text
_, _
LICENSEE EVENT REPC":T (LER)
Form R2v. 2.0 iscihty Ntase ('l)
Docket Number G)
Page (3)
Quad Cities Unit One 0l5l0l0l0l2l5l4 1 l of l 0 l 5 team Line Radiation Monitor functional test not performed within frequency es:ablished for Technical Specification when in Refheling mode due to incomplete docurnentation of a Technical Specification Interpretnion Event Date (5)
LER Number (6)
Report Date (7)
Other Facihties involved (8)
Month Day Year Year Sequential Revision Month Day Year Facihty Docket Numberts)
Nder Number Nann g
0l5l0l0l0l l
l 0l9 0l4 9l6 9l6 ol1l9 0l0 1l0 ol4 9
6 0l5lol0l0l l
l OPERATING THit REPORT IS SUBMJ TrED PUR$UANT TO THE REQU REN ENTS OF 10CFR MODE (9)
(Check one or more of the following) (11) 2 20.402(b) 20.405(c) 50.73(a)(2)(iv) 73.71(b)
POWLR 20.405(s)(1)O) 50.36(c)(1) 50.73(a)G)(v) 73.71(c)
LEVEL 20.405(a)(1)01) 50.36(c)(2) 50.73(a)(2)(vii)
Other (Specify (10) l l
8
- - 20.405(a)(1)0ii)
T50.73(a)(2)0) 50.73(a)(2)(viii)(A) tn Abstract 20.405(a)(1)0v) 50.73(a)(2)Oi) 50.73(a)(2)(viii)(B) below and in 20.405(a)(1)(v) 50.73(a)(2)Oii) 50.73(a)(2)(x)
Text)
LICENSEE CON FACF FOR THIS LER (12)
NAME TELEPHONE NUMBER i
AREA CODE Ch:.rles Peterson, Regulatory Affairs Manager, ext. 3602 3
0l9 6l5l4l-l2l2l4l1 COMPLETE ONE LINE FOR EACH COMPONENT FAILURE DESCRIBED IN THIS REPORT (13)
CAU5E SYSTEM COMPONENT MANUFAGURER REN RTABI.E CAU5E SY5 TEM COMFONENT MANUFACTURER RENRTABM TO NPRDS TO NPRDS I
I I
I I
I I
I I
I I
I I
I l
i I
I I
I I
I l
I I
I SUP >LEh&NTAL REPORT EXPECTED t14)
Expected Month Day Year Submmeion lYES Of yee. complete EXPECTED SUBMIS$10N DATE) 70 Date (15) l l
l ABSTRACT (Luvut to 4400 speece, ts., appronunately fitteen omgie-space typewntien ames) (16)
ABSTRACT:
During a review by the station of Technical Specification Interpretations (TSI), as a result of a recent Zion Generating Station issue, it was determined that QCIS 1700-01,
" Weekly Main Steam Line Radiation Monitor [RT] Functional Test", had not been performed when required on several occasions dating back to a TSI (dated 10/05/92). The root cause of this event is the incomplete documentation of the 10/05/92 TSI.
The immediate corrective action was for Operations to verify QCIS 1700-01 was current for both Units.
On 09/23/96, Quad Cities Station implemented Amendment 171 to Docket number 50-254 and Amendment 167 to Docket number 50-265.
These Amendments put in place revised Technical Specifications (TS) which eliminated all TSIs, including the earlier referenced TSI. These new TSs provide clearer operability requirements as well as mode specific surveillance requirements. Also on 09/23/96, QCOS 0500-09, "Transitioning from No Mode (All Fuel Removed) to Mode 5", was implemented providing the Operations Department with the means to ensure all Technical Specification requirements including surveillances, are satisfied prior to transferring to the REFUEL Mode. A review was conducted of other similarly denoted surveillances listed on the TSI and no further problems were identified.
A change will be made to QCAP 2300-11, " Technical Specification Clarification Request," to require all future Clarification Requests be approved by the Plant Operations Review V(~TNittee.
