l CLINTON POWER STATION l

INSERVICE INSPECTION

[

PUMP AND VALVE TESTING PROGRAM l

NOVEMBER, 1985 e

G O

l l

l

{

I hh2300166 851226 0

ADOCK 05000461 -

PDR

I.

INTRODUCTION This program describes how safety-related pumps and valves will be tested to satisfy the requirements of the ASME Boiler and Pressure Vessel Code Section XI, Rules for the Inservice Inspection of Nuclear Power Plant Components, 1980 Edition, Winter 1981 Addenda.

The requirements of this edition and addenda will be used during the first 10 year inspection interval or until a later edition is selected to be used.

Later editions must be endorsed in 10CFR50.55a or approved by the appropriate enforcement and regulatory agencies prior to their use.

II.

PUMP TESTING A.

Scope The requirements of this program shall be applied to Class 1,2, and 3 pumps which are required to perform a specific function in shutting down the reactor or in mitigating the consequences of an accident and are arovided with an emergency power source.

The pumps which are included in this program are listed in Table 1, Pumps Requiring Inservice Testing.

TABLE #1 Pumps Requiring Inservice Testing Equipment Number Equipment Name IC41-C001A Standby Liquid Control (SLC) Pump A

,'41-C001B Standby Liquid Control Pump B lbOO1PA Diesel Oil Transfer Pump A 1D001PB Diesel Oil Transfer Pump B ID001PC Diesel Oil Transfer Pump C 1E12-C002A Residual Heat Removal Pump A 1E12-C002B Residual Heat Removal Pump B IE12-C002C Residual Heat Removal Pump C 1E12-C003 Water Leg Pump 1E21-C001 Low Pressure Core Spray Pump 1E21-C002 Water Leg Pump 1E22-C001 High Pressure Core Spray Pump 1E22-C003 Water Leg Pump 1E51-C001 Reactor Core Isolation Cooling (RCIC)

Pump 1E51-C003 Water Leg Pump 3X01PA Shutdown Service Water Pump A ISX01PB Shutdown Service Water Pump B ISX01PC Shutdown Service Water Pump C LJE51 B.

Frequency of Testing Inservice tests of pumps shall be aerformed every 3 months during normal plant operations.

Tais frequency shall be maintained during extended cold shutdowns and refueling outages whenever possible.

If this frequency can not be maintained during these shutdown periods, the pump (s) shall be tested within 1 week of the plant being returned to normal operating conditions.

C.

Inservice Test Quantities The following test parameters shall be observed or measured during inservice testing of pumps, unless relief has been requested from the testing requirements (See Appendix A, Pump Testing Relief Requests).

1.

Speed (RCIC pump only, all other pumps are constant speed type).

2.

Inlet pressure (measured prior to pump startup and during testing).

3.

Differential pressure.

4.

Flow rate.

5.

Vibration amplitude.

6.

Proper lubrication level (RCIC and SLC pumps only, other pumps lubrication is supplied by the fluid being pumped).

Relief from measuring bearing temperature has been requested for all pumps (except RCIC).

The technical justification for this request is in Appendix A.

D.

Reference Values 1.

Pump testing baseline reference values shall be established prior to fuel load or at the first operational surveillance test after it has been determined that the reference values represent acceptable pump operation.

2.

After a aump has been remlaced, a new set of reference values s'aall be establis'aed using the results of the first inservice test run after the pump is returned to service.

LJE51 3.

After a pump is repaired or receives routine service that may affect the established reference values, a new set of values shall be established or the previous values confirmed by an inservice test performed prior to returning the pump to normal service.

Any deviations between the previous agd new values shall be identified.

The new values shall then be verified that they represent acceptable pump operation.

E.

Duration of Tests Each pump shall be run at least 5 minutes under conditions as stable as the associated system permits.

At the end of this time, at least one measurement or observation of each of the quantities shall be made and recorded.

The RCIC aump shall be run until bearing temperatures stabilize during tie annual test.

F.

Instruments l.

Accuracy Instrument accuracy shall be within the following limits:

a.

Pressure - 1 2% of full scale.

b.

Differential pressure - 1 2% of full scale.

Flow rate - 1 2% of full scale.

c.

d.

Speed - 1 2% of full scale.

e.

Vibration amplitude - 15% of full scale.

f.

Temperature -

5% of full scale.

2.

Range The full scale range of each instrument shall not exceed 3 times the reference value of the parameter being measured.

3.

Calibration Instruments shall be calibrated prior to establishing reference values and on a regular basis as established by the measuring and test equipment calibration schedule.

Prior to performing any inservice tests, the calibration dates for the instruments to be used in the test shall be verified.

LJE51..

G.

Analysis of Results 1.

Test results shall be analyzed within 96 hours0.00111 days <br />0.0267 hours <br />1.587302e-4 weeks <br />3.6528e-5 months <br /> of i

completion of the test.

This analysis shall consist of a comparison of the measured test quantities and the ranges defined in Table 2, Allowable Ranges Of Test Quantities.

If these ranges cannot be met, an analysis shall be performed to determine lower range limits that will allow the pump to fulfill its function.

These lower limits shall then be included in the pump test record and utilized during subsequent tests.

2.

When test quantities fall within the alert range of Table 2, the testing frequency shall be doubled until the cause of the deviatYon is determined and the condition corrected.

3.

When test quantities fall within the required action range of Table 2, the pump shall be declared inoaerable and not returned to service until the cause of tie deviation is determined and the condition corrected.

4.

When a test shows deviation greater than allowed by Table 2, the instruments involved may be recalibrated and the test rerun.

H.

Corrective Action After the cause of deviations to test quantities has been determined, the condition shall'be corrected by either repairing or replacing the pump or by performing an analysis to demonstrate that the condition does not impair pump operability and the pump will perform its function.

A new set of reference values shall be established af ter such an analysis.

I.

INSERVICE TEST RECORDS 1.

Summary Listing A list of pumps shall be maintained by the ISI coordinator to record the current status of the test program.

2.

Pump Records l

Manufacturers' pump records shall be maintained in the CPS vault.

3.

Inservice Test Plans The inservice inspection program manual shall. include the following information:

l LJE51 '

f I'

TABLE 2 ALLOWABLE RANGES OF Test Quantities Alert Range Required Action Range Test Quantity Acceptable Range Low Values High Values Imv Values High Values Pg [ Note (l)]

AP 0.93 to 1.02 P 0.90 to.93 P 1.02 to 1.03 P

< 0.90 P

>1.03 P

r Q

0.94 to 1.02Q 0.90. to 0.94Q 1.02 to 1.03Q 4 0. W

> 1. 03Q, r

r r

r O to 1 mil None 1 to 1.5 mil None

> 1.5 mil V, when 0 < V g 0.5 mil V, when 0.5 mil <Vr $ 2.0 mil O to 2V mil None 2V "II

  • 3Y mil N ne

>3V "Il r

r r

r V, when 2.0 mil ( Vr f 5.0 mil O to (2 + V ) mil None (2+V )"I1 * (4*V ) mil None

>(4 + V ) mil r

r r

V, when V > 5.0 mil 0 to 1.4V mil Mone 1.4V mil to 1.8V mil None 1.8V "i1 r

r P - Inlet pressure 6P - Differential pressure Q - Flow rate V - Vibration r - Reference value NOTE 1 - Inlet pressure shall be within limits specified by Illinois Power s

s LJE51

f a.

Test flow path to be used, b.

Instruments to be used to measure the various test quantities.

c.

Reference values and limits for the quantities to be measured.

4,.

Record of Tests The pump test record shall include the following information:

a.

Date of test.

b.

Measured and observed quantities.

c.

Instruments used.

d.

Comparisons with allowable ranges of test values.

e.

Analysis of any deviations in test quantities.

f.

Corrective action requirements.

g.

Signature of personnel conducting the test and analyzing its results.

5.

Record of Corrective Action a.

Replacements When a pump is replaccd, the following information-shall be included in the replacement records, as a minimum:

1)

Summary of replacement activities.

ii)

Signature of the individual responsible for the replacement activities.

b.

Repairs and Routine Service When a pump has been repaired or received routine servicing which could affect the established the following reference values of a pump, d in the activity information shall be include records.

1)

Summary of the activities performed, 11)

Results of the inservice test performed to confirm the previous reference values.

LJN51 111)

Analysis of any deviation between previous and new values to assure that the new values represent acceptable pump operation.

iv)

Signature of personnel responsible for the repair / servicing activities and subsequent testing and analysis.

c.

Analysis of Deviation Found During Testing When an analysis of deviations between test quantities and allowable ranges is performed to confirm pump operability, the following information shall be recorded.

1)

Summary of the analysis and confirmation of acceptable pump operability, 11)

New reference values that are established during the subsequent inservice test.

iii)

Signature of personnel responsible for performing the analysis and subsequent inservice test.

III. Valve Testing A.

Scope The requirements of this program apply to Class 1, 2, and 3 valves (and their actuating and position indicating systems) which are required to perform a specific function in shutting down the reactor to a cold shutdown condition or in mitigating the consequences of an accident.

The following valves are exempt from the requirements of this program:

1.

Valves used as operating conveniences (such as manual vent, drain, instrument, and test valves).

2.

Valves used for system control (such as pressure regulating valves).

3.

Valves used only for maintenance.

4.

External control and protection systems responsible for sensing plant conditions and providing signals for valve operation.

The valves which are to be tested under this program are listed in Appendix B, Valves Requiring Inservice Testing.

LJE51

  • l-B.

Definitions 1.

Active valve - A valve which is required to change position to accomplish a specific function.

2.

Passive valve - A valve which is not required to change position to accomplish a specific function.

3.

Category A - Valves for which seat leakage is limited to a specific maximum amount in the closed position to fulfill their function.

4.

Category B - Valves for which seat leakage in the closed

' position is inconsequential to fulfill their function.

5.

Category C - Valves which are self-actuating in response to some system characteristic, such as; pressure or flow direction.

6.

Category D - Valves which are actuated by an energy source capable of only one operation, such as explosive -

actuated valves.

C.

Testing Requirements for Active and Passive Valves Active and passive valves shall be tested in accordance with the requirements of Table 3, Inservice Test Requirements.

i,.

D.

Frequency of Testing 1.

Seat leakage tests shall be performed at least once every 2 years,during refueling outages or extended cold shutdown periods.

2.

Valve exercising and stroke: timing shall be performed every 3 months unless such testing is not practical during normal plant operations. In such cases, the valves will be fully stroked during refueling outages or extended cold shutdown periods.

3.

Relief valve setpoints shall be verified in accordance with a schedule that provides for all applicable relief valves to be tested every 5 years.

4.

Explosive - actuated valves shall be tested at least once every 2 years during refueling outages or extended cold shutdown periods.

LJE51 TABLE 3 INSERVICE TEST REQUIREMENTS VALVE SEAT LEAKAGE STROKE TIME EXERCISE SPECIAL CATEGORY FUNCTION TEST TEST TEST TEST A

Active Yes Yes Yes No A

Passive Yes No No No B

Active No Yes Yes No B

Passive No No No No C-Relief Active No No No Yes Valves Passive No No No No C-Check Active No No Yes No Valves Passive No No No No D

Active No No No Yes D

Passive No No No No LJE51,

.p

5.

Valves with remote position indication shall be observed at least once every 2 years to verify that valve indication is accurately indicated.

6.

For valves in a system declared inoperable or not required to operate, the exercising and stroke timing schedule need not be followed, however, within 30 days prior to returning the system to operable status, the valves shall be tested as applicable and the test frequency resumed.

E.

Test Procedures 1.

Seat Leakage Tests a.

Valve seat leakage tests shall be made with the pressure differential in the same direction as when the valve is performing its function unless one of the following exceptions is taken:

1)

Globe valves may be tested with pressure under the seat.

ii)

Butterfly valves may be tested in either direction if their seat construction is designed for sealing against pressure from both sides.

iii)

Gate valves with 2 piece disks may be tested by pressurizing between the seats.

iv)

Valves (except check valves) may be tested in either direction if the functional differential pressure is 15 psi or less.

v)

Types of valves in which service pressure tends to diminish overall leakage may be tested at lower than service differential pressure. In such cases, the observed leakage (l ) shall be adjusted. This adjustment shall g

be made by utilizing the following formula:

P 1

g If=l P

e g

l

= observed leakage e

if = functional leakage P

= test pressure g

Pg = functional pressure LJE51 _

b.

Seat leakage shall be measured by:

1)

Draining the line, closing the valve,

~

bringing one side to tesc pressure, and measuring leakage through a downstream telltale connection.

ii)

Measuring the feed rate required to maintain pressure between two valves, provided the total apparent leak rate is charged to the valve being tested.

However, if the leak rate of the valve not being tested is known, the leak rate of the test valve shall be determined by subtracting the leak rate of the valve not under test from the feed rate.

c.

Seat leakage rates shall be evaluated for acceptability _by comparing the test results with previous test results and the maximum permissible leakage rate.

2.

Valve Exercising _

a.

Valves shall be exercised to the position required to fulfill their function.

b.

Valve disk movement shall be determined by observing an indicator that signals the required change of disk position, or observing indirect evidence (changes in system pressure, flow rate, level, or temperature) which reflect stem or disk position.

c.

Check valves which are normally open and are required to prevent reverse flow shall be tested in a manner that proves the disk travels to the seat promptly on the cessation or reversal of flow.

d.

Check valves which are normally shut and whose function is to open on reversal of pressure differential shall be tested by proving that the disk moves away from the seat when the closing pressure is removed and flow through the valve is initiated, or when a mechanical force is applied to the disk.

e.

Valves with fail - safe actuators shall be tested by observing the operation of the valves upon loss of actuator power.

3.

Valve Stroke Timing a.

Stroke time shall be that time interval from initiation of the actuating signal to th? Jesired position indication.

LJE51.

e

-+m

b.

The stroke time of valves shall be measured to the nearest second.

4.

Relief Valve Testing Relief valve set points shall be tested in accordance with ASME PTC 25.3-1976 F.

Corrective Action 1.

Seat Leakage Tests If any of the following conditions are found during testing, the valve shall be repaired or replaced.

a.

Leakage rates exceeding the maximum permissible rate.

b.

For valves 6 inches nominal pipe size and larger, a leakage rate that exceeds the rate determined by the grevious test by an amount that reduces the margin 3etween measured leakage rate and the maximum permissible rate by 50% or greater, c.

If tests show a leakage rate increasing with time, and projection based on three or more tests indicates that the leakage rate of the next scheduled test will exceed the maximum permissible rate by greater than 10%.

2.

Exercising and Stroke Timing a.

If a valve fails to exhibit the required change of stem or disk position or exceeds its specified limiting value of stroke time, corrective action shall be initiated immediately.

If the condition cannot be corrected within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, the valve shall be considered inoperable.

b.

When corrective action is required as a result of tests performed during cold shutdown periods, the condition must be corrected prior to starting the plant up.

LJE51 -.

The test frequency for* power operated valves shall c.

be increased to once per month if:

1)

For valves with stroke times greater than 10 seconds, the valve exhibits an increase in stroke time of 25% or more from the last test.

11)

For valves with stroke times of 10 seconds or less, the valve exhibits an increase.in stroke time of 50% or more from the last test.

3.

Relief Valve Testing

.A relief valve failing to function properly during testing shall be repaired or replaced.

G.

Valve Replacement, Repair, and Maintenance When a valve or its control system has been replaced, repaired, or has undergone maintenance that could affect its performance and prior to the time it is returned to service, it shall be tested to demonstrate that the affected performance parameters are within acceptable limits.

The results of these tests shall be used during subsequent inservice testing as appropriate.

H.

Inservice Test Records 1.

Summary Listing The ISI Coordinator shall maintain a list of valves in this program and the current status of the program.

2.

Preservice Tests Preservice test results and manufacturers' functional test results shall be maintained in the CPS vault.

3.

Test Results The test results records shall include the dated signature of the individual responsible for the test.

LJE51 1

e APPENDIX A PUMP TESTING RELIEF REQUESTS LJE51.

RELIEF REQUEST 001 I.

Component Identification A.

Name:

All pumps listed in Table 1 (Except RCIC)

B.

Number:

See Table 1 C.

Function:

Safely shutdown the reactor or mitigate the consequences of an accident.

D.

ASME Section III Code Class:

See Table 1 II.

