ML20107E181

From kanterella
Jump to navigation Jump to search
Forwards AO Rept 50-219/74/3
ML20107E181
Person / Time
Site: Oyster Creek
Issue date: 01/24/1974
From: Ross D
JERSEY CENTRAL POWER & LIGHT CO.
To: Anthony Giambusso
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML18039A986 List: ... further results
References
FOIA-95-258 NUDOCS 9604190231
Download: ML20107E181 (1)


Text

y.

D

.)

.ersey Central Power & Lig1t Company L'V 2

MADISON AVENUE AT PUNCH BOWL ROAD

  • MORRISTOWN.N.J. 07960
  • 201-539-6111 us== a or sus g'7. j,]', Public UtJI6 ties Corporation General umu January 24, 1974 QA f f(h

',a q

U

' ' 6 (j

{

Mr. A. Giambusso 9'

~

'Q

,ANg81974

  • L J

Deputy Director for Reactor Projects

,,,,,. ; r;m j7 Directorate of Licensing United States Atomic Energy Commission

/

t":: 24 M

h didI.ik h'ashington, D. C. 20545

'/

\\

Dear Mr. Giambusso:

' ' ) 8 i5

Subject:

Oyster Creek Station Docket No. 50-219 Abnormal Occurrence Report No. 50-219/74/3 The purpose of this letter is to forward to you the attached Abnormal Occurrence Report in compliance with paragraph 6.6.2.a of the Technical Specifications.

Enclosed are forty copics of this submittal.

Very truly yours,

" '\\

r im, (h ">' E fs,f A p)f Donald A. Ross Manager, Nucicar Generating Stations cs

' Enclosures cc: Mr. J. P. O'Reilly, Director Directorate of Regulatory Operations, Region I h

', i'

  • v 737'
.t 9604190231 960213 POR FOIA PDR DEKOK95-250,

~C

.)

OYSTER CREEK NUCLEAR GENFPATING STATION FORKED RIVER, NEW ' JERSEY 08731 Abnormal Occurrence Report No. 50-219/74/3 4

Report Date:

January 24, 1974 Occurrence Date:

January 13, 1974 Identification of Occurrence:

- Failure of Hydraulic Shock and Sway Arrestors on one Core Spray System and on both Isolation Condenser Systems. This event is considered to be an. abnormal occurrence as defined in the Technical Specifications, paragraph 1.15D.

Conditions Prior to Occurrence:

The plant was in a cold shutdown condition with reactor coolant at <212*F.

Description of Occurrence:

During the required inspection of the Bergen Paterson HSSA-10 units in the primary containment, five units were discovered to be devoid of fluid.

They were located as follows:

3 "A" Isolation Condenser 1

"B" Isolation Condenser 1 - Core Spray System No. 2 Apparent Cause of Occurrence:

The cause of snubber inoperability was due to a loss of hydraulic fluid.

Disassembly of each of the inoperable snubbers has revealed no visually obvious-deterioration of the seal material except for some brittleness.

Analysis of Occurrence:

. The safety significance of this occurrence was a partial loss. of the seismic restraining ability _ for the two affected systems.

Had the plant suffered a design bases earthquake, the probability that these two systems would have suffered structural damage was increased.

- Corrective Action:

i The failed units were replaced with units that were rebuilt with ethylene

. propylene (Parker Grade E652-90) seal material.

Four of the inoperable

{

r

b

)

Abnormal Occurrence Report No. 50-219/74/3 Page 2 units were located above the biological shield, a relatively hot area in the containment, and had been rebuilt in September 1973 with molded polyurethane and viton type seal material. All of the units in that area, regardless of condition, have been replaced with units rebuilt with the ethylene propylene type material.

Failure Data:

Manufacturer:

Bergen Paterson Type:

HSSA-10 Serial Nos. :

487517 487487 477376 470924 469962 8

-,