(NTS# 254-180-96-01901)
LER254\\96\\019. WPF 9610160340 961004 PDR ADOCK 05000254 S
PDR
..___m
_m_
LICENSEE EVENT REPORT (LER) TEXT COPrrINUATION Form Rev. 2.0 FACILTTY NAME (1)
DOLTJrr NUMBER (2)
LER NUMBER (6)
PAGE (3)
Year Sequential Revision v
Number Nusnber ities Unit one 0l5l0 0l0l2 5l4 9l6 0l1l9 0l0 2 lOFl 0 l 5 h
E., Industry " " "non System (EII5) M : are identifies in the text as MX)
PLANT AND SYSTEM IDENTIFICATION
General Electric - Boiling Water Reactor - 2511 MWt rated core thermal power.
1 EVENT IDENTIFICATION:
Unit: One Event Date: 09/04/96 Event Time: 2400 Reactor Mode:
2 Mode Name:
Startup Power Level:
8%
A.
- - CONDITIONS PRIOR TO EVENT:
This report was initiated by Licensee Event Report LER254\\96-019.
Startup (2) - Mode switch in Startup/ Hot Standby position with average reactor coolant temperature at any temperature.
B.
DESCRIPTION OF EVENT
l On 09/04/3G, Unit One (U1) was in the STARTUP Mode operating at 8% of rated core i
thermal power.
During a review by the Station of Techr.ical Specification Interpretations (TSI) as a result of a recent Zion Generating Station issue, it was determined that QCIS 1700-01, " Weekly Main Steam Line Radiation Monitor (RT]
Functional Test", had not been performed when required during the Unit I refueling outage QlR14.
Further investigation from the time the TSI (dated 10/05/92) was approved to the presa:it uncovered the following missed TS surveillances.
On 10/05/92, a Technical Specification Interpretation (TSI) request titled
" Surveillance Requirements Not Applicable During Shutdown" was submitted for approval by the Instrument Maintenance (IM) Department. The TSI was to determine if instrumentation that is not required to be operable, because its associated systems or components were inoperable, could have its surveillances suspended during the period when it is not required to be operable.
The interpretation included surveillance QLIS 1700-0l* as not required during cold shutdown and refueling under a system heading " Reactor Protection System (RPS)[JC]/ Primary Containment' Isolation *" (PCI)[JM).
The asterisk denoted that the portions of QCIS 1700-01 which supported Primary Containment Isolation operability were not applicable during shutdown or refueling although a partial surveillance of QCIS 1700-01 would still be required for Reactor Protection System operability as long as there was fuel in the reactor vessel [RCT] and the reactor scram was reset.
The definition of the asterisk, however, was never documented in the TSI or associated supporting documentation. Technical Specification Table 4.1-1 requires a weekly functional test of the Main Steam Line Radiation Monitors (MSLRMs) in the REFUEL, STARTUP/ HOT STANDBY, and RUN Modes.
Since this TSI was appr N d, the following missed TS surveillances have occurred.
9 LER254\\96\\019. WPF I
FACILITY NAME (1)^
LICENSEE EVEPG REPORT (LER) TEXT COfGINUATION Form Rev. 2.o DOCAET NUMBER (2)
LER NUMBER (6)
PAGE (3)
Year Sequenu.!
R. vision Nun br Number
'ities Unit One 0l5l0 0l0l2 5l4 9l6 0l1l9 0l0 3 lOFl 0 l 5 tex 1 En.rsy inau.uy na.,niric.iion sy.i.m (Elis; coa
.r. ia.nuri. in ih. i.xi.. too 1.
From 11/15/92 until 12/16/92 during the QlR12 Refuel Outage, QCIS 1700-01 was not performed as required.
4 2.
From 11/02/93 to 11/24/93, during ths QlM09 Maintenance Outage, QCIS 1700-01 was not performed as required.
3.
From 12/14/93 to 12/30/93, during the QlF34 Forced Outage, QCIS 1700-01 was not performed as required.
j 4.
From 06/24/94 to 07/29/94, during the QlR13 Refuel Outage, QCIS 1700-01 was not performed as required.
5.
From 02/08/96 to 02/26/96, and from 04/19/96 to 04/30/96 during the QlR14 Refuel Outage, QCIS 1700-01 was not performed as required.