Relief from:

A.

ASME Code Requirement:

IWP-3410 Bearing Temperature B.

Reason for Relief:

The measurement of annual pump bearing temperature does not increase any confidence in the reliability of the pumps because bearing temperature rises just minutes prior to failure. of the pump bearing.

Therefore measurement of annual pump bearing temperature as required by the code will not be recorded.

III.

Alternate In-Service Test:

- None -

LJE51,

l 1

1

RELIEF REQUEST 002 I.

Component Identification:

A.

Name:

Diesel Fuel Oil Transfer pump 1A, 1B, and 1C e

B.

Number:

1D00lPA, ID00lPB, and 1D00lPC C.

Function:

The Diesel Fuel Oil Transfer pumps transfe diesel fuel from diesel storage tank to diesel fuel day tank.

D.

ASME Section III Code Class:

3 II. -

Relief from:

A.

ASME Code Requirement:

IWP-4600 Flow rate B.

Reason for Relief:

Flow rate measuring instrument not installed.

-III.

Alternate In-Service Test:

The flow rate of diesel fuel oil transfer pumps will be calculated by dividing the change in level of the diesel fuel day tank by the time the diesel fuel oil transfer pump is in operation.

LJE51 -_

J RELIEF REQUEST 003 I.

Component Identification:

A.

Name:

Standby Liquid Control pump 1A & IB B.

Number:

1C41-C001A & IC41-C001B C.

Function:

Supply a neutron absorbing solution into the reactor in sufficient concentration and quantity to overcome the maximum positive reactivity.

5 D.

ASME Section III Code Class:

2 II.

Relief from:

t A.

ASME Code Requirement:

IWP-4600 Flow rate B.

Reason for Relief:

Flow rate measuring instrument not installed.

O III.

Alternate In-Service Test:

The flow rate of the SLC pump will be calculated by dividing the change in level of the SLC test tank by the time the SLC pump is in operation.

j LJE51 e

4 m.

RELIEF REQUEST 004 I.

Component Identification:

A.

Name:

Shutdown Service Water Pdmps lA, IB, and 1C B.

Number:

ISX0lPA, 1SX01PB, & ISX0lPC C.

Function:

Shutdown Service Water Pumps provide a reliable source of cooling water for station auxiliaries which are essential to shutdown the reactor safely following the unlikely event of a LOCA or a complete loss of offsite AC Power.

D.

ASME Section III Code Class 3

II.

Relief from:

A.

ASME Code Requirement:

IWP-4200 Inlet Pressure B.

Reason for Relief:

These pumps are deep draft and take suction from a lake where level is essentially constant throughout the year.

III.

Alternate In-Service Test:

- None -

t LJE51 -

O

APPENDIX B VALVES REQUIRING INSERVICE TESTING e

LJE51 -- -

VALVE TESTING LEGEND Type B

-Butterfly Valve C

-Check Valve CV

-Control Valve EFC -Excess Flow Check Valve EX

-Explosive Valve G

-Gate Valve GL

-Globe Valve NC

-Non-Slam Check Valve P

-Plug _ Valve R

-Relief Valve

. Safety Relief Valve SR VR

-Vacuum Relief Valve Actuator AO

-Air Operated H0

-Hydraulic Operated M

-Manually Operated MO

-Motor Operated SO

-Solenoid Operated MFC

- Manual Flow Control

.GSC

- Discharge Stop Check Normal Position / Test Position 0

-Open C

-Closed LO

- Locked Open Test Method

1. -

Valve shall be exercised to the position required to fulfill its function.

2.

The stroke time of the valve shall be measured.

3.

Valve seat leakage test.

4.

Twenty percent (20%) of explosive charges shall be removed, fired, and replaced every two (2) years.

5.

Bench testing with suitable hydraulic or pneumatic equipment.

P LJE51.

h

Test Method (Cont'd) 6.

Verify and record valve position before performing an operation and after completing an operation.

7.

-Loss of power test.

Test During 1.

Power Operations

'2.

Startup 3.

Hot Shutdown 4.

Cold Shutdown 5.

Refueling Notes

'l.

Test position is for exercising and stroke timing only.

2.

Valves will be leak rate tested during cold shutdown periods or refueling outages.

3.

Testing may be performed by outside contractor.

LJE51.

POSITION 2

VALVE NORM P&ID TEST TEST g

NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METH COND COMMENTS C

M05-1071/2 IB21-F001 GL 2

1 A

MO C

D-4 3

4.5 C

M05-1071/2 IB21-F002 GL 2

1 A

MO C

E-4 3

4,5 0

M05-1004 See Relief IB21-F0 LOA NC 18 1

A/C

'C C-7 1,3 4,5 Request 001 0

M05-1004 See Relief C

A-7 1,3 4,5 Request 001 IB21-F010B NC 18 1

A/C 0

M05-1002/1 IB21-F016 G

3 1

A M0 C

B-1 1,2,3 1-5 0

M05-1002/1 IB21-F019 G

3 1

A M0 C

B-1 1,2,3 1-5 0

M05-1002/1 See Relief IB21-F022A CL 24 1

A A0 C

C-2 1,2,3,7 1-5 Request 053 0

M05-1002/1 See Relief IB21-F022B GL 24 1

A A0 C

F-2 1,2,3,7 1-5 Request 053 0

M05-1002/1 See Relief IB21-F022C GL 24 1

A A0 C

A-2 1.2.3,7 1-5 Request 053 0

M05-1002/1 See Relief IB21-F022D CL 24 1

A A0 C

D-2 1,2,3,7 1-5 Request 053 0

See Relief IB21-F024A C

3 C

C M10-1002/5 1

4,5 Request 042 0

See Relief i

1B21-F024B C

4 3

C C

M10-1002/5 1

4.5 Request 042 0

See Relief IB21-F024C C

h 3

C C

M10-1002/5 1

4,5 Request 042 0

See Relief-C M10-1002/5 1

4.5 Request 042 IB21-F024D C

h 3

C I

O M05-1002/2 See Relief 1B21-F028A GL 24 1

A A0 C

C-5 1,2,3,7 1-5 Requesc 053 l

0 M05-1002/2 See Relief I

IB21-F028B GL 24 1

A A0 C

E-5 1,2,3,7 1-5 Request 053 0

M05-1002/2 See Relief IB21-F028C GL 24 1

A A0 C

B-5 1,2,3,7 1-5 Request 053 O

M05-1002/2 See Relief IB21-F028D GL 24 1

A AO C

E-5 1,2,3,7 1-5 Request 053 0

See Relief IB21-F029A C

b 3

C C

M10-1002/5 1

4,5 Request 042 j

O See Relief IB21-F029B C

3 C

C M10-1002/5 1

4,5 Request 042 LJE51 A POSITION 2

VALVE NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS CATECORY ACTUATOR TEST COORD METil COND COMMENTS O

See Relief IB21-F029C C

h 3

C C

M10-1002/5 1

4,5 Request 042 O

See Relief IB21-F029D C

3 C

C M10-1002/5 1

4,5 Request 042 0

M05-1004 See Relief IB21-F032A NC 20 1

A/C A0 C

C-6 1,3,7 4,5 Request 001 0

M05-1004 See Relief IB21-F032B NC 20 1

A/C A0 C

A-6 1,3,7 4,5 Request 001 C

See Relief IB21-F036A C

h 3

C 0,C M10-1002/2 1

4,5 Request 042 C

See Relief IB21-F036F C

h 3

C 0,C M10-1002/2 1

4,5 Request 042 See Relief r

0,C M10-1002/2 1

4,5 Request 042 IB21-F036G C

h 3

C C

See Relief IB21-F036J C

h 3

c 0,C M10-1002/2 1

4,5 Request 042 C

See Relief 0,C M10-1002/2 1

4,5 Request 042 IB21-F036L C

3 C

C See Relief IB21-F036M C

h 3

C 0,C M10-1002/2 1

4,5 Request 042 C

See Relief 0,C M10-1002/2 1

4,5 Request 042 JB21-F036N C

h 3

C C

See Relief jiji-F036P C

h 3

C 0,C M10-1002/2 1

4,5 Request 042 C

See Relief u

IB21-F036R C

3 C

0,C M10-1002/2 1

4,5 Request 042 C

M05-1002/1 See Relief 0

C-6 1

4,5 Request 003 IB21-F037A VR 10 3

C C

M05-1002/1 See Relief IB21-F037B VR 10 3

C 0

E-6 1

4,5 Request 003 C

M05-1002/1 See Relief 0

A-7 1

4,5 Request 003 IB21-F037C VR 10 3

C C

M05-1002/1 See Relief 0

D-7 1

4,5 Request 003 IB21-F037D VR 10 3

C C

M05-1002/1 See Relief 0

E-4 1

4,5 Request 003 IB21-F037E VR 10 3

C C

M05-1002/1 See Relief 0

A-5 1

4,5 Request 003 IB21-F037F VR 10 3

C C

M05-1002/1 See Relief 0

A-4 1

4,5 Request 003 IB21-F037G VR 10 3

C LJE51A.

