ML20236N321

From kanterella
Jump to navigation Jump to search

Forwards Three Pages Inadvertently Omitted from Util 871030 Response to NRC Request for Addl Info Re Proposed Amend 147 to License DPR-54
ML20236N321
Person / Time
Site: Rancho Seco
Issue date: 11/09/1987
From: Croley B
SACRAMENTO MUNICIPAL UTILITY DISTRICT
To: Miraglia F
Office of Nuclear Reactor Regulation
References
DTS-87-105, TAC-63030, NUDOCS 8711160113
Download: ML20236N321 (4)


Text

- _ _ _ _ - - - - _. - _. _ - -

~

1. g l.;.

J SACRAMENTO MUNICutAL UTILITY DISTRICT O P. O. Box 15830,' Sacramento CA 95852-1830,(916) 452 3'211

'=

AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA j

L' NOV 0 9 1987 DTS87-105.

I

. U. S., Nuclear Regulatory Commission Attn: Frank J. Miraglia, Jr.

Associate Director for Projects

-Philips Bldg.

7920 Norfolk Avenue l

Bethesda, MD 20014

)

DOCKET 50-312 RANCHO SECO NUCLEAR GENERATING STATION LICENSE NO. DPR-54 TRANSMITTAL OF MISSING PAGES I

Reference:

Request for Additional Information, Proposed Amendment No.147, i

(AGM/NPP 87-348, October 30, 1987)

)

Dear Mr. Miraglia.

It has been discovered that three pages were inadvertently omitted from our transmittal of the referenced letter.

l Enclosed are the missing pages.

j i

We are sorry for any inconvenience this omission may have caused you.

]

1 Please contact me if you have any questions. Members of your staff with j

questions requiring additional.information or clarification may contact 1

Mr. Vern Grayhek at (209) 333-2935, extension 4916.

I Sincerely,

'j Bob Croley j

Director of Technical Services j

cc:

G. Kalman, NRC, Bethesda w/atch

)

A. D'Angelo, NRC, Rancho Seco w/atch J. B. Martin, NRC, Walnut Creek w/atch 8711160113 g71109 s\\

ADOCK 05%{2 PDR P-RANCHO SECO NUCLEAR GENERATING STATION O 1444o Twin Cities Road, Herald, CA 95638 9799;(209) 333-2935

)

~

]

RESPONSE TO NRC QUESTION QUESTION.

7 i

ENCLOSURE S - DESCRIPTION OF THE DISTRIBUTION SYSTEM 1

Were all the new loads added to the voltage ~ study which was approved in 19837 Confirm the assumption or submit the new study.

i j

RESPONSE

i All the new loads that have been identified have been added to the voltage study.

It should be noted that no significant loads were added during this i

outage.

New power sources and capacity were added this outage.

l I

I l

i 1

l l

L______

j

.c RESPONSE IL 'liRC QUESTIONS

'0VESTION:

-ECN'A-3748, REY. 5 (1) Page 7' (h) - Reg. Guide 1.9 position' 4, requires f requency restored to within 2% of nominal and voltage witnin 10% of nominal within 60% of each load sequence time interval. Also, there is a requirement for speed excursion and overspeed trip in this position. Confira Rancho Seco design compliance with these requirements.

RESPCNSE:

l Ine TDI diesel generators were purchased to comply witn R. G.1.9, Rev. 2.

l Final. testing in Rancho Seco - Special Test Procedure (STP) No. 961 will determine actual frequency, voltage, and engine speed responses statea in R.

G.1.9, Rev. 2, Section C.4.

-l l

e I

(

3A 9A 74 rA O

O O

O i

se 48 na 76 O

O O

O 3c 4c 7c rc O

O O

O i

30 90 70 Po O

O O

O i

1 i

1

1 x

.Hore :

Lerree Deritannes Aooto newe me i

s'atacy PC R SARG OF "r m S' PiS de 5 5/ud k

l i

1 1

1

. _ _,. _. _ _ _ _ _