Rev 3 to S1.OP-SO.CW-0001(Z), Circulating Water Pump Operation
ML20147B160
Person / Time
Site: Salem  
Issue date: 04/23/1994
From:
Public Service Enterprise Group
To:
Shared Package
ML20147B009 List:
References
FOIA-96-351 S1.OP-SO.CW, S1.OP-SO.CW-000, NUDOCS 9701300011
Download: ML20147B160 (9)


Text

-

SALEM / OPERATION Pag) 1 of 1 S1.OP-SO.CW-0001(Z)

V. 3

(

CIRCULATING WATER PUMP OPERATION su

p. 3 USE CATEGORY : b

.i REVISION

SUMMARY

+ This is a Minor Revision.

1 4

Step 2.2; Changed to conditaonal step for apphcation when starting pumps.

)

+

Step 3.2; Co..wEd cunent value to less than overcurrent protection.

J

+

Steps 5.2.5 and 5.3.3; Changed to eaadhinnal steps for "two or more Circulating Water Pumps are O/S".

1

+ ; Deleted as redundant to requirements of Abnormal Operating Procedure on loss of two or more circulating water pumps.

f C C ',

NOI'&S 6.PC Un ph OM

'~

cn,.1 n u.t

+

wh L <

1 1

\\'G(vv&

s,k o r $

} & C t+~~I A tV L

~

IMPI2 MENTATION REQUDtEMENTS 4

None

/)

/}/

i b2MV j

APPROVED:

s

"[)perstions Kfana Date 9701300011 970124 PDR FOIA O'NEILL96-351 PDR

i 1

S 1.OP-SO.CW-0001(Z)

I CIRCULATING WATER PUMP OPERATION

)

(

TABLE _OF CONTEN'IS

)

SECTION TITLE PAGE 1.0 PURPOSE

............................................2 i

2.0 PRERTQUISITES........................................ 2 3.0 PRECAU'ITONS AND LIMITATIONS...............

...........2 4.0 EQUIPMENT /MA~mRIAL REQUIRED..........................

2 5.0 P2OCEDURE......................................... 3 5.1 Starting Circulating Water Punip(s).......................3 5.2 Stopping Citrulating Water Pump (s)........

..............4 5.3 Emergency Tripping Circulating Water Pump (s)

...............5 I

5.4 Aligning And Securing Emergency Bearing Lutnication To

(

Ciituiating Water Pump (s)

............................6 6.0 RECORDS............................................ 7

7.0 REFERENCES

................................7 i

Rn.3 Salem Page 1 d 8

1 I

S1.OP-SO.CW-0001(Z) 1.0 PURPOSE 1.1 To provide instructions - ry to:

1.1.1 Start, stop, and emergency trip Cimulating Water Pumps.

1.1.2 Supply and secure cr.wgs.cy Bearing I.mbrication flow to Circulating Water Pumps.

1.2

  • Ibis penrwhne is applicable in any Mode.

2.0 PREREQUISITES l

2.1 Components "Off Normal and Off Normal Tagged" list (s) has been reviewed for the system and support system (s) associated with the evolution to be performed 'a this procedme 2.2 IE starting Circulating Water Pumps, THEN for the applicable pump (s):

l 2.2.1 Screen Wash Pumps and Traveling Screens are available.

2.2.2 Intake Structure stop logs are removed.

All Condenser inspection doors and waterbox openings are closed with all

{

2.2.3 i

closure bolts tightened 2.2.4 Water boxes are primed.

2.2.5 Bearing Lube System is operating and supplying flow to pump motors.

.O PMCAUTIONS AND LIMITATIONS 3.1 Multiple starts of Circulating Water Pumps may result in deterioration of the pump motor windings. SC.OP DD.ZZ-OD03(Z), Large Motor Starting Criteria, contains the statting restrictions for operation of the Circulating Water Pumps.