POSITION 2

NORM P&ID TEST TEST VALVE g

NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METil COND COMMENTS C

M05-1002/1 See Relief IB21-F037H VR 10 3

C 0

C-5 1

4,5 Request 003 C

M05-1002/1 See Relief 0

E-7 1

4,5 Request 003 IB21-F037J VR 10 3

C C

M05-1002/1 See Relief IB21-F037K VR 10 3

C 0

A-5 1

4,5 Request 003 C

M05-1002/1 See Relief 0

D-6 1

4,5 Request 003 IB21-F037L VR 10 3

C C

M05-1002/1 See Relief IB21-F037M VR 10 3

C 0

E-3 1

4,5 Request 003 C

M05-1002/1 See Relief 0

E-5 1

4.5 Request 003 IB21-F037N VR 10 3

C C

M05-1002/1 See Relief IB21-F037P VR 10 3

C 0

A-6 1

4,5 Request 003 C

M05-1002/1 See Relief 0

D-5 1

4,5 Request 003 IB21-F037R VR 10 3

C C

M05-10^'/1 See Relief 0

A-3 1

4,5 Request 003 IB21-F037S VR 10 3

C C

See Relief 0

M10-1002/1 1

4,5 Request 042 IB21-F039B C

h 3

C C

See Relief 0

M10-1002/1 1

4.5 Request 042 IB21-F039C C

h 3

C C

See Relief 0

M10-1002/1 1

4,5 Request 042 IB21-F039D C

h 3

C C

See Relief IB21-F039E C

3 C

0 M10-1002/1 1

4,5 Request 042 C

See Relief 0

M10-1002/1 1

4,5 Request 042 IB21-F03911 C

h 3

C C

See Relief IB21-F03SK C

h 3

C 0

M10-1002/1 1

4,5 Request 042 C

See Relief IB21-F039S C

3 C

O M10-1002/1 1

4,5 Request 042 C

M05-1071/2 See Relief e

IB21-F040 VR 2

3 C

0 D-3 1

4,5 Request 003 C

M05-1002/1 IB21-F041A SR 8x10 1

C A0 C

C-6 5

4,5 See Note 1 C

M05-1002/1 IB21-F041B SR 8x10 1

C A0 C

F-7 5

4,5 See Note 1 C

M05-1002/1 IB21-F041C SR 8x10 1

C A0 C

B-8 5

4,5 See Note i

. LJE51A

POSITION 2

VALVE NORM P&ID TEST TEST y

NUMBER TYPE SIZE CLASS CATECORY ACTUATOR TEST COORD METH COND COMMENTS C

M05-1002/1 IB21-F041D SR 8x10 1

C A0 C

D-8 5

4,5 See Note 1 C

M05-1002/1 IB21-F041F SR 8x10 1

C AO C

F-5 5

4,5 See Note 1 C

M05-1002/1 IB21-F041G SR 8x10 1

C AO C

B-6 5

4,5 See Note 1 C

M05-1002/1 IB21-F041L SR 8x10 1

C A0 C

B-4 5

4,5 See Note 1 C

M05-1002/1 IB21-F047A SR 8x10 1

C AO C

C-6 5

4,5 See Note 1 C

M05-1002/1 IB21-F047B SR 8x10 1

C A0 C

F-8 5

4,5 See Note 1 C

M05-1002/1 IB21-F047C SR 8x10 1

C A0 C

B-5 5

4,5 See Note 1 C

M05-1002/1 IB21-F047D SR 8x10 1

C AO C

'7 5

4,5 See Note 1 C

Mud-1002/1 IB21-F047F SR 8x10 1

C A0 C

F-4 5

4,5 See Note 1 C

M05-1002/1 IB21-F051B SR 8x10 1

C A0 C

F-6 5

4,5 See Note 1 C

M05-1002/1 IB21-F051C SR 8x10 1

C A0 C

B-7 5

4,5 See Note 1 C

M05-1002/1 IB21-F051D SR 8x10 1

C A0 C

D-6 5

4,5 See Note 1 C

M05-1002/1 IB21-F051C SR 8x10 1

C A0 C

B-4 5

4,5 See Note 1 0

M05-1004 See Relief IB21-F065A G

20 2

B M0 C

C-5 1,2 4,5 Request 004 0

M05-1004 See Relief IB21-F065B C

20 2

B MO C

A-5 1,2 4,5 Request 004 0,C M05-1002/2 IB21-F067A GL lh 1

A M0 C

C-6 1,2,3 1-5 0,C M05-1002/2 IB21-F067B GL 1

1 A

MO C

E-6 1,2,3 1-5 0,C M05-1002/2 IB21-F067C CL lh 1

A MO C

A-6 1,2,3 1-5 0,C M05-1002/2 IB21-F067D CL lb 1

A MO C

D-6 1,2,3 1-5 C

M05-1002/1 See Relief 0

C-6 1

4,5 Request 003 IB21-F078A VR 10 3

C LJE51 A I

POSITION' -

2 VALVE

-NORM P&ID TEST TEST 3

~ ACTUATOR TEST COORD METH COND COMMENTS NUMBER TYPE SIZE CLASS CATEGORY C

N05-1002/1 See Relief 0

E-6 1

4,5 Request 003 1B21-F078B VR 10 3

C C

M05-1002/1 See Relief 0

A-7 1

4,5 Request 003 IB21-F078C VR 10' 3

C C

M05-1002/1 See Relief 0

D-7 1

4.5 Request 003 IB21-F078D VR 10 3

C C

M05-1002/1 See Relief O

E-4 1

4,5 Request 003 lB21-F078E VR 10 3

C C

M05-1002/1 See Relief 0

A-5 1-4,5 Request 003 IB21-F078F VR 10 3

C C

M05-1002/1 See Relief 0

A-4 1

4,5 Request 003 IB21-F078G VR 10 3

C I

C M05-1002/1 See Relief 0

C-5 1

4,5 Request 003 IB21-F078H VR 10 3

C C

M05-1002/1 See Relief O

E-7 1

4,5 Request 003 IB21-F078J VR 10 3

C C

M05-1002/1 See Relief 0

A-5 1

4,5 Request 003 IB21-F078K VR 10 3

C C

M05-1002/1 See Relief IB21-F078L VR 10 3

C O

D-6 1

4,5 Request 003 C

M05-1002/1 See Relief

.0 E-3 1

4,5 Request 003 IB21-F078M VR 10 3

C C

M05-1002/1 See Relief O

E-5 1

4,5 Request 003 IB21-F078N VR 10 3

C C

M05-1002/1 See Relief 0

A-6 1

4,5 Request 003 IB21-F078P VR 10 3

C C

M05-1002/1 See Relief 1B21-F078R VR 10 3

C O

D-5 1

4,5 Request 003 C

M05-1002/1 See Relief 0

A-3 1

4,5 Request 003 l

IB21-F078S VR 10 3

C i

0 M05-1002/2 See Relief IB21-F098A G

24 2

B Mo C

C-3 1,2 4,5 Request 005 O

M05-1002/2 See Relief i

IB21-F098B G

24 2

B MO C

F-3 1,2 4,5 Request 005 O

M05-1002/2 See Relief IB21-F098C G

24 2

B MO C

B-3 1,2 4,5 Request 005 0

M05-1002/2 See Relief IB21-F098D G

24 2

B Mo C

D-3 1,2 4,5 Request 005 C

M05-1002/1 See Relief 0

F-7 1

4,5 Request 003 l

IB21-F379A VR 2

3 C

LJESIA

~26-l I

Y POSITION l

VALVE NORM P&ID TEST TEST f

NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METH COND COMMENTS l

C M05-1002/1 See Relief IB21-F379B VR 2

3 C

0 F-6 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379C VR 2

3 C

0 F-5 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379D VR 2

3 C

O F-4 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379E VR 2

3 C

0 F-3 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379F VR 2

3 C

0 E-7 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379C VR 2

3 C

O E-6 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379H VR 2

3 C

O E-5 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F3793 VR 2

3 C

O C-6 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379K VR 2

3 C

0 C-5 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379L VR 2

3 C

O B-7 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379M VR 2

3 C

0 B-6 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379N VR 2

3 C

0 B-5 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379P VR 2

3 C

O B-5 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379Q VR 2

3 C

0 B-4 1

4,5 Request 003 C

M05-1002/1 See Relief IB21-F379R VR 2

3 C

0 B-3 1

4,5 Request 003 O

See Relief IB21-F433A C

h 3

C C

M10-1004/8 1

4,5 Request 042 0

See Relief IB21-F433B C

3 C

C M10-1004/8 1

4.5 Request 042 C

M05-1072/1 IB33-F019 CV 3/4 2

B A0 C

E-5 1,2 1-5 C

M05-1072/1 IB33-F020 CV 3/4 2

B A0 C

E-8 1,2 1-5 j

O M05-1032/3 See Relief ICC049 C

10 2

B MO C

C-8 1,2 4,5 Request 019 l

}

LJE51A POSITION 2

VALVE NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST

-COORD METil COND COMMENTS 0

M05-1032/3 See Relief ICC050 G

6 2

'B M0 C

C-7 1,2 4,5 Request 019 0

M05-1032/3 See Relief ICC053 G

6 2

B MO C

C-3 1,2 4,5 Request 019 0

M05-1032/3 See Relief ICC054 G

10 2

B MO C

C-1 1,2 4,5 Request 019 0

M05-1032/3 See Relief ICC057 G

8 2

B MO C

D-8 1,2 4,5-Request 019 0

M05-1032/3 See Relief ICC060 G

8 2

B MO C

C-2 1,2 4.5 Request 019 0

M05-1032/3 See Relief 1CC065 G

2h 3

B MO C

C-6 1,2 4.5 Rac:sst 036 0

M05-1032/3 See Relief ICC067 G

24 3

B MO C

C-3/4 1.2 4.5 Request 036 0

M05-1032/3 See Relief ICC068 G

2 3

B MO C

E-6 1.2 4.5 Request 036 0

M05-1032/3 See Relief ICC070 G

215 3

B MO C

E-3 1.2 4.5 Request 036 0

M05-1032/3 ICC071 C

4 2

B MO 0,C E-2 1,2 1-5 0

M05-1032/3 ICC072 G

4 2

B MO 0.C E-1 1,2 1-5 0

M05-1032/3 100073 G

4 2

B MO 0,C F-1 1,2 1-5 0

M05-1032/3 ICC074 C

4 2

B MO 0,C F-2 1,2 4,5 0,C M05-1032/2 ICC075A B

14 3

B MO C

E-3 1,2 1-5 0,C M05-1032/2 1CC075B B

14 3

B MO C

C-3 1.2 1-5 0,C M05-1032/2 1CC076A B

14 3

B MO C

D-2 1,2 1-5 0,C M05-1032/2 1CC076B B

14 3

B M0 C

C-2 1,2 1-5 0

M05-1032/3 See Relief ICC127 G

8 2

B M0 C

D-8 1,2 4,5 Request 019 0

M05-1032/3 See Relief ICCl28 G

8 2

B MO C

C-2 1,2 4.5 Request 019 0

M05-1032/3 See Relief ICC188A C

2 3

C C

E-6 1

4,5 Request 036 LJE51A O

POSITION 2

VALVE NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METil COND COMMENTS 0

M05-1032/3 See Relief ICC188B C

2 3

C C

C-6 1

4,5 Request 036 0

M05-1034/1 ICM002A EFC 3/4 2

C C

B-7 1

1-5 0

M05-1034/1 1CM002B EFC 3/4 2

C C

A-7 1

1-5 0

M05-1034/1 1CM003A EFC 3/4 2

C C

B-4 1

1-5 0

M05-1034/1 ICM003B EFC 3/4 2

C C

B-7 1

1-5 0

M05-1034/2 See Relief

-~~ICf!0ll G

3/4 2

B SO 0,C C-7 1

1-5 Request 032 0

M05-1034/2 See Relief ICM012 G

3/4 2

B SO 0,C C-6 1

1-5 Request 032 C

M05-1034/2 See Relief ICM014 G

h 2

B SO O

B-6 1

1-5 Request 032 C

M05-1034/2 See Relief ICM015 G

2 B

SO O

F-5 1

1-5 Request 032 C

M05-1034/2 See Relief ICM016 G

h 2

B SO O

E-5 1

1-5 Request 032 C

M05-1034/2 See Relief ICM017 G

2 B

SO O

D-5 1

1-5 Request 032 C

M05-1034/2 See Relief ICM018 G

2 B

SO O

B-5 1

1-5 Request 032 C

M05-1034/2 See Relief ICM022 G

3/4 2

B SO 0,C D-3 1

1-5 Request 032 C

M05-1034/2 See Relief I Cl!023 G

3/4 2

B SO 0,C D-3 1

1-5 Request 032 C

M05-1034/2 See Relief ICM025 G

3/4 2

B SO 0,C C-3 1

1-5 Request 032

.C M05-1034/2 See Relief ICM026 G

3/4 2

B SO 0,C C-3 1

1-5 Request 032 C

M05-lO34/2 See Relief ICM028 G

2 B

SO O

B-3 1

1-5 Request 032 C

M05-1034/2 See Relief ICM031 G

h 2

B SO O

B-4 1

1-5 Request 032 C

M05-1034/2 See Relief ICM032 C

h 2

B SO O

D-4 1

1-5 Request 032 C

M05-1034/2 See Relief ICM033 G

h 2

B SO O

E-4 1

1-5 Request 032 LJF.51A POSITION 2

{

VALVE NORM P&ID TEST TEST g

j NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METH COND COhh2NTS C

N05-l&34/2 See Reliet ICH034

' C h

2 B

SO 0

F-4 1

1-5 Request 032 O

M05-1034/2 See Relief ICM047

'G 3/4 2

B SO 0,C D-6 1

1-5 Request 032 O

M05-1034/2 See Relief ICH048 G

3/4 2

,B SO O.C D-7 1

1-5 Request 032

~

O N05-1034/2 C

C-6 1

1-5 ICM051 EFC 3/4 2

C

^

O M05-1034/3 C

C-5 1

1-5 ICM053 EFC 3/4 2

C O

M05-1071/1 See Relief C

F-3 1

4.5 Request 037 ICH066 EFC 3/4 2

C O

M05-1071/1-See Relief C

E-6 1

4,5 Request 037 ICM067 EFC 3/4 2

C O

M05-1012/6 1CY016 G

6 2

B MO C

C-6 1,2 1-5 0

M05-1012/6 ICY 017 G

6 2

B MO C

C-6 1,2 1-5 0

M05-1012/6 ICY 020 G

3 2

B MO C

D-3 1,2 1-5 0

M05-1012/6 ICYO21 C

3 2

B MO C

D-2 1,2 1-5 0

ICll-F010 GL 1

2 B

A0 0,C-CLN-001 1,2,7 1-5 0

ICll-F011 GL 2

2 B

AO 0,C CLN-001 1,2,7 1-5 0

M05-1078/l See Relief ICll-F083 GL 2

2 B

NO C'

C-7 1,2,7 4,5 Request 008 O

M05-1078/l See Relief C

C-7 1,2 4,5 Request 010 ICll-F122 C

2 2

C O

ICll-F180 GL 1

2 B

AO O.C CLN-001 1,2 1-5 O

ICll-F181 GL 2

2 B

A0 0,C CLN-001 1,2 1-5 f

I C

M05-1077 IC41-F001A GL 3

2 B

MO O

C-6 1,2 1-5

?

LJE51A I

POSITION -

2 VALVE NORM P&ID TEST '

TEST g

r NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METH COND COMMENTS C

N05-1077 IC41-F001B GL 3

2 B

MO O

E-6 1,2

'l-5 C

M05-1077 IC41-F004A EX 1h 1

D M

N/A C-3 4

4-5 C

M05-1077 IC41-F004B EX lh 1

D M

N/A D-3 4

4-5 C

M05-1077 See Relief IC41-F006 NC 3

1 C

O D-2 1

4,5 Request 011 C

M05-1077 O

C-4 5

4,5 1C41-F029A R

1 x2 2

C C

M05-1077 IC41-F029B R

lhx2 2

C 0

E-4 5

4,5 C

M05-1077 O

C-4 1

1-5 3 0'e l-F033A NC lh 2

C C

M05-1077 IC41-F033B NC lh 2

C 0

E-4 1

1-5 C

N05-1077 O

E-1 1

1-5 1C41-F0336 C

4 1

C C

M05-1035/1 O

E-6 5

4,5 IDC006A R

h 3

C C

M05-1035/!

O D-6 5

4,5 IDC006B R

3 C

C M05-1035/2-O E-6 5

4,5 IDG006C R

h 3

C C

M05-1035/2 O

D-6 5

4,5 IDC006D R

h 3

C C

M05-1035/3 O

E-6 5

4,5 IDC006E R

h 3

C C

M05-1035/3 O

D-6 5

4,5 IDC006F R

h 3

C O

M05-1035/1 See Relief IDC007A CV 2

3 B

M C

E-4 1

1-5 Request 038 O

M05-1035/1 See Relief IDC007B CV 2

3 B

M C

C-4 1

1-5 Request 038 0

M05-1035/2 See Relief IDC007C CV 2

3 B

M C

E-4 1

1-5 Request 038 0

M05-1035/2 See Relief IDC007D CV 2

3 B

M C

C-4 1

1-5 Request 038 l

LJESIA POSITION 2

VALVE NORM P&ID TEST

~EST g

NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METil COND COMMENTS O

M05-1035/3 See Relief IDG007E CV 2

3 B

M C

E-4 1

1-5 Request 038 0

M05-1035/3 See Relief IDG007F CV 2

3 B

M C

C-4 1

1-5 Request 038 0

M05-1035/1 See Relief IDCOO7G CV 2

3 B

M C

F-4 1

1-5 Request 038 0

M05-1035/1 See Relief IDG00711 CV 2

3 B

M C

B-4 1

1-5 Request 038 0

M05-1035/2 See Relief IDCOO7J CV 2

3 B

M C

F-4 1

1-5 Request 038 0

M05-lO35/2-See Relief IDG007K CV 2

3 B

M C

B-4 1

1-5 Request 038 C

M05-1035/1 See Relief ILG008A MFC 2

3

_j 0

E-3 1,7 1-5 Request 038 C

M05-1035/1 See Relief IDG008B HFC 2

3 B

0 C-3 1,1 1-5 Request 038 C

M05-1035/1 See Relief 0

F-3 1,7 1-5 Request 038 IDC008C MFC 2

3 B

C M05-1035/1 See Relief 0

B-3 1,7 1-5 Request 038 IDC008D MFC 2

3 B

C M05-1035/2 See Relief 0

E-3 1,7 1-5 Request 038 IDC008E MFC 2

3 B

C M05-1035/2 See Relief 0

C-3 1,7 1-5 Request 038 IDC008F MFC 2

3 B

C M05-1035/2 See Relief 0

F-3 1,7 1-5 Request 038 IDC008G MFC 2

3 B

C M05-1035/2 See Relief 0

B-3 1,7 1-5 Request 038 IDG00811 MFC 2

3 B

C M05-1035/3 See Relief IDC008J MFC 2

3 B

0 E-3 1,7 l-5 Request 038 C

M05-1035/3 See Relief 0

D-3 1,7 1-5 Request 038 IDC008K MFC 2

3 B

C M05-1036/1 0

B-1 1

1-5 ID0001A C

1 3

C C

M05-1036/1 ID0001B C

lb 3

C 0

B-5 1

1-5 C

M05-1036/2 ID0001C C

lb 3

C 0

B-3 1

1-5 IJE51 A POSITION 2

VAI.VE NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METH COND COMMENTS C

M05-1036/1 0

C-1 5

4,5 ID0005A R

3/4xl 3

C C

M05-1036/1 ID0005B R

3/4xl 3

C 0

C-5 5

4,5 C

M05-1036/2 ID0005C R

3/4xl 3

C 0

C-3 5

4,5 0

M05-1075/4 IE12-F003A CL 14 2

B MO 0,C C-2 1,2 1-5 0

M05-1075/4 IE12-F003B GL 14 2

B MO 0,C C-7 1,2 1-5 0

M05-1075/1 IE12-F004A G

20 2

B MO 0,C A-4 1,2 1-5 0

M05-1075/2 IE12-F004B G

20 2

B HO 0,C A-6 1,2 1-5 C

M05-1075/1 IE12-F005 R

lhx2 2

C 0

B-5 5

4,5 C

M05-1075/1 IE12-F006A G

16 2

B MO O

A-5 1,2 1-5 C

M05-1075/2 IE12-F006B C

16 2

B M0 O

A-6 1,2 1-5 C

M05-1075/1 See Relief IE12-F008 C

18 1

A MO 0,C B-4 1,2,3 4,5 Request 054 C

M05-1075/1 See Relief IE12-F009 G

18 1

A MO 0,C B-2 1,2,3 4,5 Request 054 C

M05-1075/4 IE12-F0llA GL 4

2 B

MO 0,C D-4 1,2 1-5 C

M05-1075/4 IE12-F0llB CL 4

2 B

MO 0,C C-3 1,2 1-5 C

M05-1052/1 IE12-F014A G

18 3

B M0 O

D-2 1,2 1-5 C

M05-1052/2 IE12-F014B G

18 3

B MO O

D-2 1,2 1-5 C

M05-1075/1 lE12-F017A R

14x2 2

C 0

B-6 5

4,5 C

M05-1075/2 IE12-F017B R

1 x2 2

C 0

B-6 5

4,5 C

M05-1075/2 IE12-F019 C

4 1

C 0

C-5 1

1-5

. LJE51A

_. _. _.. - - _. ~.. _.. - _.. _ _ _.

.. ~ _ _..

POSITION 2

VALVE NORM P&ID TEST TEST g

NUMBER TYPE ' SIZE CLASS CATEGORY ACTUATOR TEST

~COORD METH COND COMMENTS

.i C

M05-1075/3-IE12-F021' GL 14 2

B MO 0,C D-3 1,2 1-5 i

C M05-1075/2 See Relief:

IE12-F023 CL 4

1 A

MO 0,C C-5 1,2,3 4,5 Request 054

-C M05-1075/1

}

IE12-F024A G

14 2

B MO 0,C C-7 1,2 1-5 1

C M05-1075/1 l

IE12-F024B G

14 2

B MO 0,C C-2 1,2 1-5 C

M05-1075/1

}

O D-4 5

4,5 IE12-F025A R

lxl 2

C C

M05-1075/2 l

'IE12-F025B R

lxlh 2

C 0

E-5 5

4,5 C

M05-1075/3 IE12-F025C R

1x1 2

C O

F-3 5

4,5 C

N05-1075/4 IE12-F026A G

4 2

B MO' O.C E-3 1,2 1-5 7

C M05-1075/4 l

IE12-F026B C

4 2

B MO 0,C E-6 1,2 1-5 O

M05-1075/1 IE12-F027A C

12 2

B MO 0,C D-4 1,2 1-5 O

M05-1075/2 IE12-F027B' G

12 2

B MO O.C D-5 1,2 1-5 4

C M05-1075/1 IE12-F028A G

10 2

B NO O.C F-3 1,2 1-5 C

N05-1075/2 l

IE12-F028B C

10 2

B MO 0,C F-6 1,2 1-5 C

M05-1075/1 i

0,C

-B-8 1

1-5 IE12-F031A NC 14 2

C C

N05-1075/2 0,C B-1 1

1-5 lE12-F031B NC 14 2

C 1

C M05-1075/3 O,C D-1 1

1-5 IE12-F031C NC 14 2

C C

M05-1075/4 O

E-5 5

4,5 IE12-F036 R

4x6 2

C C.

