LER 88-001-01:on 880211,improper Anchoring of Three Diesel Generator Day Tanks to Supporting Steel Beam Foundation Identified.Caused by Inadequate Design & Design Review. Tanks Weld Anchored to Steel Beam foundation.W/880518 Ltr
ML18093A840
Person / Time
Site: Salem PSEG icon.png
Issue date: 05/18/1988
From: Pollack M, Zupko J
Public Service Enterprise Group
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
LER-88-001, LER-88-1, NUDOCS 8805310116
Download: ML18093A840 (4)


Text

.* ' * *.-*.* < ::-_.. * ,.'. ..:.: ~ ** ~ .: ' ..... :,* ... ,,._** ....... * . ,_. ~ .... :

NllC 19-831 Fonn- U.I. NUCLEAll llEQULATOllY CC...*ION

"""'OVED <Mlle NO. 311!0-4104 LICENSEE EVENT REPORT (LER)

PACILITY NAMI Ill DOCKET ,._Ill 121 I r-~E l;ill Salem Generating Station - Unit 1 0 I 5 I 0 I 0 I 0 I 2 17 12 I 1 OF 0 I3 TITLE 141 Diesel Generator Dav Tanks Do Not Meet Seismic Criteria Due To' Inadequate Desian & Review IVINT DATI Ill Liii NU..E 11 111 llEPOllT DATE 171 OTHEll FACILITIU INVOLVEO Ill FACILITY NAMIE8 DOCKET NUMIERISI 01&1010101 I I o I 2 i I i a s s I s - oI ol 1 o I 1 oIs i Ia al a Ol'lllATING THll lll!POllT 11 IU. .ITTID P'UlllUANT TO THI! llEQUlllEMENTI OF 10 CPll §: (Chedt OM or,,,_ of rite followiflf) 1111 1---MOD-*...1*_*_

l'OWlll I __,_s'-+---I 1111.4021111 1111.-..1111111 -- 20.4111101 I0.31lcll11 --x I0.731.112111*1 ll0.7ac.1121M -- 7:1.71*1 7a.71lol LIVIL -

1101 0 I 0I0 1111.ac.1111111 10.-1e1121

- **7aClll211ril OTHEll (5-lfo/ In AbllNct

-=

t>>IO'# er.d In "Tel!r, NRC Fenn llll.al1111111111 20.*c.111111w1 l!0.73411121111 I0.734111211MI -- IO.nt.11211wlllllAI

  • .7ac.11211wlillll 36tlAJ 20.*C.1111M I0.7SCllC211Hll ICl.71'911allal LICENSEE CONTACT FOii THIS LEll 1121 NAME TELEPHONE NUMIER AREA.CODI!

M. J. Pollack - LER Coordinator 61 0 I 9 31 3 I 9 I - 1 4 I 0 12 I 2 COM'LETI ONE LINE FOii EACH COMl'ONENT FAILUlll DllClllllD IN THll llll'OllT 1111 CAUSE SYSTEM COMPONENT MANUFAC.

