 28.8-03 151.-03 8.5 63.75 5.01-03 24.7-03 9.0 67.50 14.1-03 65.9-03 9.5 71.25 16.1-03 71.3-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 576.-03 5.68+00 545.-03 V/ER 900 -03 E VLN 273.-06 V/CB B.00+00 E C
RRNCHO,5ECO D I E 5 E L, G E N,.
'R" 1 1 / 1,3 / 0 5 A..
g..
VELOCITY i n/see pk 6B HORIZ...
su..
16 --
d dL4
. u _.
r~
,s
(( DISPLACEMENT mits p-p
((
g..
M..
{
I
___m I
Al A E
m a
I A
l_
d a
2.OR 2.GR R/16 HZ IGG I
I FIGURE 30 w__am____._--____._.____m_
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Le6.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' I
g Date of Survey:
NOV 13, 1986 Measurement Location SC HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 13.9-03 591.-03 1.5 11.25 90.2-03 2.55+00 2.0 15.00 13.0-03 276.-03 2.5 18.75 148.-03 2.51+00 3.0 22.50 1.42-03 20.7-03 3.5 26.25 170.-03 2.06+00 4.0 30.00 227.-03 2.40+00 4.5 33.75 40.0-03 377.-03 5.0 37.50 65.5-03 553 -03 5.5 41.25 172.-03 1.32+00 6.0 45.00 44.9-03 316.-03 6.5 48.75 104.-03 672.-03 7.0 52.50 30.!-03 181.-03 7.5 56.25 93.8-03 526.-03 8.0 60.00 28.0-03 147.-03 8.5 63.75 7.46-03 36.5-03 9.0 67.50 18.7-03 87.1-03 9.5 71.25 28.8-03 127.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 419.-03 5.17+00 1.09+00 V/ER 400.-03 E VLN 546.-06 V/EB 4.00+00 E C
RRNCHO,5ECO DIESEL, GEN,.
"R"
,1 1 / 1,3 / 0 5 A..
,. VELOCITY i n / s si c pk n_
SC HORIZ. --
SU[
16 --
qg DISPLRCEME.NT mils p-p B__
\\
M__
i Ldl A141._
-Ldu A 1.
e FIGURE 31
________-_m__.___
STONE a
WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 l
Measurement Location 11 AXIAL 1
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 186.-03 7.86 00 1.5 11.25 120.-03 3.40+00
(
2.0 15.00 142.-03 3.02+00 2.5 18.75 114.-03 1.94+00 3.0 22.50 33.7-03 479.-03 3.5 26.25 168.-03 2.04+00 4.0 30.00 2.05+00 21.7+00 4.5 33.75 128.-03 1.21+00 5.0 37.50 181.-03 1.53+00 5.5 41.25 142.-03 1.09+00 6.0 45.00 92.9-03 654.-03 6.5 48.75 82.9-03 537.-03 7.0 52.50 48s2-03 288.-03 7.5 56.25 40.3-03 227.-03 8.0 60.00 106.-03 551.-03 8.5 63.75 61.2-03 301.-03 9.0 67.50 33.4-03 155.-03 9.5 71.25 26.8-03 118.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 2.12+00 25.5+00 273.-03 V/ER 3.00+0B E VLN 135.-05 V/EB 30.0+00 E C
RANCHO S E C O, DIE 5EL, GEN,.
'R' 11/1,3/85 A..
g.,. VELOCITY t n / s ur e pk 11 RXIRL
~~
SU..
16 y..
gg
___A i a * -
1___
t___
DISPLACEMENT m11s p-p 2
M..
.W A
m.
Al a
_1_
l k
A a
j 2.OA 2.OA A/15 HZ 100 8
s FIGURE 32
___._m___m..
mW STONE WEBSTER ENGINEERING CORP.
Acoustics a
Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' 5
g Date of Survey:
NOV 13, 1986 Measurement Location 11 HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 346.-03 14.7 00 1.5 11.25 325 -03 9.19+00 2.0 15.00 741.-03 15.7+00 2.5 18.75 939.-03 15.9+00 3.0 22.50 847.-03 12.0+00 3.5 26,25 1.69+00 20.4+00 4.0 30.00 3.66+00 38.7+00 4.5 33.75 925.-03 8.69+00 5.0 37.50 452.-03 3.82+00 5.5 41.25 445.-03 3.42+00 6.0 45.00 145.-03 1.02+00 6.5 48.75 483.-03 3.14+00 7.0 52.50 214'.-03 1.28+00 7.5 56.25 374.-03 2.10+00-8.0 60.00 219.-03 1.15+00 8.5 63.75 211.-03 1.04+00 9.0 67.50 89.9-03 419.-03 9.5 71.25 203.-03 893.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 4.92+00 63.7+00 109.-03 V/ER 5.00+00 E VLN 54.5-05 V/EB 50.0+00 E C
RRNCHO SECO DIE 5EL, GEN,.
"R'
,1 1 / 1,3 / 8 G A1 g
VCLOCITY t n / s er e p l.
11 HORIZ. __
1 SU 16 --
--C-pg
__^ ' -
__ DISPLACEMENT mils p-p s::
M..
n _ _ _1 2.OR 2..OA A/18 HZ 100 a
l FIGURE 33 w___________m-.mm__.._m.
4 STONE a
WEBSTER ENGINEERING CORP.
Acoustics a
Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:-
NOV 13, 1986 Heasur6 ment Location 11 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 95.4-03 4.05 00 1.5 11.25 85.4-03 2.41+00 2.0 15.00 127.-03 2.69+00 2.5 18.75 76.6-03 1.30+00 3.0 22.50 62.3-03 884.-03 3.5 26.25 391.-03 4.74+00 4.0 30.'00 1.25+00 13.2+00 4.5 33.75 f40.-03 1.31+00 5.0 37.50 60.7-03 512.-03 5.5 41.25 24.9-03 191.-03 6.0 45.00 70.6-03 497.-03 6.5 48.75 55.1-03 358.-03 7.0 52.50 49.7-03 296.-03 7.5 56.25 121.-03 675.-03 8.0 60.00 64.8-03 339.-03 8.5 63.75 46.8-03 232.-03 9.0 67.50 53.1 248.-03 9.5 71.25 40.2-03 177.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 1.41+00 22.6+00 2 7 ~3. - 0 3 V/ER 2.00+00 E VLN 135.-05 V/EB 20.0+0B E C
RRNCHO SECO DIE'5EL, GEN.
"R'
,11/13/85 R
n._ VELOCITY t es/s ee pk 11 VERT.
.L.
su::
16 --
RS
'^
^^^
^
$ DISPLACEMENT mtis p-p s::
M..
j
- ^4d,m 1
i FIGURE 34
l
(
STONE WEBSTER ENGINEERING CORP.
Acoustics a
V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' u
Date of Survey:
NOV 13, 1986 Measurement Location 14 AXIAL 1
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT l
Hz in/sec pk.
mils p p 1.0 7.50 60.5-03 2.58 00 1.5 11.25 34.7-03 981.-03 2.0 15.00 56.9-03 1.21+00 2.5 18.75 24.2-03 413.-03 3.0 22.50 45.9-03 651.-03 3.5 26.25 225.-03 2.73+00 4.0 30.00 1.50+00 15.9+00 4.5 33.75 99.5-03 940.-03 5.0 37.50 135.-03 1.15+00 5.5 41.25 69.8-03 537.-03 6.0 45.00 57.3-03 406.-03 6.5 48.75 245.-03 1.59+00 7.0 52.50 33.6-03 202.-03 7.5 56.25 164.-03 920.-03 8.0 60.00 27.0-03 145.-03 8.5 63.75 64.0-03 316.-03 9.0 67.50 23.6-03 111.-03 9.5 71.25 218.-03 961.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 1.62+00 17.4+00 273.-03 V/ER 2.5D+00 C VLN 136.-06 V/EB 25.0+00 E C
RRNCHO SECO D I E S E L, G E N,.
