M-663-00017A, Revision W03 Page G281 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1101-1974 Building:

==

Description:==

General Floor Area No. 1 Thermal Short #1 (TS1) Data Drawing:

C-OS1311 Member Type:

Beam Member Size:

21 X 155 Comments:

Auxiliary Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A There are no columns in this room.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

02.1_ Temperature_NV.xls (Version 1805.1 )

650 14.5 215 25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

25 22.5 25 A-01 Barrier Type:

Concrete Largest of two large vents used (south corridor)

Barrier Thickness (in):

24 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F) : 163.47 Room Sketch:

SC~-' E r::.nu JJor s}I()WN F{)K(.l.J9~1TY

M-663-00017A, Revision W03 Page G282 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1101-1974 Thermal Short #1 Sketch l>

Go qoo W 2.1 xt6!>

VIEW LDD~ 6/Jt>t:.TII Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B3 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

1120-1974 Building:

General Floor Area No. 2 Thermal Short #1 (TS1) Data C-051231 Beam 24 X 76 Embedded beam, no evaluation required. Sketch & photo for reference only.

Auxiliary Fire Area:

Thermal Short #2 (TS2) Data C-051001 Column 14 X 342 NUREG-1805.FDT Input Data NUREG-1805 FDT:

02.1_ Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

650 Vent Width (ft):

13 Compartment Width (ft):

24.5 Vent Height (ft):

22.5 Compartment Length (ft):

40 Top of Vent from Floor (ft):

13 Compartment Height (ft):

13 Vent

Description:

A-01 Barrier Type:

Concrete One of two vents used which are the same size Barrier Thickness (in):

24 Initial Room Temp. (F):

104 NUREG-1805.FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 246.20 Room Sketch:

WE]

I I

,_,;r: _I

-Some '0 TU'O.. f,JOr 5+\\ov.>N ~" ~*7r

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1120-1974 Thermal Short #1 Sketch VIE.

LDoKtrJ(., E.A<:.I Thermal Short #1 Photo 1 TS r ;

Page G284 of G2B-79 Appendix G2B Sc!.C.TJO/'J A*A Thermal Short #1 Photo 2 No photo required.

M-663-00017 A, Revision W03 Page G285 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1120-1974 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017 A, Revision W03 Page G2B6 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

NUREG-1805 FDT:

1121-1968 Building:

Auxiliary Fire Area:

Access Pit Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data N/A Column 14 X 264 Reviewed beams as part of Room 11 20. Center column reviewed as part of sump area. FP coating approx. 2.5" C-151001 NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

650 Vent Width (ft):

13 Compartment Width (ft):

13.5 Vent Height (ft):

62 Compartment Length (ft):

40 Top of Vent from Floor (ft):

13 Compartment Height (ft):

19 Vent Description :

A-01 Barrier Type:

Concrete One vent, open on three sides (Width = linear length along perimeter of three sides)

Barrier Thickness (in):

24 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 218.80 Room Sketch:

E.LI! \\1. I ~ C..S 1

( t-lT:,)

B~.::!=\\m~ t:=o~ TttiS l:;OOW\\ A~G ~dV\\t:f.:J./a/)

~~ ~c;or'l"l~

u-z.o ~ ll7.l.

M-663-00017A, Revision W03 Page G2B7 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1121-1968 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017 A, Revision W03 Page G288 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1122-1974 Building:

==

Description:==

General Floor Area No. 3 Thermal Short #1 (TS1) Data Drawing:

C-OS1341 Member Type:

Beam Member Size:

36 X 260 Comments:

Auxiliary Fire Area:

Thermal Short #2 (TS2) Data C-1S1001 Column 14 X 342 Building steel under N. hatch is protected by sprinklers in lieu of fireproofing NUREG-1805 FDT Input Data NUREG-1805 FDT:

02.1_Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

650 22.5 80.5 13 Concrete Barrier Thickness (in):

24 Initial Room Temp. (F):

104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

Largest of two large vents used.