3.2 DO NOT allow Circulating Water Pump motor current to excmd =330 amps.

j 4.0 EOUIPMENT/MATNAL REOUIRED None l

l Salem Page 2 of 8 Rev.3 l

l

S 1.OP-SO.CW-0001(Z) 5.0 PROCEDURE Of)j{

{

5.1 Startine Cinistine Water Pumn(s) 5.1.1 ENSURE OPEN CW9 (CW109), CIRCULATOR BYPASS VALVE.

5.1.2 -

ENSURE CLOSED CW26 (CW126), CONDENSER WATER OUTLET VALVE.

l 5.1.3 DHtBCT NEO to ENSURE the following-4 Bearing bibe is aligned to Cimulating Water Pump.

4 Circulating Water Pump Traveling Scmen is in service.

4 Panel 12461 alarms are clear for Circulating Water Pump to be staned.

C

[

5.1.4 ENSURE the following stan permissives are satisfied:

l

+ Water Box vacuum is armater than or canLle.J5 in. Haa.

$ VACUUM BREAKER r'r nm indientiari on Control Console

(

+ Bearing Lube Header pressure is greater than 15 psig.

5.1.5 START selected Circulating Water Pump.

5.1.6 When Circulating Water Pump stans, ENSURE interiocks actuate:

A. ARil (ARill), CONDENSER AIR REMOVAL OUTLET VALVE -

OPENS.

B.

After three minutes of bypass operation with discharge pressure greater than 14 psig, CW26 (CW126), CONDENSER WATER OUTLET VALVE - OPENS.

C.

Three minutes after CW26 (CW126), CONDENSER WATER OUTIET VALVE opens, and discharge pressme decreases to less than 9 psig, CW9 (CW109), CIRCULNIOR BYPASS VALVE - CLOSES.

l 1

O Salem 1 Page 3 of 8 G. 3 -

S 1.OP-SO.CW-0001(Z) 5.2 Stannine Circuhtine Water Pumo(s) 5.2.1 E radioactive liquki wasse release is aligned to Cirwa Water Pump Ca366 discharge perh, THEN EVALUATE terminating release.

5.2.2 NOIIFY Chemistry that Circulating Water Pump is to be removed from service.

5.2.3 STDP *MM Circulating Water Pump.

5.2.4 ENSURE the following interlocks actuate:

A.

CW9 (CW109), CDtCULATOR BYPASS VALVE - OPENS j

i B.

CW26 (CW126), CONDENSER WATER OUTIET VALVE - CLOSES C.

Circulating Water Pump 4KV breaker - OPENS D.

ARI1 (ARI11), CONDENSER AIR REMOVAL OUTLET VALVE -

CLOSES 5.2.5 E two or more Circulating Water Pumps are O/S, THEN INITIATE St.OP-AB.CW-0001(Q), Circulating Water System

(

Malfunction.

5.2.6 E Condenser Differential T =-+

.re exceeds requirements IAW SC.OP-DD.ZZ-OD30(Z), Operations Log No.10 - 1 Hour Condenser Delta T Readings Units 1 & 2, THEN REDUCE Main Tbrbine load as necessary to maintain computer point Ull52 within requirements.

t Salem 1 Page 4 of 8 Rev.3

i 31.OP-SO.CW-0001(Z) i 5.3

"=+---.rv Trhmine Cirenhtine Water Pumn(s) 5.3.1 EMERGENCY 'IRIP selected CirmI=h Water Pump.

5.3.2 ENSURE the following:

A. Circulating Water Pump 4KV Breaker - TRIPS i

B. WA*IER BOX VACUUM BREAKERS - OPEN l

C. AR16 (ARil6), CONDENSER PRIM 'IK SIDP VALVE - CIDSES D. ARII (AR11I), CONDENSER AIR RMVL OUT VALVE - CLOSES E.

CW9 (CW109), CIRCULATOR BYPASS VALVE - OPENS F.

When CW9 (CW109), CIRCULATOR BYPASS VALVE, is fully open, j

CW26 (CW126), CONDENSER WATER OUILET VALVE - CLOSES.

1 i

NEIE i

l Steam Dump is blocked to condensers which have both Circulating Water Pumps removed from service.