M05-1075/1 See Relief IE12-F041A NC 12 1

A/C AO O

D-2 1,3 1-5 Request 054 See Relief C

M05-1075/2 IE12-F041B NC 12 1

A/C A0 0

D-7 1,3 1-5 Request 054 4

LJESIA :

I

POSIT 19N VALVE.

NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METH COND

, C0!!MENTS C

M05-1075/3 See Relief IE12-F041C NC 12 1

A/C A0 0

E-7 1,3 1-5 Request 054

~

C M05-1075/1 See Relief IE12-F042A G

12 1

A MO O

D-3 1,2,3 1-5 Request 054 C

M05-1075/2 See Relief IE12-F042B C

12 1

A MO O

D-6 1,2,3 1-5 Request 054 C

M05-1075/3 See Relief IE12-F042C G

12 1

A MO O

E-5 1,2,3 1-5 Request 054 0,C M05-10'5/1 0

B-7 1

1-5 IE12-F046A C

4 2

C 0,C M05-107i/2 0

B-2 1

1-5 IE12-F046B C

4 2

C 0,C M05-1075/3 0

B-2 1

1-5 IE12-F046C C

4 2

C 0

M05-1075/4 IE12-F047A C

14 2

B M0 C

C-2 1,2 1-5 0

M05-1075/4 IE12-F047B G

14 2

B MO C

C-8 1,2 1-5 0

M05-1075/1 IE12-F048A - CL 14 2

B MO 0,C C-8 1,2 1-5 0

M05-1075/2 lE12-F048B CL 14 2

B MO 0,C C-1 1,2 1-5 C

M05-1075/1 See Relief 0

D-5 1,3 1-5 Request 054 IE12-F050A NC 10 2

A/C C

M05-1075/2 See Relief IE12-F050B NC 10 2

A/C 0

E-5 1,3 1-5 Request 054 0,C M05-1075/4 IE12-F051A CV 6

2 B

A0 0.C E-3 1,2 1-5 0,C M05-1075/4 IE12-F051B CV 6

2 B

A0 0,C E-7 1,2 1-5 0,C M05-1075/4 IE12-F052A GL 8

2 B

MO 0,C E/F-3/4 1,2 1-5 0,C M05-1075/4 IE12-F052B GL 8

2 B

MO 0,C E/F-5/6 1,2 1-5 C

M05-1075/1 See Relief IE12-F053A GL 10 2

A MO 0,C D-6 1,2,3 4,5 Request 054 C

M05-1075/2 See Relief IE12-F053B GL 10 2

A MO 0,C E-4 1,2,3 4,5 Request 054 0,C M05-1075/4 IE12-F054A C

4 2

C 0

D-3 1

1-5 LJE51A i-POSITION--

+

2 VALVE

. NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS

' CATEGORY ACTUATOR' TEST COORD METH COND CO N S

~

N05-1075/4 O.C I'

IE12-F054B C

4 2

C-0 D-6 1

"l-5 C.

M05-1075/4

t IE12-F055A R

Ex12 2

C 0

C-2' S

4,5 See Note 1 M05-1075/4 C

l[ '

IE12-F055B R

8x12 2

'C 0

C-7 5-4,5 See Note 1 C

M05-1075/4 See Relief ll IE12-F060A 2-way 3/4 2

B SO O

B-4 1,7 1-5 Request 045 C

M05-1075/4 N

See Relief j;

IE12-F060B 2-way 3/4 2

B 30 0

'B-5 1,7 1-5 Request 045 O

M05-1075/1 lE12-F064A G

4 2

B' MO 0,C B-8 1,2 1-5 I

O N05-1075/2

- MO 0,C B-1 1.2 1-5 lE12-F064B G

4 2

B 0

M05-1075/3 lE12-F064C G

4 2

B MO 0,C B-1 1,2 1-5 0,C M05-1075/4 lE12-F065A CV 2

2 B

A0 0,C D-3 1,2 1-5 0,C M05-1075/4 lE12-F065B CV 2

2 B

A0 0,C C-6 1,2 1-5 i

C M05-1052/1 l'

IE12-F068A G

18 3

B MO O

C-1 1,2 1-5 C

M05-1052/2 i

lE12-F068B C

18 3

B.

NO O

C-1 1,2 1-5 1

l' C

M05-1075/1 lE12-F073A GL 1

2 B

MO O

C-3 1,2 1-5 C

M05-1075/2 h

IE12-F073B GL 1h 2

B MO O

B-7 1,2 1-5 C

M05-1075/1 I

IE12-F074A GL 1

2 B

MO O

C-4 1,2 1-5 C

M05-1075/2 i

IE12-F074B CL 1

2 B

MO O

B-5 1,2 1-5 i

C M05-1075/4 See Relief IE12-F075A 2-way 3/4 2

B SO O

B-4 1,7 1-5 Request 045 4

C M05-1075/4 See Relief lE12-F075B 2-way 3/4 2

B SO O

B-5 1,7 1-5 Request 045 t

3 O

M05-1075/1 it

.j IE12-F084A C

2

-2 C

C B-7 1

1-5 i

0

.M05-1075/2 s

C

-B-2 1

1-5 1

1 lE12-F084B C

2 2

C

.T

?'

LJE51 A,

3

. - ~ -

POSITION-2'

' VALVE NORM P&ID-TEST TEST NUMBER TYPE -SIZE CLASS CATEGORY ACTUATOR TEST -

COORD.

METH.

COND COletENTS O

N05-1075/3

~C E-2>

1 1-5 IE12-F084C C'

2h 2

C LO

.M05-1075/1 IE12-F085A GSC 2'

2 C

0,C B-8 1

1-5" LO M05-1075/2 0,C B-1 1

1-5 IE12-F085B GSC 2-2 C'

LO

.H05-1075/3 0,C E-1 1

1-5 IE12-F085C GSC 2-2~

C C

M05-1075/4 lE12-F087A CL 6

2 B

MO O.C E-3 1,2 5 C

M05-1075/4 IE12-F0878 GL 6

2' B

MO 0,C E-6 1,2 1-5' C

M05-1075/4 IE12-F094 G

4 3

B MO O

E-7/8 1,2 1-5 0

M05-1075/4 See Relief i

IE12-F095 2-way 3/4-2 B

SO C'

E-7 1,7 1-5 Request 045 C

M05-1075/4 l;

lE12-F096 G

4 2

B MO O

E-7/8 1,2 1-5 C

M05-1075/4 0

D-7 1

1-5

-lE12-F098 C

4 2

C C

N05-1075/3 IE12-F101 R

lx1 2

C O

C-5 5

4.5 C

M05-1075/4 lE12-F103A VR 2

2 C

O B-1 1

1-5' C

M05-1075/4 0

B-8 1

1-5 IE12-F103B VR 2

2 C

I C

M05-1075/4 l

0 B-1 1

1-5 IE12-F104A VR 2

2 C

C M05-1075/4-0 B-8 1

1-5' IE12-F104B VR 2

2 C

O M05-1075/3 IE12-F105 G

20 2

B MO 0,C B-5

'1,2 1-5 C

M05-1075/4 0

B-3 1

1-5 IE12-F110A VR 2

2 C

i C

M05-1075/4 0

B-7 1

1-5 IE12-F110B VR 2

2 C

j j,

LJE51A I

+

POSITION 2

VALVE NORM P&ID TEST TEST 3

NUMBER TYPE SIZE CLASS CATECORY ACTUATOR TEST COORD METH COND COMMENTS C

M05-1075/4 0

B-3 1

1-5 IE12-FlllA VR 2

2 C

C M05-1075/4 IE12-FillB VR 2

2 C

0 B-7 1

1-5 0

M05-1073 lE21-F001 G

20 2

B MO 0,C B-4 1,2 1-5 C

M05-1073 See Relief 0

E-6 1

1-5 Request 054 IE21-F003 NC 12 2

C C

M05-1073 See Relief IE21-F005 C

10 1

A MO O

E-4 1,2,3 1-5 Request 054 C

M05-1073 See Relief IE21-F006 NC 10 1

A/C AO O

E-2 1,3 1-5 Request 054 0

M05-1073 IE21-F011 0

4 2

B MO 0.C D-6 1,2 1-5 C

M05-1073 IE21-F012 GL 10 2

B MO 0,C D-5 1,2 1-5 C

M05-1073 IE21-F018 R

lhx2 2

C 0

E-5 5

4,5 C

M05-1073 1E21-F031 R

1hxl 2

C 0

C-8 5

4,5 0

M05-1073 IE21-F033 C

2 2

C C

D-6 1

1-5 LO M05-1073 IE21-F034 CSC 2

2 C

C D-6 1

1-5 C

M05-1073 IE21-F303 NC 10 2

C 0

C-5 1

1-5 C

M05-1073 See Relief 0,C F-4 1

4,5 Request 041 IE21-F306 C

3 2

C 0

M05-1074 IE22-F001 G

16 2

B MO 0,C A-6 1,2 1-5 O

M05-1074 IE22-F002 C

16 2

B C

A-5 1

1-5 C

M05-1074 IE22-F004 G

10 1

A MO 0,C E-7 1,2,3 1-5 C

M05-1074 IE22-F005 NC 10 1

A/C A0 0,C E-8 1,3 1-5 0

M05-1074 IE22-F006 GSC 2

2 C

M C

D-4 1

1-5 0

M05-1074 IE22-F007 C

2h 2

C C

D-4 1

1-5 LJESIA

. _ -. ~. _ _.... _...

POSITION' 2

i VALVE NORM P&ID TEST TEST g

NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METH COND COMMENTS C

M05-1074 IE22-F010 CL 10 2

B MO C

D-6 1,2 1-5 C

M05-1074 1

IE22-F0ll GL 10 2

B MO C

D-5 1,2 1-5 C

M05-1074 IE22-F012 G

4 2

B MO 0,C' D-3 1,2 5 C

M05-1074 O

C-5 5

4,5 lE22-F014 R

lx3/4 2

C l

C N05-1074 l

IE22-F015 G

20 2

B MO O

B-7 1,2 1-5 C

M05-1074 O,C B-6 1

1-5 1

lE22-F016 C

20 2

C I

C M05-1074 IE22-F023 GL 10 2

B MO 0,C D-6 1,2 1-5 C

M05-1074 lE22-F024 NC 14 2

C O

E-3 1

1-5 C

M05-1074 l

y IE22-F035 R

lx3/4 2

C O

E-3 5

4,5 C

M05-1074 IE22-F039 R

1x3/4 2

C O

C-6 5

4,5 O

lE22-F330 EFC 3/4 2

C C

M10-1074/3 1

1-5 a

r O

IE22-F332 EFC 3/4 2

C C

M10-1074/3 1

1-5 i

O M05-1041/4 See Relief IE31-F014 G

1 2

B SO C

E-8 1

1-5 Request 033

[

4 O

M05-1041/4 See Relief IE31-F015 C

1 2

B SO C

E-7 1

1-5 Request 033 C

M05-1041/4 See Relief E-8 1

1-5 Request 040 i

IEl-F016 G

1 2

B SO O

M05-1041/4 See Relief

]

IE31-F0l?

G 1

2 B

SO C

C-7 1

1-5 Request 033 4

I O

M05-1041/4 See Relief i

lE31-F018 G

1 2

B SO C

C-8 1

1-5 Request 033 l

C M05-1041/4 See Relief C-8 1

1-5 Request 040 IE31-F019 G

1 2

B SO C

M05-1070

'k IE32-F001A CL l\\

l B

MO 0,C C-7 1,2 1-5 C

M05-1070

,]

i 1E32-F001E GL 1

1 B

MO 0,C E-7 1,2 1-5 I

~

LJESIA i 1

~

~

STN E

M MO C

TD 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 SN EO 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 TC 2TH 2,

2, 2,

2, 2,

2, 2,

2, 2,

2, 2,

2, 2,

2, 1

1 1

1 1

1 ST EE 1

1 1

1 1

1 1

1 1

1 1

1 1

1 TM 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 7

7 7

7 7

7 7

7 7

7 7

7 7

7 7

7 7

7 7

7 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 D

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

DR IO 57 57 57 57 57 57 57 57 57 57 54 53 54 53 S4 52 54 54 54 54

&O 0 -

0 -

0 -

0 0 -

0 -

0 0 -

0 -

0 -

0 -

0 -

U -

0 -

0 -

0 -

0 -

0 -

PC MB MD MC ME MB MD MC ME MB MD MC MC MA MA ME MB MA MA MA MA T

N S

C, C,

C, C,

C, C,

C, C,

C, C.

C.

C, C,

C, C,

C, I

T 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 O

E T

-0 I

S 4

P R

C C

C C

C C

C C

C C

C C

C C

C C

C C

C C

O M ON RO A

O O

O O

O O

O O

O O

O O

O O

T U

M M

M M

M M

M M

M M

M M

M M

TCA YR G

B B

B B

B B

B B

B B

B B

B B

C C

C C

C C

O E

TAC S

A 1

1 2

2 2

2 2

2 2

2 2

2 2

2 2

2 2

2 2

2 S

L C

4 4

4 4

4 4

Z h h b b

b h

h h h

/

/

/

/

/

/

E I

l l

l 1

l 1

1 l

l 1

2 2

2 2

3 3

3 3

3 3

S P

L L

L L

L L

L L

L L

G G

G C

C C

C C

C C

E Y

G G

G C

G G

G G

G G

T J

N A

E J

N A

E J

N A

B C

l l

2 2

2 2

3 3

3 3

6 7

8 9

0 l

5 5

5 D

0 0

0 0

0 0

0 0

0 0

0 0

0 0

1 l

1 1

1 5

ER 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 3

3 3

1 VE F

F F

F F

F F

F F

F F

F F

F F

F F

F F

3 A

LB F

1 AM 2

2 2

2 2

2 2

2 2

2 2

2 2

2 2

2 2

2 2

5 VU 3

3 3

3 3

3 3

3 3

3 3

3 3

3 3

3 3

3 3

2 E

N E

E E

E E

E E

E E

E E

E E

E E

E E

E E

3 J

l l

l I

I I

l I

l l

l l

1 I

I 1

L 1__

l 1

I

POSITION 2

VALVE NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METH COND COMMENTS O

M05-1079/2 IE51-F010 G

6 2

B MO 0.C A-6 1,2 1-5 C

M05-1079/2 IE51-F0ll C

6 2

C 0

A-4 1

1-5 C

M05-1079/2 See Relief IE51-F013 G

6 1

A MO 0,C F-6 1,2,3 1-5 Request 054 0

M05-1079/2 See Relief IE51-F015 CV 1

2 SC C-4 Request 046 C

M05-1079/2 IE51-F018 R

2x3 2

C 0

C-5 5

4,5 C

M05-1079/2 IE51-F019 CL 2

2 B

M0 0.C D-6 1.2 1-5 C

M05-1079/2 IE51-F021 C

2 2

C 0

D-5 1

1-5 C

M05-1079/2 e

IE51-F022 CL 4

2 B

MO 0,C E-5 1,2 1-5 0

M05-1079/1 lE51-F025 CV 1

2 B

A0 0,C D-5 1,2,7 1-5 0

M05-1079/1 lE51-F026 CV 1

2 B

A0 0,C D-5 1,2,7 1-5 C

M05-1079/2 0

B/C-4 1

1-5 IE51-F030 C

6 2

C C

M05-1079/2 IE51-F031 C

6 2

B MO 0,C B/C-6 1,2 1-5 C

M05-1079/1 1E51-F040 C

12 2

C 0

C-4 1

1-5 C

M05-1079/1 lE51-F045 CL 4

2 B

M0 O

D-4 1,2 1-5 C

M05-1079/1 IE51-F046 CL 2

2 B

MO O

C-3/4 1,2 1-5 C

M05-1079/1 0,C B-1 1

1-5 lE51-F047 C

2b 2

C C

M05-1079/2 IE51-F059 G

4 2

B M0 C

E-5 1,2 1-5 0

M05-1079/1 IE51-F061 C

2h 2

C 0,C B-4 1

1-5 0

M05-1079/1 lE51-F063 G

8 1

A MO 0.C E-8 1,2,3 1-5 0

M05-1079/1 IE51-F064 G

8 1

A MO 0.C E-5 1,2,3 1-5 LJE51A 4

S f5 T

e0 N

i E

l t es te R e lo u

C eq ee SR 5

5 5

5 5

5 5

5 5

5 5

5, TD 5

5 5

5 5

5 5

SN EO 1

1 1

1 1

1 1

4 1

1 1

1 1

1 1

1 1

1 1

TC 7,

7,

,'T H 3,

2, 2,

2, 2,

2, 2,

2, 2,

1 1

2, 2,

ST 1

1 1

5 1

1 1

1 1

1 EE 1

1 1

1 1

1 1

TM 2

2 2

1 1

1 1

2 1

2 2

3 3

1 1

3 3

3 3

/

/

/

/

/ /

/

/

/

/

/

/ /

/ /

/

/ / /

9 9

9 9

9 9

9 9

9 9

9 7

7 7

7 7

7 7

7 77 7'

7 7

7 7

7 7

7 7

7 3

3 3

3 2

3 3

3 0/

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

D 16 1

1 1

1 7 1

1 1

1 1

1 1

1 5 1

1 2 1 8 18 1

1 DR

/

/

/

/

.IO 5F 58 55 55 56 56 56 55 54 0

0 55 5B 52 51 57 57 57 57

&O 0/

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

1 1

0 -

0/

0 -

0 -

0 -

0 -

0 -

0 -

PC ME MF MC MC MC MC MC ME MD M

M ME MA MB MB ME MA ME MA T

N S

C,

.I T

'O 0

C C

C O

0 0

0 C

C 0

0 C

C C

C C

C O

E

.T I

2 C,

C, C,

C, C.