'R' 11/1,3/06 A..
M-VELOCITY in/sec pk 14 AXIAL SU.
16 --
LM RS DISPLACEMENT mtIs p-p O
1 l
M..
I I
L. J 1
A Ab $
m A
2.OA 2.OA A/16 HZ 100 l
l FIGURE 35 j
1 STONE a
WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A'
{
Date of Survey:
NOV13,198d i
Measurement Location 14 HORIZ.
l ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p l
1.0 7.50 172.-03 7.30 00 1.5 11.25 163.-03 4.62+00 2.0 15.00 84.2-03 1.78+00 2.5 18.75 479.-03 8.12+00 3.0 22.50 134.-03 1.88+00 3.5 26.25 1.28+00 15.5+00 4.0 30.00 2.13+00 22.6+00 4.5 33.75 387.-03 3.64+00 5.0 37.50 82.1-03 694 -03 5.5 41.25 103.-03 787.-03 6.0 45.00 54.9 383.-03 6.5 48.75 225.-03 1.46+00 7.0 52.50 50.1-03 301.-03
{
7.5 56.25 141.-03 789.-03 8.0 60.00 32.4-03 172.-03 8.5 63.75 17.2-03 83.2-03 9.0 67.50 52.4-03 244.-03 9.5 71.25 55.6-03 244.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 2.62+00 31.6+00 273.-03 V/ER 4.00+0B E VLN 136.-05 V/EB 40.0+00 E C
RRNCHO 5ECO D I E S E L, G E N,.
'R'
,1 1 / 1,3 / 0 5 VELOCITY in/sme pk g
14 HORIZ. __
su::
is __
A h
h
_k
- = _ _ -
__~ DISPLACEMENT mtis p-p s::
n__
e19
_N A
m k
1 l
i FIGURE 36
M 1 STONE WEBSTER ENGINEERING CORP.
Acoustics V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 l
Measurement Location 14 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/see pk.
mils p p 1.0 7.50 251.-03 10.7 00 1.5 11.25 90.4-03 2.56+00 2.0 15.00 127.-03 2.71+00 2.F 18.75 139.-03 2.35+00 3.0 22.50 78.9-03 1.12+00 3.5 26.25 279.-03 3.38+00 4.0 30.00 1.36+00 14.4+00 4.5 33.75 134.-03 1.27+00 5.0 37.50 34.1-03 290.-03 5.5 41.25 134.-03 1.03+00 60 45.00 26.9-03 189.-03 6.5 48.75 192.-03 1.25+00 7.0 52.50 40.9-03 247.-03 7.5 56.25 177.-03 997.-03 8.0 60.00 271.-03 1.43+00 8.5 63.75 112.-03 555.-03 9.0 67.50 70.6-03 328.-03 9.5 71.25 43.5-03 192.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 1.50+00 18.8+00 l
273.-03 V/ER 2.50+00 E VLN 136.-06 V/EB 25.0+00 E C
PRNCHO,5ECO DIESEL, GEN,.
'R' 1 1 / 1,3 / 0 6 A..
g..
VELOCITY i n / z ar e pk 14 VERT.
SU 2 2
16 --
A
-a x
1 DISPLACEMENT mi1s p-p B__
M..
T 1
kLULLx1 i-i,_it.
FIGURE 37
)
STONE WEBSTER ENGINEERING CORP.
Acousties V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 16 AXIAL ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 9.88-03 420.-03 1.5 11.25 9.31-03 263.-03 2.0 15.00 2.33-03 49.6-03 2.5 18.75 15.8-03 268.-03 3.0 22.50 7.15-03 101.-03 3.5 26.25 8.20-03 99.3-03 4.0 30.00 32.0-03 339.-03 4.5 33.75 8.94-03 83.9-03 5.0 37.50 20.0-03 170.-03 5.5 41.25 9.68-03 74.5-03 6.0 45.00' 3.I5-03 22.2-03 6.5 48.75 8.75-03 56.8-03 7.0 52.50 4.71-03 28.4-03 7.5 56.25 7.37-03 41.6-03 8.0 60.00 11.4-03 60.2-03 8.5 63.75 5.12-03 25.3-03 9.0 67.50 3.20-03 15.0-03 l
9.5 71.25 6.42-03 28.5-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 53.9-03 704.-03 2.?'2+00 V/ER 50.0-03 E VLN 1.37-03 V/EB 500.-03 E C
RRNCHO,5ECO DICsCL, GEN,.
"R"
,1 1 / l,3 / 8 5 A..
g._ VELOCITY in/sec pk 18 RXIAL l
su::
16 --
l MLA1 N Ah.. ik ys
- orseLRcEnENT mii. p-p B""
~~
~'
l M_
I k d i h 4_.
i FIGURE 38
STONE WEBSTER ENGINEERING CORP.
Acoust1cs V16ratloris Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV13,198$
Measu.rement Location 16 HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 58.6-03 2.49 00 1.5 11.25 5.14-03 146.-03 2.0 15.00 16.7-03 354.-03 2.5 18.75 29.1-03 494.-03 3.0 22.50 31.3-03 442.-03 3.5 26.25 14.9-03 181.-03 4.0 30.00 63.4-03 672.-03 4.5 33.75 14.9-03 140.-03 5.0 37.50 38.6-03 326.-03 5.5 41.25 53.7-03 412.-03 6.0 45.00 33.4-03 234.-03 6.5 48.75 23.9-03 155.-03 7.0 52.50 21.0-03 126.-03 7.5 56.25 25.6-03 144.-03 8.0 60.00 12.5-03 65.6-03 8.5 63.75 46.3-03 228.-03 9.0 67.50 19.0-03 88.4-03 9.5 71.25 13.1-03 57.7-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 140.-03 2.28+00 2.72+00 V/ER 100.-03 E VLN 1.37-03 V/EB 3.00+00 E C.
RRNCHO SECO DIE SEL, GEN,.
"R" 11/1,3/05 A _
VELOCITY in/see pk n
16 HORIZ.
l SU.."
~
)
16 --
L JU JJUbLLLILd)LL 2 DISPLACEMENT mtis p-p 2
B}_~
[,"
M_.
1 A
_A s-n l =
b b&
A$
A A-b 2.OA 2.OA R/16 HZ 100 I
I FIGURE 39 I
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 16 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 44.1-03 1.87 00 1.5 11.25 23.2-03 655.-03 2.0 15.00 15.2-03 322.-03 2.5 18.75 18.7-03 317.-03 3.0 22.50 26.3-03 372.-03 3.5 26.25 19.9-03 241.-03 4.0 30.00 69.7-03 737.-03 4.5 33.75 4.68-03 43.9-03 5.0 37.50 36.6-03 309.-03 5.5 41.25 26.2-03 202.-03 6.0 45.00 10.3-03 72.3-03 6.5 48.75 30.5-03 198.-03 7.0 52.50 10.5-03 63.2-03 7.5 56.25 28.0-03 157.-03 8.0 60.00 12.6-03 66.2-03 8.5 63.75 4.77-03 23.6-03 9.0 67.50 5.65-03 26.3-03 9.5 71.25 13.5-03 59.7-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 114.-03 1.92+00 2.72+00 V/ER 100.-03 E VLN 1
1.37-03 V/EB 2.00+00 C C
RRNCHO SECO DIE SEL, GEN.
'R'
,1 1 / 1,3 / 8 6 M_.
VELOCITY in/sme pk I
A__
is VERT.
su::
is __
i 1 JJuju)Uu_Au;
[
j R,
(( DISPLACEMENT mils p-p
_[
I M
E JLAlbi b. L.2.
I a.es a.on s Is
~2 1o.
j FIGURE 40 I
STONE a
WEBSTER ENGINEERING CORP.