NUREG-1805 FDT Results Hot Gas layer Temperature@ 180 minutes (F): 220.98 Room Sketch :

E/J:~ 197'1 f (NTS) o... ~

11171 F

I I

13 22.5 13 A-01

M-663-00017 A, Revision W03 Page G289 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1122-1974 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1122-1974 Thermal Short #2 Sketch A I F-rr---;::t~~;..d,'=-=i IO"J VIeW L.Aolt:tA/14 N61':T'H Page G2810 of G28-79 Appendix G2B WI_. X34(

sc:c. T1okl A* A Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

1130-1974 Building:

==

Description:==

North Corridor Thermal Short #1 (TS1) Data Drawing:

C-081321 Member Type:

Beam Member Size:

16 X 36 Comments:

Page G2B 11 of G28-79 Appendix G2B Auxiliary Fire Area:

A-01 Thermal Short #2 (TS2) Data N/A N/A No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

02.1_ Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW) :

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

650 13.25 40 25 Concrete 24 Initial Room Temp. (F):

104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

25 13.25 25 One of two vents used of equal size. Max Temp.

of 104 entered due all other open adjacent rooms, not in USAR Table 3.11 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 225.78 Room Sketch:

a.r.;y. 197+'

NT""?

M-663-00017A, Revision W03 Page G2B12 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1130-1974 Thermal Short #1 Sketch SeC. fi()AJ A - ~

Loo~ t t-.IG !O. A!.T Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2813 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1202-1988 Building:

Auxiliary Fire Area:

A-01

==

Description:==

Access Area B & Chiller Surge Tank Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS1331 C-OS1002 Member Type:

Beam Column Member Size:

16 X 36 14 X 314 Comments:

Additional attachments in close proximity.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 14 37.5 11 Concrete 24 96 Vent Width (ft):

Vent Height (ft) :

Top of Vent from Floor (ft):

Vent Description :

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 303.33 Room Sketch:

G.I..S'I11 7t*~ 11"'

( u r<r)

I)OU~


~~------~~~ ~ \\~1 11 15.5 11

M-663-00017A, Revision W03 Page G2814 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1202-1988 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data 1202-1988 Thermal Short #2 Sketch 19" I

Page G2815 of G28-79 Appendix G2B Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017 A, Revision W03 Page G2816 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1117-1974 Building:

Auxiliary Fire Area:

==

Description:==

Boric Acid Tank Room A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

C-OS1421 Beam 27 X 84 N/A N/A N/A Comments:

Additional 4" W shape in close proximity.

There are no columns in this room.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 19.5 225 51 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

31 19.5 51 Barrier Type:

Concrete Natural air movement from transfer grilles Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 191.12 Room Sketch:

o P£ t

eQ:Irr\\

N 1

I'-'~

~--------~----------------~ -~(~

' 1117 l A-03

M-663-00017 A, Revision W03 Page G2817 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1117-1974 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

1301-2000 Building:

==

Description:==

Corridor No. 1 Thermal Short #1 (TS1) Data Drawing:

C-1 8141 1 Member Type:

Beam Member Size:

21 X 62 Comments:

Page G2B18 of G2B-79 Appendix G2B Auxiliary Fire Area:

A-08 Thermal Short #2 (TS2) Data N/A N/A N/A No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

02.1_ Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

650 Vent Width (ft):

25 Compartment Width (ft):

14.5 Vent Height (ft) :

14.5 Compartment Length (ft):

215 Top of Vent from Floor (ft):

25 Compartment Height (ft):

25 Vent

Description:

Barrier Type:

Concrete One of two large vents of equal size used (North Corridor)

Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 172.58 Room Sketch:

- DCD ~ 11ol "l.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1301-2000 Thermal Short #1 Sketch I *. t..

~

~

Ll

~

1 ur*

  • a.' <J *
  • t>

..q* ft>.Bt:

~'i'L C.Ro\\.5 m.,,.1a (T'O)

W 1..1 X t.. l (o TI<:Ai

~I'T VIe~ o0/4.1/Jf.. Ncf<TII 3"x a**

TU~(; ~TL C "~"'<'P)

~ ~

Page G2819 of G2B-79 Appendix G2B Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

1314-2000 Building:

==

Description:==

Corridor No. 3 Thermal Short #1 (TS1) Data Drawing:

C-1S1411 Member Type:

Beam Member Size:

27 X 84 Comments:

Page G2820 of G28-79 Appendix G2B Auxiliary Fire Area :

A-08 Thermal Short #2 (TS2) Data C-OS1002 Column 14 X 228 Large area caused by 2 ea. Tube steel orientated across column.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

02.1_ Temperature_NV.xls (Version 1805.1) 650 20 121 25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft) :

Vent

Description:

25 33 25 Barrier Type:

Concrete Largest opening vent used of two large openings.

Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 164.57 Room Sketch:

(O>ITA IIJ Me:: NT

M-663-00017 A. Revision W03 Page G2821 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1314-2000 Thermal Short #1 Sketch w Z.7 )( 94 SI!LT lO.J A. - lt.

Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data 1314-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 IO"Tu~5Tl.

~I!! (T'1l)

Page G2B22 of G2B-79 Appendix G2B Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2823 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1315-2000 Building:

Auxiliary Fire Area:

A-08

==

Description:==

Ctmt Spray Additive Tank Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS1421 Member Type:

Beam Member Size:

24 X 84 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

C-OS1 002 Column 14 X 398 Additional attachments in close proximity.

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 13 21.5 25 Concrete 24 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 FDT Results 7.5 3.5 7.5 Hot Gas Layer Temperature@ 180 minutes (F): 500.83 Room Sketch:

~

~.

1-------------. -

1~

~~ I t' r31""' I

M-663-00017 A, Revision W03 Page G2824 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1315-2000 Thermal Short #1 Sketch l>lOO I

~I.A* :.TI'NT Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B25 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1315-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B26 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1318-2000 Building:

Auxiliary Fire Area:

A-08

==

Description:==

Valve Compartment Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-05 142 1 Member Type:

Beam Member Size:

33 X 11 8 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

N/A N/A N/A No columns.

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 17 21.5 25 Concrete 36 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 481.16 Room Sketch:

L o~tl Itt~~ e llll RRCA I '313

[ITil.

I~

-- ~--~-~------

~ '

~

a *

~R, I 3/81J

' iJ

  • 0 :1-
    • -.,- - --- -----.-.:l-.-.,........ lt:::=/= 'f* *.

6: * * *

  • AI.

Q>

u of *.

  • ~

7.5 3.5 7.5

M-663-00017A, Revision W03 Page G2B27 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1318-2000 Thermal Short #1 Sketch W 3.3X liB

~-- 3o'~

~U.710f..l A-A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2B28 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1320-2000 Building:

Auxiliary Fire Area:

==

Description:==

Corridor No. 4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-08 1441 Member Type:

Beam Member Size:

16 X 40 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft) :

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

C-1 81 001 Column 14 X 264 Building steel under N. hatch is protected by sprinklers in lieu of fireproofing.

NUREG-1805 FDT Input Data 02.1_Temperature_NV.xls (Version 1805.1) 650 Vent Width (ft):

25 36 Vent Height (ft):

14 53 Top of Vent from Floor (ft):

25 25 Vent

Description:

Concrete Largets of two large opening used 24 104 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 194.13 Room Sketch:

A-08

M-663-00017A, Revision W03 Page G2829 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1320-2000 Thermal Short #1 Sketch m

I I

St:C.T IO t.l A.-A-Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B30 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1320-2000 Thermal Short #2 Sketch

- W~I 4"4

~... b\\ A,/~7 sm.. "' ~<>e I

D-4~*7'('

...J...:.:,.i_

SU'ilt>IJ A -A Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2B31 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1401-2026 Building:

Auxiliary Fire Area:

A-16

==

Description:==

Component Cooling Pump & Heat Exch Area 8 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-1 51511 C-051002 Member Type:

Beam Column Member Size:

24 X 76 14 X 158 Comments:

Tube steel is orientated to cause 144 square Inches of unprotected steel.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 36.75 66 20 Concrete 12 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor {ft):

Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 176.12 Room Sketch:

£U:1'Alt~loJ zou.'

(o\\IT<o)

I l

L_--~~~~~--~~

jtc..o'S j 20 36.75 20

M-663-00017A, Revision W03 Page G2832 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1401-2026 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2B33 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1401-2026 Thermal Short #2 Sketch

.1f 1\\10 OM l Sl4 1'-il-r-44 sq 1t-.1 om*~ScO'-)

Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2B34 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1402-2026 Building:

Auxiliary Fire Area:

==

Description:==

Corridor No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

C-1 S1511 Beam 24 X 68 N/A N/A N/A Comments:

Additional angle steel within close proximity.

