j; To James P. O'Reilly.

Directorate of Reguistory Operations Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 a

t i

i Jersey Central Power 4 Lidt Company Fam:

Oyster Creek Nuclear Generating Station, Docket #50-219 Forked River, New Jersey 08751

/

I i

Stbject:

Abnossal;0ccurrence Repy 50-}19/{4/29 1he following is a preliminary report.being submitted in compliance with,the Technical Specifications, paragraph 6.6.2.

n.

Pielic? nary Approval:

i I

h

&44/f 4l26/74V

h. h. Carroll, Jr.[

Date 1

l 2

cc: Mr. A. Gia6 usso i

l 9604240237 965213 PDR FotA DEKOK95-258 PDR

l 1ritial Written o Report Dates 4/26 $

ceu ce:

1720 OYSTER CREEK NUCl.!!AR GENERATING STATION FORKED RIVER, NEW JBRSBY 08731 Abnomal Occurrence Report No. 50 219/74/29 IDENTIFICATION Violation of the Technical Specifications, paragraph 2.3.4, J

OF OCCURRENCE:

Electromatic Relief Valve Pressure Switches, IA838 and 1

1AB3D, were found to trip at pressures in excess of the maxi-num allowable value of 1070 psig.

Ris event is considered to be an abnormal occurrence as de-fined in the Technical Specifications, paragraph 1.15A.

CONDITIONS PRIOR Steady State Power Routine Shutdown TO OCCURRENT:

Hot Standby Operation Cold Shutdown Load Otanges During X

Refueling Shutdown Routine Power Operation Routine Startup Other (Specify)

Operation ne reactor mode switch was in the REPUBL position with reactor coolant tegerature approximately 100'F.

DESCRIPTION On Tuesday, April 23,1974,"while perfoming surveillance OF OCCURRENCB:

on the five Electmaatic Relief Valve Pressure Switches, it was found that 1A83B and 1A830 tripped at 1090 psig and 1096 psig, respectively. These values are in excess of the maximum allowable trip pointe of 1084 psig and 1082 psig, respectively, which are derived by adding appropriate head correction factors to the Technical Specification limit of-1070 psig. It is noted here that switches 1A83B and 1A83D are associated with valves NR108B and NR1080, respectively.

. = - -

Rep:rt Ns. 50-219/74/29 rags e 0

0-

)

i l

Me "as found" and "as left" switch settings were:

~

Associated-

"As Pomd"'

"As Inft" I

switch Valve Settina Settina q

4 1A85A NR108A' 1979 psig 1079 sig q

h 1A838 NR1088 1000 psig 1084 sig jl

.1/ <3C.

NR108C 1077 psig 1077 psig 4

1A85D NR108D 1996 psig 1082 psig i[

1A85E NR108E-1082 psig 1982 psig

{;

APPARBNT CAUSB-X Design Procedure jl OF OCCURRENCE:'

Nanufacture thusual Service Condition Installation /

Inc. Environmental'

~t

~

Construction Component' Failure Operator Other-(Specify) 1

o ji 2-,

' Instrument Erift has been tentatively identified as the r,ause I'

of this occ.urrence.'-

4

L ANALYSIS OF Se relief valves are pavided to remove sufficient energy i

OCCURRENCE:

j from the primary system to prevent the safety valves from 1

)

lifting during a transient. De limiting pressum transient IIi is that which is produced upon a turbine trip from rated 4

t

[

design power with a failure of the bypass system to function.

4 Under these conditions, the five (5) relief valv'es are re-

]i;'

quired to operate.in order to prevent reaching the lowest i

set point of the primary system safety valves.

It should be noted that a 25 psi margin exists between the resulting

  • i L

peak pressure and the lowest safety valve set point as added assurance that the safety valves will not lift during this transient. With valves NR108B and NR108D actuating at t

6 pig and 14 psig, respectively, above the maximum allow-able trip point of 1070 psig, and assuming the most limiting

'?

i!

^

._.._ Z.~...

J #7@EM $nD l

i

i Neptre no. w-nv/ screw rags a

()

)

f l

pmssure transient had' occurred, the lowest set point safety 3 *; '

j valve or valves may have been wquired to actuate in order to

)

limit the pressure transient. Since the. safety valve capacity (f

is based upon providing sufficient vessel over-pressure pro-i i

tection upon failum of ali pressure release devices, in it.

additha to a failure of the reactor to scrsa, over-pressuriza-tion,of.the vessel would not have occurred, 4

OGARECTI W no involved pressure switches, IA838 and 1A83D, were immed-ACTIW :

l intely reset to trip at allowable pressure levels. Additional items of corrective action will be determined following re-4 view of this occurrence by the Plant Operations Review Consmittee.-

i FAIIMRB DATA:

Manufacturer data pertinent to these switches are as follows:-

t I;

Manufacturer - Dresser

[

Type - 1539VX Serial Nos. - BK3339 (IA83B) il BK3338(1A83D) l1 i

d

i 1

l!

l Papared by: _\\.

wd..

Date:

4/26/74

}

)

~

i J

1 s

l 1

-