Report Number:
78-82/03L Report Date:
01/22/79 Occurrence Date:
12-28-78 Facility:
Salem Generating Station Public Service Electric & Gas Company Hancock's Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:
Plant Vent Flow Recorder Inoperable CONDITIONS PRIOR TO OCCURRENCE:
Operational Mode 1 Reactor Power 99%
DESCRIPTION OF OCCURRENCE:
At 1000 hours0.0116 days <br />0.278 hours <br />0.00165 weeks <br />3.805e-4 months <br />, a Control Room operator observed a zero flow indication on the plant vent recorder.
Action as required by Environmental Technical Specification 2.3.4.b was implemented.
The recorder was returned to service at 1750 hours0.0203 days <br />0.486 hours <br />0.00289 weeks <br />6.65875e-4 months <br /> and inservice tests were run to verify operability.
DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:
The cause of this occurrence was frozen condensation in the flow traris-mi tter sensing line due to installed temporary heat tracing being de-energized.
-~* ANALYSIS OF OCCURRENCE:
Environmental Technical Specification 2.3.4.b requires that gaseous releases to the environment, except from the Turbine Building ventilation exhaust and as noted in Specification 2.3.4.c, shall be continuously monitored for gross radioactivity and the flow continuously measured and recorded.
Whenever these monitors are inoperable, grab samples shall be taken and analyzed daily for gross radioactivity.
If these monitors are inoperable for more than seven (7) days, these releases shall be terminated.
The flow recorder was returned to service within eight (8) hours.
The plant vent effluent radiation monitor Rl6 channel was operational throughout this occurrence.
No gaseous releases or contain-ment ventilation occurred during the inoperability time of the flow recorder.
CORRECTION ACTION:
Condensation in the flow transmitter sensing line was blown out and the temporary heat tracing was energized.
A Design Change Request has been initiated to install permanent heat tracing on the sensin.( line.
790.A.26 Od-Q<t)
LER No. 78-82/03L FAILURE DATA:
Not Applicable Prepared by A. W. Kapple Manager salem Gen rating Station SORC Meeting No.
2-79
._ __ -*-**---*---------------- -*--* ***----~.
NRC FOR~~6 (7-7'7'!-
U.S. NUCLEAR REGULATURY COMMISSION 9-tCENSEE EVENT REPORT e
CONTROL BLOCK:._I _..___.__.____.___..l..__.... l CD (Pl.EASE PRINT OR TYPE ALL REQUIRED INFORMATION) 1 6
rn 1 N 1J 1 s 1 G 1 s 11 101 a 1 a 1 _, a 1a.1*a1 o 1 o 1 - 1 o 1 a 101 4 11 11 11 1 1 101. 1 10 7
8 9
LICENSEE CODE 14 15 LICENSE NUMBER 25 26 LICENSE TYPE
- JO 57 CAT 58 CON'T
[§:IQ 7
8
~;:~~~ L1J© I. o I s I o ! o I o I 2 ! 7 I 2 IC?)! 1 12 I 2 I B j 7 I s lG) I o 11 ! 2 I 2 I 7 I 9 I G) 60 61 DOCKET NUMBER 68 69 EVENT DATE 74 75 REPORT DATE 80 EVENT DESCRIPTION AND PROBABLE CONSEQUENCES@
. ())2] I During normal operation, a Control Operator noticed a zero flow indication on the plant vent recorder.
Action required by ETS 2.3.4.b was implemented.
The recorder was returned to service within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
The plant vent effluent radiation monitor Rl6 channel was operable throughout this occurrence.
No gaseous releases or containment ven-E2.I?J tilation was conducted during the recorders inope~ability. This is th3
_,. ()))) I first occurrence of this type.
8 9 80 [ITIJ 7
8 SYSTEM CODE IB IB I@
9 10 I:':::\\
LERtRO LVENTYEAR
\\:..:,) REPORT I 7 I 8 I NUMBER 21 22
CAUSE
CAUSE CODE SUBCODE COMPONENT CODE lli.J@ ~@ Ir IN Is tr /R ju I@
11 12 lJ 18 SEQUENTIAL OCCURRENCE REPORT NO.
CODE I I I o I s 12 I I /I
- I o I 3 I 2J 24 26 27 28 29 COMP.
SUBCODE
~@
19 REPORT TYPE UJ 30 VALVE SUBCODE
~@
20 l=1 31 ACTION FUTURE TAKEN ACTION ON PLANT METHOD HOURS SUBMITTED FORM :SUB.