A c o us t.i c s Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECD DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 198$
Measurement Location 19 AXIAL ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 1.02-03 43.8-03 1.5 11.25 996.-06 28.9-03 2.0 15.00 345.-06 7.21-03 2.5 18.75 2.05-03 35.1-03 3.0 22.50 584.-06 8.03-03 3.5 26.25 f.86-03 22.5-03 4.0 30.00 3.39-03 36.3-03 4.5 33.75 2.71-03 25.1-03 5.0 37.50 10.9-03 92.7-03 5.5 41.25 3.51-03 26.8-03 6.0 45.00 1.17-03 8.47-03 6.5 48.75 6.90-03 44.9-03 7.0 52.50 3.63-03 21.6-03 7.5 56.25 6.89-03 38.6-03 8.0 60.00 31.6-03 165.-03 8.5 63.75 10.5-03 52.1-03 9.0 67.50 9.44-03 43.8-03 9.5 71.25 11.3-03 49.7-03 Overall Vibration Level 25.0.Hz to 1000.0 Hz 414.-03 2.15+00 1.09+00 V/ER 500.-03 E VLN 545.-05 V/EB 3.00+00 E C
RANCHO SECO DIESEL, GEN,.
'R" 11/1,3/06 Al M-VELOCITY tn/sec pk 19 RXIRL SU((
~
16 --
gg
.A
$$ DISPLACEMENT mils p-p
[$
M__
I ^
1_.
8 Y I
M_
FIGURE 41
STONE WEBSTER ENGINEERING CORP.
A c o us t i c s a
Ulbrations La6.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' i
Date of Survey:
NOV 13, 1986 Measurement Location 19 HORIZ.
l l
l ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT I
Hz in/sec pk.
mils p p 1.0 7.50 1.83-03 78.3-03
)
1.5 11.25 1.40-03 40.1-03 l
2.0 15.00 591.-06 12.8 03 d
2.5 18.75 5.30-03 90.0-03
)
3.0 22.50 2.06-03 29.2-03 3.5 26.25 13.2-03 159.-03 4.0 30.00 16.0-03 170.-03 4.5 33.75 5.89-03 55.2-03 5.0 37.50 20.4-03 172.-03 5.5 41.25 28.5-03 219.-03 6.0 45.00 7.28-03 51.3-03 6.5 48.75 7.39-03 47.9-03 7.0 52.50 5.29-03 31.8-03 7.5 56.25 19.0-03 107.-03 8.0 60.00 17.1-03 90.4-03 8.5 63.75 4.06-03 20.0-03 9.0 67.50 21.5-03 100.-03 9.5 71.25 4.70-03 20.7-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 168.-03 924.-03 2.72+00 V/CR 250.-03 E VLN 1.37-03 V/EB 1.25+0B E C
RRNCHO 5ECO D I E 5 E L, G E N,.
'R'
,1 1 / 1,3 / 8 5 g,y VCLoCITY A
tn/ sac pk
!9 HORIZ...
SU..
1 6 -*-
gg hJ W.u.
-~
[.~ DISPLACEMENT mtis p-p g.
\\
M..
l I
3 A
A J
m.M M A
M.-
FIGURE 42 e=
.__2__
I STONE a
WEBSTER ENGINEERING CORP.
A c o u.s t.L e s Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 19 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT I
Hz in/sec pk.
mils p p 1.0 7.50 6.99-03 296.-03 1.5 11.25 4.41-03 125.-03 2.0 15.00 2.99-03 63.6-03 2.5 18.75 2.50-03 42.1-03 3.0 22.50 2.76-03 39.4-03 3.5 26.25 5.08-03 61.8-03 4.0 30.00 4.93-03 52.3-03 4.5 33.75 1.54-03 14.9-03 5.0 37.50 22.6-03 192 -03 5.5 41.25 20.2-03 156.-03 6.0 45.00 2.33-03 16.2-03 6.5 48.75 12.1-03 78./-03 7.0 52.50 8.27-03 49.9-03 7.5 56.25 16.1-03 90.3-03 8.0 60.00 57.4-03 302.-03 8.5 63.75 30.8-03 152.-03 9.0 67.50 18.2-03 84.8-03 9.5 71.25 12.5-03 54.9-03 Overall Vibration Level 25.0 Hz to 1000,0 Hz 387.-03 2.28+00 1.09+00 V/ER 600.-03 E VLN 546.-06 V/EB 3.00+00 E C
RANCHO SECO DIEEEL, GEN,.
'A' 11/1,3/06 A..
VELOCITY tn/sme pk M-19 VERT.
i su..
l 16 --
l
'L A>.
~~
gg
[ DISPLACEMENT miis p-p B..
I
~~
l 1
I N_
o
.3 1....
8 FIGURE 43
(
l
1 STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
l VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' 5
I Date of Survey:
NOV 13, 1986 Measurement Location 20 AXIAL ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 1.66-03 70.9-03 1.5 11.25 1.59-03 45.4-03 2.0 15.00 854.~-06 18.6-03 2.5 18.75 2.30-03 38.8-03 3.0 22.50 514.-06 6.97-03 3.5 26.25 1.91-03 23.2-03 4.0 30.00 2.92-03 30.6-03 4.5 33.75 f.82-03 17.2-03 5.0 37.50 6.44-03 54.5-03 5.5 41.25 34.1-03 262.-03 l
6.0 45.00 3.64-03 25.7-03 6.5 48,75 4.6l-03 29.8-03 l
7.0 52.50 2.23-03 13.3-03 7.5 56.25 11.4-03 64.3-03 8.0 60.00 30.6-03 161.-03 S.5 63.75 8.55-03 42.2-03 9.0 67.50 8.83-03 40.9-03 9.5 71.25 14.1-03 62.3-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 410.-03 2.14+00 1.09+00 V/ER 500.-03 E VLN 546.-06 V/EB 3.00+00 E C
RRNCHO SECO DIE SEL, GEN.
- R*
,1 1 / 1,3 / 8 G a + VELOCITY n.
in/see pk 20 RXIRL i
SU__
l 16 --
I RS
^
^-
~^
2 DISPLACEMENT mtIs p'- p g __
T
~~
M l
~C.-
.A A
~
E FIGURE 44 m
_______-.__m._
.--b
STONE WEBSTER ENGINEERING CORP.
Acou.st1cs V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 20 HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 9.45-03 403.-03 1.5 11.25 5.14-03 147.-03 2.0 15.00 4.60-03 97.8-03 2.5 18.75 7.13-03 121.-03 3.0 22.50 8.82-03 124.-03 3.5 26.25 24.9-03 301.-03 4.0 30.00 43.6-03 462.-03 4.5 33.75 16.9-03 159.-03 5.0 37.50 60.5-03 512.-03 5.5 41.25 82.3-03 633.-03 6.0 45.00 1.1.9-03 84.1-03 6.5 48.75 27.5-03 179.-03 7.0 52.50 10.6-03 63.6-03 7.5 56.25 41.1-03 231.-03 8.0 60.00 32.3-03 171.-03 8.5 63.75 14.2-03 70.2-03 9.0 67.50 9.85-03 45.8-03 9.5 71.25 2.97-03 13.0-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 158.-03 1.28+00 1.09+00 V/ER 125.-03 E VLN 546.-06 V/EB 1.00+00 E C
RRNCHO SECO D I E S E L, G E N,.
'R'
,1 1 / 1,3 / 0 6 A..
VELOCITY in/sec pk M-20 HORIZ..-
f
~
SU.
16 -
l l
RS
_$ DISPLACEMENT mils p-p B}
_}
M__
)
l dALUk a_
1,. h u 2.OA 2.OA A/16 HZ 100 I
I FIGURE 45 i
STONE a
WEBSTER ENGINEERING CORP.
I Acoustics Vibrations.