C.
APPARENT CAUSE OF EVENT:
The root cause of these events is the incomplete documentation of the 10/05/92 TSI (On Site Review 92-40). The TSI preparer did not document the meaning of the asterisk as it applied to the RPS and PCI functions. The asterisk was intended to denote that the positions of QCIS 1700-01 which supported Primary Containment 3
(V Isolation operability were not applicable during shutdown or refueling although a partial surveillance of QCIS 1700-01 would still be required for Reactor Protection System operability as long as there was fuel in the reactor vessel and the reactor scram was reset. The IM Department used the TSI as justification to suspend performance of QCIS 1700-01 during outages. This basis was documented on QAP 0500-S9 and QAP 2000-11 Attachment A each outage.
In all cases the surveillance was deferred to prior to startup.
These were approved by a Department Superviser, a System Engineer, and an Operating Engineer. None of these reviews uncovered the i
errors. For the Q1R12, QlR13, and QlR14 refuel outages, the surveillance was missed prior to core reload and for a period of time after reload.
For the QlM09 and QlF34 outages, the surveillance was suspended for the entire outage. Also, during the Q1R14 outage, the surveillance was erroneously suspended for 18 days prior to full core offload.
In all cases, however, the surveillance was completed prior to reactor startup.
A contributing factor to this event is the lack of a critical review of QAP 0500-S9 and QAP 2000-11, Attachment A.
During the approval process, each inadequate outage deferral could have been identified by the reviewers.
D.
SAFETY ANALYSIS OF EVENT:
i The function of the MSLRMs is to detect high radiation in the main steam line area and effect mitigating actions to limit possible releases' to the plant and ultimately, the environment. During the missed TS surveillances, the Main Steam Isolation Valves (MSIVs) were closed. Also, the. reactor was subcritical during all
. periods when QCIS 1700-01 was delinquent.
Therefore, the safety significance of Q
this event is minimal.
LER254\\%019. WPF
- - - -. -. ~ _ _ _ __ _...
- - ~ - - -
. ~.._ -...
LICENSFE EVEPrr REPORT (LER) TEXT CONTINUATION Form Rxv. 2.0 FACILTTY nam 4E (1)
DOLm NUMBER (2)
LER NUMBER (6)
PAGE (3)
Year Sequeenial Revision Number Number ities Unit One 0l5l0 0l0l2l5l4 9l6 0l1l9 0l0 4 lOFl 0 l 5 E.
,y r - a sy (Ens; m = 6ammis i. ei. i.m gxx3 imu l
l Had the MSLRMs been inoperable during a worst case design basis fuel handling accident (DBFHA), no increases to the consequences of the accident would occur.- The DBFHA utilizes the Reactor Building Ventilation and Fuel Pool Radiation Monitoring System to mitigate the consequences of thetaccident. The MSLRMs are not utilized in the Updated Final Safety Analysis (UFSAR) in this particular accident analysis.
In all of the incidents, the Main Steam Isolation Valves (MSIVs) were closed (and main steam line plugs installed during refueling outages only) to prevent filling the main steam lines during reactor flooding. These closed MSIVs prevent exposing reactor coolant to the MSLRM detectors.
l E.
CORRECTIVE ACTIONS
i Corrective Actions Completed-1.
Operations immediately verified QCIS 1700-01 was current for both Units.
l 2.
On 09/23/96, Quad Cities Station implemented Amendment 171 to Docket number 50-254 and Amendment 167 to Docket number 50-265. These Amendments put in place revised TSs and eliminated all TSIs, including the earlier referenced TSI. The new TSs provide clearer operability requirements and mode specific surveillance requirements.
Specifically, surveillances for the MSLRMs are required in Modes 1, 2, and 3 only.
Therefore, the ambiguity brought on by the TSI has been eliminated and surveillances will be performed based on clearly defined plant modes.
t 3.
On 09/23/96, QCOS 0500-09 was implemented providing the Operations Department with the means to ensure all TS requirements including surveillances, are satisfied prior to transferring to the REFUEL Mode.
4.
A review of compliance was conducted of other similarly denoted surveillances listed on the TSI. No violations were identified during the review.
