ML20107D024

From kanterella
Jump to navigation Jump to search
Forwards Preliminary AO Rept 50-219/74/4
ML20107D024
Person / Time
Site: Oyster Creek
Issue date: 01/16/1974
From: Carroll J
JERSEY CENTRAL POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML18039A986 List: ... further results
References
FOIA-95-258 NUDOCS 9604180104
Download: ML20107D024 (1)


Text

__

(

?)

~

To:

James P. O'Reilly Directorate of Regulatory Operations Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 From:

Jersey Central Power 6 t.ight Company Oystef Creek Nuclear Gennrating Station Docket #$0 219 Forked River, New Jersey 08731 subject:

Abno7 sal Occurrence Report No. 50-219/74/ 4 The following is a proliminary report being submitted in compilance with the Technical Specifications paragraph 6.6.2.

Preliminary Approval:

-e /

  1. fv4N

.1/16/74 f

hl. T. CErro11, Jr.

Date cc: Mr. A. Gitunbusso l

9604180104 960213 PDR FOIA l

DEKOK95-250 PDR

Initial Written Tine of l

Raport Dater 1/1/j74 Occurren ce; 03'45 QYSTER CREEK NUCLEAR GENERATING STATION FDPI.ED RIVER, NEW JERSEY 08731 Abnormal Occurrence Report Ho, 50219/74/J t

IDFitTIFICATION Violation of the Technical Specifications, paragraph N/A __,

OF OCCURRENCE:

htilure of Main Steam Isolation Valve NS03B to close upon receiving a manual signal to close.

Thin event is considered to be en Abnormal occurre cc as de-fined in the Technical Specifications, paragraph ~ 1.1sn CONDIT.10NS PRIOR TO OCCURRENCE:

Steady State Power Routine Shutdown

_ Hot Standby

. x., Operation

~ Cold Shutdown Load Changes During Rafueling Shutdown Routinc Power Operation Routine Startup Other (Specify)

Operation The reactor was in the shutdown condition with the ede switch in refuel.

Heactor coolant temperature was icss than 212 F with the reactor head vented.

DESCRIPTION in order to minimize airborne r-di, activity in the dryweII, OF OCCURRENCE!

a negative pressure was impressed on the reactor vc.:cel via the mechanical vacuum pump thmugh Main Steam Isolatire /alves NS03B and NSO48, At this time, a complete inspection and cleaning of the " spool" valves used in the control scher.,e for Main Steam I8olution Valves NS03A and NSO4A was in progress which necessitated these valves being closed. After the in-spection/ cleaning was completed, steps were taken to open L

geg,rg go.~gg;1TST W Fo

.-s-w O

J these valves and cloec; valves NS03n and NSO4B so that the same c

preventive maintenanco steps ' could be performed on their assoc-lated spool valves, When the close signal was inpressed on.

NS03B, the valve did not respond.

Subsequent attenpts were

]

made tu close the valve and on the third try the valve closed, An operator located in the drywell noted that the solenoid valve which operates the power vilve was functioning properly, l

it should be noted that this.valvo had previously been Alven a closure nignal on January 11, 1974 during the plant shutdown 1

at approximately 270 We and again on January 13,1974 in pre-l paration for a MSY1 lenk rate test, In both of these cases, valvo operation wn satisfactory, APPARDE CAUSE Design Procedure 0F. OCCURRENCE:

Nanufacture Unusual Service Condition

~

~~ Inst a11stion/

Inc, Environwntal const ruction Component Failure-

_ Operator Other (Specify)

The cause of this event is und-r investigation at this time.

It shoul'd be noted that this valve (NS03B) operator is con-nected to the 'dtrogen system during power operation, h'hile

\\

shutdown, the valve operators of the two MSIV's innide the drpell are switched over to the station air system when the i

drywell is purged and open for access. It 18 po8sible that i

dust in the air line (dead-ended durinB power operdtion) had

+

become lodk:cd in tho' air ports.of the volve operator during

~

the switchover from nitrogen to air, 1..

l'

u ndi s v u w as...w.

keport Ho, 50-219/74/4

. January 16, 1974

.O J

ANALYSTS OF Yhe Main Stenn Isolation Valves are intended to provido a OCCURIGNCE:

means of minimi ing fission product relene under design bases condition, $1nce the redundant valve NSDAB closed in the s

proper manner, this function would have been performod. This consideration is only important had the valve failed to close while. at power opention, Since the plant was in cold shut-down, the safety significance of this particular event is con-sidered minimal.

COMPECTIVE The spool valve was digassephled, inspected and cleant.d. The ACTION:

valve spool essenbly was observed to operate freely after re-encubly.

FAILulE DATA:

Manufacturcr; Wimatics Inc.

valve Divisiori Type: Pilot Operated Power Velve' hk;delt l'rint Reference No. 917%U and modified by General Electric Company FD1 F.122[91700 l

i

/

(%

/ /4 %

eroporca sy

__ /!A$~iy ec.. /.a-e-nate:

J

/

.1

-