Lab.
j VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 20 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 4.05-03 171.-03 1.5 11.25 1.84-03 53.1-03 2.0 15'.00 910.-06 19.3-03 2.5 18.75 2.68-03 45.0-03 3.0 22.50 2.05-03 29.3-03 3.5 26.25 12.1-03 146.-03 4.0 30.00 49.6-03 526.-03 4.5 33.75 20.9-03 196.-03 5.0 37.50 38.6-03 326.-03 5.5 41.25 202.-03 1.55+00 6.0 45.00 34.8-03 245.-03 6.5 48.75 20.8-03 135.-03 7.0 52.50 7.44-03 44.5-03 7.5 56.25 44.6-03 250.-03 8.0 60.00 8.91-03 46.4-03 8.5 63.75 23.2-03 114.-03 9.0 67.50 13.7-03 63.6-03 9.5 71 25 18.4-03 80.3-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 652.-03 3.61+00 1.09+00 V/ER 1.00+00 E VLN 545.-05 V/EB 5.00+00 E C
RANCHO,5ECO D I E 5 E L, G E N,.
'G'
,11/l,3/05 A
g._
VELOCITY in/mme pk 20 VERT.
SU$'
~~
16 --
RS
^ - - - - - ^
' ^ ^
$_' DI5 PLACEMENT m11s p-p
((
M__
l
. I aha t) k.m _,
m 2.OA 2.OR A/IS HZ 100 l
l FIGURE 46 l
-m_--_._ _ _ - - _ _
STONE WEBSTER ENGINEERING CORP.
A c o us t.1. c s Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' i
Date of Survey:
NOV 13, 1986 Measurement Location 21 AXIAL ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 2.25-03 96.2-03 1.5 11.25 120.-03 3.40+00 2.0 15.00 1.28-03 27.1-03 2.5 18.75 7.58-03 129.-03 3.0 22.50 7.04-03 99.7-03 3.5 26.25 52.2-03 632.-03 4.0 30.00 15.9-03 169.-03 4.5 33.75 4.32-03 40.7-03 5.0 37.50 12.3-03 104.-03 1
5.5 41.25 8.42-03 64.5-03 6.0 45.00 622.-06 4.33-03 6.5 48.75 1.32-03 8.23-03 7.0 52.50 1.70-03 10.1-03 7.5 56.25 4.71-03 26.5-03 8.0 60.00 7.03-03 36.9-03 8.5 63.75 f.17-03 5.88-03 9.0 67.50 1.36-03 6.34-03 9.5 71.25 4.22-03 18.7-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 137.-03 3.54+00 2.?2+00 V/ER 200.-03 E VLN 1.37-03 V/EB S.00+00 E C
RANCHO KEco DIE 5EL, GEN,.
'R'
,1 1 / 1,3 / 0 5 A
I M-.VELCCITY t n / s ar e pk 21 RXIRL su::
16 --
gg w
._A_____
'[ DISPLACEMENT mt1s p-p
[_
B.'"
_~~
M..
I l_ < _ k_
m_
m,
i u
i
~~
FIGURE 47
-' ~~ ~~
STONE WEBSTER ENGINEERING CORP.
Acou.stics a
Vibrations Lab.
VIBRATION BASELINE SURVEY.
RANCHO SECO DIESEL GENERATOR
'A' i
3 I
Date of Survey:
NOV 13, 1986 Measurement Location 21 HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 630.-06 26.3-03 1.5 11.25 27.2-03 770.-03 2.0 15.00 1.02-03 21.4-03 2.5 18.75 14.6-03 249.-03 3.0 22.50 19.8-03 279.-03 3.5 26.25 12.0-03 144.-03 4.0 30.00 28.3-03 300.-03 4.5 33.75 4.23-03 39.6-03 5.0 37.50 3.03-03 25.6-03 5.5 41.25 5.91-03 45.3-03 6.0 45.00 456.-06 3.25-03 6.5 48.75 1.81-03 11.8-03 7.0 52.50 744.-06 4.46-03 7.5 56.25 1.64-03 9.21-03 8.0 60.00 405.-06 2.00-03 8.5 63.75 1.54-03 7.54-03 9.0 67.50 1.44-03 6.72-03 9.5 71.25 4.70-03 20.7-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz
'54.5-03 947.-03 5.45+00 V/ER 50.0-03 E VLN 2.73-03 V/EB 1.25+00 E C
RRNCHO SECO DIE 5EL, GEN,.
'R'
,1 1 / 1,3 / 8 5 A..
g._
VELOCITY in/see pk
'l HORIZ.
SU..
l 16 -
l
_)L.d - -_-
h i
1 gg
(( DISPLACEMENT mtis pp 2
U N N
M__
4 NJm A -- -- _ --
.i 2.OR 2 OA A/16 HZ 100 s
FIGURE 48 m-_--,-_.-----
-4 S T O f.'t E a
WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' i
i Date of Survey:
NOV 13, 1986 Measurement Location 21 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 1.04-03 44.3-03 1.5 11.25 13.0-03 369.-03 2.0 15.00 172.-06 3.67-03 2.5 18.75 2.80-03 47.6-03 3.0 22.50 3.19-03 45.2-03 3.5 26.25 2.97-03 36.0-03 4.0 30.00 878.-06 9.36-03 4.5 33.75 3.19-03 30.0-03 1
5.0 37.50 860.-06 7.27-03 5.5 41.25 10.0-03 77.3-03 6.0 45.00 1.98-03 14.0-03 6.5 48.75 1.29-03 8.36-03 7.0 52.50 781.-06 4.67-03 7.5 56.25 3.08-03 17.3-03 8.0 60.00 5.09-03 26.7-03 8.5 63.75 4.25-03 21.0-03 9.0 67.50 7.19-03 33.5-03 9.5 71.25 5.23-03 23.1-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 26.6-03 405.-03 10.9+00 V/ER 20.0-03 E VLN 5.45-03 V/EB 600.~03 E C
RRNCHO sECO DIESEL, GEN,.
"R"
,11/1,3/95 A_.
y g__
VELOCITY in/sec pk 21 VERT.
1 sU 2 2
J g
[_ DISPLACEMENT mtis p-p 2
_h.
l I
1 atw 1
i
.m am
f FIGURE 49
__-_-_-_ O
STONE WEBSTER ENGINEERING CORP.
Acoustics V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 22 AXIAL ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p I
1.0 7.50 739.-06 30.4-03 1.5 11.25 109.-03 3.10+00 2.0 15.00 4.51-03 95.8-03 2.5 18.75 3.33-03 56.2-03 3.0 22.50 6.96-03 98.3-03 3.5 26.25 53.7-03 650.-03 4.0 30.00 44.0-03 467.-03 4.5 33.75 9.51-03 89.4-03 5.0 37.50 16.3-03 138.-03 5.5 41.25 12.2-03 93.5-03 6.0 45.00 910.-06 6.47-03 6.5 48.75 5.97-03 38.7-03 7.0 52.50 4.06-03 24.2-03 7.5 56.25 13.0-03 73.0-03 8.0 60.00 14.1-03 73.7-03 8.5 63.75 4.97-03 24.5-03 9.0 67.50 11.4-03 52.9-03 9.5 71.25 5.51-03 24.3-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 156.-03 3.29+00 2.72+00 v.' E R 200.-03 E VLN 1.37-03 V/EB 5.00+00 E C
RRNC,HO S, E C O, DIE,5EL GEN.
"R" 11/1,3/95 i
i i
i VELOCITY in/see pk 4
M-22 AXIAL su::
16 --
j U
. _. A gg
. DISPLACEMENT m1is p-p B__
M.