Corrective Actions to be Completed 1.
A change will be made to QCAP 2300-11, " Technical Specification Clarification Request," to require all future Clarification Requests be approved by the Plant Operations Review Committee.
(NTS# 254-180-96-01901).
This item will be completed by December 1, 1996.
lO LER254\\96T019. WPF
i LICEN5EE EVENT REPORT (LER) TEXT CONTINUATION Form Rev. 2.0 iFACulTY NAME(1)
DOCKET NUMBER (2)
LER NUMBER (6)
PAGE (3)
Year Sequential Revision Number Number stics Unit One 0l5l0 0l0l2 5l4 9l6 0l1l9 ol0 5 lOFl 0 l 5 TEXT Energy Industry identi6ceuon System (EIIS) codes ero idenu6= in the text as LG)
F.
PREVIOUS EVENTS:
A search for LERs in the last 2 years involving missed TS surveillances revealed the following events:
1 11/07/94 LER 254/94-14, Fire system surveillance went past their critical due date without the systems being declared inoperable and compensatory actions put in place due to inadequate training and written 1
communication.
11/05/95 LER 254/95-06, The RPS EPA relays had nrt been tested prior to the mode switch being moved to Refuel due to an inadequate written communication.
The primary cause of these previous events was inadequate procedural guidance. In this event the appropriate data was available but not used.
G.
COMPONENT FAILURE DATA
i There were no component failures in this event.
[U 3
a
- t i
j h
%.)
LER254\\%\\019. WPF
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000254/LER-1996-001-07, :on 960303,B CR HVAC Sys Inoperable Due to Malfunctioning Relay Which Prevented Isolation of Air Handling Unit Fan.Ems Replaced Relay & Forwarded Damaged Relay to Engineering for Evaluation |
- on 960303,B CR HVAC Sys Inoperable Due to Malfunctioning Relay Which Prevented Isolation of Air Handling Unit Fan.Ems Replaced Relay & Forwarded Damaged Relay to Engineering for Evaluation
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(iv), System Actuation | | 05000265/LER-1996-001, Forwards LER 96-001-00.Listed Commitments Made,Including Event Will Be Included as Part of Continuing Training for Both Licensed Operators & Engineering Dept | Forwards LER 96-001-00.Listed Commitments Made,Including Event Will Be Included as Part of Continuing Training for Both Licensed Operators & Engineering Dept | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000265/LER-1996-001-10, :on 960417,HPCIS Was Declared Inoperable Due to Procedural Deficiency Which Allowed Isolation of Turbine Exhaust Vacuum.Licensed Operators Have Been Trained on Procedure Changes |
- on 960417,HPCIS Was Declared Inoperable Due to Procedural Deficiency Which Allowed Isolation of Turbine Exhaust Vacuum.Licensed Operators Have Been Trained on Procedure Changes
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000265/LER-1996-002, Forwards LER 96-002-00.Licensee Revised Qcop 2300-1 to Ensure That Piping Downstream of Sys Isolation Valve Is Filled & Vented After Maint | Forwards LER 96-002-00.Licensee Revised Qcop 2300-1 to Ensure That Piping Downstream of Sys Isolation Valve Is Filled & Vented After Maint | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000265/LER-1996-002-10, :on 961009,HPCI Sys Declared Inoperable.Caused by Improper Filling & Venting After Aug 1996 Maint.Air Purged from Sys & line-up Procedure Revised to Ensure Filling & Venting of Piping |
- on 961009,HPCI Sys Declared Inoperable.Caused by Improper Filling & Venting After Aug 1996 Maint.Air Purged from Sys & line-up Procedure Revised to Ensure Filling & Venting of Piping
| | | 05000254/LER-1996-002-04, :on 960220,CR HVAC Sys Inoperable.Caused by Design Oversight Involving Toxic Gas Anlayzer.On 960223 Procedure Change to Qcop 5750-09, CR Ventilation Sys, Made to Allow for Operation of Booster Fans |
- on 960220,CR HVAC Sys Inoperable.Caused by Design Oversight Involving Toxic Gas Anlayzer.On 960223 Procedure Change to Qcop 5750-09, CR Ventilation Sys, Made to Allow for Operation of Booster Fans