EFFECT SHUTDOWN
~
ATTACHMENT NPRD-4 W@W@ W W 10 10101 I ~@ ~@
PRIME COMP.
SUPPLIER
~@)
33 34 35 36 37 40 41.
42 CAUSE DES.CRIPTION AND CORRECTIVE ACTIONS @
43 I Frozen condensation in the transmitter sensing lines due to de-energized temporary heat tracing caused this occurrence.
REVISION NC. w 32 COMPONENT MANUFACTURER IL 11 I 3 !o I@
44 47 The lines were blown down and the heat tracing was energized.
Inservice tests o::IIl I verified operability.
rrm 7.
8 9
FACILITY tJQ\\
STATUS
% POWER OTHER STATUS \\:::J rrm w 1o19 1 91@1 N/A 7
8 9
10 12 1'3 ___
A~V~ ~ITT~
Q RELEASED OF RELEASE AMOUNT OF ACTIVITY ~
[ill] LlJ@ W@I N/A 7.
8 9
10 11 80 METHOD OF DISCOVERY DESCRIPTION DISCOVERY
&.J@I Operator observation 44 45 46 BO LOCATION OF RELEASE @
NiA 44 45 80 PERSONNEL EXPOSURES t:;;:;-.,
NUMBER
~TYPE~
DESCRIPTION
ITITI I a I a I a lW~ ___
N
__ /_A_. _____________________
___,j 7
8 9
11 12 13 PERSONNEL INJURIES t:":'\\
NUMBER DESCRIPTION~
GJI] I ol al ol@).__ _____ -=N~A=-------------------------------------------------------~
7 8
9 11 12 LOSS OF OR DAMAGE TO FACI LITV ~
TYPE
DESCRIPTION
'::::;J filTI LIJ@)
N A 1
a 9 1~0~---------------'=-.;;.;;..------------------------------------------------------------.Jso
. PUBLICITY Q\\
ISSUED/,;".;\\ DESCRIPTION~
ITTI] L.z.J~~I ~-----------~N/~A~-----------------------------------J I I I I I I I I I I I !J 7
8 9
10 68 69 80 so NRC USE ONLY eo NAMEOFPREPARER~~~~-A_. ___ w=--*=--K~a~p~p~l~e~~===:~~~~P~H~ON~E~:~-~(=60=9~)=3=6=5=-=7=0=0=0=Sal===em=*::::::Ext~2S,50
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000272/LER-1978-022, Forwards LER 78-022/01T-0 | Forwards LER 78-022/01T-0 | | | 05000272/LER-1978-022-01, /01T-0 on 780404:Fischer & Porter 10B2496 Transmitters for Coolant Low Flow Monitoring Had High Output Deviation During Seismic Test.Caused by Vibration of Mounting Plate.Design Change Initiated | /01T-0 on 780404:Fischer & Porter 10B2496 Transmitters for Coolant Low Flow Monitoring Had High Output Deviation During Seismic Test.Caused by Vibration of Mounting Plate.Design Change Initiated | | | 05000272/LER-1978-029, Forwards LER 78-029/01X-1 | Forwards LER 78-029/01X-1 | | | 05000272/LER-1978-029-01, /01X-1 on 780610:during Training Startups,Two Power Range Channels Found Inoperable.Caused by Personnel Error in Which Wrong Leads Were Disconnected from Reactivity Computer.Procedures Revised | /01X-1 on 780610:during Training Startups,Two Power Range Channels Found Inoperable.Caused by Personnel Error in Which Wrong Leads Were Disconnected from Reactivity Computer.Procedures Revised | | | 05000272/LER-1978-035-03, /03L-0:on 780630,gas Starting Turbine Relay Operation Caused Loss of Power to Station Power Transformer. Caused by Personnel Error in Preparing Unit for Svc.Operator Reinstructed on Proper Breaker Operation | /03L-0:on 780630,gas Starting Turbine Relay Operation Caused Loss of Power to Station Power Transformer. Caused by Personnel Error in Preparing Unit for Svc.Operator Reinstructed on Proper Breaker Operation | | | 05000272/LER-1978-035, Forwards LER 78-035/03L-0 | Forwards LER 78-035/03L-0 | | | 05000272/LER-1978-043-03, /03L-0 on 780808:during Normal Oper,After 45% Pwr Reduction to Less than 50% for Maint,Reactor Pwr Increased to 51%.Deviation Alarm Would Not Clear & QPTR Was 1.03%.QPTR Was Not Discovered Sooner Because of Alarm Indications | /03L-0 on 780808:during Normal Oper,After 45% Pwr Reduction to Less than 50% for Maint,Reactor Pwr Increased to 51%.Deviation Alarm Would Not Clear & QPTR Was 1.03%.QPTR Was Not Discovered Sooner Because of Alarm Indications | | | 05000272/LER-1978-043, Forwards LER 78-043/03L-0 | Forwards LER 78-043/03L-0 | | | 05000272/LER-1978-046, :Number Not Used |