I j
t_
lt U
2.OA 2.OA A/16 HZ 100 t
I FIGURE 50
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' Date of Surve'y:
NOV 13, 1986 Measurement Location 22 HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 576.-06 25.0-03 1.5 11.25 17.6-03 497.-03 2.0 15.00 881.-06 18.6-03 2.5 18.75 14.9-03 252.-03 3.0 22.50 18.8-03 266.-03 3.5 26.25 10.7-03 130.-03 4.0 30.00 38.5-03 408.-03 4.5 33.75 6.51-03 61.3-03 5.0 37.50 8.49-03 71.9-03 5.5 41,25 3.94-03 30.2-03 6.0 45.00 524.-06 3.68-03 6.5 48.75 3.54-03 23.0-03 7.0 52.50 1.15-03 6.95-03 7.5 56.25 6.22-03 35.0-03 8.0 60.00 1.52-03 7.90-03 8.5 63.75 2.86-03 14.2-03 9.0 67.50 2.83-03 13.2-03 9.5 71.25 4.07-03 18.0-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 59.7-03 800.-03 5.45+00 V/ER 60.0-03 E VLN 2.73-03 V/CD 800.-03 E C
RANCHO SECO DIESEL, GEN,.
'R'
,1 1 / 1,3 / 0 6 a+
M-VELOCITY tn/sec pk
((
- 2 HORIZ. --
SU 16 --
l pg
(( DISPLACEMENT mils p-p Et l
i
'N Y_)
JLu x_b._-,.
FIGURE 51
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 22 VERT.
ENGINE ORDER FREQUENCY VELOCITY DI'SPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 1.22-03 52.0-03 1.5 11.25 4.65-03 131.-03 2.0 15.00 4.44-03 94.3-03 2.5 18.75 627.-06 10.7-03 3.0 22.50 2.43-03 34.3-03 3.5 26.25 1.73-03 20.9-03 4.0 30.00 6.80-03 72.0-03 4.5 33.75 4.95-03 46.5-03 5.0 37.50 1.34-03 11.4-03 5.5 41.25 11.1-03 85.6-03 6.0 45.00 1.45-03 10.3-03 6.5 48.75 1.93-03 12.5-03 i
7.0 52.50 909.-06 5.45-03 7.5 56.25 5.37-03 30.2-03 8.0 60.00 17.8-03 93.6-03 8.5 63.75 5.44-03 26.9-03 9.0 67.50 5.38-03 25.I-03 9.5 71.25 10.7-03 47.0-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 48.8-03 304.-03 5.45+00 V/ER 40.0-03 E VLN 2.73-03 V/EB 200.-03 C C
RRNCHO SECO D I E 5 E L, G E N,.
'R*
,1 1 / 1,3 / 0 5 A..
f.
. VELOCITY in/sec pk n.
22 VERT.
SU ?.
16 --
j RS
$' DISPLACEMENT mtis p-p
((
B.
n..
j.
blu.
LLbb.
2.OA 2.OR A/16 HZ 100 i
FIGURE 52
_--e_---
J STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECD DIESEL GENERATOR
'A' E
I Date of Survey:
NOV 13, 1986 Measurement Location 23 AXIAL ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 12.5-03 532.-03 1.5 11.25 47.9-03 1.36+00 2.0 15.00 28.0-03 594.-03 2.5 18.75 60.7-03 1.03+00 3.0 22.50 31.4-03 443.-03 3.5 26.25 149.-03 1.81+00 4.0 30.00 677.-03 7.16+00 4.5 33.75 45.3-03 427.-03 5.0 37.50 76.6-03 648.-03 5.5 41.25 38.6-03 296.-03 6.0 45.00 34.4-03 242.-03 6.5 48.75 36.7-03 238.-03 7.0 52.50 9.39-03 57.0-03 7.5 56.25 28.4-03 160.-03 8.0 60.00 15.6-03 82.0-03 8.5 63.75 12.1-03 60.3-03 9.0 67.50 16.7-03 77.9-03 9.5 71.25 10.7-03 47.1-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 714.-03 7.83+00 545.-03 V/ER 1.00+0B E VLN 273.-06 V/EB 10.0+0B C C
RRNCHO SECO D I E S E L, G E N,.
- R' 11/1,3/05 I
A
. VELOCITY 6 e, / s e c: pk n.
23 AXIAL l
SU$.~
.5 16 --
~
Av -
Rs DISPt.RCEMENT mils p-p B__
M..
I U_ ^
_A A Aa
_1
_i
-t a
I FIGURE 53
,l STONE WEBSTER ENGINEERING CORP.
Acou.stics V 16 r a t l o ri s Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A'
~~,
Date of Survey:
NOV 13, 198G Measurement Location 23 HORIZ.
l ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 38.4-03 1.63 00 1.5 11.25 139.-03 3.93+00 2.0 15.00 6.62-03 142.-03 2.5 18.75 261.-03 4.42+00 3.0 22.50 54.3-03 764.-03 3.5 26.25 589.-03 7.13+00 4.0 30.00 873.-03 9.25+00 4.5 33.75 139.-03 1.31+00 5.0 37.50 14.0-03 118.-03 5.5 41.25 51.7-03 397.-03 6.0 45.00 16.4-03 117.--03 6.5 48.75 74.6-03 484.-03 7.0 52.50 13.4-03 80.7-03 7.5 56.25 36.9-03 207.-03 8.0 60.00 33.1-03 174.-03 8.5 63.75 45.8-03 227.-03 9.0 67.50 44.7-03 208.-03 9.5 71.25 46.0-03 202.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 1.13+00 13.4+00 545.-03 V/CR 1.50+00 E VLN 273.-05 V/EB 15.0+00 E C
RRNCHO SECO D I E S E L, G E N,.
"P'
,1 1 / 1,3 / 8 5 A..
]
g__
VELOCITY in/sec pk
- 3 HORIZ...
SU55 2
16 --
]-
A
- - -mJ -
_M gg
- oIereecEnE~r
.,i.
B__
M..
-T.
I _ h. o A
f-2.OA 2.OA A/16 HZ 100 t
E FIGURE 54
7-STONE WEBSTER ENGINEERING CORP.
Acoustics Ulbrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SE'C0 DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 24 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p i
1.0 7.50 82.6-03 3,50 00 i
1.5 11.25 88.4-03 2.50+00 l
2.0 15.00 116.-03 2.46+00 2.5 18,75 105.-03 1.78+00 3.0 22.50 57.5-03 812.-03 3.5 26.25 64.1-03 775.-03 4.0 30.00 134.-03 1.41+00 4.5 33.75 65.9-03 618.-03 5.0 37.50 53.1-03 449.-03 5.5 41.25 53.4-03 410.-03 6.0 45.00 40.2-03 282.-03 6.5 48.75 17.6-03 114.-03 7.0 52.50 17.f-03 103.-03 i
7.5 56.25 20.0-03 112.-03 8.0 60.00 26.4-03 138.-03 8.5 63.75' 19.3-03 94.8-03 9.0 67.50 9.86-03 45.5-03 9.5 71.25 16.2-03 71.6-03 Overall Vibration Level l
25.0 Hz to 1000.0 Hz 277.-03 5.26+00 1.09+00 V/ER 200.-03 E VLN
$46.-05 V/EB 4.00+00 E C
RRNCHO SECO D I E S E L, G E N,.
"R'
,1 1 / 1,3 / 8 6 A..
VELOCITY in/sec pk l
M-24 VERT.
(
1 SU..
jg..
i l
RS
'd
- orseLacEMENT m,i.
s::
M j
A RU LAtu......
. - k~
s FIGURE 56
STONE WEBSTER ENGINEERING CORP.
Acoustics V 16 r a t l o ri s Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 25 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p-I.0 7.50 23.8-03 1.01 00 1.5 11.25 98.5-03 2.79+00 2.0 15.00 96.8-03 2.05+00 2.5 18.75 115.-03 1.95+00 3.0 22.50-19.4-03 274.-03 3.5 26.25 54.2-03 656.-03 4.0 30.00 126.-03 1.34+00 4.5 33.75 46.4-03 436.-03 5.0 37.50 16.0-03 136.-03 5.5 41.25 57.6-03 443.-03 6.0 45.00 38.1-03 268.-03 6.5 48.75 29.4-03 190.-03 7.0 52.50 9.02-03 53.7-03 7.5 56.25 16.4-03 91.5-03 8.0 60.00 34.0-03 178.-03 8.5 63.75 13.6-03 67.0-03 9.0 67.50 2.05-03 9.66-03 9.5 71.25 19.6-03 86.1-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 252.-03 4.47+00 1.09+00 V/ER 200.-03 C VLN 546.-06 V/CB 4.00+00 C C
RRNCHO ilECO DIE 5EL GEN.
