MONTHYEARML23011A0622023-01-11011 January 2023 Written Part 21 Notification of a Defect Associated with Imi CCI Supplied Main Steam and Main Feedwater Isolation Valves ML22220A2362022-08-0202 August 2022 Leonardo DRS, 16-AAT907B Power Supply 10 CFR Part 21 Notification ML19346H8732019-12-12012 December 2019 Westinghouse Electric Company - Notification of the Potential Existence of Defect Pursuant to 10 CFR Part 21 ML19168A0122019-05-31031 May 2019 Paragon Energy Solution LLC-10 CFR Part 21 Report of Defect GS2 Terry Turbine Introl Positioners ML18039A2922018-01-24024 January 2018 Velan, Inc. - Corrected Notification for 4NPS Class 150 Through 900 Swing Check Valve Disc (Part Number 8205-012) ML18024A0032018-01-16016 January 2018 Velan Inc. - Part 21 Notification for Disc (Part Number 8205-012) in 4NPS Class 150 Through 900 Swing Check Valve ML17194A8252017-07-11011 July 2017 Part 21 Report Re Wedge Pin Failure in Anchor Darling Motor Operated Double Disc Gate Valves with Threaded Stem to Upper Wedge Connections ML17114A0702017-04-13013 April 2017 Part 21 Notification - Identified Fisher 546S Electro-Pneumatic Transducers Standard Mounting Brackets Failed Seismic Testing Standards ML17104A2882017-04-13013 April 2017 Emerson Process Management, LLC - Fisher Information Notice, (FIN) 2017-02 ML16321A4512016-10-21021 October 2016 Part 21 Reporting of Defects and Noncompliance ML16278A4712016-09-22022 September 2016 Notification of 10 CFR Part 21 Condition, Masterpact Breaker Fail to Close ML16281A2702016-09-22022 September 2016 Part 21 - Initial Notification of Masterpact Breaker Fail to Close ML16243A4722016-08-25025 August 2016 Part 21 Reporting of Defects and Noncompliance ML16229A4442016-08-15015 August 2016 Potential Part 21 on Safety Clip, Siemens Part Number 401158 ML16203A1792016-07-0707 July 2016 Curtiss-Wright 10 CFR Part 21 Report Regarding Disposition of a Nonconformance on Struthers-Dunn Relay Part Number B225XCXP125V Supplied to PSEG Nuclear, LLC ML16139A8342016-05-10010 May 2016 Electroswitch - Transmittal of 10CFR Part 21 Reporting of Defects and Noncompliance Regarding Vendor Inspection of Electroswitch Corporation Docket No. 99900833 ML16126A1112016-04-29029 April 2016 National Technical Systems (Nts) Request for Extension, for Potential Part 21 on Safety Clip, Siemens Part Number 401-158 ML16112A2102016-03-14014 March 2016 National Technical Systems - Potential Part 21 on Siemens 401-158 Safety Clip, Per Wolf Creek, Salem, and Arkansas Nuclear One ML15103A4852015-04-0707 April 2015 Itt Engineered Valves - 2nd Interim Report to the NRC of 10 CFR 21 Event 50285, Reported by Itt 07/18/14 Concerning M I Diaphragms, Customer Testing ML15022A6502015-01-20020 January 2015 Letter from Steven R. Eisenberg USNRC 10CFR Part 21 Notification ML14261A1502014-09-17017 September 2014 Interim Report to the NRC of 10 CFR 21 Event 50285, Reported by Itt 07/18/14 Concerning M1 Diaphragms, Customer Testing ML14094A4452014-04-0101 April 2014 Notification of Part 21 Report on Defective Raw Material Used to Manufacture Valve Stems ML14069A4682014-03-0202 March 2014 Part 21 Report - Defective Raw Material Used to Manufacture Valve Stems ML14034A1892014-01-23023 January 2014 Part 21 - Loose Battery Vent Assemblies ML13211A1682013-07-26026 July 2013 Westinghouse, Notification of Potential Existence of Defects Pursuant to 10 CFR Part 21 Inconsistency Between the Intended Design Functionality of the Shield Passive Thermal Shutdown Seal (SDS) and That Observed During Post-Service Testing ML13165A3422013-06-12012 June 2013 60-Day Interim Report Involving an Evaluation of a Design Change to Magne-Blast Circuit Breakers ML13073A1072013-03-12012 March 2013 Notification of Potential Part 21 Report - Defective Raw Material Used to Manufacture Valve Stems ML13064A0122013-02-25025 February 2013 Notification of Potential Part 21 Report Re Wedge Pin Failure of an Anchor/Darling Double-Disc Gate Valve ML13045A8932013-02-0101 February 2013 Notification of Part 21 Report - Defective Raw Material Used to Manufacture Valve Stems ML12348A1362012-12-13013 December 2012 Part 21 60-Day Interim Report Notification: Adequacy of Design Change in Am Magne-Blast Circuit Breakers ML12352A1232012-12-13013 December 2012 60-Day Interim Report Involving an Evaluation of a Design Change to Magne-Blast Circuit Breakers ML12066A1182012-03-0202 March 2012 Part 21 Report - Rosemount