LER 79-002/03L-0 on 790203:alarm for Fire Protection Panel 25-236 Annunciated in Control Room.Panel Was Not Alarmed Condition.Caused by Normal End of Life Electrical Failure of Annunciator Point Card.Card Replaced & Sys Normalized
ML18024A713
Person / Time
Site: Browns Ferry Tennessee Valley Authority icon.png
Issue date: 03/01/1979
From:
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML18024A712 List:
References
LER-79-002-03L-02, LER-79-2-3L-2, NUDOCS 7903070335
Download: ML18024A713 (2)


Text

'

NRC FORM 366 ~ ov44cssh hcvvLAA vss ~ ~ 4vlossossavsvso PTTl i LlCENSEE EVENT REPORT CONTROL BLOCK: Qi (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATIONI 1 6

~o 7 8 A L B LICENSEE CODE R F 2QT 14 15 0 0 0 0 0 LICENSE NUMBER 0 0 0 0QT 25 26 4 1 1 LICENSE TYPE 1 1QA~QA 30 57 CAT 58 CON'T

~o 8 60 QO 5 0 0 0 2 6 0 66 1

69 0 2 0 EVENT DATE 3 7 9 74 6

75 0 3 0 REPORT DATE 1 7 9 80 QB 7 81 DOCKET NUMBER EVENT DESCRIPTION AND PROBABLE CONSEQUENCES QIO During normal operation, an alarm for fire rotection anel 25-236 annunciated in t contro 1 room. The pane 1 was not in an alarmed condition; however the annunciator would not clear. The fault would have masked an alarm si nal from the encl which is required to be operational (T. S ~ 3~ 11. Cs 1) ~ There was no hazard to the publ ic health or safety. Thexe are no redundant systems. Previous occurrences: None.

~07

~08 80 7 8 9 SYSTEM CAUSE CAUSE COMP VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUSCODE

~DB ~AB Qll ~E Qls ~F QIT 1 N 0 T R 0 QIA ~2 Qls ~2 Qls 7 8 9 lo II 12 13 I8 19 20 SEQUENTIAL OCCURAENCE REPORT AEVISION Qls LEAIRO ATPOAT ACTION FUTURE EVENT YEAR

~79 21 22 EFFECT

~

23 SHUTDOWN

~00 24 AEPOAT NO.

2 28

~~

'27

~03 28 ATTACHMENT CODS 29 NPRDQ TYPE

~L 30 PAIME COMP.

~31

~0 32 NO.

COMPONENT TAKEN ACTION 33 QIB ~ZQIB 34 ON PLANT

~ZQ20 35 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS Q21 METHOD

~Q2' 38 3 HOURS +22

~

40

~

SUBMITTED 41 Q23 FORM SUB.

~Q24 42 SUPPLIER MLQ26 43 44 MANUFACTURER T 0 7 6 47 Q26 0 Normal end of life electrical failure of the annunciator oint caxd P 4 cause the inabilit to clear the annunciator. The cax'd was turned to normal operation. A fire watch was established to monitor the affected area.

4 7 8 9 80 F AC I I.IT Y QSO METHOD OF STATUS N POWER oTHERsTATUs OI5COVERY DlscovERY DESCRIPTION A2 5 ~E Qss ~~~ 4 Qss ~A Q31 Operator observed annunciatoY'5 7 8 9 10 I'2 12 44 So ACTIVITY CONTENT

~Q ~Q34 Il AELFASED OP RILEASE AMOUNT OF ACTIVITYQ36 I.OCATIoN OF AELEAsE Q36 6 NA NA 7 8 9 10 44 45 80 PEASONNEL EXPOSURES 7 8 9 II 12 13 So PERSONNEL IN)URIE5 7 8 9 11 12 sossol'll AAMAos TOTAAIIITT Qso TYPE DE5CRIPTION B ~ZQ42 NA 7 8 9 lo So PUBLICITY NRC USE ONLY ISSUED DESCRIPTION ~4II NA as

~

0 ~NQ44 89 IO 89 SO a 0

IVAME OF PREPARER PHONE,'8 0 7 903 O'70'33~

Form BF-17 BF 15.2 6/09/78 l~

LER SUPPLENENTAL INFORMATION BFRO-50-~te Technical SPecification Involved 3. 11. C. 1 Reported Under Technical Specification 6. 7.2. b(2)

Date of Occurrence 2/3/79 Time of Occurrence 142S Unit 2 Identification and Descri tion of Occurrence:

normal operation, an alarm for fire protection panel 2S-236 annunciated

'uring in the control room. The panel was not in an alarmed condition; however, the annunciator would not clear.

Conditions Prior to Occurrence:

Normal power operation at 94K power.

Action specified in the Technical Specification Surveillance Requirements met due to ino erable e ui ment. Describe.

investigation revealed no fire and no alarm at fire protection panel 25-236.

A arent Cause of Occurrence:

Failure of the associated annunciator point card (Technology, Inc. P/N 314773) caused the annunciator to alarm continuously.

Anal sis of Occurrence:

There are no redundant systems. There was no hazard to the public health or safety.

Corrective Action:

The annunciator point card was replaced and the system was referred to normal operation. A fire watch was established to monitor the affected area.

Failure Data; Hone previous.

Tennessee Valley Authority - Browns Ferry Nuc1ear P1ant