- Number Not Used
| | | 05000272/LER-1978-061, Forwards LER 78-061/01X-2 | Forwards LER 78-061/01X-2 | | | 05000272/LER-1978-061-01, /01X-2 on 780907:noted Defect in Protection Sys Which Could Allow Airborne Activity to Be Released to Outside Atmosphere.Caused by Design Deficiency.Design Change Installed in Protection Sys | /01X-2 on 780907:noted Defect in Protection Sys Which Could Allow Airborne Activity to Be Released to Outside Atmosphere.Caused by Design Deficiency.Design Change Installed in Protection Sys | | | 05000272/LER-1978-062, Forwards LER 78-062/03L | Forwards LER 78-062/03L | | | 05000272/LER-1978-062-03, /03L-0 on 780913:during Normal Oper the 12 Reactor Coolant Flow Channel 2 Was Not Indicating Due to Failure of a Hagan Controls Signal Isolator | /03L-0 on 780913:during Normal Oper the 12 Reactor Coolant Flow Channel 2 Was Not Indicating Due to Failure of a Hagan Controls Signal Isolator | | | 05000272/LER-1978-063-03, /03X-1 on 780910:containment Fan Cooling Unit 13 Inoperable. Caused by Flow Control Transmitter Failure Due to Silt Buildup in Low Pressure Sensing Line.Transmitter Cleaned & Sensing Line Blown Out | /03X-1 on 780910:containment Fan Cooling Unit 13 Inoperable. Caused by Flow Control Transmitter Failure Due to Silt Buildup in Low Pressure Sensing Line.Transmitter Cleaned & Sensing Line Blown Out | | | 05000272/LER-1978-063, Forwards LER 78-063/03X-1 | Forwards LER 78-063/03X-1 | | | 05000272/LER-1978-064-03, /03L-0 on 780912:reactor Trip Setpoint Greater than T/S Limit During Check of Pressure Protec Channel 2. Caused by Unstable Output from Comparator Feeding Trip Bistable.Comparator Replaced | /03L-0 on 780912:reactor Trip Setpoint Greater than T/S Limit During Check of Pressure Protec Channel 2. Caused by Unstable Output from Comparator Feeding Trip Bistable.Comparator Replaced | | | 05000272/LER-1978-064, Forwards LER 78-064/03L-0 | Forwards LER 78-064/03L-0 | | | 05000272/LER-1978-067, Forwards LER 78-067/03X-1 | Forwards LER 78-067/03X-1 | | | 05000272/LER-1978-067-03, /03X-1 on 780929:during Normal Operation,Resident NRC Inspector Noted Missing Fire Barrier in Cable Penetration.Caused by Failure of Administrative Controls. Penetration Immediately Sealed | /03X-1 on 780929:during Normal Operation,Resident NRC Inspector Noted Missing Fire Barrier in Cable Penetration.Caused by Failure of Administrative Controls. Penetration Immediately Sealed | | | 05000272/LER-1978-069-03, /03L-0:on 781011,while Investigating Diesel 1B Alarm,Heater Leaking Chromated Water Into pre-lube Pump Motor Discovered.Caused by Corrosion of Element Sheath in Two of Three Heater Elements | /03L-0:on 781011,while Investigating Diesel 1B Alarm,Heater Leaking Chromated Water Into pre-lube Pump Motor Discovered.Caused by Corrosion of Element Sheath in Two of Three Heater Elements | | | 05000272/LER-1978-069, Forwards LER 78-069/03L-0 | Forwards LER 78-069/03L-0 | | | 05000272/LER-1978-070, Supplemental LER 78-070/01X-1:on 781021,during Mode 4 Operation,While Heating Up to Enter Mode 3,high Flow Through RCP Seals & Other Alarms Indicating RCS Leakage Were Observed.Cause Undetermined.Instructions Have Been Revised | Supplemental LER 78-070/01X-1:on 781021,during Mode 4 Operation,While Heating Up to Enter Mode 3,high Flow Through RCP Seals & Other Alarms Indicating RCS Leakage Were Observed.Cause Undetermined.Instructions Have Been Revised | | | 05000272/LER-1978-070-01, /01T-0:on 781021,during Mode 4 Operation,While Heating Up to Enter Mode 3,high Flow Through RCP Seals Noted & Alarms Went Off Indicating RCS