Pressure Transmitters with Nonzero Based Calibrations ML12097A3162012-03-0202 March 2012 Part 21 Report - Rosemont Pressure Tranmitters Out of Tolerance Condition ML1005129082010-02-12012 February 2010 Notification of Potential Part 21 Report Re Interim Report Concerning an Issue in Sump Blockage Generic Tests ML1004801382010-02-12012 February 2010 Interim Report of the Evaluation of a Deviation Pursuant to 10CFR21.21(a)(2) ML0926802462009-09-23023 September 2009 Notification of Potential Part 21 on Reportable Occurrence Under 10 CFR Part 21: Firmware Anomaly in the Model RM-80 Radiation Monitoring System ML0831900172008-11-12012 November 2008 Notification of Potential Part 21 on All Dimensionally Verified Commercial Grade Items Processed Per Fisher Manufacture Procedure Fmp 2K28 ML0823901062008-08-25025 August 2008 Notification of Potential Part 21 on Failure of F and G Switches ML0809906342008-04-0404 April 2008 Part 21 Notification Regarding Failure to Comply with the Requirements for Dedication of Commercial Grade Items ML0734402112007-12-0707 December 2007 Deficiency Report Part 21 Potential Insufficient Thread Engagement for Certain Pressure Transmitters ML0713703092007-03-0707 March 2007 Velan, Inc., Piston Check Cv Information ML0627702242006-09-27027 September 2006 Part 21 Report from Tyco Valves & Controls LP, Improper Valve Springs in Pressure Relief Valves ML0626204942006-09-15015 September 2006 Part 21 Report by Tyco Valves and Controls, LP Re Improper Valve Springs in Pressure Relief Valves. Corrective Actions Taken by Tyco Listed ML0413205472004-04-23023 April 2004 Deficiency Report Re Potential Safety Hazard That Exists for Woodward Digital Reference Unit (Drus) 2023-01-11
[Table view] |
Text
August 15, 2016 Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001
Subject:
Potential Part 21 on Safety Clip, Siemens Part Number 401158
Dear Sirs,
National Technical Systems (NTS) recently submitted a request for extension to complete a failure analysis of the Siemens 401158 Safety Clip. NTS has completed the failure analysis and hereby provides its final evaluation.
Pursuant to the requirements of 10 CFR Part 21, NTS notified the NRC previously of a potential Part 21 condition. The subject Safety Clip is used in commercial grade item medium voltage circuit breakers. The subject circuit breakers are manufactured by Siemens Industry Inc. and are dedicated for use as a basic component by NTS. Affected circuit breakers are Siemens Type 5-3AF-GER-350-1200-78, which are a 350 MVA vertical lift type. The Safety Clip in question is made of a black finish steel and retains the Close Pawl Roller.
During an inspection at Wolf Creek Nuclear Operating Company, it was shown that the subject Safety Clips were cracked, broken, missing, or degraded after 600 to 850 operations. If the Safety Clip breaks and falls off, and the washers and Close Pawl Roller outside bearing and race fall off, then future circuit breaker close operations beyond the next close cycle may not be assured.
Based on NTS's evaluation, it is judged that the failure of the Siemens 401158 Close Pawl Roller Safety Clip was most probably due to a manufacturer lot batch tolerance issue coupled with the acceleration and shock excitation present at the clip's mounting location. It is further judged that the Close Paw Roller Safety Clip location within the Siemens Type 3AF 350 MVA operating mechanism is the only clip location subject to this excitation level.
NTS has provided the Siemens Type 3AF 350 MVA circuit breakers to WCNOC Wolf Creek, PSEG Nuclear LLC Salem, and Entergy ANO. NTS has contacted each utility and recommended that Close Pawl Roller Safety Clip Part Number 401158 be replaced with Safety Clip Part Number 40115. This safety clip is a yellow zinc plated safety clip of different design, and no known problems exist with this safety clip on different type Siemens circuit breakers dedicated by NTS .
....:--flq
~
~~R-NTS Huntsville
- Huntsville, AL 35806 * (256) 837-4411
NTS Thank you for your consideration in this matter and if you have any questions, please contact NTS' Senior Director of Nuclear Engineering and Test Services, Tom Brewington at (256) 716-4512 or email at tom.brewington@nts.com.
Sincerely,
- -. ****~-1Jr ;i:._ __ ;.-o..._ ... - * - - --** -** * .--
C.:>
Megan Toomey Sr. Contracts Manager NTS Huntsville NTS Huntsville
- Huntsville, AL 35806 * (256) 837-4411