No column in this room.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 15 41 20 Concrete 24 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 238.98 Room Sketch:

~--------~----- ---~------ --

I!

I II I

I 20 14.5 20 A-16

M-663-00017 A, Revision W03 Page G2835 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1402-2026 Thermal Short #1 Sketch 0

. Q,

- b

  • l>

6

17.

Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2836 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1406-2026 Building:

Auxiliary Fire Area:

A-16

==

Description:==

Component Cooling Pump & Heat Exch Area A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-1S1521 C-081002 Member Type:

Beam Column Member Size:

27 X 84 14 X 228 Comments:

Additional items within close proximity.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 26 61 20 Concrete Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent Description :

Room (vent) is open on two sides Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 170.15 Room Sketch:

20 76.5 20

M-663-00017A, Revision W03 Page G2837 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1406-2026 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1406-2026 Thermal Short #2 Sketch Thermal Short #2 Photo 1 ITS\\

\\ 2 I SC!C.TION A-A Page G2838 of G2B-79 Appendix G2B Thermal Short #2 Photo 2

M-663-00017 A, Revision W03 Page G2839 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1408-2026 Building:

Auxiliary Fire Area:

==

Description:==

Corridor No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-1 81541 Member Type:

Beam Member Size:

21 X 55 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

C-1 8 1 001 Column 14 X 158 Building steel under N. hatch is protected by sprinklers in lieu of fireproofing per drawing.

NUREG-1805 FDT Input Data 02.1 _ Temperature_NV.xls (Version 1805.1) 650 18 215 20 Concrete 12 104 Vent Width (ft) :

Vent Height (ft):

Top of Vent from Floor (ft) :

Vent

Description:

NUREG-1805 FDT Results 20 88.5 20 Hot Gas Layer Temperature @ 180 minutes (F): 147.76 Room Sketch:

A-16

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1408-2026 Thermal Short #1 Sketch

-~**

A *.

l:l

. O * *.

t

==

l D * *

{.) *. tl

. -~ -

. b,*

Thermal Short #1 Photo 1 l.>

I>*

p S2.C.T!OIJ A* A Page G2840 of G28-79 Appendix G2B

]

Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2B41 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1408-2026 Thermal Short #2 Sketch Sfc.no~ A.-A I

158 Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2B42 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1504-2047 Building:

Auxiliary Fire Area:

A-19

==

Description:==

Ctmt Purge Exhaust & Mech Equip Rm B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-081631 C-081002 Member Type:

Beam Column Member Size:

24 X 68 14 X 184 Comments:

Additional attachments in close proximity.

Additional attachments in close proximity (53" angle supports).

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 39.75 89 25.25 Concrete 12 104 Vent Width (ft) :

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 179.58 Room Sketch:

I N IIJ I

25.25 14 25.25

M-663-00017A, Revision W03 Page G2B43 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1504-2047 Thermal Short #1 Sketch VIi Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1504-2047 Thermal Short #2 Sketch

~;o;:==-;;jl( ku.*

  • 1

):::!:!:==~P4 " :-:-:-'::!

r===ll=l*= *.-.. }

1----+l---- !

I

'E===~.,.-.-.::.:1 1

I J===:t:j ~:. ::-:::TI 1----foi -* --t I Thermal Short #2 Photo 1 Page G2844 of G28-79 Appendix G2B Si!.C..TI6JJ A* A Thermal Short #2 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B45 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1506-2047 Building:

Auxiliary Fire Area:

A-19

==

Description:==

Ctmt Purge Supply Air Handling Unit A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-1 S1641 C-1S1 001 Member Type:

Beam Column Member Size:

24 X 76 14 X 370 Comments:

Monorail determined to be not worse case, spacers and fire proofing insulate attachment configuration.

Orientation of tube steel causes 56 plus 16 square inches of unprotected surface.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F) :

NUREG-1805 FDT Input Data 02.1_Temperature_NV.xls (Version 1805.1) 650 48 94 25.25 Concrete 12 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 175.17 Room Sketch:

~"\\~!: ~n:EL N 6T

&to'/IJJ ~

(.t.l/117)"

25.25 14 25.25

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1506-2047 Thermal Short #1 Sketch w~ x 1G.