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2) | | 05000265/LER-1996-003-01, :on 961112,Unit 2 LPCI Was Declared Inoperable. Caused by Failure of 2D RHR Pump Discharge Check Valve.Lpci Kf Pressure Was re-established within One Hour |
- on 961112,Unit 2 LPCI Was Declared Inoperable. Caused by Failure of 2D RHR Pump Discharge Check Valve.Lpci Kf Pressure Was re-established within One Hour
| | | 05000265/LER-1996-003-13, :on 961112,Unit 2 LPCI Was Declared Inoperable to 2D RHR Pump Discharge Check Valve Failure.Lpci Kf Was re-established within 1 Hour & Operability Determination Was Completed for PIF 96-3196 |
- on 961112,Unit 2 LPCI Was Declared Inoperable to 2D RHR Pump Discharge Check Valve Failure.Lpci Kf Was re-established within 1 Hour & Operability Determination Was Completed for PIF 96-3196
| | | 05000265/LER-1996-003, Forwards LER 96-003-00 Submitted IAW Requirements of 10CFR50.73(a)(2)(v)(D).Commitments Made by Ltr,Submitted | Forwards LER 96-003-00 Submitted IAW Requirements of 10CFR50.73(a)(2)(v)(D).Commitments Made by Ltr,Submitted | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000254/LER-1996-003-02, :on 960222,unanticipated Start Occurred on Unit 1 Edg.Caused by Inadequate Guidance within Procedure Qcmms 6600-03.Procedure Qcmms 6600-03 Will Be Revised to Clarify Switch Settings |
- on 960222,unanticipated Start Occurred on Unit 1 Edg.Caused by Inadequate Guidance within Procedure Qcmms 6600-03.Procedure Qcmms 6600-03 Will Be Revised to Clarify Switch Settings
| 10 CFR 50.73(a)(2) | | 05000254/LER-1996-003, Forwards LER 96-003-00 Re Unit 1 Start of Egd Due to Inadequate Procedure | Forwards LER 96-003-00 Re Unit 1 Start of Egd Due to Inadequate Procedure | 10 CFR 50.73(a)(2)(iv), System Actuation | | 05000254/LER-1996-004-01, :on 960130,HPCI Sys Declared Inoperable Due to Gland Exhauster Breaker Trip.Hpci Gland Exhauster Breaker Replaced & Tested for Proper Operation & AOP Time Delay Bypass Switches in Starting Circuit Replaced |
- on 960130,HPCI Sys Declared Inoperable Due to Gland Exhauster Breaker Trip.Hpci Gland Exhauster Breaker Replaced & Tested for Proper Operation & AOP Time Delay Bypass Switches in Starting Circuit Replaced
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2) | | 05000254/LER-1996-005-07, :on 960203,B CR HVAC Sys Declared Inoperable Due to Outside Air Temp.Submitted TS Change Requesting That Heater Power Be Measured Instead of Differential Temp Across Heater to Determine Operability |
- on 960203,B CR HVAC Sys Declared Inoperable Due to Outside Air Temp.Submitted TS Change Requesting That Heater Power Be Measured Instead of Differential Temp Across Heater to Determine Operability
| | | 05000254/LER-1996-006, :on 960210,TS 3.0.A Incorrectly Invoked Due to Procedural & Operator Knowledge Deficiencies.Policy Statement Developed & Presented to Licensed Operator Re Expectations for Use & Entry Into TS 3.0.A |
- on 960210,TS 3.0.A Incorrectly Invoked Due to Procedural & Operator Knowledge Deficiencies.Policy Statement Developed & Presented to Licensed Operator Re Expectations for Use & Entry Into TS 3.0.A
| 10 CFR 50.73(a)(2)(i) | | 05000254/LER-1996-007-02, :on 960510,secondary Containment Damaged.Caused by Tornado.Initiated Shutdown,Ac Power Restored to Prompt Notification Sys & Station Blackout Bldg Cables Spliced Per Er 9603099 |
- on 960510,secondary Containment Damaged.Caused by Tornado.Initiated Shutdown,Ac Power Restored to Prompt Notification Sys & Station Blackout Bldg Cables Spliced Per Er 9603099
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(1) 10 CFR 50.73(e)(2)(vii) | | 05000254/LER-1996-008-02, :on 960607,TS Required Pressure Not Met During Local Leak Rate Testing.Caused by Procedural Deficiency. Procedure Changes Submitted & Check Valves Retested Using Appropriate Vent Paths |