- R-1 1 / 1,3 / 0 6 A..
M.. VELOCITY in/sen pk 25 VERT.
SU._
16 --
pg
._A_Aa u La h
- exemec m 1 B,,,,
M i
g..
6M k_.
l d 8 I ki
- h A
Ih
- I J
a FIGURE 57
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE' SURVEY.
RANCHO SECD DIESEL GENERATOR
'A' 3
E Date of Survey:
NOV 13, 1986 Measurement Location 26 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 55.4-03 2.34 00 1.5 11.25 104.-03 2.95+00 2.0 15.00 35.4-03 750.-03 2.5 18.75 120.-03 2.04+00 3.0 22.50 46.2-03 653.-03 3.5 26.25 18.7-03 225.-03 4.0 30.00 120.-03 1.27+00 i
4.5 33.75 10.7-03 101.-03 5.0 37.50 40.3-03 340.-03 5.5 41.25 58.4-03 449.-03 6.0 45.00 9.51-03 67.0-03 6.5 48.75 37.2-03 241.-03 7.0 52.50 18.3-03 109.-03 7.5 56.25 3.03-03 17.4-03 8.0 60.00 34.6-03 182.-03 8.5 63.75 1.35-03 6.77-03 9.0 67.50 5.56-03 25.6-03 9.5 71.25 20.2-03 88.8-03.
Overall Vibration Level 25.0 Hz to 1000.0 Hz 234.-03 4.41+00 1.09+00 V/ER 200.-03 E VLN 546.-06 V/EB 5.00+00 E C
RRNCHO SECO D I E S E L, G E N,.
'R'
,1 1 / 1,3 / 0 6 R._
VELOCITY in/see pk m.
26 VERT.
su::
16 --
J d pg
.$ DISPLACEMENT mtis p-p
[
~
B ~[
[_~
M..
T. i hhhi
. a 1.
- x. _
m _
FIGURE 58 I
.j STONE a
WEBSTER ENGINEERING CORP.
Acoustics a
Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' 1
Date of Survey:
NOV 13,1986 Measurement Location 27 VERT.
ENGINE 090ER FREQUENCY VELOCITY DISPLACEMENT l
Hz in/sec pk.
mils p p 1
1.0 7.50 62.2-03 2.64 00 1.5 11.25 68.4-03 1.93+00 2.0 15.00 136.-03 2.87+00 1
2.5 18.75 81.8-03 1.39+00 3.0 22.50 32.4-03 457.-03 3.5 26.25 35.9-03 435.-03 4.0 30.00 121.-03 1.28+00 4.5 33,75 26.5-03 249.-03 5.0 37.50 21.6-03 183.-03 5.5 41.25 39.1-03 300.-03 6.0 45.00 46.2-03 325,-03 6.5 48.75 28.9-03 167.-03 7.0 52.50 12.5-03 74.8-03 7.5 56.25 11.8-03 66.1-03 8.0 60.00 34.2-03 179.-03 8.5 63.75 5.12-03 25.4-03 9.0 67.50 5.36-03 25.1-03 9.5 71.25 16.2-03 71.0-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 240.-03 4.58+00 1.0D+00 V/ER 200.-03 C VLN 546.-05 V/EB 5.00+00 E C
RRNCHO SECO D I E E E L, G E N,.
"R'
,1 1 / 1,3 / 0 6 A._
M-VELOCITY in/zac pk 27 VCRT.
su::
16 --
1 RS
- ozsetacencNT mii. n-p B"
l MN-l
)
k_A d kAA I
i.,x A m.
i FIGURE 59 L
I STONE a
WEBSTER ENGINEERING CORP.
Acoustics V16 rations Lab.
' VIBRATION BASELINE SURVEY.
RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 198G Measurement Location 28 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 109.-03 4.63 00 1.5 11.25 16.9-03 475.-03 2.0 15.00 156.-03 3.30+00 2.5 18.75 22.0-03 373.-03 3.0 22.50 68.2-03 964.-03 3.5 26,25 18.9-03 228.-03 l
4.0 30.00 120.-03 1.27+00 4.5 33.75 15.0-03 14I.-03 5.0 37.50 53.9-03 456.-03 5.5 41.25 6.53-03 49.8-03 6.0 45.00 54.3-03 382.-03 6.5 48.75 12.3-03 79.4-03 7.0 52.50 22.6-03 135.-03 7.5 56.25 5.37-03 29.9-03 8.0 60.00 34.9-03 183.-03 8.5 63.75 7.28-03 36.2-03 9.0 67.50 10.9-03 50.6-03
~
9.5 71.25 2.25-03 10.1-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 246.-03 5.19+00 1.09+00 V/ER 250.-03 E VLN 545.-05 V/CB 5.00+00 E C
RRNCHO SECO D I E S E L, G E N,.
'R'
,1 1 / 1,3 / 9 5 3
A__
1 g..
VELOCITY in/sec pk 28 VERT.
SU 2 16 --
7
'I Rs
.$ DISPLACEMENT mtIs p-p
((
~~
'?
B --
M..
..e 4-48he rkm n.I.3 A,0,. 0, A,_
A _,.
2 2.GA 2.OA A/16 HZ 100 t
i FIGURE 60
STONE WEBSTER ENGINEERING CORP.
Acoustics a
Vibrations Lab.
VIBRATION BASELINE SURVEY.
RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV13,198E l
l Measurement Location 29 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p l
1.0 7.50 36.3-03 1.54 00 1.5 11.25 76.3-03 2.15+00 2.0 15.00 125.-03 2.64+00 2.5 18.75 90.7-03 1.54+00 3.0 22.50 18.3-03 260.-03 3.5 26.25 41.8-03 506.-03 4.0 30.00 116.-03 1.23+00 4.5 33.75 29.6-03 279. 5.0' 37.50 15.4-03 130.-03 5.5 41.25 38.6-03 296.-03 6.0 45.00 42.4-03 298.-03 6.5 48.75 11.9-03 76.6-03 7.0 52.50 9.09-03 54.6-03 7.5 56.25 9.28-03 52.0-03 8.0 60.00 35.2-03 185.-03 8.5 63.75 7.85-03 38.8-03 9.0 67.50 2.86-03 13.3-03 9. 5' 71.25 7.80-03 34.4-03 Overall Vibration Level 25.0 Hz to 1000.0.Hz 230.-03 4.24+00 1.09+00 V/ER 200 -03 E VLN 345.-05 V/EB 4.00+00 E C
RANCHO SECO D I E 5 E L, G E N,.
'R'
,1 1 / 1,3 / 9 5 A..
n._ VELOCITY in/sec pk 29 VERT.
SU gg..
pg J
DISPLACEMENT m11s p-p
[
s::
M..
'E_A j!)
k a A Ll x..x 4 m 2.OR 2.OR R/16 HZ 100 a
FIGURE 61
STONE a
WEBSTER ENGINEERING CORP.
Acoustics V.tbrations Lab.
VIBRATION BASELINE SURVEY.