C, 4

S

.O M 0

0 P R C

C 0

0 O

C C

C C

0 0

0 0

0 0

0 0

O N

. R OTA 0

O O

0 O

0 0

O O

O O

U

,A M

M M

M A

A M

M M

M T

CA

. Y RO C

G C

/

B B

B C

C C

B C

C B

B B

B B

B C

C E

A TAC SSA 1

1 2

2 2

2 2

2 2

2 2

3 3

2 2

3 3

3 3

LC l

E x

4 4

Z 4

4 2

3 2

2 4

1

/

/

8 8

0 0

4 4

4 4

c I

1 1

/

3 3

1 1

1 1

1 1

S 3

E C

C P

C C

C L

G R

R R

G F

F V

V C

C B

B C

C Y

N N

C V

V E

E C

C N

N T

A B

5 6

8 7

8 9

1 0

5 7

7 6

6 6

7 7

7 8

9 9

7 7

ER 0

0 0

0 0

0 0

0 0

3 3

A B

A B

A B

VE F

F F

F F

F F

F F

F F

4 4

7 8

l l

3 3

A l

l 1

1 I

LB 0

0 0

0 AM 1

1 1

1 1

1 1

1 1

1 1

0 0

0 0

0 o

0 0

S VU 5

5 5

5 5

5 5

5 5

5 5

C C

C C

C C

C C

E N

E E

E E

E E

E E

E E

E F

F F

F F

F F

F J

l I

I I

I l

l l

l l

I I

I I

I I

I I

I L

t l!

!ij 1

POSITION 2

VALVE NORM P&ID TEST TEST g

NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METil COND COMMENTS 0,C M05-1037/3 IFC015A B

14 3

B MO C

E-2 1,2 1-5 0,C M05-1037/3 IFC015B B

14 3

B MO C

A-2 1,2 1-5 0,C M05-1037/3 IFC016A B

8 3

B MO C

D-6/7 1,2 1-5 0,C M05-1037/3 IFC016B B

8 3

B MO C

D-6/7 1,2 1-5 0

M05-1037/3 IFCol7 B

8 3

B A0 C

C-6 1,2,7 1-5 0

M05-1037/3 IFC023 B

8 3

B A0 C

C/D-3 1,2,7 1-5 0,C M05-1037/3 IFCO24A B

8 3

B M0 C

D/E-2/3 1,2 1-5 0,C M05-1037/3 IFCO24B B

8 3

B M0 C

C-2/3 1,2 1-5 0,C M05-1037/3 IFCO26A B

14 3

B M0 C

E-2 1,2 1-5 0,C M05-1037/3 IFCO26B B

14 3

B MO C

B-2 1,2 1-5 0

M05-1037/1 IFC036 C

8 2

B M0 C

E-1 1,2 1-5 0

M05-1037/2 IFC037 G

8 2

B M0 C

E-2 1,2 1-5 0

M05-1039/9 IFP050 G

6 2

B MO C

D-3 1,2 1-5 0

M05-1039/9 IFP051 G

10 2

B MO C

C-7/8 1,2 1-5 0

M05-1039/9 IFP052 G

10 2

B M0 C

C-6/7 1,2 1-5 0

M05-1039/9 IFP053 G

10 2

B MO C

C-4 1,2 1-5 0

M05-1039/9 C

C-2 1,2 1-5 IFP054 C

10 2

B MO

, LJESIA

POSITICE 2

VALVE NORM P&ID

'IEST TEST NtNBER TYPE SIZE CIASS CFRY ACIUKIOR

'IESM C00E0 MEIH COND 03NENIS O

MD5-1039/9 1FP078 G

4 2

B FO C

D-5 1,2 1-5 0

MD5-1039/9 1FP079 G

4 2

B

}O C

D-6 1,2 1-5 0

MD5-1039/9 1FP092 G

6 2

B

}O C

D-3 1,2 1-5 0

M05-1076/4 1G33-F001 G

6 1

A

}O C

B-8 1,2,3 1-5 0

MD5-1076/4 1G33-F004 G

6 1

A FO C

B-5 1,2,3 1-5 C

MD5-1076/4 FO C

E-8 1,2 1-5 1G33-F028 G

4 -

2 B

C MD5-1076/4 1G33-F034 G

4 2

B FD C

E-7 1,2 1-5 0

MD5-1076/4 1G33-F039 G

4 2

B MD C

D-7 1,2 1-5 0

MD5-1076/4 1G33-F040 G

4 2

B 10 C

D-8 1,2 1-5 O

MD5-1076/4 See Relief D-6 1

1-5 Request 047 IG33-F051 NC 4

2 C

0 MD5-1076/4 See Relief D-5 1

1-5 Request 047 1G33-F052A NC 4

2 C

0 M05-1076/4 See Relief 1G33-F052B NC 4

2 C

D-5 1

1-5 Request 047 0

MD5-1076/4 1G33-F053 G

4 2

B MD C

C-8 1,2 1-5 0

MD5-1076/4 1G33-F054 G

4 2

B

}O C

C-7 1,2 1-5 C

M05-1063 lHG001 B

2 2

B 10 0,C D-3 1,2 1-5 C

MD5-1063 1HG004 B

2 2

B 10 0,C C-3 1,2 1-5 C

MD5-1063 1HG005 B

2 2

B FO 0,C E-3 1,2 1-5 C

MD5-1063 1HG008 B

2 2

B 10 0,C E-3 1,2 1-5 IJE51A - -

POSITION 9

!!ORM P&ID TEST' TEST VALVE NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METil COND COMMENTS C

M05-1063 IHC009A C

6 2

B MO O

E-4/5 1,2 1-5 C

M05-1063 Il1G009B C

6 2

B MO O

E-6/7 1,2 1-5 C

M05-1063 liiG010A VR 10 2

C 0

C/D-4 1

1-5 C

M05-1063 1110010B VR 10 2

C 0

C/D-7 1

1-5 C

M05-1063 111C010C VR 10 2

C 0

B/C-4 1

1-5 C

M05-1063 tilC010D VR 10 2

C 0

B/C-7 1

1-5 C

M05-1063 IHGollA VR 10 2

C 0

C/D-4/5 1

1-5 C

M05-1063 1110011B VR 10 2

C 0

C/D-6/7 1

1-5 C

MJ5-1063 t

1110011C VR 10 2

C 0

B/C-4/5 1

1-5 C

M05-1063 IHC0llD VR 10 2

C 0

B/C-6/7 1

1-5 0

M05-1040/5 IIA 005 CV 3

2 B

A0 C

D/E-2 1,2,7 1-5 0

M05-1040/5 IIA 006 CV 3

2 B

A0 C

D/E-5 1,2,7 1-5 0

M05-1040/5 IIA 007 CV 3

2 B

A0 C

D/E-5 1,2,7 1-5 0

M05-1040/5 IIA 008 CV 3

2 B

A0 C

D/E-6/7 1,2,7 1-5 0,C M05-1040/7 See Relief IIA 012A CL 1

2 B

MO 0,C D/E-2/3 1,2 4.5,

Request 028 0

M05-1040/7 See Relief IIA 012B CL 1

2 B

MO 0,C C/D-3 1,2 4,5 Request 028 0,C M05-1040/7 See Relief IIA 013A CL 1

2 B

MO 0,C D/E-7 1,2 4,5 Request 028 0,C M05-1040/7 See Relief IIA 013B CL 1

2 B

MO 0,C C/D-6/7 1,2 4,5 Request 028 0

M05-lO40/7 See Relief C

D/E-6 1

4,5 Request 042 IIA 042A C

1 2

C 0

M05-1040/7 See Relief C

D/E-4 1

4,5 Request 042 IIA 042B C

1 2

C LJE51A POSITION VALVE NORM P&lD TEST TEST g

NUMBER TYPE SIZE CLASS CATECORY ACTUATOR TEST COORD METH COND COMMENTS O

M05-1040/7 See Relief IIA 043A C

1 3

C C

D-7 1

1-Request 042 0

M05-1040/7 See Relief IIA 043B C

1 3

C C

D-2 1

1-Request 042 C

M05-1040/7 IIAl28A R

lxlb 2

C

'O E-4 5

4.5 C

M05-1040/7 0

E-6 5

4,5 IIAl28B R

1x1 2

C 0

M05-1042/4 OMC009 G

4 2

B MO C

E-5 1,2 1-5 O

M05-1042/4 OMC010 G

4 2

B M0 C

D-5 1,2 1-5 C

M05-1045/12 See Relief IPS004 G

3/4 2

B So C

E-6 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS005 G

3/4 2

B SO C

E-6 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS009 G

3/4 2

B SO C

E-6 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPSulo G

3/4 2

B SO C

E-5 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS016 C

2 B

SO C

E-5 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS017 G

h 2

B SO C

E-5 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPSO 22 C

2 B

SO C

E-4 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPSO 23 C

2 B

SO C

E-4 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS031 G

3/4 2

B SO C

E-2 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS032 G

3/4 2

B SO C

E-2 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS034 C

3/4 2

B SO C

F-1 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS035 G

3/4 2

B SO C

E-1 1,7 1-5 Request 043 LJE51A

e POSITION 2

NORM P&ID TEST TEST VALVE NUMBER TYPE SIZE CLASS CATECORY ACTUATOR TEST COORD METil COND

' COMMENTS C

M05-1045/12 See Relief IPSO 37 G

3/4 2

B SO C

E-8 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPSO 38 G

3/4 2

B SO C

E-8 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPSO 43A G

3/4 2

B SO C

F-2 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPSO 43B C

3/4 2

B SO C

F-3 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPSO 44A C

3/4 2

B SO C

E-2 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPSO 44B C

3/4 2

B SO C

E-3 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPSO 47 C

3/4 2

B SO C

F-7 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPSO 48 G

3/4 2

B SO C

E-7 1,7 1-5 Request 043 C

M05-1045/12 See Relfef IPS055 C

h 2

B SO

.C C-3 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS056 G

h 2

B SO C

C-3 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS069 C

2 B

SO C

B-3 1,7 1-5 Request 043 C

M05-1045/12 See Relief IPS070 C

h 2

B SO C

B-3 1,7 1-5 Request 043 0

M05-1065/7 See Relief ORA 026 CV 1

2 B

A0 C

D-8 1,7 1-5 Request 027 0

M05-1065/7 See Relief ORA 027 CV 1

2 B

A0 C

D-7 1,7 1-5 Request 027 0

M05-1065/7 See Relief ORA 028 CV 1

2 B

A0 C

D-6 1,7 1-5 Request 027 0

M05-1065/7 See Relief ORA 029 CV 1

2 B

A0 C

D-5 1.7 1-5 Request 027 C

M05-1065/8 0

C-7 5

4,5 1RA016A R

lxth 3

C C

M05-1065/8 1RA016B R

lxlh 3

C 0

C-3 5

4,5

. LJESIA

POSITION 2

NORM P&ID TEST TEST VALVE y

i NUMBER TYPE SIZE CLASS CATECORY ACTUATOR TEST COORD METil COND COMMENTS 0

M05-1065/8 See Relief IRA 017A CV 3

B SC C-7 1,2 Request 044 0

M05-1065/8 See Relief IRA 017B CV h

3 B

SC C-3 1,2 Request 044 O.C M05-1046/4 1RE019 CV 3

2 B

A0 C

A-7 1,2,7 1-5 1

0,C M05-1046/3 1RE020 CV 3

e B

AO C

A-4 1,2,7 1-5 0,C M05-1046/3 1RE021 CV 2

2 B

A0 C

A-5 1,2,7 1-5 0,C M05-1046/3 1RE022 CV 3

2 B

A0 C

A-7 1,2,7 I-5 0C M05-1047/3 1RF019 CV 3

2 B

A0 C

C-2 1,2,7 1-5 0,C M05-1047/3 1RF020 CV 3

2 B

A0 C

C-2 1,2,7 1-5 0,C M05-1047/3 1RF021 CV 3

2 B

AO C

C-5 1,2,7 1-5 0,C M05-1047/3 1RF022 CV 3

2 B

A0 C

C-5 1,2,7 I-5 M05-1048/6 ISA029 CV 3

2 B

A0 C

D/l:-2 1,2,7 1-5 0

M05-1048/6 ISA030 CV 3

2 B

A0 C

D/I:-3 1,2,7 1-5 0

M05-1048/6 ISA031 CV 3

2 B

A0 C

D/l:-4 1,2,7 1-5 0

M05-1048/6 ISA032 CV 3

2 B

AO C

D/E-5 1,2,7 1-5 C

M05-1060 ISF001 G

10 2

B MO 0,C E-5 1,2 1-5 C

M05-1060 s

ISF002 G

10 2

B MO 0,C E-5/6 1,2 1-5 l

LJESIA.

S TN E

M M

O C

TD 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 SN EO 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 TC 2 TH 2,

2, 2,

2, 2,

2, 2,

2, 2,

5 5

1 1

1 1

1 1

1 ST 1

1 1

1 EE 1

1 1

1 1

TM 1

2 3

1 2

3 1

/

/

/

/

/

/

/

0 9

9 9

9 9

9 9

9 9

9 2

2 2

2 2

2 2

6 6

6 6

6 6

6 64 6

64 6

5 5

5 5

5 5

5 0/

0 0/

0 0

0 0

0 0

0 0

04 0

0 0

0 0

0 13 1 4 1 3 1 4 1

1 1

1 1

1 1

D 1

1 1

1 1

1 5 1

DR

/

/

I O 55 55 54 55 54 5E 5E 5B 53 5D 53 57 57 57 56 56 56 55

&O 0 -

0 -

0 -

0 -

0 -

0/

0I 0/

0 -

0/

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

PC MC MD MD MD MD MD MD MA MC MC MB MD MD MD MD MD MD MD y

T N

S C,

C, C,

C, C,

O E

I T

0 O

O O

O 0

0 C

C C

C 0

0 0

0 0

0 0

T I

9 S

4 O M P

R C

C C

C C

C C

0 0

0 0

C C

C 0

0 0

0 ON ROTA O

O O

O O

O O

O O

U M

M M

M M

M M

M M

TCA YRO C

B B

B B

B C

C C

C C

C C

C C

B B

B B

ETAC S

SA 2

2 2

2 2

2 2

2 2

2 2

3 3

3 3

3 3

3 L

C 1

1 E

x x

4 4

4 4

Z 2

4 4

4 4

/

/

/

/

0 0

0 0

0 0

0 I

1 2

2 2

2 4

4 3

3 3

3 3

3 1

3 3

1 3

/

/

S 3

3 E

C C

C C

P G

B B

B B

R R

F F

F F

C C

C B

B B

B Y

E E

E E

N N

N T

ER A

B A

B A

B A

B C

A B

C A

V. E 4

1 1

2 2

3 3

8 9

0 l

1 1

I 3

3 3

4 A

0 0

D 0

0 0

0 I

l B 0

0 0

0 0

0 0

0 0

1 l

AM 0

0 0

0 0

0 0

0 0

0 0

0 0

O 0

0 0

0 S

VU F

M M

M M

M M

M M

M M

X X

X X

X X

X E

N S

S S

S S

S S

S S

S S

S S

S S

S S

S JL I

I I

I I

I I

I I

I I

I I

I I

I I

I

POSITION 2

VALVE NORM P&ID TEST TEST g

NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METl!

