p License No. R-65 10 OCT 1977 APPE'! DIX A NOTICE OF VIOLATION l
Based on the results of an ?!RC inspection conducted on September 22, 1977, it appears that certain of your activities were not conducted in t
full compliance with the conditions of your license as indicated below.
shese are categori:ed as Infractions.
i A.
Technical Specification 4. states, in part, "The Facilities Engin-eering 3 ranch (FEB) shall perfem the folicwing activities.
i (a) Heating and Ventilating System f
(1) A weekly visual inspection.
l (2) A :ronthly check of all equipment in accordance with a written checklist...
l Contrary to the above, conthly checks of the Heating and Ventilating l
systems were not perfomed during the months of February and July, 1977.
I This violation appears to be repetitive in that a violation of l
Technical Specification 4.a was identified during another inspection, (47/75-01).
3.
10 CFR 20.203(c)(l) statas: "Each hign radiation area shall be conspicuously posted with a sign or signs ': earing the radiation
[
caution symbol and the words "CAUTI0ii (or CA;;GER) HIGH RADIATIC:t i
AREA."
10 CFR 20.202(b)(3) states, "High Radiation Area reans any
}
area, accessible to personnel, in which there exists radiation in i
whole er in part within licensed material at such levels that a i
major portion of the body could receive in any one hour a dose in j
excess of 100 millirec."
I t
j Contrary to the above, the area inside the reactor pool above the core plate was not posted as a High Radiation Area on September 22, l
1977. A servey of this area perfomed on July 25, 1977, shcwed a contact reading of 2400 mrec/hr en the core plate. A survey conducted l
on October 10, 1977, showed a r:aximum contact reading of 2950 aren/nr and a general area reading of 265 mrea/hr three feet fren l
r the core plata.
I kN3h12s11005
(