RANCHO SECO DIESEL GENERATOR
'A' 1
s u
Date of Survey:
NOV 13, 1986 Measurement Location 30 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT i
Hz in/sec pk.
mils p p
!.0 7.50 63.2-03 2.68 00 1.5 11.25 107.-03 3.02+00 2.0 15.00 14.5-03 307.-03 2.5 18.75 123.-03 2.08+00 3.0 22.50 52.9-03 747.-03 3.5 26.25 22.5-03 271.-03 4.0 30.00 112.-03 1.19+00 4.5 33.75 21.7-03 204.-03 5.0 37.50 45.6-03 385.-03 5.5 41.25 65.0-03 499.-03 6.0 45.00 9.68-03 67.9-03 6.5 48.75 32.7-03 212.-03 7.0 52.50 18.0-03 108.-03 7.5 56.25 10.9-03 61.2-03 8.0 60.00 35.8-03 188.-03 8.5 63.75 6.54-03 32.0-03 9.0 67.50 5.89-03 27.2-03 9.5 71.25-11.4-03 50.2-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 236.-03 4.54+00 1.09+00 V/ER 200 -03 E VLN 545.-05 V/EB 5.00+0B E C
RRNCHO SECO DIE 5EL, GEN.
- R'
,1 1 / 1,3 / 8 5 A.
M..
VELOCITY in/see pk 30 VERT.
SU..
16 --
L.)
A.J 1 ag DISPLACEMENT mtis p-p g _
M__
I g
"O t A A
x L
AA_A.
~~
1.
2 2.' O R 2.OR A 16 HZ 100 8
s FIGURE 62
STONE a
WEBSTER ENGINEERING CORP.
Acoustics V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' NOV 13, 1986 Date of Survey:
Measurement Location 31 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 28.0-03 1.19 00 1.5 11.25 98.0-03 2.77+00 2.0 15.00 106.-03 2.26+00 2.5 18.75 108.-03 1.83+00 3.0 22.50 20.4-03 289.-03 3.5 26,25 59.9-03 725,-03 4.0 30.00 89.6-03 949.-03 4.5 33,75 50.6-03 477.-03 5.0 37.50 19.6-03 166.-03 5.5 41,25 61.2-03 470.-03 6.0 45.00 34.9-03 245 -03 6.5 48,75 34.9-03 226.-03 7.0 52.50 4.54-03 27.3-03 7.5 56.25 18.9-03 106.-03 8.0 60.00 31.2-03 164.-03 8.5 63.75 13.6-03 67.1-03 9.0 67.50 6.14-03 28.5-03 9.5 71.25 5.47-03 24.0-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 238.-03 4.47+00 1.09+00 V/ER 200.-03 E VLN 546.-06 V/EB 4.00+00 E C
RRNCHO SEco DIE 5EL, GEN,.
"R" 11/1,3/85 A..
g..
VELOCITY in/nec pk 31 VERT.
SU..
1
((
i A
JAL h
Rs
(( DISPLACEMENT mtis p-p
.5 M..
I a..
a.e k
k N
hI d
2.OA 2.OA A/16 HZ 100 f
I FIGURE 63
_J
STONE a
WEBSTER ENGINEERING CORP.
Acoustics V1brations Lab.
I VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR 'A' s
Date of Survey:
NOV 13, 1986 Measurement Location 32 AXIAL ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT l
HI in/sec pk.
mils p p l
1.0 7.50 12.3-03 521.-03 1.5 11.25' 15.4-03 439.-03 2.0 15.00 24.2-03 512.-03
-2. 5 18.75 19.1-03 323.-03 3.0 22.50 87.4-03 1.24+00 3.5 26.25 135.-03 1.63+00 4.0 30.00 487.-03 5.16+00 4.5 33.75 16.3-03 153.-03 5.0 37.50 27.6-03 234.-03 5.5 41.25 285.-03 2.19+00 6.0 45.00 11.7-03 82.5-03 6.5 48.75 220.-03 1.43+00 7.0 52.50 15.7-03 93.9-03 7.5 56.25 52.9-03 296.-03 8.0 60.00 31.0-03 163.-03 8.5 63.75 3.59-03 18.0-03 9.0 67.50 21.3-03 99.2-03 9.5 71.25 76.3-03 336.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 657.-03 6.44+00 545.-03 V/ER 900.-03 C VLN 273.-05 V/EB O.00+0B C C
RRNCHO SECO D I E S E L, G E N,.
'R' 11/1,3/95 A..
I g._
VELOCITY in/sec pk 32 AXIRL 1
su::
I 16 --
O_ _ -
pg I
- oIseLRcEnENr
.,i..-,
l 2
[
[.
M j
A b
A
[
_A
$ _d
_J 2.GA 2.OR A 16 HZ 100 i
i I
FIGURE 6 /-4
STONE WEBSTER ENGINEERING CORP.
Acoustics V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Heasur'ement Location 32 HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 14.1-03 596.-03 1.5 11.25 22.4-03 631.-03 2.0 15.00 12.7-03 268.-03 2.5 18.75 227.-03 3.86+00 3.0 22.50 28.5-03 403.-03 3.5 26,25 369.-03 4.47+00 4.0 30.00 305.-03 3.24+00 4.5 33.75 36.0-03 339.-03 5.0 37.50 42.5-03 361.-03 5.5 41.25 117.-03 900.-03 6.0 45.00 9.15-03 64.6-03 i
6.5 48,75 50.6-03 329.-03 7.0 52.50 2.61-03 15.8-03 7.5 56.25 37.9-03 213.-03 8.0 60.00 60.0-03 315.-03 8.5 63.75 61.4-03 303.-03 9.0 67.50 5.84-03 26.9-03 9.5 71.25 9.86-03 43.0-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 594.-03 7.08+00 545.-03 V/ER 600.-03 C VLN 273.-05 V/EB 5.00+00 E C
RRNCHO SECO D I E 5 E L, G E N,.
"R'
,11/l,3/06 A__
M-VELOCITY tn/sec pk 32 HoRIZ...
gn l
SU.
.m 16 RS knzsetscentsr mii.
p-,
B.".
~~
M4 I
~iI LLu W i m I x1 i ib,.
1
~
2.OA 2.OA A/16 HZ 100 8
a j
FIGURE 65
l 2
STONE WEBSTER ENGINEERING CORP.
l Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERAIOR
'A' Date of Survey:
NOV 13, 198E i
Measurement Location 33 AXIAL
)
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 38.4-03 f.63 00 1.5 11.25 35.5-03 1.00+00 2.0 15.00 57.5-03 1.22+00 2.5 18.75 39.4-03 669.-03 3.0 22.50 88.0-03 1.25+00 3.5 26.25 236.-03 2.86+00 4.0 30.00 1.37+00 14.5+00 4.5 33.75 95.8-03 902.-03 5.0 3'7 50 147.-03 1.25+00 5.5 41.25 61.9-03 474.-03 6.0 45.00 94.5-03 667.-03 6.5 48.75 138.-03 896.-03 7.0 52.50 62.0-03 373.-03 7.5 56.25 161.-03 902.-03 8.0.
60.00 91.8-03 482.-03 8.5 63.75 36.7-03 181.-03 9.0 67.50 19.5-03 91.1-03 9.5 71.25 34.2-03 151.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 1.45+00 15.4+00 273.-03 V/ER 2.50+00 E VLN 135.~O5 V/EB 25.0+00 C C
RANCHO SECO DIE'5EL, GEN.
'R'
,1 1 / 1,3 / 0 5 A4 i " ' 8 8b Pk MfVCLOCITT 33 AXIRL.
SU..
i 16 --
~
M
- h. _ _ _
gg
.'.' DISPLACEMENT mtis p-p M
l l
]A A
A i.;k am A.i e
- A A1 A
2 i
_i 1
2.OA 2.OA A/18 HZ 100 E
R FIGURE 66
_____.__________________m____
a STONE WEBSTER ENGINEERING CORP.