COND COMMENTS 0

M05-1052/2 ISXOO4B B

30 3

B MO 0,C D-5 1,2 3-5 0

M05-1052/3 ISXOO4C B

10 3

B MO 0,C D-5 1,2 1-3 C

M05-1052/3 ISXOO6C B

8 3

B MO O

D-3 1,2 1-5 C

M05-1052/1 ISX008A B

20 3

B MO O

E-6 1,2 1-5 C

M05-1052/2 ISXOO8B B

20 3

B MO O'

E-6 1,2 1-5 C

M05-1052/3 ISX008C B

8 3

B M0 O

D-6 1,2 1-5 C

M05-1052/1 See Relief ISX010A CV 2

3 B

AO O

E-3 1,7 1-5 Request 048 C

M05-1052/2 See Relief ISX010B CV 2.

3 B

A0 0

E-3 1,7 1-5 Request 048 C

M05-1052/3 See Relief ISX010C CV 1

3 B

A0 0

E-4 1,7 1-5 Request 048 C

M05-1052/1 ISXOllA B

16 3

B MO O

D-3 1,2 1-5 C

M05-1052/1 ISX011B B

16 3

B MO O

E-3 1.2 1-5 C

M05-1052/1 See Relief ISX012A B

14 3

B M0 O

C-3 1,2 4,5 Request 030 C

M05-1052/2 See Relief iry012B B

14 3

B MO O

C-3/4 1,2 4,5 Request 030 C

M05-1052/1 See Relief ISX013D P

3 3

B MO O

C-5 1

1-5 Request 049 C

M05-1052/2 See Reliet ISX013E P

3 3

B MO O

D-5 1

1-5 Request 049 C

M05-1052/3 See Relief ISX013F P

2 3

B MO O

C-5 1

1-5 Request 049 0

M05-1052/1 ISX014A B

20 3

B M0 C

F-3 1,2 1-5 0

M05-1052/2 ISX014B B

20 3

B M0 C

F-3 1,2 1-5 0

M05-1052/3 ISX014C B

8 3

B MO C

E-4 1,2 1-5 C

M05-1052/1 See Relief ISXOl6A G

2 3

B MO O

C/D-3/4 1,2 4,5 Request 017 LJE51A POSITION VALVE NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS CATECORY ACTUATOR TEST COORD METH COND COMMENTS C

M05-1052/2 See Relief ISX016B C

2 3

B-MO O

D-3/4 1,2 4,5 Request 017 O

M05-1052/1 ISX017A B

8 3

B MO 0,C B-7 1,2 1-5 0

M05-1052/2 ISX017B B

8 3

B MO 0,C B-7 1,2 1-5 0

M05-1052/1 ISX019A CV 8

3 B

HO 0,C B-6 1,2 1-5 0

M05-1052/2 ISX019B CV 8

3 B

HO 0,C B-6 1,2 1-5 O

M05-1052/1 ISX020A B

12 3

B MO 0,C C-4 1,2 1-5 0

M05-1052/2 ISX020B B

12 3

B MO O.C C-4 1,2 1-5 C

M05-1052/1 See Relief ISX023A CV 2

3 B

A0 0

C-2 1,7 1-5 Request 048 C

M05-1052/2 See Relief ISX023B CV 2

3 B

A0 0

C-2 1,7 1-5 Request 048 0

M05-1052/4 See Relief ISX025A CV 2

3 B

A0 0,C E-6 1,7 1-5 Request 048 0

M05-1052/4 See Relief ISX025B CV 2

3 B

A0 0C E-2 1,7 1-5 Request 048 0

M05-1052/3 See Relief i

ISX025C CV 1

3 B

A0 0,C C-2 1,7 1-5 Request 048 C

M05-1052/4 See Relief ISX027A C7 2

3 B

A0 0

D-6 1,7 1-5 Request 048 C

M05-1052/4 See Relief ISX027B CV 2

3 B

A0 0

D-2 1,7 1-5 Request 048 C

M05-1052/4 See Relief ISX027C CV 2

3 B

A0 0

C-2 1,7 1-5 Request 048 i

C M05-1052/4 See Relief ISX029A CV lh 3

B A0 0

D-6 1,7 1-5 Request 048 C

M05-1052/4 See Relief ISX029B CV lh 3

B AO O

D-2 1,7 1-5 Request 048 1

C M05-1052/4 Se0 Relief ISX029C CV lh 3

B A0 0

B-2 1,7

'l-5 Request 048 C

M051052/4 See Relief ISX033 CV 2

3 B

A0 0

C-6 1,7 1-5 Request 048 C

M05-1052/4 See Relief j

j ISX037 CV 1

3 B

A0 0

B-6 1,7 1-5 Request 048

.I

[I j

LJE51A !

POSITION VALVE NORM P&ID TEST TEST g

NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METH COND COMMENTS C

M05-1052/3 See Relief ISXO41A CV 2

3 B

A0 0

C-2 1,7 1-5 Request 048 C

M05-1052/3 See Relief ISXO41B CV 2

3 B

A0 0

B-2 1,7 1-5 Request 048 C

M05-1052/1 See Relief ISXO62A B

14 3

B MO O

B-4 1,2 4,5 Request 030 C

M05-1052/2 See Relief ISXO628 B

14 3

B MO O

B-4 1,2 4,5 Request 030 C

M05-10521 ISXO63A B

8 3

B MO O

C-2 1,2 1-5 C

M05-10521 ISXO63B B

8 3

B MO O

C-2/3 1,2 1-5 C

M05-1052/5 See Relief ISXO71A G

3 3

B MO F-7 Request 050 C

M05-1052/5 See Relief ISXO71B G

3 3

B MO F-3 Request 050 C

M05-1052/5 See Relief ISXO72A NC 3

3 C

E-7 Request 050 C

M05-1052/5 See Relief ISXO72B NC 3

3 C

E-3 Request 050 C

M05-1052/5 See Relief ISX073A C

3 3

B MO F-6 Request 050 C

M05-1052/5 See Relief ISX073B C

3 3

B MO F-2 Request 050 C

M05-1052/5 See Relief ISXO74A G

3 3

B MO E-7 Request 050 C

M05-1052/5 See Relief Request 050 ISX074B C

3 3

B MO E-3 C

M05-1052/5 See Relief ISXO75A NC 3

3 C

D-7 Request 050 C

M05-1052/5 See Relief D-3 Request 050 ISXO75B NC 3

3 C

C M05-1052/5 See Relief D-7 Request 050 ISXO76A G

3 3

B MO C

M05-1052/5 See Relief D-3 Request 050 ISXO76B C

3 3

B MO 0

M05-1052/1 ISX082A G

3 3

B MO 0,C D-1 1,2 1-5 0

M05-lOS2/2 ISXO82B C

3 3

B MO 0.C D-1 1,2 1-5 LJE51A i

POSITION VALVE NORM P&ID TEST' TEST NUMBER TYPE SIZE CLASS CATECORY ACTUATOR TEST COORD METil COND COMMENTS 0

M05-1052/1 l

C D-1 1

1-5 ISXO83A NC 3

3 C

0 M05-1052/1 l

ISX083B NC 3

3 C

C D-1 1

1-5 0

M05-1052/5 ISXO88A G

3 2

B M0 C

C-8 1,2 1-5 0

M05-1052/5 ISX088B C

3 2

B MO C

C-4 1,2 1-5 0

M05-1052/5 ISXO89A C

3 2

B M0 C

C-7 1,2 1-5 0

M05-1052/5 ISX089B C

3 2

B M0 C

C-3 1,2 1-5 C

M05-1052/5 l

1SXO95A G

215 3

B MO O

C-6 1,2 1-5 C

M05-1052/5 ISXO95B C

2 3

B MO O

C-2 1,2 1-5 O

M05-1052/5 l

ISXO96A G

3 2

B M0 C

C-5/6 1,2 1-5 O

M05-1052/5 ISXO96B C

3 2

B M0 C

C-2 1,2 1-5 C

M05-1052/5 ISX097A G

3 2

B MO O

C-5 1,2 1-5 C

N05-1052/5 ISXO97B C

3 2

B M0 C-1 1,2 1-5 C

M05-1052/5 See Relief Request 050 ISX105A G

3 3

B MO D-7 C

M05-1052/5 See Relief ISX105B C

3 3

B MO D-3 Request 050 C

M05-1052/5 See Relief ISX106A C

3 3

C D-7 Recuest 050 C

M05-1052/5 Fee Relief Request 050 D-3 ISX106B C

3 3

C C

M05-1052/5 See Relief ISX107A G

3 3

B MO D-7 Request 050 C

M05-1052/5 See Relief D-3 Request 050 l

ISX107B C

3 3

B MO C

M05-1052/4 ISX149 R

3 /4xl 3

C 0

C/D-5/6 5

4,5 C

M05-1052/4 0

B-6 5

4,5 ISX150 R

3/4xl 3

C l

LJESIA l

STNE M

M O

C TD 5,

5, 5,

5, 5,

5, 5,

5, 5,

5, 5,

5, 5,

5, 5,

5, 5,

5, 5,

5, EO 4

4 4

4 4

4 4

4 4

4 4

4 4

4 4

4 4

4 4

4 SN TC 2 Ti l

ST 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 EE TM 4

4 4

1 2

1 2

4 4

3 1

2 3

3 3

5 5

1 2

3

/

/

/

/

/

/

/

/

/

/

/

/

/

/

/

/

/

/

/

/

2 2

2 2

2 2

2 2

2 2

2 2

2 2

2 2

2 2

2 2

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

D 1 6 1

1 1

1 1

1 1

1 1

1 1 4 1

1 1

1 1

1 1

1 DR

/

/

1 O 55 52 52 53 52 56 56 55 52 52 54 53 54 52 52 56 52 53 53 52

&O 0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

PC ME ME MC MC MC MB MB ME ME MC ME MF MD MC MB MC MC MC MC MD T

N S

I T

O O

O 0

O 0

0 O

0 O

O 0

O 0

O 0

0 0

0 O

O E

T I

4 S

5 P R C

C C

C C

C C

C C

C C

C C

C C

C C

C C

C O M O

N ROT A

UTCA YROC C

C C

C C

C C

C C

C C

C C

C C

C C

C C

C ETAC S

SA 3

3 3

3 3

3 3

3 3

3 3

3 3

3 3

3 3

3 3

3 LC 1

l l

l l

l 1

l l

l l

l l

l l

l l

l 1

l E

x x

x x

x x

x x

x x

x x

x x

x x

x x

x x

Z 4

4 4

4 4

4 4

4 4

4 4

4 4

4 4

4 4

4 4

4 I

/

/

/

/

/

/

/

/

/ /

/

/

/

/

/

/

/

/

/

/

S 3

3 3

3 3

3 3

3 3

3 3

3 3

3 3

3 3

3 3

3 E

P R

R R

R R

R R

R R

R R

R R

R R

R R

R R

R YT ER A

B C

A B

A B

A B

C A

B C

A B

A B

A B

C 1

I 1

2 2

3 3

4 4

4 5

5 5

6 6

7 7

9 9

9 A

VE LB 5

S 5

5 5

5 5

5 5

5 5

5 5

5 5

5 5

6 6

6 1

1 I

I 1

1 1

I 1

1 1

1 1

1 1

1 1

1 1

1 1

5 AM VU X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X E

N S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S J.

I I

I I

I I

I I

I I

I I

I I

I I

I I

I I

1

POSITION 2

VALVE NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METH COND COMMENTS C

M05-1052/1 ISX170A R

3/4xl 3

C O

B-3 5

4,5 C

M05-1052/2 O

B-3 5

4,5 ISX1708 R

3/4xl 3

C C

M05-1052/1 ISXI73A C

10 3

B MO O

D-2 1,2 1-5 C

M05-1052/2 ISX173B C

10 3

B MO O

D-2 1,2 1-5 C

M05-1052/1 See Relief ISX181A CV 2h 3

B A0 0

F-1 1,7 1-5 Request 048 C

M05-1052/2 See Relief ISX181B CV 2h 3

B AO O

F-1 1,7 1-5 Request 048 C

N05-1052/1 See Relief ISX185A CV 2h 3

B AO O

E-1 1,7 1-5 Request 048 C

M05-1052/2 See Relief ISX185B CV 2h 3

B AO O

E-1 1,7 1-5 Request 048 C

M05-1052/2 See Relief ISX189 CV 2

3 B

AO O

B-4 1,7 l-5 Request 048 C

M05-1052/1 See Relief ISX193A CV 1

3 B

AO O

B-7 1,7 1-5 Request 048

~

C M05-1052/2

.See Relief ISX1938 CV lh 3

B A0 0

B-4 1,7 1-5 Request 048 C

M05-1052/1 See Relief ISX197 CV 2

3 B

AO O

B-4/5 1,7 1-5 Request 048 C

M05-1052/1 ISX'00A R

3/4xl 3

C 0

F-1 5

4,5 C

M05-1052/1 ISX200B R

3 /4xl 3

C 0

F-1 5

4,5 C

M05-1052/1 O

E-1 5

4,5 ISX201A R

3/4xl 3

C C

M05-1052/2 O

E-1 5

4,5 ISX201B R

3/4xl 3

C C

M05-1052/2 0

A-7 5

4,5 ISX202A R

3/4xl 3

C C

M05-1052/2 O

C-4/5 5

4,5 ISX202B R

3 /4x1 3

C C

M05-1052/2 O

B-4/5 5

4,5 ISX203 R

3/4x1 3

C C

M05-1052/1

'O B/C-5 5

4,5 ISX204 R

3/4xl 3

C C

M05-1052/2 O

B-2 5

4,5 ISX207 R

3/4xl 3

C LJESI A,

POSITION 2

VALVE NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS CATECORY ACTUATOR TEST COORD METH COND COMMENTS C

M05-1052/1 ISX208A R

4x6 3

C 0

D-1 5

4,3 C

M05-1052/2 ISX208B R

4x6 3

C 0

D-1 5

4,5 C

M05-1052/2 See Relief ISX209 CV lh 3

B A0 0

A-1 1,7 1-5 Request 048 C

M05-1052/1 ISX294 R

3/4xl 3

C 0

D-7 5

4,5 C

M05-1052/1 See Relief Request 051 2SX017A B

8 3

B MO C-8 C

M05-1052/2 See Relief Request 051 2SX017B B

8 3

B MO C-8 C

M05-1052/5 See Relief 2SXO73A G

3 3

B MO E-7 Request 051 C

M05-1052/5 See Relief 2SXO73B C

3 3

B MO E-3 Request 051 C

M05-1052/5 See Relief 2SX076A G

3 3

B MO E-7 Request 051 C

M05-1052/5 See Relief 2SXO76B G

3 3

B MO E-3 Request 051 C

M05-1052/5 See Relief 2SX107A G

3 3

B MO D-7 Request 051 C

M05-1052/5 See Relief 2SX107B C

3 3

B MO D-3 Request 051 C

M10-Il05/4 IVG056B EFC 3/4 2

C 0

1 1-5 C

M10-1105/10 IVG057B EFC 3/4 2

C 0

1 1-5 0

M05-1109/2 IVP004A G

10 2

B M0 C

D-3 1,2 1-5 0

M05-l!09/3 IVP004B C

10 2

B M0 C

D-3 1,2 1-5 O

M05-1109/2 IVP005A G

10 2

B MO C

D-2 1,2 1-5 l

LJESIA e 1

STNE et loC 5

5 5

5 5

5 5

5 5

5 5

5, 5,

TD 5

5 5

5 5

SN EO 1

1 1

1 1

4 4

4 4

1 1

1 1

1 1

1 1

1 TC 7,

7, 7,

7, 7,

7, 7,

,'T H 2,

2, 2,

2, 2,

2, 2,

ST 5

5 5

5 2,

2, 2,

2, 2,

2, 2,

1 1

EE 1

1 1

1 1

1 1

1 1

1 1

1 TM 3

2 3

2 3

2 3

2 3

2 2

2 2

2 2

2 2

2

/ /

/ /

/

/

/

/

/

/

/

/

/

/

/

/

/ /

9 9

9 9

9 9

9 9

9 0

0 0

0 0

0 0

0 O

0 0

0 0

0 0

0 0

0 1

1 1

1 1

1 1

1 l

1 1

1 l

1 1

1 1

l l

1 1

l l

1 1

1 l

D 1

1 1

I 1

1 1

1 I

l 1

1 l 6 l 4 1 5 1 6 1

l 5 DR

/

/

I O 52 53 53 52 52 53 53 53 53 58 57 56 55 5D 5D 5D 54 54

&O 0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0 -

0/

0/

0/

0 -

0 -

PC MD ME ME ME ME MD MD MF MF HC MC MC MC MC MC NC MC MC d

N S

C, C,

C, C,

C.