(

a 4

j 5.3.3 E two or more Circulating Water Pumps are O/S, l

THEN INITIATE S t.OP-AB.CW-0001(Q), Circulating Water System Malfunction.

e i

5.3.4 E radioactive liquid waste release is aligned to Circulating Water Pump j

C0366 discharge path, j

TIIEN EVALUATE tenninating itlease.

5.3.5 NOTIFY Chemistry that Circulating Water Pump is removed from service.

5.3.6 E Condenser Differential Temperature exceeds requirements IAW SC.OP-DD.ZZ-OD30(Z), Operations Img No.10 - 1 Hour Candaaw Delta T u*=* ass Units 1 & 2, THEN REDUCE Main Turtnne load as - y to maintain computer point U1152 within requirements.

I Salem 1

/ age 5 of 8 Rev.3

S 1.OP-SO.CW-0001(Z) 5.3.7

(

When directed by SNSS/NSS, RESET Circulating Water Pump for normal startup as follows:

A. PRESS STOP for Cirad=*ia-Water Pump to reset start circuit.

B.

PRESS START for Circulating Water Pump to reset Circulating Water VACUUM BP.EADet.

C. E AUTO 3 TART of Circulating Water Pump is NOT requised, IBM PRESS STOP for Circulating Water Pump before Water Box prime indicates 15 in. Hga.

5.4 Alienine And _hrine Rnweency brina inhrieneinn To Circulmeine Water Pumn(d l

5.4.1 WHEN abgning um.wy Bearisig h to Circulating Water Pumps.

THEN PERFORM the following:

A.

OPEN EMERGENCY. LUBE WATER SUPPLY VALVES:

l

+

ISC15

+

ISC18 B.

START additional Screen Wash Pumps as required to provide adequate

[

Bearing Lube pressure to operating Circulating Water Pumps.

5.4.2 WHEN normal Bearing Lubrientina to Cuculating Water Pumps is restored, THEN PERFORM the following:

A. CLOSE EMERGENCY LUBE WATER SUPPLY VALVES:

4 ISC15

+

ISC18 B.

STOP Screen Wash Pumps started to supply emergency Beanng Lube.

END OF PROCEDURE SEC110N i,'

Salem 1 Page 6 of 8 Rev.3 e

3 i.

S1.OP-SO.CW-0001(2) 6.0 RECORDS

?

i None i

i

7.0 REFERENCES

7.1 Undstad Final Safety Analysis Reoort:

7.1.1 Section 10.5, Cuculating Water System i

i 7.2 Tehaie=1 Mn-ific=* inns - Unit 1:

I None I

7.3 Procedures

None j

7.4 Drawings

1 7.4.1 205209, Circulating Water PalD 7.4.2 232303, Circulating Water System Cirmlating Water Pumps, Cin:. Beanng Lube Pumps, & Screen Wash Pumps, instrument Schematic

-(

i i

i I

i 1

t Salem 1 Page 7 of 8 Rev. 3

S1.QP-SO.CW-0001(Z)

(

7.5 Others-7.5.1 Westinghouse Technical Manual, Main Turbine, I.L.

1250 3959-A,Section II. A, Lirnks, Settings, and Precautions 7.5.2 Engineering later 90-161, Radiatian Monitor Operability 7.5.3 NRC Nut N87013, Reactor Trip and False Rimekand Signal, Corrective Actions involving Ciraldia-Water Pumps 7.5.4 NSO INCI 91-051, Operability of Radiation Monitors due to Circulating Water Pump Manipulations 7.5.5 NSO INCI 91-105, Faihue to Stop Waste Releases when Circulating Water Purnp Stopped 7.6 Cross References-7.6.1 SC.OP-DD.ZZ-OD30(Z), Operations Iog No.10 - 1 Hour Condenser Delta T Readings Units 1 & 2 7.6.2 SC.OP-DD.ZZ-OD03(Z), Large Motor Starting Criteria 7.6.3 St.OP-AB.CW-0001(Q), Circulating Water System Malfunction

7.7 Commitments

7.7.1 C0366, NSO INCI 9I-051 l

Salem 1 Page 8 of 8 Rev. 3 i