Thermal Short #1 Photo 1 Page G2846 of G28-79 Appendix G2B Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B47 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1506-2047 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2848 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1513-2047 Building:

Auxiliary Fire Area:

==

Description:==

Control Bldg Vent Supply A/C Unit Rm Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-081621 C-08 1002 Member Type:

Beam Column Member Size:

24 X 76 14 X 184 Comments:

Additional strut connection in close proximity.

Additional angle in close proximity.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartme.nt Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 35 15 25.25 Concrete 12 104 Vent Width (ft):

Vent Height (ft) :

Top of Vent from Floor (ft):

Vent Description :

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 222.58 Room Sketch:

A 15"1~1 v

~

I

~

I

-/ I

~

~ ~

'I """II r--;;.o.<<-----------.j-I I

II

'I" -'1

~~-..._JD_* ---- ~t7' El£V. Zo47. J 1

IVT5 1-OPe.. TO b\\ I'SO'o 25.25 15 25.25 A-19

M-663-00017 A, Revision W03 Page G2B49 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1513-2047 Thermal Short #1 Sketch

<':>~CTICW A-A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2850 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1513-2047 Thermal Short #2 Sketch VIEW L.o6 t 1J

':>EC.T!ON A-A Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2851 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1502-2047 Auxiliary Fire Area:

A-20

==

Description:==

Component Cooling Water Surge Tank Area B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-051631 N/A Member Type :

Beam N/A Member Size:

21 X 55 N/A Comments:

Monorail attachment, only 1 point is No columns.

required to be evaluated.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft) :

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 39.75 16 25.25 Concrete 12 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 'FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 219.21 Room Sketch:

I ~

£LeY lt:-4-7 Nrs 25.25 14 25.25

M-663-00017 A. Revision W03 Page G2852 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1502-2047 Thermal Short #1 Sketch I)

W'l.l-1.. 55 t"'P ""'0 ('0.\\ l..

S 2.4 X 00 VJi.W Lool<tNI. WGS7 Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B53 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1503-2047 Building:

Auxiliary Fire Area:

A-20

==

Description:==

Component Cooling Water Surge Tank Area A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

C-081631 Beam 21 X 55 N/A N/A N/A Comments:

Monorail attachment, only 1 point is required to be evaluated.

No columns.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (tt):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_ Temperature _NV.xis (Version 1805.1) 650 32 15 25.25 Concrete 12 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 228.21 Room Sketch:

LEV.

Nrs

\\

l1.;o~l )

/

N.....-

25.25 14 25.25

M-663-00017A, Revision W03 Page G2854 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1503-2047 Thermal Short #1 Sketch stCTtot.J A-A VIEW LooKII.JCi W~T Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2855 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1505-2047 Building:

Auxiliary Fire Area:

==

Description:==

Corridor Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS1631 Member Type:

Beam Member Size:

24 X 76 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft) :

N/A N/A N/A No exposed column.

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 10 9

25.25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent Description :

25.25 9

25.25 A-20 Barrier Type:

Barrier Thickness (in):

Concrete 12 One of two large vent (equal in size) was used.

Temp not in USAR Table 3.11, used adjacent rooms Temp that are open to this room.

Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 317.54 Room Sketch:

~Lt Z047 1

NT'S

o.

! ::p

t-_~-------'1 ::. : -

~ ---

OPc!..l 'TO ~001011 1'1)07

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1505-2047 Thermal Short #1 Sketch 7~

Thermal Short #1 Photo 1 W Z4X7~

Page G2856 of G2B-79 Appendix G2B 5~5.. X~

~

8E S Tt;1;1.

Sc:c..T 1 o t--1 A *A Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B57 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1507-2047 Building:

Auxiliary Fire Area:

A-20

==

Description:==

Personnel Hatch Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS1631 C-1 S1001 Member Type:

Beam Column Member Size:

24 X 75 14 X 158 Comments:

Additional attachments in close proximity.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

02. 1_ Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

650 Vent Width (ft) :

Compartment Width (ft):

Vent Height (ft):

Compartment Length (ft):

32 33 Top of Vent from Floor (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

25.25 Concrete 12 104 Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 223.79 Room Sketch:

cLV. 2o47 I

25.25 9

25.25

M-663-00017 A, Revision W03 Page G2858 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1507-2047 Thermal Short #1 Sketch Thermal Short #1 Photo 1 I I

~

Sc~-~~T~

Io--~.-----------~

c."'~"' l,'(~l"f Ul""'7)

Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2859 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1507-2047 Thermal Short #2 Sketch St:ci'ION A *A VIEW LIXJ~IN~ liAST Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2860 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1508-2047 Building:

Auxiliary Fire Area:

Description :

Drawing:

Main Steam Isolation Valve Rm No.