C, C,

C, C,

O E

I T

C C

C C

C O

O 0

0 0

0 0

0 0

0 0

0 0

T I

7 S

5 O M P R O

0 O

0 O

C C

C C

C C

C C

C C

C C

C ON ROTA O

O O

O O

0 O

0 0

0 O

O O

O U

M M

M M

M A

A A

A A

A A

M M

TCA YROG B

B B

B B

C C

C C

B B

B B

B B

B B

B ETAC SSA 2

2 2

2 2

2 2

2 2

2 2

2 2

2 2

2 2

2 LC 1

l l

1 x

x x

EZ 0

0 0

0 0

4 4

4 4

4 4

4 6

6 6

0 4

4 I

1 1

1 1

1

/

/

/

/

2 2

2 3

3 3

1 S

3 3

3 3

E P

C G

G C

C R

R R

R B

B B

B B

B B

L L

G C

YT ER B

A B

A B

A B

A B

A B

A B

A B

VE 5

4 4

5 5

3 3

7 7

I l

2 3

4 4

5 6

6 A

LB 0

1 l

1 1

2 2

2 2

D O

O O

O O

0 O

O 1

AM 0

0 o

0 0

0 0

0 0

O O

U O

O O

0 O

O 5

VU P

P P

P P

P P

P P

Q Q

Q Q

Q Q

Q Q

Q E

N V

V V

V V

V V

V V

V V

V V

V V

V V

V J

I I

I I

I I

I I

I I

I I

I I

I I

I I

L l

l

POSITION 2

VALVE NORM P&ID TEST TEST NUMBER TYPE SIZE CLASS CATEGORY ACTUATOR TEST COORD METil COND COMMENTS C

M05-ll11/1 IVR001A B

36 2

B A0 0,C E-2 1,2,7 1-5 C

M05-1111/1 IVR001B B

36 2

B A0 0C E-1 1,2,7 1-5 C

MOS-Illl/l IVR002A CL 4

2 B

MO 0,C E-2 1,2 1-5 C

M05-1111/1 IVR002B CL 4

2 B

MO 0.C E-1 1,2 1-5 0

M05-1111/1 IVR006A B

12 2

B A0 C

E-3 1,2,7 1-5 0

M05-1111/1 IVR006B B

12 2

B A0 C

E-2 1,2,7 1-5 0

MOS-Illl/l IVR007A B

12 2

B A0 C

B-7 1,2,7 1-5 0

M05-Illl/l IVR007B B

12 2

B AO C

B-7 1,2,7 1-5 0

IVRol6A EFC 3/4 2

C C

M10-Illl/5 1

1-5 0

IVR016B EFC 3/4 2

C C

M10-Illl/5 I

l-5 0

IVR018A EFC 3/4 2

C C

M10-Illl/5 1

1-5 0

C M10-Illl/5 1

1-5 IVR018B EFC 3/4 2

C O

See Relief IVR035 2 way 3/4 2

B SO C

M10-Illl/19 1,7 1-5 Request 035 0

See Relief IVR036 2 way 3/4 2

B SO C

M10-Illl/19 1,7 1-5 Request 035 0

See Relief IVRO40 2 vay 3/4 2

B SO C

M10-Illl/19 1,7 1-5 Request 035 See Relief 0

IVR041 2 way 3/4 2

B SO C

M10-Illl/19 1,7 1-5 Request 035 0

M05-1117/9 See Relief IW0001A C

6 2

B MO C

E-5 1,2 4,5 Request 021 0

M05-ill7/9 See Relief IW0001B C

6 2

B MO C

E-6 1,2 4,5 Request 021 0

M05-lll7/9 See Relief IWOOO2A C

6 2

B MO C

F-5 1,2 4,5 Request 021 LJESI A -

POSITION VALVE NORM P&ID TEST TEST g

NUMBER TYPE SIZE CLASS CATECORY ACTUATOR TEST COORD METH COND COMMENTS O

M05-ll17/9 See Relief i

IWOOO2B C

6 2

B MO C

F-6 1,2 4,5 Request 021 O

M05-1117/26 See Relief IWO551A C

4 2

B MO C

E-7 1,2 4,5 Request 052 O

M05-1117/26 See Relief IWO551B C

4 2

B MO C

E-7 1,2 4,5 Request 052 O

M05-ll17/26 See Relief IWO552A C

4 2

B MO C

D-7 1,2 4,5 Request 052 O

M05-ill7/26 See Relief IWO552B C

4 2

B MO C

D-7 1,2 4,5 Request 052 C

H05-ill?/26 O

E-7 1,2 4,5 IWO570A R

3/4xl 2

C C

M05-lll7/26 IWO570B R

3/4xl 2

C O

D-7 5

4,5 0,C M05-1089/2 IWX019 P

2 2

B AO C

E/P-6 1,2,7 1-5 0,C M05-1089/2 IWX020 P

2 2

B AO C

E/P-5 1,2,7 1-5 LJESIA I

t RELII.F REQUEST'001 I.

Component Identification:

A.

Name:

Feedwater Supply Check Valves B.

Number:

IB21-F010A, 1B21-F010B, 1B21-F032A, 1B21-F032B C.

Function:

Prevent back flow of feedwater from Reactor D.

ASME Section III Code Class:

1 E.

ASME Section XI Valve Category:

A/C II.

Relief From:

AI ASME Code Requirement:

IWV-3410, 3520: Exercise Valves every three (3) months.

B.

Reason for Relief:

Exercising these valves would interrupt flow to the-Reactor and would severely affect plant operation.

C.

Alternate In-Service Test:

Exercise valve for operability during refueling outages.

LJE51-.

m, a

a 4

4m...%

__4_.

--i..a-4___J.

4._a1...%

>_a

--a_A.ah_r_,M-4

._m_,.

h_

,m.u_.

mwauem _

A.__m RELIEF REQUEST 002 DELETED 4

i L

J 1

k i

t i

I i

1 4

i LJE51 ;-. - -. - _- -.., _, -.....,..,___- - _,___,.,

RELIEF REQUEST 003 I.

Component Identification:

1 A.

Name Vacuum Relief Valves B.

Number:

1B21F037A-H.J-N,P,R,S, 1B21F078A-H,J-N,P,R,S 1B21F379A-H,J-N,P,Q,R, AND 1B21-F040 C.

Function:

Prevent drawing vacuum in safety relief valve discharge and vent lines following relief valve operation D.

ASME Section III Code Class:

3 E.

ASME Section XI Valve Category:

C II.

Relief from:

A.

ASME Code Requirement:

IWC-3520 Exercise and stroke time valve every three (3) months.

B.

Reason for Relief:

Valves are located inside the drywell and are inaccessible during normal plant operations C.

Alternate In-Service Test:

Exercise and stroke time valves for operability during refueling outages.

LJE51 RELIEF. REQUEST 004 I.

Component Identification:

+

A.

Name:

Feedwater RPV Inlet Isolation 9

B.

Number:

1B21-F065A, B C.

Function:

Isolate RPV from the feedwater system D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requiremen.:

IWV-3410, Exercise and stroke time valve every three (3) months B.

Reason for Relief:

Exercising these valves during operation would interrupt flow of feedwater to the RPV and would severely affect plant operation.

C.

Alternate In-Service Test:

Exercise and stroke time valve for operability during refueling outages.

d e

i 4

i LJE51.

RELIEr REQUEST 1)05 I.

Component Identification:

A.

Name:

Main Steam Line Isolation Valves B.

Number:

IB21-F098A,B,C,D i

C.

Function:

Isolation Main Steam Lines from the Turbine Building j D.

ASME Section III Code Class:

2

+

E.

ASME Section XI Valve Category:

B II.

Relief from:

A. ;

ASME Code Requirement:

IW-3410 Exercise and stroke time y

valve every three (3) months.

]

.B.

Reason for Relief:

Valve cannot be exercised during normal plant operation without curtailing flow to the main turbine and affecting plant operations C.

Alternate In-Service Test:

Exercise and stroke time valve for operability during extended cold shutdowns or refueling outages.

4,

i L TE51. -. - -

RELIEF REQUEST 006 DELETED 4

LJE51 _

RELIEF REQUEST 007 DELETED 9

4 LJE51 '

RELIEF REQUEST 008 I.

Component Identification:

A.

Name:

CRD Pump Discharge Isolation Valve

~

B.

Number:

ICll-F083 C.

Function:

Containment isolation.

D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B i

II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Exercise and stroke time valve every three (3) months B.

Reason for Relief:

Testing this valve requires that the CRD System be shutdown, which renders rod motion inoperative and stops seal flow to the recirculation pumps.

C.

Alternate In-Service Test:

Exercise and stroke time valve during refueling outage.

I LJE51 -

h

.. ~,

RELIEF REQUEST 009 DELETED e

LJE51 RELIEF REQUEST 010 I.

Component Identification:

A.

Name:

CRD Drive Water Header Check Valve B.

Number:

ICll-F122 t

C.

Function:

Containment Isolation and prevent back flow to reactor water when CRD pumps are secured.

D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

C II.

Relief from:

A.

ASME Code Requirement:

IWV-3520 Exercise valve every three (3) months.

B.

Reason for Relief:

Testing this valve requires that the CRD system be shutdown, thus rendering rod motion inoperative and stopping seal flow to the recirculation pumps.

i C.

Alternate In-Service Test:

Operability of valve shall be confirmed during local leak rate testing (normally open value).

LJE51,

. _. _ _ _ _. ~ - _ - _.

1 RELIEF REQUEST 011 1.

Component Identification:

A.

Name:

Drywell Isolation Check Valves B.

Number:

1C41-F006 C.

Function:

Prevent back flow of reactor water into the standby liquid control system and provide drywell isolation D.

ASME Section III Code Class:

1 E.

ASME Section XI Valve Category:

C II.

Relief from:

A.

ASME Code Requirement:

IWV-3520 Exercise valve every three (3) months.

B.

Reason for Relief:

Valve is held closed by reactor pressure and cannot be opened during plant operation.

4 C.

Alternate In-Service Test:

Exercise valve during refueling outage.

4 i

LJE51..

RELIEF REQUEST 012 DELETED 4

9' LJE51. _ _ _. _ _ __.

a I

RELIEF REQUEST.013 DELETED LJE51 9

RELIEF REQUEST 014 DELETED i

i f

i t

i I

i LJE51 '

- ~... - -. - -..

,,y--,_...-,

,,,,,._r,-,

,yp__,

r - - - ' ~ ~ - ' ' = -

RELIEF REQUEST 015 DELETED e

1 LJE51 -- -

,,m--

O RELIEF REQUEST 016 4

DELETED O

LJE51._

RELIEF REQUEST 017 I.

Component Identification:

A.

Name:

Fuel Pool Emergency Makeup e

B.

Number:

ISX016A, B i

C.

Function:

Provide Emergency Makeup Water to the Fuel Pools from the lake D.

ASME Section III Code Class:

3 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Exercise and stroke time valve every three (3) months.

B.

Reason for Relief:

Testing these valves will allow lake 1

water into the fuel pools i

C.

Alternate In-Service Test:

Exercise and stroke time valv'es l

during refueling outage.

l l

l I

LJE51 l

RELIEF REQUEST 018 DELETED LJE51,

RELIEF REQUEST 019 I.

Component Identification:

A.

Name:

Component cooling containment /drywell isolation valves.

B.

Number:

ICC049, ICC050, ICC053, ICC054, ICC057, ICC060, ICC127, ICC128 C.

Function:

Isolate component cooling system supply and return to containment, i

D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B d

II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Valve exercising and stroke 1

time test.

B.

Reason for Relief:

These valves are normally open during plant operation.

Exercising these valves would eliminate cooling water to the NRHX's and the Reactor Recire Pumps.

C.

Alternate In-Service Test:

Exercise and stroke time these f

valves during refueling outages.

{

O l

^

i l

LJE51 l

-y< -,,

--y w-,

RELIEF REQUEST 020 DELETED C

< LJE51 _ _ _ _

RELIEF REQUEST 021 I.

Component Identification:

A.

Name:

Chilled water supply / return containment isolation valves.

B.

Number:

lWOOOlB, lWO002B, 1WO001A, lWO002A C.

Function:

Isolate the chilled water system from the steam tunnel area coolers, RWCU regen and non-regen hx air handling units, and the containment bldg. air handling units.

D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Category A&B valves shall be exercised and stroke time tested at least once every 3 months.

B.

Reason for Relief:

Prevent losing chilled water to certain air handling units that are important while the plant is operating.

To lose chilled water could cause a high temperature initiated containment isolation.

C.

Alternate In-Service Test:

Perform exercising and stroke time testing during refueling outages.

1 LJE51 -._..

.A 2

.n.,-

-- +, -_ + -,

m RELIEF REQUEST 022 DELETED e

f 1

4 b

=

LJE51.- -.

r RELIEF REQUEST 023 DELETED LJE51 _

F+"

RELIEF REQUEST 024 DELETED O

LJE51 RELIEF REQUEST 025 DELETED LJE51.. _.

RELIEF REQUEST 026 DELETED A

e I

9 LJE51. - -.

RELIEF REQUEST 027 I.

Component Identification:

A.

Name:

Breathing Air Isolation Valve o

B.

Number:

ORA 026, ORA 027, ORA 028, ORA 029 C.

Function:

Containment and Drywell Breathing Air Isolation Valves.

D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B Re'ief from:

l II.

A.

ASME Code Requirement:

IWV-3410 Valve exercising and stroke time test.

B.

Reason for Relief:

These valves are normally open and supply breathing air ring headers inside containment.

These valves are 1" solenoid operated valves and timing them is not practical due to their rapid movement.

C.

Alternate In-Service Test:

Fully stroke valves every 3 months.

e LJE51 RELIEF REQUEST 028 I.

Component Identification:

A.

Name:

Compressed Air Supply Containment Isolation Valves B.

Number:

lIA012A, B and IIA 013A, B i

C.

Function:

Isolation valves for ADS Division 1 and 2 operating air i

D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Stroke Time and Exercise

~

Valve every 3 months.

f B.

Reason for Relief:

Failure of valve to return to original position would cause a loss of operating air to SRV's C.

Alternate In-Service Test:

Exercise and stroke time valves during refueling outages.

t t

J t

LJE51 '

1 l

i RELIEF REQUEST 029 DELETED LJE51 s

RELIEF REQUEST 030 I.

Component Identification:

A.

Name:

FPCC HX Backup cooling water isolation valves B.

Number:

1SX012A, B and ISX062A, B C.

Function:

Isolate the FPCC heat exchanger from its backup cooling water supplied from the lake.

D.

ASME Section III Code Class:

3 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 requires exercising and stroke time testing every 3 months.

B.

Reason for Relief:

After valves are stroked, the heat exchangers must be flushed and sampled to ensure the normal cooling water does not become contaminated by the lake water.

C.

Alternate In-Service Test:

Exercise and time the valves each refueling outage.

LJE51.

RELIEF REQUEST 031 DELETED LJE51.

RELIEF REQUEST D32 1.

Component Identification:

A.

Name:

Containment Monitoring Containment Isolation Valves B.

Number:

See Table-32-1 C.

Function:

Isolate the containment monitoring system from the containment t

D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Valve Exercising and stroke time test B.

Reason for Relief:

These valves perform only a containment isolation function and do not serve as a reactor coolant boundary.