Acoust1cs V16 rations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 33 HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 17.8-03 758.-03 1.5 11.25 180.-03 5.07+00 2.0 15.00 20.2-03 428.-03 2.5 18.75 460.-03 7.79+00 3.0 22.50 72.6-03 1.02+00 3.5 26.25 1 42+00 17.2+00 4.0 30.00 2.41+00 25.5+00 4.5 33.75 338.-03 3.18+00 5.0 37.50 52.8-03 447.-03 5.5 41.25 151.-03 1.16+00 6.0 45.00 58.0-03 406.-03 6.5 48.75 190.-03 1.23+00 7.0 52.50 24.5-03 146.-03 7.5 56.25 78.6-03 441.-03 8.0 60.00 48.1-03 253.-03 8.5 63.75 23.0-03 113.-03 9.0 67.50 28.6-03 132.-03 9.5 71.25 26.9-03 118.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 2.89+00 32.7+00
- ,3.-03 V/ER 4.00+00 E VLN
'35.-05 V/EB 40.0+00 E C
'R'
,1 1 / 1,3 / 0 5 VELOCITY 1 rs /s sr c pk 33 HORIZ. __
l SU..
16 --
~
La i
mS
(( DISPLACEMENT m Is p-p
[
M__
i
.b.,
k
,a
~
u 1
2,OA 2.OA A/16 HZ 100 l
E R
FIGURE 67
_~
STONE WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESE!. GENERATOR ' A' Date of Survey:
NOV 13, 1986 Measurement Location 33 VERT.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 106.-03 4.51 00 1.5 11.25 58.0-03 1.64+00 2.0 15.00 101.-03 2.14+00 2.5 18.75 123.-03 2.08+00 3.0 22.50 79.6-03 1.12+00 3.5 26,25 320.-03 3.87+00 4.0 30.00 1.01+00 10.7+00 4.5 33.75 116.-03 1.09+00 5.0 37.50 32.3-03 273.-03 5.5 41,25 157.-03 1.21+00 6.0 45.00 36.1-03 254.-03 6.5 48,75 I?7.-03 1.15+00 7.0 52.50 61.7-03 370.-03 7.5 56.25 177.-03 991.-03 8.0 60.00 24.8-03 130.-03 8.5 63.75 70.5-03 348.-03 9.0 67.50 78.0-03 363.-03 9.5 71.25 15.5-03 67.6-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 1.15+00 12.8+00 545.-03 V/ER 1.50+00 E VLN 273.-06 V/EB 15.0+00 E C
RPNCHO SECO DI E"5EL, GEN,.
'R' 1 1 / 1,3 / 8 5 a + VELOCITY n __
in/see pk 33 VERT.
7 I
SU__
l 16 --
b W _^
pg
$_~ DISPLACEMENT miis p-p
~
B_~
~~
M__
4W 9-
.l I
i A
} I O A
I-E m.
3 2.OR 2.OA A/16 HZ 100 I
I FIGURE 68
l STONE a
WEBSTER ENGINEERING CORP.
I Acoustics V1brations Lab.
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' Date of Survey:
NOV 13, 1986 Measurement Location 34 AXIAL ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 37.6-03 1.59 00 1.5 11.25 30.8-03 870.-03 2.0 15.00 48.7-03 1.03+00 2.5 18.75 30.2-03 515.-03 3.0 22.50 73.9-03 1.04+00 3.5 26.25 191.-03 2.31+00 l
4.0 30.00 1.05+00 11.'1+00 1
4.5 33.75 97.7-03 918.-03 5.0 37.50 105.-03 886.-03 5.5 41.25 46.5-03 357.-03 6.0 45.00 68.9-03 484.-03 6.5 48.75 139.-03 903.-03 7.0 52.50 51.2-03 309.-03 7.5 56.25 129.-03 724.-03 8.0 60.00 66.7-03 349.-03 8.5 63.75 28.1-03 139.-03 9.0 67.50 25.4-03 119.-03 9.5 71.25 36.2-03 160,.-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 1.11+00 11.8+00 545.-03 V/ER 2.00+00 C VLN 273.-05 V/EB 20.0+0B E C
RRNCHO SECO DI ESEL, GEN,.
'R*
,1 1 / 1,3 / B 5 R..
M-VELOCITY in/sec pk 34 RXIAL su::
16--
~~
l as d
h ---=- =
$$ DISPLACEMENT miis p-p
((
M__
~
LA A
- 1. A-A
.4 u
.Ai.
A i a
1 2.GR 2.OR R/16 HZ 1GO I
E FIGURE 69
STONE a
WEBSTER ENGINEERING CORP.
Acoustics Vibrations Lab.
~
VIBRATION BASELINE SURVEY, RANCHO SECO DIESEL GENERATOR
'A' 5
I Date of Survey:
NOV 13, 1986 Measurement Location 34 HORIZ.
ENGINE ORDER FREQUENCY VELOCITY DISPLACEMENT Hz in/sec pk.
mils p p 1.0 7.50 24.5-03 1:05 00 1.5 11.25 173.-03 4.90+00 2.0 15.00 17.3-03 366.-03 2.5 18.75 411.-03 6.97+00 3.0 22.50 70.1-03 983.-03 3.5 26.25 1.20+00 14.5+00 4.0 30.00 1.97+00 20.8+00 4.5 33.75 276.-03 2.60+00 5.0 37.50 38.5-03 325 -03 5.5 41.25 109.-03 834.-03 6.0 45.00 38.4-03 269.-03 6.5 48.75 115.-03 747.-03 7.0 52.50 14.5-03 07 8-03 7.5 56.25 54.2-03 305.-03 8.0 60.00 25.2-03 132.-03 8.5 63.75 15.0-03 73.5-03 9.0 67.50 12.1-03 56.2-03 9.5 71.25 11.2-03 48.6-03 Overall Vibration Level 25.0 Hz to 1000.0 Hz 2.39+00 27.3+00 2?3.-03 V/ER 3.00+00 E VLN 135.-06 V/CB 30.0400 E C
RRNCHO SECO D I E S E L, G E N,.
"R'
,1 1 / l,3 / 9 5 A__
i h__ VELOCITY t n / s er e pk 34 HORIZ.._
-y 1
I
+
SU 1 I
le 1 RS
[$ DISPLACEMENT mtIs p-p B _'"
j
.~~
My i
I
{
.ga mn -
g f
A_i.
k m J1 j
_1 i
2.OR 2.OA A/16 HZ 100 i
FIGURE 70
____________ _ ______ - __-__ D
8 1
/
1 5
3 3
0 l
0 1
P
/
689 R
1 1
O 1l b
3 C
1 a
Z V
O L
I N
G 6
N R
~
1 s
Al O
i
=
I n
N R o' H
E g
t V
i E
2 t
1 N a Nl i
~
n 1
na I
H E
Grb G
k N
N i
l p
i E
US V L C
R E
c
~
EP E
S e
S S
T El s
M s
R eI
/
z S
B O
H A
i r
h E
C t
i W
5 i.
s Ol uC 0
&oE Y
z tn 1
I lh E c Sl T
H 1
UU A
EE N
I
//
VV O
O C
0 5
1 00 T
H O
3 ee S
96 Cl L
04
/
A V
t t
y 5
1 N
I 00 22 s
i AB o
0 c
.s 0eQ UlNC w y
DC Nr
(
7
.1
8 70
/
8 0:
3 2
l 0
1 P
/
689 R
1 1
O 1l b
3 C
1 a
V O
L N
G T
6 N
R 1
s Al E
=
I n
N R o' V
E g
t W
i E
3 2
t N a Nl 3
~
nna I
H E
Grb G
k N
M i
p E
l US V
L C
R E
c E
P E
S e
S SM T
El s
l s
R eI
/
z S
B O
n H
A i
h E
C t
i W
5 s Ol uC 0
&oE Y
z tn 1
I
/
E c Sl T
H 1
UU A
E E N
I
/ /
V V O
O C
O 1 4 0 0 T
H O
3 ee S
5 3 Cl L
4 7 N
l
- 5. 2 N
E t
C C
{
A V
AA 00 R
22 AB 5
O 2
1 5 a' ols5
-HDC7e C
_