Forwards AO Rept 50-219/74/19
ML20107C191
Person / Time
Site: Oyster Creek
Issue date: 03/18/1974
From: Ross D
JERSEY CENTRAL POWER & LIGHT CO.
To: Anthony Giambusso
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML18039A986 List: ... further results
References
FOIA-95-258 NUDOCS 9604170266
Download: ML20107C191 (1)


Text

c3

/g e

p.

4y j (n f ti

.ersey Centra Power & Light Company f./

so MADISON AVENUE AT PUNCH BOWL ROAD

  • MORRISTOWN, N.J. 07960
  • 201-539-6111 NIN0t 9 O* THE General g

' Public Utilities Corporation. _...._....._.

SYST&M 1

March 18, 1974 i

y:

s' s

Mr. A. Giantusso Deputy Director for Reactor Projects Directorate of Licensing United States Atomic "nergy Commission Washington, D. C. 20545

Dear =Mr. Giambusso:

Subject:

Oyster Creek Station Docket No. 50-219 Abnormal Occurrence Report No. 50-219/74/19 The purpose of this letter is to forward to you the attached Abnormal Occurrence Report in conpliance with paragraph 6.6.2.a of the Technical Specifications.

Enclosed are forty copies of this submittal.

1 i

Very truly yours, YWh

.6 v.?L 1

Donald A. Ross Manager, Nuclear Generating Stations es

~

Enclosures cc: ~Mr..J.

P. O'Reilly, Director Directorate of Regulatory Operations, Region I' h

1 i

i n..

c n u...'.-

w 9604170266 96021'3' PDR FOIP.

DEKOK95-256 PDR

{)

0YSTER CREEK NUCLEAR GENERATING STATION FORKED RIVER, NEW JERSEY 08731 Abnormal Occurrence Report No. 5)-219/74/19

~

Report Date March 18,1974 Occurrence Date March 9,1974 Identification of Occurrence _

Violation of the Technical Specifications, paragraph 3.5. A.1, failure to main-tain primary containrent integrity with reactor water temperatt

  • above 212*F and fuel in the reaccor vessel.

This event is considered to be an abnormal occurrence as defined in the Technical Specifications, paragraph 1.15B.

Conditions Prior to Occurrence The plant was shut down with reactor coolant <212*F.

Description of Occurrence At 1000 on March 8,1974, an orderly shutdown of the plant commenced to perform i

maintenanc.e on six of the fourteen torus to drywell vacuum breaker valves.

Although thirteen of the valves were considered to be operable at this time, the plant was shut down in order to effect more permanent repairs.cn the valves.

(See Abnormal Occurrence Report No. 50-239/'M/16 dated March 15, 1974).

In accordcnce with the requirements of paragrup 3.5. A.1 of the Technical Specif-4 ications, maintenance on these valves did not begin until reactor coolant tec-perature was below 212*F.

At approximately 0500 on March 9,1974, the control room operator noticed that the reactor vessel head metal temperature was increasing at a rate of 10'F/hr after being stable at 231*F for about a 3-hour period.

A check of the recirculation loop temperature recorder, which was being used as th'e primary indication of j

reactor water temperature, showed the recorder trace to be constant at 160 F.

j While this inconsistency was being investigated, a radiation protection technician reported to the shift foremn that water vapor appeared to be issuing from a-special manometer which had been installed for monitoring of the pressure difference between the drywell and reactor vessel. The shift foreman's investi-gation revealed that the reactor side of the manometer was hot.

The recirculation loop temperature recorder was then rechecked and again indirated a temperature of 160*F. However, the indication jumped to approximately 250'F when the

- recorder was bumped.

Since two of the torus to drywell vacuum breaker valves c ere undergoing maintenance at this time (0531 on March 9,1974), primary i

1

(>

Abnormal Occurrence No. 50-219/74/19 Page 2 containment integrity was not in effect.

Shutdown cooling system flow was then increased to decrease the reactor water temperature.

Reactor water tempercture was reduced to less than 212*F within approximately 30 minutes.

h'ithin approxi-mately 130 minutes, a reactor water temperature of 160*F was established and maintained.

Apparent Cause of Occurrence This abnormal occurrence is attributed to equipment malfunction and operator error.

The recirculation loop recorder did stick cnd give a false indication of reactor coolant temperature.

Ilowever, the control room operator failed to

. react properly to indications that reactor. water temperature was increasing.

Specifically, a revi'ew of the chart paper from the recorder monitoring shutdown cooling system temperatures showed that the "C" loop heat exchanger inlet temperature was increasing at a rate of about 10*F/hr during the 3-hour period prior to 0230 on March 9,1974.

At this time, the control room operator secured flow in this loop and thereby contributed to the rise in zeactor water temperature.

i Analysis of Occurrence The primary containment system provides a barrier against uncontrolled release of fission products to the environs in the event of a break in the reactor coolant sys t ems. hhenever the reactor coolant water temperature is above 212*F, failure of the reactor coolant system could cause rapid expulsion of the coolant from the reactor with an associated pressure rise in the primary contcinment.

Primary containment is required, therefore, to contain the thermal energv of i

the expelled coolant and fission products which would be released from any fuel failures resulting from the accident.

The safety significance of this event is that primary containment integrity was not maintained during the period that the reactor coolant temperature was in excess of 212*F due to the maintenance being performed on the vacuum breaker valves. At the condition that existed, the safety significance is considered minimal.

Correct,ive Action The following corrective actions will be taken:

1.

The operator retraining program will emphasize that all available indications are to be used when critical parameters such as reactor water temperature are being monitored.

In additon, the operators will be instructed in their retraining to regard extremely straight recorder traces as suspect and to view confirming indications whenever such suspicious recorder traces are encountered, both while operating and shut down.

e

[,

)'

.' Ahnomal. Occurrence No. 50-219/74/19.

Page-3 i

2. - 1he shutdown log.will be reviewed and modified to require the recording of additional system temperatures related to the reactor coolant ten-perature..

Failure Data

Basic recorder data are as follows

l Manufacturer: General Electric Company

' Type :.

.GE/MAC 531-t, Span:

4 inches i