05000293/LER-1981-050-01, /01T-0:on 810812,during Normal Operation,Ground Fault Indication on 125-volt Dc Sys Was Received.Caused by Short Circuit in Topaz Dc to Ac Inverter.Inverter Repaired & Procedures Rewritten

From kanterella
(Redirected from ML20011A434)
Jump to navigation Jump to search
/01T-0:on 810812,during Normal Operation,Ground Fault Indication on 125-volt Dc Sys Was Received.Caused by Short Circuit in Topaz Dc to Ac Inverter.Inverter Repaired & Procedures Rewritten
ML20011A434
Person / Time
Site: Pilgrim
Issue date: 09/29/1981
From: Whitney G
BOSTON EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20011A430 List:
References
LER-81-050-01T, LER-81-50-1T, NUDOCS 8110130344
Download: ML20011A434 (2)


LER-1981-050, /01T-0:on 810812,during Normal Operation,Ground Fault Indication on 125-volt Dc Sys Was Received.Caused by Short Circuit in Topaz Dc to Ac Inverter.Inverter Repaired & Procedures Rewritten
Event date:
Report date:
2931981050R01 - NRC Website

text

-

LICENSEE EVENT REPORT CONTROL sLOCK. l l

l l

l l

jh (PLk ASE PRINT oR TYPE ALL REQUIRED INFCRMATIONI e

6 lo lt] l Ml Al P lP lS l 1 l@l 0 l0 l-l0 l 0l 0l 0l 0l -l 010 l@l 4 l 1 l 1 l I I 1 l@l l

l@

7 8 9 LICENSE E CODE 14 15 LICENSE NUMSER "25 26 LICENSE TYPE Jo 57 CAT 54 CON'T l10121

.OU LI.J@l 0 l s 10 l-10 l219 l3 }@l 01 A l '. l I R I 1 )@l 0 l 9 l 219 l8l1l@

7 3

60 El DOCKET NUMBEf-6e 69 EVENT DATE 24 75 REPORT DATE 80 EVENT DESCRIPTION AND PROBABt E CONSEQUENCES h lo lal l During normal operation, on 9/12/81 a ground fault indication on the 125 Vnc syntom I

, g o i3; g wu received. Elimination of this fault culminated in the tripping of breaker D4-3. _J l Tripping breaker D4-3 resulted in an inadvertent reduction below the minimum numhar I

o,

gol5j g of PCIS instrument channels needed for some RCIC valve isolations. This condition I

i o s l was corrected on 9/16/81 by restoring the D4-3 breaker. At no time durine this I

[73 ] l period was primary containment violated, therefore there was no threat to the I

7 I

io;ej g public safety.

v ss

' $o'E

  • '"Y s eC$0E COMPOf.dNT COC E SU8 O'E E

C C0O jolsj

' l E l C l@ l Elh [A_j h l G l E I N I E l R l A l@ LP_l@ l ZJ @

y 3

9 10 ft 12 33 18 19 20 SEOL 8 NTI AL OCCURRENCE REPORT R E VISION i

_, EVENT YEAR REPORT NO.

CODE TYPE N O.

@,ag/Ro 1811l l-l 1015l01 Ld I o! !J LIJ L-J Led LE R

,_ 21 22 23 24 26 27 28 29 30 31 32 O fP NT MET D HOUR $

$8 i D

FOR B.

$UPPL1 R MAP FA TURER K N AC ON l B QW@

W@

[Zj@

l0l0l0l0l [Y_j@

[N_j@

lN I@

lT l2 l 4 l 8l@

33 34 35 M

37 40 41 42 43 44 47 cAUSE DESCRsPTION AND CORRECTIVE ACTIONS h I

g i g o ; [ The cause of the ground fault was determined to be a short circuit in a Tooaz DC to L

[i li j l AC inverter which was repaired. The cause of the PCIS channel reduction una nrn-I

,,,g cedural. To correct this inadequacy a revision to the " Inspection / Trouble Shooting-I y,y.,y l Electrical Circuits" Procedute 3.M.3-8 has been initiated. This will be completed l

8 i y October 1, 1981.

b m

y s,

'57

% POWER CfHa!N STATUS is O Y

DISCOVERY DESCRIPTION I

(E_,l@ l 0 l 9 l 7 lhl N.A.

l W hl Onorationni Event l

i s 44 45 46 80 7

3 9 10 12 11 l

ACTIVITY CONTENT RELE ASED OF RELEASE AMOUNT OF ACTivtTY LOCATION

>$ LEASE N.A.

l l

N A.

1Z_j h (_Zj@l 1 6 7

s 9 10 11

.4 45 80 PER$0NNEL EXPO 5Ue'ES l

WuMBER TYPE DE SC HIPTION 39 l

l0l0l0j@[Zj@l N_A_

i 7 l-nR50~NEl'~uks CRiPTiONh NUMeER oE 10 10 10 l@l N.A.

']

i e 80 7

8 9 11 12 Loss OF OF. DAMAGE TO FACILITY Q l

TYPE

DESCRIPTION

v N.A.

l [Zj@l -

(

i 9 80 7

8 9 to N AC USE ONLY PUSLICITY Q

ISSUED @ DESCRIPTION D [N_j l

N.A.

l lllllllllllll*g i

j a O 68 69 80 -

1$o!

ONO 3

G. G. Whitney pggggf_WhN in PM l

S

BOS'TCN EDISON COMPANY PILGRIM NUCLEAR POWER STATION DOCKTT J0 50-29.1 Attachment to LER 81-050/017-0

Event Description

During normal operations en September 12, 1981, 9 ground fault indication on the 125 VDC System was received. An investigation was immedir.tely initiated.

Following procedure, a number of breaker isolations determined the fault to be in the systems served by breaker D4-3.

Individual fuses were then pulled and returned until the fault was isolated in the circuit serving the Topaz DC to AC inverter. No replacement inverter was available, therefore, permission to remove the inverter for repair was requested from the Watch Engineer. He indi-cated the RCIC System would be made inoperative when the breaker was opened.

This condition lasted until September 16, 1981.

Primary containment was maintained throughout this period but some of the logic contributing to the automatic isolatien of RCIC valves MO 1101-16 & 17 did not have the minimum number of operable instrument channels available.

Cause and Corrective Actions

The root cause of the ground fault has been determined to be a failed capacitor in the inverter which was repaired. In addition, conclusions to be dravn from the investigation were that station personnel were not aware that they had antered a limiting ccndition of operation of the PCIS, and did not perform the required action. The cause was an improper isolation due to implications of associated logic circuitry. The long term corrective action is to implement a policy whereby isolations of the D4, DS, D6 and Yl, Y2, Y3 and Y4 breaker panels will be allowed on a single component only basis unless e detailed study is performed and ap-proved by the ORC. The policy hae been incorporated by special order on 9/24/81.

In addition, it I o-been recognized that routine trouble shooting procedures do not fully document the controls presently imposed. Revision to the existing

" Inspection / Trouble Shooting-Electrical Circuits" Procedure, 3.M.3-8 will be initiated to provide that guidance and record thereof. This action will be completed by October 1, 1981.