/01T-0:on 801209,wall Sampling Tests Revealed Omission of Vertical Reinforcing &/Or Accompanying Grout. Caused by Const Activities Not Performed in Accordance W/Design Drawings.Block Walls to Be Tested
ML19340D398
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 12/23/1980
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19340D396 List:
References
LER-80-076-01T, LER-80-76-1T, TAC-42861, TAC-43966, NUDOCS 8012300530
Download: ML19340D398 (2)


LER-1980-076, /01T-0:on 801209,wall Sampling Tests Revealed Omission of Vertical Reinforcing &/Or Accompanying Grout. Caused by Const Activities Not Performed in Accordance W/Design Drawings.Block Walls to Be Tested
Event date:
Report date:
3481980076R01 - NRC Website

text

LICENSEE EVENT REPORT O -CONTiotstocel I

i 1

1 I

l (PLEASE PRINT OR TYPE ALL REQUlHED INFORMATION)

IotillAII,lJlMlFl1l@lolol IninloloIO l-l0 10 l@I 4 ! i l T I ' ! i lh!

l l@

7 3 3 L:cp.:;11 ccOg 14 15 LICENSE NUV6(R 25 26 LiciNSE Tvet JJ 57 6AT 64 CON'T lolil 0% LtJ@l o t s l o l o l o l ' I s l a lGl ' I' l0 lo la in l@l I

I I

I I

l@

8 60 61 CocM ET NUveER 68 69 EVENT oATE 74 75 REPORT oATE 33 EVENT DESCRIPTION AND PROBA8tE CONSEQUENCES h M lAs a result of construction deficiencies viet-en m nen k 1 n c te elle in fu4 9

e,mt_

l g ling of Unit i valls were tested and also found to have construction deficiencies. 'i.e.

I h l portions of vertical reinforcing and/or accompanying trout were emitted. An eneineertnol t o I s l levaluation has determined tha't a total of 69 walls may not meet seismic ooerational I

g l requirements. Of the 69 total, 38 have safety related piping, conduit or eauipment I

[o l 7 l lactached to the wall or ad positioned such that should their failure occur during a l

lotsl Iseismic event, damage to safety related equipment might occur. The remaining 31 1

S$[obt

    1. "c'Eco ' ssc'$$E couroNENT eoDE sus of

'coI[E

^

ioisi I z l z lO l.8J@ LcJ@ l z I z l z I z I z I z l@ L2J@ L7J @

r 8

9 to 13 12 13 15 19 20 sEQutNTIAL OCCURRENCE REPORT Revision LE R/Ro EVENTYEAR REPORT No.

CCO'i TYPE No.

@,Rg,;

18 10 l L--J lo 17 16 I M

lo It i ITI l--I LoJ a

20 22 23 24 28 27 28 29 3J 31 32 K

co P

7-M MoVRs s e if PoM 5.

PL UF e RER 2-IXI@lXt@

12 l@

LZJO 101010101 LJ J@

lN lQ IZ l@

IZ 19 19 l9 l@

3J 34 35 36 37 40 di 42 43 44 47 CAUSE DESC'llPTION AND CORRECTIVE ACTIONS @

l: lollThis occurrence is attributable to construction activities not being performed in l

. g laccordance with design drawings. APCo plans to test the block walls to determine l

l construction deficiencies, obtain design approved corrective action and implement 1

i,;3, lthe design approved corrective action. Additional details will be submitted in a l

t l

g plollow-up to this report.

a0 r

a 9

'sY2E oTuERsTATus @"'sEoEv" oiscovERv oEscRirTroN @

spewER i

80-11 TenH ne I

NA

^ l' U @l IE Bt:11 erin t 15 l [7J@ Io I o lo I@l

' !nv n caTENr A

ftELEASt AMOUNT of ACTivlTY LOCATION oF RELEASE i I s I L2J @o oF RELEASELzJ@l NA I

I I

,ERso~~a Ex,os#Es mcR,, Tion @

~u.ER n,E I

i I 71 101 o I o l@L.zJ@l NA

,ERsoNNEl%UR'IEs oEscRirnoN@

NuweER I

la l l ol o l o l@l NA i

e S 9 11 12 SO

'#$/E "1s^c"'?Tio' '^*" @

NA l

_i I 9 I I z l@l aususu 8012300530

^

uRC usE ONov is3UEo oEscRIPTioN NA l

lllllIlIIIllI$

2101 LZ_jhl 68 69 80 $

s 9 10 NAME OF PREPARER PHON E:

l l

b 3

I LER NO. 80-076/01T-0 4

i Page 2 i

E l

5 I;

I do not fall in the above category. This report is being submitted under Tech.

Spec. 6.9.81.

The health / safety of the public were not affected by this l

1 occurrence.

1 i

l i

r l

l

+9 i

Y e

~ se "M*-

G-met **WF"-'-'-TTTT9*ft"'iu'+W~TWV4rW-"&*7NP v 91" -M N9'S"?**T1r 9*-Pre-1

- M
  • P---9N-**
  • =fr**

'9*=pf M

  • 'N
- W-t-9
- WW'-am*-

Ad

+th1w 5#

-"NW-