- on 960607,TS Required Pressure Not Met During Local Leak Rate Testing.Caused by Procedural Deficiency. Procedure Changes Submitted & Check Valves Retested Using Appropriate Vent Paths
| 10 CFR 50.73(a)(2)(viii)(B) | | 05000254/LER-1996-008, Forwards LER 96-008,Rev 00 & Makes Following Commitment: Procedure Qcts 0600-34 Will Be Revised to Ensure Appropriate Vent Path Exists When Leak Rate Testing 2251(2)-81A/B Panels | Forwards LER 96-008,Rev 00 & Makes Following Commitment: Procedure Qcts 0600-34 Will Be Revised to Ensure Appropriate Vent Path Exists When Leak Rate Testing 2251(2)-81A/B Panels | 10 CFR 50.73(a)(2)(1) | | 05000254/LER-1996-009-01, :on 960523,noted Discrepancy in Cable Length Modeled in Existing Degraded Voltage Calculations.Caused by Design Analysis Deficiency.Performed Design Changes to Correct Voltage Problems |
- on 960523,noted Discrepancy in Cable Length Modeled in Existing Degraded Voltage Calculations.Caused by Design Analysis Deficiency.Performed Design Changes to Correct Voltage Problems
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(B) | | 05000254/LER-1996-010-02, :on 960611,discovered Installed Gallery Steel Configuration Lacked Required Cross Bracing.Caused by Deficiency in Original Design Configuration Control Process. Installed Gallery Cross Bracing |
- on 960611,discovered Installed Gallery Steel Configuration Lacked Required Cross Bracing.Caused by Deficiency in Original Design Configuration Control Process. Installed Gallery Cross Bracing
| 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) | | 05000254/LER-1996-011, Forwards LER 96-011-00.Circuit Mods & Procedure Changes Will Be Implemented Prior to Startup & Review of Sample of Assumptions from Safe Shutdown Repts & Calculations Investigated | Forwards LER 96-011-00.Circuit Mods & Procedure Changes Will Be Implemented Prior to Startup & Review of Sample of Assumptions from Safe Shutdown Repts & Calculations Investigated | 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition | | 05000254/LER-1996-011-02, :on 960708,determined Postulated Fire Could Have Caused Disabling Damage to Selected Motor Operated Valves.Caused by Inadequate Design Analysis Review.Movs Analyzed for Susceptibility to Single Failure |
- on 960708,determined Postulated Fire Could Have Caused Disabling Damage to Selected Motor Operated Valves.Caused by Inadequate Design Analysis Review.Movs Analyzed for Susceptibility to Single Failure
| | | 05000254/LER-1996-012-02, :on 960620,diesel Fuel Oil Transfer Piping Noted in Unanalysed Condition Due to an Incomplete Safety Classification Upgrade.Minor Mod Has Been Completed Which Removes Autofill Capability for Fire Pump Day Tanks |
- on 960620,diesel Fuel Oil Transfer Piping Noted in Unanalysed Condition Due to an Incomplete Safety Classification Upgrade.Minor Mod Has Been Completed Which Removes Autofill Capability for Fire Pump Day Tanks
| | | 05000254/LER-1996-012, Forwards LER 96-012-00,for Quad Cities Nuclear Power Station.Review Plan Will Be Prepared to Identify Open Items within Component Classification Program & Ensure Resolution of Items.Plan Will Be Completed by 970301 | Forwards LER 96-012-00,for Quad Cities Nuclear Power Station.Review Plan Will Be Prepared to Identify Open Items within Component Classification Program & Ensure Resolution of Items.Plan Will Be Completed by 970301 | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | | 05000254/LER-1996-013-01, :on 960808,zebra Mussels Were Discovered on Fire Pump Suction Strainers.Caused by Inadequate Insp Frequency of Fire Pump Suction Strainers.Divers Removed & Cleaned Zebra Mussels from Fire Pump Suction Strainers |
- on 960808,zebra Mussels Were Discovered on Fire Pump Suction Strainers.Caused by Inadequate Insp Frequency of Fire Pump Suction Strainers.Divers Removed & Cleaned Zebra Mussels from Fire Pump Suction Strainers