Leakage.Cause Unknown | /01T-0:on 781021,during Mode 4 Operation,While Heating Up to Enter Mode 3,high Flow Through RCP Seals Noted & Alarms Went Off Indicating RCS Leakage.Cause Unknown | | | 05000272/LER-1978-071, Forwards LER 78-071/01T-0 | Forwards LER 78-071/01T-0 | | | 05000272/LER-1978-071-01, /01T-0:on 781023:during Mode 5,fire Pumps 1 & 2 Put in Manual Due to Low Air Pressure Causing Actuation of air-operated Deluge Valves.Station Air Compressors Could Not Be Started Due to Low Cooling Water Flow | /01T-0:on 781023:during Mode 5,fire Pumps 1 & 2 Put in Manual Due to Low Air Pressure Causing Actuation of air-operated Deluge Valves.Station Air Compressors Could Not Be Started Due to Low Cooling Water Flow | | | 05000272/LER-1978-072-01, /01X-1:on 781107,svc Water Isolation Valves to All Five Containment Fan Coil Units Found Tripped Closed.Caused by Design Deficiency in Installation of RMS Detectors for Containment Fan Coil Unit Svc Water.Detectors Shielded | /01X-1:on 781107,svc Water Isolation Valves to All Five Containment Fan Coil Units Found Tripped Closed.Caused by Design Deficiency in Installation of RMS Detectors for Containment Fan Coil Unit Svc Water.Detectors Shielded | | | 05000272/LER-1978-072, Forwards LER 78-072/01X-1.Detailed Event Analysis Encl | Forwards LER 78-072/01X-1.Detailed Event Analysis Encl | | | 05000272/LER-1978-073, Forwards LER 78-073/01X-1.Detailed Event Analysis Encl | Forwards LER 78-073/01X-1.Detailed Event Analysis Encl | | | 05000272/LER-1978-073-01, /01X-1:on 781127,loss of Vital Instrument Bus 1B de-energized RCP Breaker Open Relay in Solid State Protection Sys,Initiating Reactor Trip.Caused by Failure of Output Transformer in Supply Inverter | /01X-1:on 781127,loss of Vital Instrument Bus 1B de-energized RCP Breaker Open Relay in Solid State Protection Sys,Initiating Reactor Trip.Caused by Failure of Output Transformer in Supply Inverter | | | 05000272/LER-1978-075, Supplemental LER 78-075/03X-1:on 781130,while Containment Entry in Progress,Inner Door of Air Lock Elevation 130 Ft Would Not Fully Open.Caused by Failed Cam Roller on Inner Door Operating Mechanism.Cam Roller Replaced | Supplemental LER 78-075/03X-1:on 781130,while Containment Entry in Progress,Inner Door of Air Lock Elevation 130 Ft Would Not Fully Open.Caused by Failed Cam Roller on Inner Door Operating Mechanism.Cam Roller Replaced | | | 05000272/LER-1978-075-03, /03L on 781130:during Oper W/Containment Entry in Progress,Inner Door of Air Lock 130 Would Not Fully Open, Caused by Failed Cam Roller on Inner Door Operating Mechanism.Air Lock Repaired,Tested,Returned to Svc | /03L on 781130:during Oper W/Containment Entry in Progress,Inner Door of Air Lock 130 Would Not Fully Open, Caused by Failed Cam Roller on Inner Door Operating Mechanism.Air Lock Repaired,Tested,Returned to Svc | | | 05000272/LER-1978-076, Forwards LER 78-076/03L-0 | Forwards LER 78-076/03L-0 | | | 05000272/LER-1978-076-03, /03L-0 on 781208:during Surveillance of Meteorological Instruments,Noted That Normal Power Had Failed & Inverter Had Not Shifted to Batteries.No Cause for Failure Discerned;Inverter Tested Satisfactorily | /03L-0 on 781208:during Surveillance of Meteorological Instruments,Noted That Normal Power Had Failed & Inverter Had Not Shifted to Batteries.No Cause for Failure Discerned;Inverter Tested Satisfactorily | | | 05000272/LER-1978-077-03, /03L-0 on 781128:pressurizer Level Read 10% Higher than Other Channels.Calibr of Sensor Showed Tech Spec Limit for Low Level Trip Was Exceeded by 2% Due to Failure of Strain Gauge in Pressurizer Level Sensor | /03L-0 on 781128:pressurizer Level Read 