TUR ER

~~~::g;e l!!!!l!!!!ll!!ll!l!!!!!ll!!ll!lllll!!l!!l!!!ll!!!!!I ~use IYll'TEM COMPONENT MANUFAC.

TUllER

  • =.-:." * .

I I I I I I I I I I I I I I I I I I I I I I I I I I I I IUPl'LIMINTAL llEPOllT IXPICTID 1141 MONTH DAY ¥JAR EXPECTED MYES (ff ..... ~ EX,..CT'IED SU*MIS$10N DATE}

AISTllACT fUmlr 111 t400 -

  • I.&, ~1-ly fl'- ,,,,.._. rr-lrrH lilMIJ kl NO 1111 SUIMISllO.N QATE 11111 I I I On February 11, 1988 at 1800 hours0.0208 days <br />0.5 hours <br />0.00298 weeks <br />6.849e-4 months <br />, PSE&G engineering personnel identified a deficiency associated with the Salem Unit.1 Diesel Generator (D/G) Day Tanks {DC}. The three tanks were not properly anchored to the supporting steel beam foundation. Had a seismic event occurred, the tanks could have shifted possibly resulting .in the stoppage of fuel oil flow to the respective D/G {EK}. The root cause of this event has been attributed to inadequate design .and design review. The Day Tanks have apparently been in the as found condition since installation. A review of the historical documentation (e.g.,

prints and specifications} re~ealed that anchoring of the Day Tanks was not specified. Upon discovery of the Salem Unit 1 Day Tank design concern, Salem Unit 2's Day Tanks were inspected. The Unit 2 tanks were found to be properly anchored. The Unit 1 Day Tanks were weld anchored to the wide flange steel beam foundation on February 12, .1988 in accordance with seismic design criteria. Also, the Day Tank civil.

drawings have been updated to identify the anchor requirements.

NllC,,_ . .

IM31

LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem Generating Station DOCKET NUMBER LER NUMBER PAGE Unit 1 5000272 88-001-01 2 of 3 PLANT AND SYSTEM ID~N_'J;'IFICATION:

Westinghouse - Pressurized Water Reactor Energy Industry Identification System (EIIS) codes are identified in the text as f xx}

IDENTIFICATION OF OCCURRENCE:

Diesel Generator Day Tanks Do Not Meet Seismic Criteria Event Date: 02/11/88 Report Date: 05/18/88 This report was initiated by Incident Report No.88-048.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 5 Reactor Power 0% - Unit Load 0 MWe DESCRIPTION OF OCCURRENCE:

On February 11, 1988 at 1800 hours0.0208 days <br />0.5 hours <br />0.00298 weeks <br />6.849e-4 months <br />, PSE&G engineering personnel identified a deficiency associated with the Salem Unit 1 Diesel Generator (D/G) Day Tanks {DC}. The three tanks were not properly anchored to the supporting steel beam foundation. Had a seismic event occurred, the tanks could have shifted possibly resulting in the stoppage of fuel oil flow to the respective D/G {EK}.

The Nuclear Regulatory Commission was notified at 1845 hours0.0214 days <br />0.513 hours <br />0.00305 weeks <br />7.020225e-4 months <br /> on February 11, 1988 in accordance with Code of Federal Regulations 10CFR 50.72(b) (2) (iii) (D).

APPARENT CAUSE OF OCCURRENCE:

.The root cause of this event has beeri attributed to inadequate design and design review.

The Day Tanks have apparently been in the as found condition since installation. A review of the historical documentation {e.g., prints and specifications) revealed that anchoring of the Day Tanks was not specified.

ANALYSIS OF OCCURRENCE:

There are three (3) D/G Day Tanks, one per D/G. They contain the supply of fuel oil for their respective D/G. If a design base seismic event occurred with the tanks not properly anchored, the Day Tanks could have shifted resulting in the possible discontinuation of fuel oil flow to the D/G's thereby rendering all three D/G's inoperable.

The D/G's are required to be available to mitigate the consequences of a loss of off-site AC power during normal and accident conditions.

.***. _*:. .*. ~ '* ...... ~ _1.,. ****"JO . .,_-., :....*

LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Salem Generating Station DOCKET NUMBER LER NUMBER PAGE U_n~i_t~l--~~~~~~~~~~~~~5~0_0_0_2_7_2~~~~~8~8_-~0_0_l_-_0_1~~~--=3 of 3 ANALYSIS OF OCCURRENCE: (cont'd)

Since the Day Tanks condition could have prevented the fulfillment of the D/G's from operating during a design basis event this event is reportable to the Nuclear Regulatory Commission in accordance with Code of Federal Regulations 10CFR 50.73 (a) (2) (v) (D).

CORRECTIVE ACTION:

Upon discovery of the Salem Unit 1 Day Tank design concern, Salem Unit 2's Day Tanks were inspected. The Unit 2 tanks were found to be properly anchored.

On February 12, 1988 weld anchoring of the Unit 1 Day Tanks to the wide flange steel beam foundation in accordance with seismic design criteria was completed and the D/G's were declared operable.

The PSE&G Day Tank civil drawings have been updated to address the anchor requirements.

Ge&&i tt+/-r9-.

Salem Operations MJP:pc SORC Mtg.88-045

e PS~G Public Service Elect1*ic and Gas Company P.O. Box E Hancocks Bridge, New Jersey 08038 Salem Generating Station May 18, 1988 U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555

Dear Sir:

SALEM GENERATING STATION LICENSE NO. DPR-70 DOCKET NO. 50-272 UNIT NO. 1 LICENSEE EVENT REPORT 88-001-01~ SUPPLEMENT This Supplemental Licensee Event Report is being submitted pursuant to the requirements of 10CFR 50.73(c). The Apparent Cause of Occurrence Section and the Corrective Action Section have peen updated. The original LER did not specify the apparent root cause due to continuing investigation(s) associated with the described event. This supplement identifies the apparent root cause based upon the results of the completed investigation(s). Additionally, a corrective action has been added.

Sincerely yours, General Manager-Salem Operations MJP:pc Distribution The Energy People