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) | | 05000254/LER-1996-013, Forwards LER 96-013,Rev 0 IAW Requirements of 10CFR50.73(a)(2)(i)(B).Commitments Made by Ltr,Listed | Forwards LER 96-013,Rev 0 IAW Requirements of 10CFR50.73(a)(2)(i)(B).Commitments Made by Ltr,Listed | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | | 05000254/LER-1996-014, Forwards LER 96-014-00.All Personnel Will Be Briefed in Event by 961215,reinforcing Expectations to Initiate Procedure Changes When Needed | Forwards LER 96-014-00.All Personnel Will Be Briefed in Event by 961215,reinforcing Expectations to Initiate Procedure Changes When Needed | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | | 05000254/LER-1996-014-03, :on 960927,electrical Distribution Weekly Surveillance Did Not Document Voltage Verification Due to an Inadequate Procedure.Qcos 0005-06 Has Been Revised to Ensure Verification of Proper Voltages |
- on 960927,electrical Distribution Weekly Surveillance Did Not Document Voltage Verification Due to an Inadequate Procedure.Qcos 0005-06 Has Been Revised to Ensure Verification of Proper Voltages
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000254/LER-1996-015-01, :on 960816,HPCI Sys Jet Impingement Support Baseplate/Concrete Expansion Anchors Were Improperly Installed,Due to Ineffective Work Practices & QA Program. Review Will Be Completed |
- on 960816,HPCI Sys Jet Impingement Support Baseplate/Concrete Expansion Anchors Were Improperly Installed,Due to Ineffective Work Practices & QA Program. Review Will Be Completed
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) | | 05000254/LER-1996-015, Forwards LER 96-015-00.Commits to Completion Review of All Pipe Whip & Vibration Restraint Configuations by 961231 | Forwards LER 96-015-00.Commits to Completion Review of All Pipe Whip & Vibration Restraint Configuations by 961231 | 10 CFR 50.73(a)(2)(1) | | 05000254/LER-1996-016-01, :on 960823,secondary Containment Would Not Have Satisfied All UFSAR Requirements,Due to Siding Explosion Bolts Which Were Damaged by Either High Winds or Ineffective Work Pratices.Damaged Bolts Replaced |
- on 960823,secondary Containment Would Not Have Satisfied All UFSAR Requirements,Due to Siding Explosion Bolts Which Were Damaged by Either High Winds or Ineffective Work Pratices.Damaged Bolts Replaced
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000254/LER-1996-017, Forwards LER 96-017-00,for Quad Cities Nuclear Power Station.Review Plan Will Be Prepared to Identify Open Items | Forwards LER 96-017-00,for Quad Cities Nuclear Power Station.Review Plan Will Be Prepared to Identify Open Items | 10 CFR 50.73(a)(2)(iv), System Actuation | | 05000254/LER-1996-017-01, :on 960825,manual Scram Taken During Reactor Startup When Reactor Water Level Increased Following Unplanned Opening of All Main Turbine Bypass Valves Occurred,Due to Inadequate Procedures.Procedures Revised |
- on 960825,manual Scram Taken During Reactor Startup When Reactor Water Level Increased Following Unplanned Opening of All Main Turbine Bypass Valves Occurred,Due to Inadequate Procedures.Procedures Revised
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2) | | 05000254/LER-1996-018, Forwards Supplemental Info Re LER 96-018-00,correcting Editorial Error | Forwards Supplemental Info Re LER 96-018-00,correcting Editorial Error | | | 05000254/LER-1996-018-01, :on 960903,TS Surveillance Requirements Were Misinterpreted Due to Conservative Misunderstanding of Requirement.Memo Was Written to Explain Which Min TS Surveillances Must Be Performed Re Mode Switch |
- on 960903,TS Surveillance Requirements Were Misinterpreted Due to Conservative Misunderstanding of Requirement.Memo Was Written to Explain Which Min TS Surveillances Must Be Performed Re Mode Switch
