Forwards ERDS Data Point Library (Dpl) Changes,Per NUREG 1394,Rev 1,Section 3.6, Administrative Implementation Requirements. Changes Currently in Effect on Plant Computers Providing Data to ERDS Computer
ML20064H139
Person / Time
Site: Beaver Valley
Issue date: 03/09/1994
From: Sieber J
DUQUESNE LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
RTR-NUREG-1394 NUDOCS 9403170164
Download: ML20064H139 (3)


Text

- - . . . . - . .-. . -- .. ,

s

  1. #. Beaver Valley Power Station

. Smppingport. PA t5077-0004 JOHN D. SIEBER (412) 393-5255 '

Senior Vice President and March 9, 1994 ran (4t2) 643-8069 CNef Nuclear Officer Nuclear Power Division U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

Subject:

Beaver Valley Power Station, Unit No. 1 2

BV-1 Docket No. 50-334, License No. DPR-66 Emergency Response Data System (ERDS)

In accordance with the requirements published in NUREG 1394, Rev. 1, Section 3.6, " Administrative Implementation Requirements," j the enclosed Data Point Library (DPL) changes are being submitted.

These .two (2) DPLs have undergone a change in their unique system descriptions. These were incorporated to more closely match th Beaver Valley Power Station Operations ManualLdescriptions for these particular data points. These changes are currently in effect on the Beaver Valley Plant computers which provide the-data to the'ERDO computer.

Any questions regarding this DPL change should be addressed to Glenn McKee at (412) 393-5778.

Sincerely, J. D.

'lm Sieber Attachments cc: Mr. L. W. Rossbach, Sr. Resident Inspector Mr. T. T. Martin, NRC Region I Administrator Mr. J. R. Jolicoeur, USNRC Incident Response Branch 1

Mr. T. P. LaRosa, NUS Corporation /EI Division Mr. E. C. McCabe, NRC Region 1, Emergency Preparedness Mr. C. 2. Gordon, NRC Region 1, Emergency Preparedness Mr. G. E. Edison, Project Manager S

b Q -D K. ,

d' m g' le 'g hjj317016494o3o9 nooCe onoooss4

.e PDR

, ~ . . . -

a. .

BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY BV1 ERDS INPUT Date: 02/23/94 Reactor Unit: BV1 Data Feeder: PVC NRC ERDS Parameter: HP SI FLOW Point 10: FS940A Plant Spec Point Dese.: FILL HEADER HHS! FLOW F S1940 Generic /Cond Dese.: HIGH PRESS SAFETY INJECTION FLOW Analog / Digital: A Engr Units / Dig Statos: GPM Engr Units Conversion: N/A Minintsu Instr Range: 0 Manimum Instr Range: 1000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Nunber of Sensors: 1 How Processed: N/A Sensor Locations: SEE UNIQUE SYSTEM DESCRIPfl0N FIELD

, Alarm /frip Set Points: N/A NI Detector Power Supply Cut off Power Level: N/A NI Detector Power Supply Turn-on Power Level N/A Instrument Failure Modo: LOW Tenperature Coppensation for DP f ransmitters: N Level Reference Leg; N/A Unique System Dese.: THIS VALUE IS THE FLOW FROM THE HIGH HEAD SAFETY INJECTION PuhPS IN TO THE HOT AND COLD REACTOR COOLATN LOOPS A,B, AND C. CH P 1A,B.C.

PROVIDE A HMSI FLOW RATE OF 150 GPM AT 2500 PSIG. IT 1SI-940 3 EMS ES FLOW AT THE DISCHARCE OF CH P-1A,B, ARD C PRIOR TO THE HLADER CO NNECTION TO THE HOT AND COLD LEGS OF REACTOR COOLANT LOOPS A. 5, AN

D C. OP MANUAL CHAPTER 11, RM 411 1, RM 407 1 l

l i

._ - , . . .. . ._, . . . .. ,. . . _.. . _ . . m - . - _ _

s 1 i

s + ,

BEAVER VALLEY POWER STATION EROS DATA POINT LIBRARY

. BV1 EROS INPUT Date: 02/23/94 Reactor Unit: BV1 l

Data Feeders PVC 1 1

j NRC EROS Parameter: HP St FLOW Point 10: F5943A Plant Spec Point Desc.: BIT HHS! FLOW F S1943 Generic /Cond Dese.: HIGH PRESS SAFETY INJECTION FLOW Analog / Digital: A i

Engr Units / Dig States: GPM Engr Units Conversion: N/A Minimura Instr Range: 0 Maxifmsn Instr Ranges 1000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Numtier Of Sensors: 1 How Processed: N/A Sensor Locations: SEE UNIQUE SYSTEM DESCRIPTION FIELD -

Alarm / Trip Set Points: N/A NI Detector Power Supply Cut off Power Level: N/A NI Detector Power Supply Turn-on Power Level N/A Instri.rnent f ailure Mode: LOW Temperature Compensation For DP Transmitters: N Level Reference Leg: N/A Unique System Dese.: THIS VALUE IS THE FLOW FROM THE HIGH HEAD SAFETT INJECTION PUMPS IN 10 THE BORON INJECTION TANK HEADER. CH P 1A,B,C. PROVIDE A HHS! FLO W RATE OF 150 GPM AT 2500 PSIG. FT-151-943 SENSES FLOW FROM THE D ISCHARGE OF CH P-1A,B, AND C TO THE HIGH HEAD SAFETY INJECTION HEAD ER CONNECTION TO THE BORON INJECTION TANK OP MANUAL CHAPTER 11, R M 411-1, RM-407 1

.