Thermal Short #1 (TS1) Data C-1 S1452 Thermal Short #2 (TS2) Data N/A Member Type:

Beam Member Size:

30 X 99 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

N/A N/A No columns.

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 Vent Width (ft):

22 35 48 Vent Height (ft):

Top of Vent from Floor (ft):

Vent Description :

32 35 48 Barrier Type:

Concrete Open to room below and at Missile Sheilds Barrier Thickness (in):

24 Initial Room Temp. (F):

120 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 184.77 Room Sketch:

S~.(J10 "'"AJO llAtL A-23

M-663-00017A, Revision W03 Page G2B61 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1508-2047 Thermal Short #1 Sketch i.;'x 1./ ((JII/flt

o/'11# u F Pc:r:ruN r tt ru, IJ7.

~2.41l1Ul

,n N() itoAII.,

St C. T lo IJ A -A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

No photo required.

M-663-00017A, Revision W03 Page G2862 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1509-2047 Building:

Auxiliary Fire Area:

==

Description:==

Main Steam Isolation Valve Rm No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-1S1452 Member Type:

Beam Member Size:

30 X 99 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

N/A N/A N/A No columns.

NUREG-1805 FDT Input Data

02. 1_ Temperature_NV.xls (Version 1805.1) 650 22 35 48 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

32 35 48 Barrier Type:

Concrete Open to room below and at Missile Sheilds Barrier Thickness (in):

24 Initial Room Temp. (F):

120 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 184.77 Room Sketch:

~~-f----------+ /it()AJt> R~'l StqJCtt()

A-23

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1509-2047 Thermal Short #1 Sketch Thermal Short #1 Photo 1 No photo required.

Page G2863 of G28-79

. u 0

6o ~"" :z

~c.- liFFifCTitr!

"111£'""1.

s-t4.J( t'Z.o St:LTibN A-A Thermal Short #1 Photo 2 Appendix G2B No photo required.

M-663-00017A, Revision W03 Page G2864 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1324-2000 Building:

Auxiliary Fire Area:

==

Description:==

Feedwater Pump Valve Compartment No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

C-1S1352 Beam 14 X 34 N/A N/A N/A Comments:

Additional attachments in close proximity (3" x 1/4" angle).

No columns.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 10 10 12 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

3.5 3.5 10 Barrier Type:

Concrete Vent at ceiling to Room 1304 (3.5 X 3.5)

Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 975.88 Room Sketch:

c;a-v.looo' Nts N IJ A

I3Z41 r---.1.---

---r v El ZO<:IO' A-29

M-663-00017 A, Revision W03 Page G2B65 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1324-2000 Thermal Short #1 Sketch S.E C. T ION Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2866 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1330-2000 Building:

Auxiliary Fire Area:

A-30

==

Description:==

Feedwater Pump Valve Compartment No. 4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

C-1 S1352 Beam 8 X 17 N/A N/A N/A Comments:

Column encapsulated in concrete, no issues w/column.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 Vent Width (ft):

10 Vent Height (ft):

10 Top of Vent from Floor (ft):

12 Vent

Description:

3.5 3.5 10 Barrier Type:

Concrete Open at ceiling (3.5 X 3.5) Hatchway Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 975.88 Room Sketch:

Elr:.v. z oeo '

J')r>

l~ool

.v

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data 1330-2000 Thermal Short #1 Sketch Loo IN'\\ No1!nl Thermal Short #1 Photo 1

~

p._. --~,*. 0 t

  • ,Cl:l *

~

W£$Xt7 Page G2867 of G2B-79 Appendix G2B Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type :

Member Size:

Comments:

1206-1989 Building:

Pipe Chase Thermal Short #1 (TS1) Data C-1 81352 Beam 14 X 34 Additional attachments in close proximity.