| 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) | | 05000254/LER-1996-019, Forwards LER 96-019 IAW Requirements of 10CFR50.73(a)(2)(ii)(B) & Discusses Listed Commitments | Forwards LER 96-019 IAW Requirements of 10CFR50.73(a)(2)(ii)(B) & Discusses Listed Commitments | 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition | | 05000254/LER-1996-019-01, :on 960904,main Steam Line Radiation Monitor Functional Test Was Not Performed within Frequency Established for TS When in Refueling Mode Due to Incomplete Documentation of TS Interpretation.Qcap 2300-11 Was Changed |
- on 960904,main Steam Line Radiation Monitor Functional Test Was Not Performed within Frequency Established for TS When in Refueling Mode Due to Incomplete Documentation of TS Interpretation.Qcap 2300-11 Was Changed
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000254/LER-1996-020, Forwards LER 96-020-00.Commitments Included in LER & Submitted | Forwards LER 96-020-00.Commitments Included in LER & Submitted | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000254/LER-1996-020-01, :on 960907,CR Emergency Filtration Sys Declared Inoperable.Caused by Operator Knowledge Weakness.Operators Declared CR Emergency Filtration Sys Inoperable & Entered 14-day LCO |
- on 960907,CR Emergency Filtration Sys Declared Inoperable.Caused by Operator Knowledge Weakness.Operators Declared CR Emergency Filtration Sys Inoperable & Entered 14-day LCO
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000254/LER-1996-021-01, :on 961011,B CR HVAC Sys Was Declared Inoperable Due to Crankcase Heater Power Supply Design Deficiency.Design Change Notice 9600380 Issued,Which Replaced Crankcase Heater W/Safety Related Heater |
- on 961011,B CR HVAC Sys Was Declared Inoperable Due to Crankcase Heater Power Supply Design Deficiency.Design Change Notice 9600380 Issued,Which Replaced Crankcase Heater W/Safety Related Heater
| | | 05000254/LER-1996-021, Forwards LER 96-021-00,for Quad Cities Nuclear Power Station.No Commitments Being Made | Forwards LER 96-021-00,for Quad Cities Nuclear Power Station.No Commitments Being Made | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000254/LER-1996-022-01, Extends Commitment Date for Completing Rev to Plant CR Dose Analysis of Record,Per LER 96-022-01 | Extends Commitment Date for Completing Rev to Plant CR Dose Analysis of Record,Per LER 96-022-01 | | | 05000254/LER-1996-023-01, :on 961124,CR Emergency Filtration Sys Failed to Maintain Required Airflow Due to Cognitive Personnel Error.Instrument Loop for Gauge Fi 1/2-5795-307 Calibr |
- on 961124,CR Emergency Filtration Sys Failed to Maintain Required Airflow Due to Cognitive Personnel Error.Instrument Loop for Gauge Fi 1/2-5795-307 Calibr
| | | 05000254/LER-1996-023, Provides Commitments Re LER 96-023.Predefined Model Work Request Which Initiates Perodic Maint Procedure Initiated | Provides Commitments Re LER 96-023.Predefined Model Work Request Which Initiates Perodic Maint Procedure Initiated | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | | 05000254/LER-1996-025, Forwards LER 96-025-00 Re Operability Calculations Performed on ECCS Suction Strainers W/Incorrect Head Loss Values | Forwards LER 96-025-00 Re Operability Calculations Performed on ECCS Suction Strainers W/Incorrect Head Loss Values | | | 05000254/LER-1996-025-01, :on 961220,discovered Original Value for Strainers Head Loss Incorrect.Cause Could Not Be Determined. Training Provided for Operators to Recognize Pump Cavitation During Design Basis Accidents |
- on 961220,discovered Original Value for Strainers Head Loss Incorrect.Cause Could Not Be Determined. Training Provided for Operators to Recognize Pump Cavitation During Design Basis Accidents
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
|