10% Higher than Other Channels.Calibr of Sensor Showed Tech Spec Limit for Low Level Trip Was Exceeded by 2% Due to Failure of Strain Gauge in Pressurizer Level Sensor | | | 05000272/LER-1978-077, Forwards LER 78-077/03L-0 | Forwards LER 78-077/03L-0 | | | 05000272/LER-1978-078-03, /03L-0 on 781130:channel Checks Showed Deviation Between Steam Flow Channels I & II of Steam Generator 13. Caused by Transmitter Zero Shift | /03L-0 on 781130:channel Checks Showed Deviation Between Steam Flow Channels I & II of Steam Generator 13. Caused by Transmitter Zero Shift | | | 05000272/LER-1978-078, Forwards LER 78-078/03L-0 | Forwards LER 78-078/03L-0 | | | 05000272/LER-1978-079, Forwards LER 78-079/03L-0 | Forwards LER 78-079/03L-0 | | | 05000272/LER-1978-079-03, /03L-0 on 781201:steam Generator 12,level Channel III Found to Be Inoperable;Channel Bistables Tripped Per Tech Specs.Caused by Partially Clogged Sensing Lines | /03L-0 on 781201:steam Generator 12,level Channel III Found to Be Inoperable;Channel Bistables Tripped Per Tech Specs.Caused by Partially Clogged Sensing Lines | | | 05000272/LER-1978-080, Forwards LER 78-080/03L-0 | Forwards LER 78-080/03L-0 | | | 05000272/LER-1978-080-03, /03L-0 on 781228:leak Rate Test Showed Excessive Seal Leakage & Air Lock Was Declared Inoperable.Caused by Failure of Outer Door Seal from Normal Wear of the Seal During Air Lock Operation | /03L-0 on 781228:leak Rate Test Showed Excessive Seal Leakage & Air Lock Was Declared Inoperable.Caused by Failure of Outer Door Seal from Normal Wear of the Seal During Air Lock Operation | | | 05000272/LER-1978-081-03, /03L-0 on 781206:noted That Sump Pump Magnetrol Was Overdue for Calibr.Caused by Incorrect Assignment of Responsibility for 18 Month Calibr Surveillance | /03L-0 on 781206:noted That Sump Pump Magnetrol Was Overdue for Calibr.Caused by Incorrect Assignment of Responsibility for 18 Month Calibr Surveillance | | | 05000272/LER-1978-081, Forwards LER 78-081/03L-0 | Forwards LER 78-081/03L-0 | | | 05000272/LER-1978-082-03, /03L-0 on 781228:zero Flow Was Indicated on Plant Vent Recorder Because of Frozen Condensation in Transmitter Sensing Lines.Caused by de-energized Temporary Heat Tracing | /03L-0 on 781228:zero Flow Was Indicated on Plant Vent Recorder Because of Frozen Condensation in Transmitter Sensing Lines.Caused by de-energized Temporary Heat Tracing | | | 05000272/LER-1978-082, Forwards LER 78-082/03L-0 | Forwards LER 78-082/03L-0 | | | 05000272/LER-1978-083, Forwards LER 78-083/03L-0 | Forwards LER 78-083/03L-0 | | | 05000272/LER-1978-083-03, /03L-0 on 781213:Number 13 Auxiliary Feed Pump Tripped on Overspeed Because Governor Operating Speed Was Set at 4200 Rpm.Governor Speed Reset & 3 Tests Confirmed Operability | /03L-0 on 781213:Number 13 Auxiliary Feed Pump Tripped on Overspeed Because Governor Operating Speed Was Set at 4200 Rpm.Governor Speed Reset & 3 Tests Confirmed Operability | | | 05000272/LER-1978-084-03, /03L-0 on 781127:boron Injection Tank Rendered Inoperable Due to Reduced Boron Concentration Resulting from Safety Injection | /03L-0 on 781127:boron Injection Tank Rendered Inoperable Due to Reduced Boron Concentration Resulting from Safety Injection | | | 05000272/LER-1978-084, Forwards LER 78-084/03L-0 | Forwards LER 78-084/03L-0 | | | 05000272/LER-1978-085-03, /03L-0 on 781211:svc Water Flow Through Fan Coil Unit Was Less than Required 2500 Gal Per Minute.Caused When Solenoid Control Coil Developed an Open Circuit | /03L-0 on 781211:svc Water Flow Through Fan Coil Unit Was Less than Required 2500 Gal Per Minute.Caused When Solenoid Control Coil Developed an Open Circuit | |
|