Page G2868 of G2B-79 Appendix G2B Auxiliary Fire Area:

A-33 Thermal Short #2 (TS2) Data C-1 S 1001 Column 14 X 111 NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

02.1_ Temperature_NV.xls (Version 1805.1) 650 23 38 10 Concrete 24 Vent Width (ft):

10 Vent Height (ft):

12 Top of Vent from Floor (ft):

10 Vent

Description:

Lragest of two large vent openings used. Not in USAR Table 3.11, used 1207 Temp because it is open to 1207 and directly adjacent.

Initial Room Temp. (F):

106 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 316.93 Room Sketch:

I

\\~,i\\~

~I I

I I

M-663-00017A, Revision W03 Page G2B69 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1206-1989 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2B70 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1206-1989 Thermal Short #2 Sketch L 00~1 f.J'-> Sou It StC.TIC A-A Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2B71 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1207-1989 Building:

Auxiliary Fire Area:

==

Description:==

Pipe Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-181352 C-1 8 1001 Member Type:

Beam Column Member Size:

18 X 40 14 X 111 Comments:

Additional attachments in close proximity.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height {ft):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 23 38 10 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

10 12 10 Barrier Type:

Concrete Lragest of two large vent openings used.

Barrier Thickness (in):

24 Initial Room Temp. (F):

106 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes {F): 316.93 Room Sketch :

A-33

M-663-00017A, Revision W03 Page G2872 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1207-1989 Thermal Short #1 Sketch w-18JI. 40

'S~t: flO// A A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2873 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1207-1989 Thermal Short #2 Sketch AA Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2B74 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

3401-2016 Building:

Control Fire Area:

C-35

==

Description:==

Corridor No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-053511 N/A Member Type:

Beam N/A Member Size:

24 X 68 N/A Comments:

No columns.

NUREG-1805 FDT Input Data NU REG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

02.1_ Temperature_NV.xls (Version 1805.1) 650 6

86.5 15.25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

15.25 11 15.25 Barrier Type:

Block Temp. not in USAR Table 3.11, used all adacent room temp of 90 Barrier Thickness (in):

8 Initial Room Temp. (F):

90 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 276.82 Room Sketch:

OPe.,,

I

  • *~

M-663-00017A, Revision W03 Page G2875 of G28-79 Structural Steel Fireproofing Data Appendix G2B 3401-2016 Thermal Short #1 Sketch tJ, rs L

St:.c.ftON A-A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3406-2016 Building:

Corridor No. 2 Thermal Short #1 (TS1) Data C-OS3511 Beam 24 X 68 Additional Items in close proximity. (6" long x 1/2" Plate).

Page G2B76 of G2B-79 Appendix G2B Control Fire Area:

C-35 Thermal Short #2 (TS2) Data C-OS3001 Column 14 X 426 Column embedded on both sides. ALBI is 2-1 /2" thick minimum due to finish requirements.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

02.1_ Temperature_NV.xls (Version 1805.1) 650 11 20.75 15.25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

15.25 11 15.25 Barrier Type:

Block Temp. not in USAR Table 3.11, used all adacent room temp of 90 Barrier Thickness (in):

8 Initial Room Temp. (F):

90 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 357.53 Room Sketch:

M-663-00017A, Revision W03 Page G2877 of G28-79 Structural Steel Fireproofing Data Appendix G2B 3406-2016 Thermal Short #1 Sketch S.c.TIO A -fl..

Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3412-2016 Building:

==

Description:==

Emergency Shower & Eyewash Area Thermal Short #1 (TS 1) Data Drawing:

C-OS3511 Member Type:

Beam Member Size:

24 X 68 Comments:

Page G2878 of G28-79 Appendix G2B Control Fire Area:

C-35 Thermal Short #2 (TS2) Data N/A N/A N/A No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

02.1_ Temperature_NV.xls (Version 1805.1) 650 11 17 15.25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

1525 11 15.25 Barrier Type:

Block Temp. not in USAR Table 3.11, used all ada cent room temp of 90 Barrier Thickness (in):

8 Initial Room Temp. (F):

90 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 373.15 Room Sketch:

ww*}-

t:u z.o16.

(~)

c

M-663-00017A, Revision W03 Page G2879 of G28-79 Structural Steel Fireproofing Data Appendix G2B 3412-2016 Thermal Short #1 Sketch