The speed at which these air operated valves close 1

does not influence the mitigation of an accident.

C.

Alternate In-Service Test:

NONE (Valve 64 position will be verified during the normal performance of containment isolation surveillance requirements.)

LJE51..

\\

+.

/

.. s TABLE 32-1 4

'F Valve Size

/,

-1CM011 3/4 1CM012 3/4 1CM014 1/2 1CM015 1/2 1CM016 1/2 1CM017 1/2 ICM018 1/2 1CM022 3/4 ICM023 3/4 1CM025 3/4 1CM026 3/4 1CM028 j.

1/2 ICM031 1/2

~

1CM032 1/2 1CM033 1/2 i

-1CM034 1/2 1CM047 3/4

-1CM048 3/4 4

4 r

e,--

i i

i LJE51,

_ p

==

....,_..--.,_,w,..,

RELIEF REQUEST 033 I.

Component Identification:

A.

Name:

Leakage Detection Containment Isolation Valves B.

Number:

1E31-F014, F015, F017, F018 C.

Function:

Isolate the leakage detection system from the containment D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Valve Exercising and stroke timing test B.

Reason for Relief:

These valves perform only a containment isolation function and do not serve as a reactor coolant boundary.

Timing these solenoid operated valves is not practical due to their rapid movement.

C.

Alternate In-Service Test:

Fully stroke these valves every l

3 months.

l l

l LJE51 j

RELIEF REQUEST 034 DELETED O

e S

LJE51 RELIEF REQUEST 035 I.

Component Identification:

A.

Name:

Containment Ventilation Containment Isolation Valves B.

Number:

lVR035, IVR036, IVR040, IVR041 C.

Function:

Isolate the containment ventilation system from the containment.

D.

ASME Section III Code Class:

2 j

E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Valve Exercising and Stroke Time Test B.

Reason for Relief:

These valves perform only a containment isolation function and do not serve as a reactor coolant boundary.

Timing these solenoid operated valves is not practical due to their rapid movement.

C.

Alternate In-Service Test:

Fully stroke valves every 3 months.

i 5

s e

LJE51,

l

RELIEF REQUEST 036 I.

Component Identification:

A.

Name:

Reactor Recire. Pumps A & B Seal /0il Cooling Inlet and Outlet Valves B.

Number:

ICC065, ICC067, ICC068, ICC070, ICC188A, ICC188B C.

Function:

Supply cooling water to reactor recire. pumps D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement:

IW-3410 and IW-3520 valve exercising and stroke timing test.

B.

Reason for Relief:

These valves are normally open during l

plant operation.

Exercising these valves would eliminate Cooling water to Reactor Recirc Pumps.

i C.

Alternate In-Service Test:

Exercise and stroke time test these valves during refueling outages.

i P

t LJE51 l t

i

, _ ~,. _ _. _ _ _ _ -

4 RELIEF REQUEST 037 I.

Component Identification:

A.

Name:

Containment Monitorine Excess Flow Check Valve o

B.

Number:

ICM066 and 1CM067 C.

Function:

Containment Monitoring System D.

ASME Section III Code Class:

2

~

E.

ASME Section XI Valve Category:

C II.

Relief from:

A.

ASME Code Requirement:

IWV-3520 Valve Exercise Test B.

Reason for Relief:

Testing will require isolation of reactor pressure instrt. mentation.

.a C.

Alternate In-Service Test:

Exercise during refueling.

't 4

F 9

9 LJE51 RELIEF REQUEST 038

.I.

Component Identification:

A.

Name:

Diesel Starting Air Pressure Control Valves B.

Number:

See Table 38-1 C.

Function:

Supply Starting Air to Diesel Generators D.

ASME Section III Code Class:

3 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement: IWV-3410 valve exercising and stroke timing test.

B.

Reason for Relief: Exercising of these valves will be satisfied by monthly diesel generator surveillance test, required by Plant Technical Specification.

C.

Alternate In-Service Test:

- None -

LJE51 '

l

I Table 38-1 I

Valve Number Size 1DG007A 2

4 1DG007B 2

1DG007C 2

1DG007Df 2

1DG007E 2

1DG007F 2

1DG007G 2

1DG007H 2

1DG007J 2

1DG007K 2

1DG008A 2

1DG008B 2

1DG008C 2

1DG008D 2

1DG008E 2

1DG008F 2

1DG008G 2

1DG008H 2

1DG008J 2

1DG008K 2

I 5

LJE51 RELIEF REQUEST 039 DELETED 4

LJE51

' -100-

)

RELIEF REQUEST 040 1.

Component Identification:

A.

Name:

Drywell Isolation Bypass B.

Number:

1E31-F016, 1E31-F019 C.

Function:

Leak Detection Drywell Isolation Bypass D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement: IWV-3410 Valve Exercise and stroke timing Test.

B.

Reason for Relief: These valves are not connected to control switch.

They are installed for backup.

C.

Alternate In-Service Test:

- None -

LJE51

-101-

RELIEF REQUEST 041 I.

Compornent Identification:

A.

Name:

Supply Line Check Valve i

B.

Emher:

lE21-F306 C.

Function:

Cycled Condensate Flushing Supply Line t

D.

ASME Section III Code Class:

2 l

E.

ASME Section XI Valve Category:

B s

- II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Valve Exercise and Stroke Time Test B.

Reason for Relief: Exercising this valve will require low pressure core spray system to be inoperable.

C.

Alternate In-Service Test:

Exercise this valve during refueling outages.

f 1

LJE51

-102-

RELIEF REQUEST 042 I.

Component Identification:

A.

Name:

Air Accumulator Supply Check Valves B.

Number:

See Table 42-1 C.

Function: Prevent the back flow from Safety Relief Valves /

-Automatic Depressurization System Air Accumulators D.

ASME Section III Code Class:

3 E.

ASME Section XI Valve Category:

C II.

Relief from:

A.

ASME Code Requirement: IWV-3520 Valve Exercise Test B.

Reason for Relief: These valves are normally closed during plant operation.

Exercising these valves will require bleeding SRV/ ADS accumulators down and these valves are located in high radiation areas.

C.

Alternate In-Service Test: Exercise these valves during refueling outage.

LJE51

-103-O

5 Table 42-1 Valve Number Size IB21-F036A 1B21-F036F 3B21-F036G 1B21-F036J 1B21-F036L 1B21-F036M 1B21-F036N 1B21-F036P 1B21-F036R 1B21-F039B 1B21-F039C 1B21-F039D 1B21-F039E IB21-F039H 1B21-F039K 1B21-F039S IB21-F024A-D 1B21-F029A-D 1B21-F433A/B IIA 042A/B 1

lIA043A/B 1

s O

LJE51

-104-

RELIEF REQUEST 043 I.

Component Identification:

A.

Name:

Process Sampling Containment Isolation Valves B.

Number:

See Table 43-1 C.

Function: Isolate the process sampling system from the containment.

D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B II.

Relief from:

A '.

ASME Code Requirement: IWV-3410 Valve Exercising and Stroke Time Test B.

Reason for Relief: These valves perform only a containment isolation function and do not serve as a reactor coolant boundary.

The speed at which these air operated solenoid valves close does not influence the mitigation of an accident.

C.

Alternate In-Service Test:

NONE (Valve position will be verified during the normal performance of containment isolation surveillance requirements.)

IJE51

-103-

Table 43.-l Valve Number Size 1PS004 3/4 1PS005 3/4 1PS009 3/4 2

1PS010 3/4 IPS016 1/2 IPS017 1/2 1PS022

'1/2 1PS023 1/2 1PS031 3/4 1PS032 3/4 4

IPS034 3/4 1PS035 3/4 1PS037 3/4 1PS038 3/4 1PS043A 3/4 IPS043B 3/4 1PS044A 3/4 1PS044B 3/4 1PS047 3/4 4

IPSO 48 3/4 1PS055 1/2 IPS056 1/2 IPS069 1/2 1PS070 1/2 I

f I

LJE51

-106-

RELIEF REQUEST 044 1.

Component Identification:

A.

Name:

Emergency Air Bottles Control Valves B.

Number:

1RA017A, 1RA017B C.

Function:

Supply Emergency Air to Various Manifolds D.

ASME Section III Code Class:

3 E.

ASME Section XI Valve Category:

B

- II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Valve Exercising and Stroke Time Test B.

Reason for Relief: These control valves are normally open

'during plant operation.

These are installed to control the air flow from emergency air bottles and cannot be exercised.

C.

Alternate In-Service Test:

- None -

1 I

LJE51

-107-

RELIEF REQUEST 045 I.

Component Identification:

A.

Name:

RHR HX Isolation Valves B.

Number:

1E12-F060A, lE12-F060B, IE12-F075A, IE12-F075B, 1E12-F095 C.

Function: Residual Heat Removal Heat Exchanger Process Sample Isolation D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement: IWV-3410 Valve Exercising and Stroke Time Test B.

Reason for Relief: These valves are'normally closed.

These valves are 3/4 inch solenoid operated valves and timing them is not practical due to their rapid movement.

C.

Alternate In-Service Test: Fully stroke valves every three months.

LJE51

-108-

RELIEF REQUEST 046 I.

Component Identification:

A.

Name:

Turbine Oil Cooling Water Supply Regulating Valve B.

Number:

1E51-F015 C.

Function:

Supply Cooling Water to RCIC Lube Oil Cooler D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement:.IWV-3410 Valve Exercising Stroke Time Test B.

Reason for Relief: This control valve supplies the cooling water to the RCIC Lube Oil Cooler and is set at downstream pressure of 110 psig.

This valve cannot be exercised.

The proper operation of this valve is evident by the satisfactory operation of RCIC pump during quarterly surveillance.

C.

Alternate In-Service Test:

- None -

f i

LJE51

-109-

. -. - ~ _ -

RELIEF REQUEST 047 1.

Component Identification:

A.

Name:

Return to RHR Header i

B.

Number:

1G33-F051, 1G33-F052A, 1G33-F052B C.

Function: Supply water from Reactor Water Cleanup System to the Feedwater System i

D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Category:

C II.

Relief from:

l l

A.

ASME Code Requirement:

IWV-3520 Valve Exercising Test i

B.

Reason for Relief: These valves are normally open during operation.

The proper function of these valves is not L

required to maintain the plant in cold shutdown or to mitigate the consequences of an accident.

i C.

Alternate In-Service Test:

None -

4 j

l J

c. a r e - -- -

I a

LJE51

-110-J

RELIEF REQUEST 048 I.

Component Identification:

A.

Name:

Area Cooler Outlet Valvec B.

Number:

See Table 48-1 C.

Function:

Isolate Shutdown Service Water Flow Through Area Coolers D.

ASME Section III Code Class:

3 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

.ASME Code Requirement: IWV-3410 Exercise and Stroke Time Test B.

Reason for Relief: These valves are not required to open within a specified time range.

They are interlocked with the room fans to open when the room fans energize.

C.

Alternate In-Service Test: Exercise values for operability every three months.

LJE51

-111-

c-Table 48-1 1

Valve Number Size 1SX010A 2

ISX010B 2

ISX010C 1

ISX023A 2

ISX023B 2

ISX025A 2

ISX025B 2

ISX025C 1%

'1SX027A 2

ISX027B 2

ISX027C 2

ISX029A 1

ISX029B l 's 1SX029C 1%

ISXO33 2

ISX037 1

ISX041A 2

ISX041B 2

ISX181A 2

ISX181B 2

ISX185A 2

ISX185B 2%

ISX189 2

1SX193A 1

ISX193B 1

ISX197 2

ISX209 1

LJE51-

-112-

RELIEF REQUEST 049 I.

Component Identification:

A.

Name:

Strainer Backwash Plug Valves B.

Number:

ISX013D, ISX013E, ISX013F C.

Function:

Provide discharge of strainer backwash D.

ASME Section III Code Class:

3 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement: IWV-3410 Exercising and Stroke Timing Valve Test B.

Reason for Relief: The proper operation of shutdown service water system strainers is evident that these valves are operating properly.

C.

Alternate In-Service Test:

- None -

LJE51

-113-

)

RELIEF REQUEST 050 I.

Component Identification:

A.

Name:

Manual Deluge Valves B.

Number:

See Table 50-1 C.

Finction: Provide Shutdown Service Water to SGBT Charcoal Beds, Makeup Air Filter Package, Air Filter Package D.

ASME Section III Code Class:

3 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement: IWV-3410, IWV-3520 Valve Exercising and Stroke Time Test B.

Reason for Relief: These systems are not designed to perform any surveillance testing.

The proper operation of these valves is not required to mitigate the consequences of an accident or to keep reactor in cold shutdown.

C.

Alternate In-Service Test:

- None -

me l

l l

LJE51

-114-l

(

Table 50-1 Valve Number Size

~1SX071A 3

ISX071B 3

ISX072A 3

1SXO72B 3

ISX073A 3

ISX073B 3

ISX074A 3

ISXO74B 3

1SX075A 3

ISX075B 3

ISXO76A 3

ISX076B 3

ISX105A 3

ISX105B 3

ISX106A 3

ISX106B 3

ISX107A 3

ISX107B 3

e i

LJE51

-115-

RELIEF REQUEST 051 I.

Component Identification:

A.

Name: Cross Connect from Unit 2 Shutdown Service Water System B.

Number:

2SX017A, 2SX017B, 2SX073A, 2SX073B, 2SX076A, 2SX076B, 2SX107A, 2SX107B C.

Function:

- None -

Unit 2 piping is not installed D.

ASME Section III Code Class:

3 E.

ASME Section XI Valve Category:

B II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Valve Exercising and Stroke Time Test B.

Reason for Relief: These valves are installed as crossconnect from Unit 2 and piping is either capped or has blank flanges.

C.

Alternate In-Service Test:

None i

1 i

i LJE51

-116-i i

5

RELIEF REQUEST 052

~

I.

Component Identification:

A.

Name:

Drywell Cooling Chilled Water Drywell Isolation Valves B.

Number:

1WO551A, lWO551B, 1WO552A, 1WO552B C.

Function:'

Provide chilled water to Drywell Cooling System Coil Cabinets D.

ASME Section III Code Class:

2 E.

ASME Section XI Valve Catego,ry:

B II.

Relief from:

A.

ASME Code Requirement:

IWV-3410 Valve Exercising and Stroke Time Test B.

Reason for Relief: Exercising these valves every three months will require Drywell Chilled Water System Coil Cabinet to be inoperable.

These coil cabinets are required for safe operation of the plant.

C.

Alternate In-Service Test: Exercise and stroke time these valves during refueling outages.

LJE51

-117-

RELIEF REQUEST 053 I.

Component Identification:

A.

Name:

Main Steam Isolation Valves B.

Number:

1B21-F022A, 1B21-F022B, 1B21-F022C, 1B21-F022D, 1B21-F028A, IB21-F028B, 1B21-F028C, 1B21-F028D C.

Function: Main Steam Containment Inboard and Outboard Isolation D.

ASME Section III Code Class:

1 E.

ASME Section XI Valve Category:

A II.

Relief from:

A.

ASME Code Requirement: IWV-3410 valve exercising and stroke time test B.

Reason for Relief: Exercising these valves every three months will significantiv reduce plant's power output.

C.

Alternate In-Service Test: Full stroke testing and exercising during refueling outage.

Partial stroke testing as recuired by Plant's Technical Specification.

LJE51-

-118-

RELIEF REQUEST 054 I.

Component Identification:

A.

Name:

Pressure Isolation Valves B.

Number: 1E21-F003, IE21-F005, lE21-F006, lE12-F041A, lE12-F041B, lE12-F041C, IE12-F042A, lE12-F042B, IE12-F042C, IE12-F050A, lE12-F050B, lE12-F053A, IE12-F053B, IE12-F009, IE12-F008, IE12-F023, lE51-F066, 1E51-F013 C.

Function: Provide Isolation Between Reactor Coolant System and Low Pressure S" stems D.

ASME Section.III Code Class:

1,2 E.

ASME Section XI Valve Category:

A, B, C II.

Relief from:

r' A.

ASME Code Requirement: IWV-3410, IWV-3520 Valve exercising and stroke timing test.

B.

Reason for Relief: Exercising these valves during plant operation may cause inte*-system LOCA.

9 C.

Alternate In-Service Test: Exercise and stroke time these valves during refueling outages.

LJE51

-119-